EG001 B00 OWNER:


SHEET NO. BLDG NO. PROJECT NO.

R GENERAL NOTES :- LIGHTING & SMALL POWER NOTES :- R


B.N SYMBOLS DESCRIPTIONS B.N SYMBOLS DESCRIPTIONS CLIENT:
THE FOLLOWING NOTES SHALL APPLY TO ALL DRAWINGS 1- MOUNTING HEIGHTS SHALL BE : GENERALLY AS INDICATED BELOW OR AS
SO1 F1 UNLESS OTHERWISE NOTED OR INDICATED INSTRUCTED BY ENGINEER WITHOUT ANY COST IMPLICATION TO THE CONTRACT
- LIGHTING SWITCH : 1200mm A.F.F.L
1- THE ELECTRICAL INSTALLATION SHALL COMPRISE :- - GENERAL SOCKET OUTLET : 450mm A.F.F.L
SO2 E
F1E MAIN AND SUB-MAIN DISTRIBUTION NETWORK AND DISTRIBUTION CABLING
ETC. INSIDE AND OUTSIDE THE BUILDINGS. FINAL SUB-CIRCUITS ( LIGHTING - HAND DRYERS : 1100mm A.F.F.L
Q SMALL POWER, CONDITIONING EQUIPMENT, VENTILATION SYSTEMS AND - ISOLATOR SWITCH : ADJACENT TO EQUIPMENT Q
SO3
D1
ANY INSTALLED EQUIPMENT IN GENERAL ), EARTHING AND BONDING MAIN CONSULTANT:
SYSTEM AND LIGHTING FIXTURES
SO4 2- WIRE SIZES SHALL BE STRICTLY FOLLOWED ACCORDING TO THE INDICATED
SIZES SHOWN IN PANEL DETAILS WIRES SHALL BE COLOR
D1E
2- THE INTENT OF THESE DRAWINGS IS TO GUIDE THE CONTRACTOR IN CODED AS SPECIFIED
SO6
THE SCHEME OF WORKS. CONTRACTOR SHALL MAKE PROPER SHOP
DRAWINGS FOR THE APPROVAL BY THE ENGINEER AND SUBMIT IT 3- WIRING FOR NORMAL CIRCUITS SHALL BE TOTALLY SEGREGATED. THIS IS
D2 INCLUDING PANELS, RACEWAYS, WIRES, BOXES, SWITCHES ..ETC.
P SO7 BEFORE THE WORK COMMENCES AT SITE P

