, DOC NO:
2X77, 1X80, 1X180 MW THERMAL POWER PLANT, GUMMIDIPOONDI OPGPG/0/O&E/SOP/01/005
DOC TITLE HEAT RATE AND ITS DEVIATION REV NO: 1 REV. DT. 12/11/13
There are several different definitions of heat rate that are used. Each definition is
valid and useful when properly applied. In General, Heat rate is a ratio of Heat Input to the Power
Output.
Heat rate monitoring is focused on identifying heat rate problems and then identifying
and implementing corrective actions to eliminate the efficiency loss. In this approach, heat rate
deviations from expected or design levels are identified and quantified. Then using fault trees or
other resources the cause(s) are identified. This method is useful, but the fact is, the heat
rate should not be allowed to deteriorate to the point that unexpected or unknown deviations
exist.
deterioration and corrective action should be taken prior to the point that it significantly
impacts the heat rate. By following good O&M practices and proactive action, heat rate
deteriorations can be avoided (or at least accounted for) before they are reflected in the overall
performance statistics.
indicators” , monitoring them and taking corrective actions immediately as indicated. If this
is done, the improvement in higher-level performance parameters (heat rate, availability, etc.)
will follow.
DOC TITLE HEAT RATE AND ITS DEVIATION REV NO: 1 REV. DT. 12/11/13
Responsibilities:
Role Responsible
Data Collection – from DCS O&E Engineer
Deviation Report:
If any performance deviation is noted during analysis means, the following channel is
followed for conveying the report to management
O & E Head
President - Operations
JMD
ASSUMPTIONS
The following assumptions have been made for the analysis of station Heat Rate:
1. Design Station Heat Rate has been evaluated based on design data of turbine heat rate and
boiler efficiency
2. The data related to various parameters of station heat rate such as generation, fuel
consumption, calorific values of fuels, etc. has been found.
3. Weighted average of Coal Gross Calorific Value (GCV) which is AR basis and Oil GCV has
been computed monthly/yearly for calculating heat rate.
EVALUATION METHOD
There are two methods for heat rate evaluation of Thermal Power Stations, i.e., Indirect
Method and Direct Method.
OPG POWER GENERATION PVT LTD., DOC NO:
2X77, 1X80, 1X180 MW THERMAL POWER PLANT, GUMMIDIPOONDI OPGPG/0/O&E/SOP/01/005
DOC TITLE HEAT RATE AND ITS DEVIATION REV NO: 1 REV. DT. 12/11/13
Indirect Method
Indirect method of Heat Rate Measurement is an instantaneous method which is used for
short duration and not possible throughout the year. It is a very complex method and basically a
loss based method of measurement of Heat Rate. This method is generally adopted during the
Energy Audit Studies.
Direct Method
Direct Method of Heat Rate Assessment is suitable for long duration in which averaging
gives almost actual Heat Rate because Coal consumption measurement is fairly accurate if taken
over a month/Year. Therefore, this method is employed at almost all stations as per the standard
practice.
Data Required
a) Coal Bunkered in MT
b) Oil Consumed in kL
c) Coal Weighted Avg. GCV in kCal/kg
d) Oil GCV in kCal/kg
e) Total Power Generated in kWh
f) Feed water Flow in TPH
g) Spray water Flow in TPH
h) Make up water Flow in TPH
i) Main Steam Temp in ° C
j) Main Stream Press in bar (gauge pressure)
k) Enthalpy of Main Steam in kcal / kg
l) Enthalpy of Feed Water in kcal / kg
m) Heat rate is expressed in kCal / kWh
OPG POWER GENERATION PVT LTD., DOC NO:
2X77, 1X80, 1X180 MW THERMAL POWER PLANT, GUMMIDIPOONDI OPGPG/0/O&E/SOP/01/005
DOC TITLE HEAT RATE AND ITS DEVIATION REV NO: 1 REV. DT. 12/11/13
COAL BASIS:
Sample Calculation:
DOC TITLE HEAT RATE AND ITS DEVIATION REV NO: 1 REV. DT. 12/11/13
COAL BASIS
(33637 𝑥 1000) 𝑥 4443 )
Unit Heat Rate =
47630000
Heat rate deviations are calculated on the basis of parameter having direct impact on
Heat Rate. For arriving at best possible deviation value duration of data collection and
frequency of data collection plays vital role. Input data for all the parameter is available in Daily
DCS log and the final average value to be used for calculations.
The parameters used for Accountable Heat Rate Deviations are as follows,
Load
MS Pressure
MS Temperature
Condenser Back Pressure
FW Temperature at HPH2 Outlet
Make Up Water %
Dry Flue Gas Loss
Impact of Coal on Dry Gas Loss
Wet Flue Gas Loss
OPG POWER GENERATION PVT LTD., DOC NO:
2X77, 1X80, 1X180 MW THERMAL POWER PLANT, GUMMIDIPOONDI OPGPG/0/O&E/SOP/01/005
DOC TITLE HEAT RATE AND ITS DEVIATION REV NO: 1 REV. DT. 12/11/13
1. LOAD
MS HR DEV
Average load based on gross energy meter reading is to Pressure(g) kCal/kWh
90 0
be taken for calculation. This average value of Load is to be
89 0
compared with Full load capacity of unit. The difference of Load 88 2.236
87 4.472
will be taken for Heat rate deviation calculation. The heat rate 86 6.708
deviation is to be derived from Load Vs HR deviation curve. Till 85 8.944
84 11.18
such time the customized correction curve is not available the 83 13.416
correction curves provided by manufacturer may be used. 82 15.204
81 17.44
80 19.676
Sample Calculation:
Expected Load = 80 MW
Actual Load = 80.14 MW
Variance = -0.145 MW
DOC TITLE HEAT RATE AND ITS DEVIATION REV NO: 1 REV. DT. 12/11/13
Sample Calculation:
Design Pressure = 89 kg/cm2 (abs)
Expected Pressure = 89 kg/cm2 (abs)
Actual Pressure = 92.18 kg/cm2 (abs)
Variance = -3.175 kg/cm2 (abs)
DOC TITLE HEAT RATE AND ITS DEVIATION REV NO: 1 REV. DT. 12/11/13
4. VACUUM PRESSURE
Condenser backpressure based on average of 24 hrs is to be
taken every day and the monthly average is used for calculation. This Vacuum
HR DEV
kg/cm2 (g)
average value of Condenser backpressure is to be compared with -0.87 -16.0992
expected condenser backpressure The difference of Average value -0.86 -13.8632
-0.85 -11.18
of Day and Expected value of condenser backpressure is to be -0.84 -8.0496
taken for Heat rate deviation calculation based on customized -0.83 -3.354
-0.82 0
correction curves developed by station.
