Project Name hh
Job No. hh
Calculation Name Cable Calculation
Table1 Standards
ON
Australian Standard AS/NZS 3008.1.1
AS/NZS 3000:2018 Wiring Rules
Table2 Cable
Insulation XLPE or Elastomer (90 deg.C.)
Conductor Copper Solid/Stranded
Cores Single core
SI
Installation Unenclosed Touching
Table3 Load
Current (A) ER 2800
Power Factor 0.85
Phase Angle (degrees) 31.8
Table5 Supply
Phases 3 ph
Voltage (V) 400 (ph-ph)
Permissible Voltage Drop (%) 2.5
TR
Table6 Protection
Short-circuit Clearing Time (s) 0.1
Device Type MCB
Rating (A) 100 A
Page 1 of 4
Software by Electrotechnik
Cable Pro 2020 (V4.9)
- www.ELEK.com.au
Cable Pro Report 22/3/2021, 19:23
Curve D
Earth Fault Time 0.4 s
Trip Current (A) 3000
Trip Multiplier 30
ON
RCD FALSE
SI
ER
LV
IA
TR
Page 2 of 4
Software by Electrotechnik
Cable Pro 2020 (V4.9)
- www.ELEK.com.au
Cable Pro Report 22/3/2021, 19:23
Table7 Results
Minimum conductor cross-
sectional area (mm2) No. of circuits
Active Conductor 300 5
ON
Neutral Conductor 300 5
Earth Conductor 150 5
SI
Conductor Operating Temperature (deg.C.) 114.2
Reference (Ambient) Temperature (deg.C.) 40
Tabulated Current-carrying Capacity of Cable (A) 602
Standard TABLE No. Ref. 8
Standard Column No. Ref. 8
ER
Table9 Voltage Drop: PASS
Page 3 of 4
Software by Electrotechnik
Cable Pro 2020 (V4.9)
- www.ELEK.com.au
Cable Pro Report 22/3/2021, 19:23
ON
Min. Active Size to Withstand Short-circuit (mm2) 54.09
SI
56.99
ER
LV
IA
TR
Page 4 of 4
Software by Electrotechnik
Cable Pro 2020 (V4.9)
- www.ELEK.com.au