SUB CONSULTANT:
4- WIRING FOR SMALL POWER AND LOW CURRENT CIRCUITS SHALL BE TOTALLY
FB1 D2E 3- ALL ELECTRICAL WORKS SHALL BE EXECUTED IN STRICT ACCORDANCE SEGREGATED. THIS IS INCLUDING PANELS, RACEWAYS, WIRES, BOXES,
WITH THE PROJECT SPECIFICATIONS, AND LATEST EDITIONS OF LOCAL CODES SWITCHES ..ETC.
AND INTERNATIONAL STANDARDS.
FB2 F2 5- ALL ISOLATORS DESIGNATED FOR ELECTRIC APPLIANCES OR EQUIPMENT
4- THE RATING OF CABLES SHOWN ON DRAWINGS IS FOR GUIDANCE ONLY SHALL BE LABELED WITH THE EQUIPMENT REFERENCE OR TAG AND LOCKABLE.
N JB1 IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO CHECK, N
F2E AT THE STAGE OF TENDER, THE RUNS OF ALL CABLES IN RELATION 6- CONDUITS SHALL BE GALVANIZED STEEL IN THE MECHANICAL & WET AREA
Notes
TO STRUCTURAL RESTRICTION SO THAT ALL MATERIALS SUCH AS MINIMUM CONDUIT DIAMETER SHALL BE Ø20mm FOR LIGHTING AND
JB2 CONDUITS AND THEIR ACCESSORIES ARE INCLUDED IN HIS PRICE. Ø25mm FOR POWER OR AS PER SPECIFICATIONS
F2 ISOLATOR SWITCH SHALL BE INSTALLED FOR ANY REMOTE EQUIPMENT
7-
WH 5- ACTUAL LOCATIONS OF ALL OUTLETS MUST BE VERIFIED BY THE ADJACENT TO IT BEFORE TERMINATION, FOR MAINTENANCE SAFETY.
SITE ENGINEER BEFORE INSTALLATION COMMENCES RATING, VOLTAGE AND NUMBER OF POLES SHALL BE SUITABLE FOR THE
F4 EQUIPMENT SERVED
M
HD HD 6- ALL ELECTRICAL EQUIPMENT SHALL BE SUPPLIED BY AN APPROVED M
MANUFACTURER AND THE CONTRACTOR SHALL ENSURE THAT ALL 8- FIGURE SHOWN ON HOME RUN INDICATES THE CIRCUIT REFERENCE
F4E EQUIPMENT ARE SUITABLE FOR THE PURPOSE FOR WHICH IT IS TO FROM THE DESIGNATED PANEL BOARD TO THE CIRCUIT.
DS1
E BE USED AND THAT IT IS FUNCTIONING PROPERLY AFTER INSTALLATION.
9- WIRING FOR LIGHTING CIRCUITS ARE FOR GUIDANCE ONLY.
DS2 7- AS-BUILT DRAWINGS TOGETHER WITH EQUIPMENT TEST CERTIFICATES, THE CONTRACTOR MAY CHOOSE THE MOST CONVENIENT ROUTE,
LS-1
MANUALS, AND INSTRUCTIONS TO USE , ALL IN THREE COPIES ARE TO MATCHING THE PROJECT SPECIFICATIONS AND SHOW IT IN HIS
DS3
BE SUBMITTED UPON COMPLETION OF WORKS. SHOP DRAWINGS
L L
LS-2 8- COORDINATE WITH OTHER DISCIPLINES TO ACHIEVE THE MOST SUITABLE
10- THE CONTRACTOR SHALL SUBMIT PANEL BOARDS DETAILS ALONG WITH
DS4 MOUNTING LOCATIONS IN ORDER TO AVOID ANY CONFLICT MAY OCCUR IN
THE REQUIRED SUBMITTALS AND SHOP DRAWINGS SHOWING:
LS-3 9- GENERALLY INDEX OF PROTECTION SHALL BE IP55 FOR ALL ELECTRICAL - CIRCUIT REFERENCE SHOWN ON LAYOUTS
FITTINGS LOCATED IN WET AREAS & OUTDOOR AREAS - ACTUAL LOAD OF EACH CIRCUIT PER PHASE IN VA
UNLESS OTHER WISE NOTED OR INDICATED. - SUMMATION OF EACH PHASE LOAD ASSURING 3 PHASE LOAD BALANCE
LS-4 - AREAS SERVED BY EACH CIRCUIT
10- ALL EQUIPMENT LAYOUT ARE PROVISIONAL. FINAL LAYOUT SHALL BE - RATING OF ALL COMPONENTS
K K
DETERMINED BY THE CONTRACTOR FROM THE WORKSHOP DRAWINGS - WIRE SIZE AND NO. OF WIRES
LS-5 - DETAILED DIAGRAMS FOR CONTROL CIRCUITS , IF ANY
AND AFTER COORDINATION WITH OTHER TRADES & OPERATOR. - ENCLOSURE AND BUSES SPECIFICATIONS
DC 11- EARTH CONTINUITY CONDUCTORS ARE NOT INDICATED ON THE DRAWINGS,
LS-6
BUT SHALL BE RUN WITH ALL CIRCUITS AND FEEDERS ON ACCORDANCE 11- ALL LIGHTING FIXTURES WITH BUILT IN BATTERY SHALL BE FED BY 4 WIRES
(PHASE, NEUTRAL, EARTH, AND DEDICATED WIRE FOR THE BATTERY CHARGER).
WITH THE PROJECT SPECIFICATIONS AND/OR STANDARDS.
LS-7 12-
J THE SIZE OF CONDUITS AND/OR CABLE TRAYS SHOWN IN DRAWINGS J
A.T
IS FOR GUIDANCE, THE ACTUAL SIZE OF CONDUITS AND/OR POWER DISTRIBUTION NOTES :-
CABLE TRAYS SHALL BE SELECTED BY THE CONTRACTOR
IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS AND/OR 1- BASED ON THE SHOP DRAWINGS OF THE EQUIPMENT INSTALLED
STANDARDS AND REGULATIONS. THE CONTRACTOR SHALL FURNISH AND VERIFY THE FOLLOWING:-
SW1
13- THE CONTRACTOR SHALL PROVIDE ALL STEEL ANGLES & FIXING ACCESSORIES A. SWITCHGEAR ROOMS
H H
REQUIRED FOR COMPLETE INSTALLATION OF LIGHTING FIXTURES, CABLE - SWITCHGEAR MOUNTING
SW2 TRAYS, BUSBARS AND THEIR ELECTRIC OUTLETS AND CONDUITS. - EXACT CABLE RACEWAYS LAYOUT
- EXHAUST SYSTEM
SW3
DRAWINGS SHALL BE CONSIDERED BY THE CONTRACTOR DURING
SINGLE LINE DIAGRAM NOTES:- THE SELECTION OF SWITCHBOARDS TO COMPLY WITH THE
RECOMMENDATION OF THE MANUFACTURERS FOR CLEARANCES
SW4 1- THE CONTRACTOR SHALL VERIFY THE FINAL LOADS IN COORDINATION WITH BETWEEN ENCLOSURES AND THE ADJACENT SURFACES.
G G
OTHER TRADES. ACCORDINGLY FINAL SIZES OF CABLES & CIRCUIT BREAKERS
SHALL BE ADJUSTED. 2- CABLES SHALL BE ARRANGED ON CABLE TRAYS AND/OR LADDERS
SW5
NEATLY WITH A SPACING EQUAL TO THE LARGEST DIAMETERS
2- THE SHORT CIRCUIT RATING INDICATED ON DRAWINGS REPRESENT OF TWO ADJACENT CABLES.
SW6 THE SERVICE SHORT CIRCUIT Isc WHICH ALL THE COMPONENTS OF PANEL SEPARATE RACEWAYS SHALL BE FURNISHED FOR EACH OF
B.N SYMBOLS DESCRIPTIONS
BOARDS SHALL WITHSTAND INCLUDING BUS BARS, CIRCUIT BREAKERS FIXING LV AND CONTROL CABLES.
F MATERIALS ... ECT. AS PER IEC 60947-2 ALL CIRCUIT BREAKERS SHALL BE F
SW7 3- FOR RACEWAYS TYPES AND SIZES REFER TO RELEVANT DRAWINGS
SELECTED TO ASSURING FULL DISCRIMINATION OF LOAD FAULTS. THE CONTRACTOR SHALL VERIFY THE SIZING BY CALCULATION
Sunday, September 25, 2022 11:34:35 AM