-0.81 5.59
Sample calculation: -0.80 13.416
Design Vacuum Pressure = -0.82 kg/cm2 -0.79 19.677
-0.78 23.031
Expected Vacuum Pressure = -0.82 kg/cm2 -0.77 29.068
Actual Vacuum Pressure = -0.87 kg/cm2
Tested Boiler Eff = 82.28 %
Turbine HR Deviation = -16.099 kCal/kWh
HR Deviation = -19.567 kcal/kWh
DOC TITLE HEAT RATE AND ITS DEVIATION REV NO: 1 REV. DT. 12/11/13
Sample Calculation:
Design FW Temperature = 244.9 C
Expected FW Temperature = 244.9 C
Actual FW Temperature = 249.45 C
Variance = -4.55 C
Turbine Heat Rate Dev = -3.24 kCal/kWh
Heat Rate Deviation = -3.94 kCal/kWh
6. DM MAKEUP WATER
Total DM Make up to the boiler in a unit is to be taken for calculation of % DM
makeup. For comparing Heat rate loss due to DM make up, it can be divided into 50:50 ratio
as 50 % steam side leakage and 50 % water leakage of total % of DM makeup.
Heat Value of make-up, H (Dev) = 0.5 x (H1- H2) + 0.5 x (H3- H2)
HR (Dev) = [Q x H (Dev) x 1000] / (GG)
Where
DM Makeup = Q M3
MS enthalpy = H1 kcal/kg
Makeup water enthalpy = H2 kcal/kg
Feed water enthalpy = H3 kcal/kg
Gross generation = GG kWh
Heat Rate Deviation = HR (Dev) kcal/kWh
Sample Calculation:
Design DM Make Up = 1%
Expected DM Make Up = 1%
DM Make Up-Q = 3606 m3
MS enthalpy H1 = 832.20 kcal/kg
Makeup water enthalpy H2 = 35.03 kcal/kg
Feed water enthalpy H3 = 258.67 kcal/kg
Gross Generation GG = 47.63 x 1000000 kWh
H (Dev) = 0.5 x (832.2 – 35.03) + 0.5 x (258.67 -35.03)
= 510.41 kcal/kg
OPG POWER GENERATION PVT LTD., DOC NO:
2X77, 1X80, 1X180 MW THERMAL POWER PLANT, GUMMIDIPOONDI OPGPG/0/O&E/SOP/01/005
DOC TITLE HEAT RATE AND ITS DEVIATION REV NO: 1 REV. DT. 12/11/13
DOC TITLE HEAT RATE AND ITS DEVIATION REV NO: 1 REV. DT. 12/11/13
DOC TITLE HEAT RATE AND ITS DEVIATION REV NO: 1 REV. DT. 12/11/13
Correction Factors for H2, Moisture, GCV, Ash and Ambient Temperature
Sample Calculation:
Design Wet Flue Gas loss = 10.4 %
OPG POWER GENERATION PVT LTD., DOC NO:
2X77, 1X80, 1X180 MW THERMAL POWER PLANT, GUMMIDIPOONDI OPGPG/0/O&E/SOP/01/005
DOC TITLE HEAT RATE AND ITS DEVIATION REV NO: 1 REV. DT. 12/11/13
Sample Calculation
Ash % in coal = 6.97 %
GCV = 4616 Kcal/kg
Expected Unburnt = 0.7 %
Actual Unburnt = 1.26 %
Variance = -0.56 %
Monthly Tested Boiler h = 82.28 %
Change in Boiler Efficiency with change in fly ash Unburnt CBE = 0.05 %
Heat Rate Deviation = (Turbine HR/ (Tested Boiler Eff – CBE)) - Unit HR
= (2321 / (0.8228 – 0.0005)) – 2821
DOC TITLE HEAT RATE AND ITS DEVIATION REV NO: 1 REV. DT. 12/11/13
Sample calculation
Total Oil Consumption = 37.18 KL
Total Generation = 47.630 MU
Density = 0.89 kg/L
HR Deviation = (Oil cons x Density x GCV) / Generation
= (37180 x 0.89 x 10400) / (47.63 x 106)
HR Deviation = 7.23 kCal / kWh
OPG POWER GENERATION PVT LTD.,
DOC NO:OPGPG/1 OPN/SOP/003/005
2X77, 1X80, 1X180 MW THERMAL POWER PLANT, GUMMIDIPOONDI
DOC TITLE SOP – HEAT RATE & HEAT RATE DEVIATION REV NO 04
HR
Parameter values
Deviation
No Parameters Unit Loss % Loss RS
Design Expected Actual Variance kcal/kWh