AND SUBMIT ANY MODIFICATIONS FOR APPROVAL.


LCP LCP 3- VOLTAGE DROP SHALL NOT EXCEED 5% AT FINAL LOADS POINTS.
4- THE CONNECTION OF MAIN INCOMING CABLES INCLUDING LUGS & GLANDS KEY PLAN

4- INDEX OF PROTECTION FOR ALL DISTRIBUTION BOARDS & PANEL BOARDS TO PANEL BOARDS OR ISOLATOR SWITCH SHALL BE RESPONSIBILITY OF
SHALL BE IP33 FOR FLUSH MOUNTED, IP42 FOR SURFACE MOUNTED THE CONTRACTOR.
E E
& IP55 FOR OUTDOOR & WET AREAS UNLESS OTHERWISE INDICATED.

5- ALL CIRCUIT BREAKER RATINGS SHOWN ON DRAWING ARE PRESENTING


EARTHING AND LIGHTNING NOTES :-
THE THERMAL TRIP SETTING AND FRAME SIZE. CIRCUIT BREAKERS RATED DESIGN DRAWINGS IS ONLY FOR GUIDANCE AND THE FULL CALCULATION
1-
DB 100A AND ABOVE SHALL BE EQUIPPED WITH ADJUSTABLE TRIP SETTING.
Sheet size - ISO A0 (841* 1189 mm)

AND FINAL DESIGN SHALL BE DONE BY CONTRACTOR

D
2- REQUIRED OHM FOR EACH SYSTEM SHALL BE CHECKED BY THE CONTRACTOR AS FOLLOWS: D
6- THE CONTRACTOR SHALL SUBMIT THE FOLLOWING CALCULATIONS 1- POWER EARTHING NETWORK :2 OHM
AND STUDIES FOR APPROVAL : 2- CLEAN EARTHING NETWORK :0.5 OHM
- LOAD SCHEDULES FOR ALL DISTRIBUTION BOARDS & LOAD FLOW 3- LIGHTNING EARTHING NETWORK :10 OHM
- CABLE SIZING AND VOLTAGE DROP CALCULATIONS 3- CONTRACTOR TO SUBMIT FULL CALCULATIONS AND DESIGN FOR APPROVAL PRIOR TO INSTALLATION
- SHORT CIRCUIT CALCULATIONS AT EACH BUS 4- COLUMNS REBAR TO BE USED AS A DOWN CONDUCTOR AS PER BS-62305
- DISCRIMINATION STUDY & CIRCUIT BREAKERS SETTING VALUES
5- COPPER TAPE SHALL BE CONNECTED WITH THE COLUMNS REBAR VIA WIRE 1X70 CU/PVC MM2 A DEC-2022 DETAILED DESIGN A.YBS A.MSA A.HSG A.MAA
C OBTAINED FROM THE MANUFACTURER REV DATE ISSUED FOR DRW CHK TL PM
C
100 mm

PROJECT DATA:

AL SOKHNA PORT RENOVATION

PRAYER HALL &ACCOMODATION


AL AIN AL SOKHNA , EGYPT.

DISCIPLINE

B ELECTRICAL B
50 mm

SHEET TYPE
GENERAL SHEETS
Scanning scale

SHEET TITLE

GENERAL NOTES AND SYMBOLS


SCALE PROJECT NO. SITE NO/BLDG NO SHEET NO. REV .
10 mm

A NTS 047 PO 22E B00 EG001 A A