Cable Pro Report 22/3/2021, 19:23

Project Name hh
Job No. hh
Calculation Name Cable Calculation
Table1 Standards

ON
Australian Standard AS/NZS 3008.1.1
AS/NZS 3000:2018 Wiring Rules

Table2 Cable
Insulation XLPE or Elastomer (90 deg.C.)
Conductor Copper Solid/Stranded
Cores Single core

SI
Installation Unenclosed Touching

Table3 Load
Current (A) ER 2800
Power Factor 0.85
Phase Angle (degrees) 31.8

Table4 Derating Factors

Overall Derating Factor 0.76


TABLE 26(2) Groups of single (combined) or
multi-core enclosed buried circuits
LV

Summary of Factors Derating factor: 0.83


Spacing (m): Spaced 0.3 m
No. of circuits: 5 groups
TABLE 28(1) Depth of burial - direct buried
Derating factor: 0.92
Depth of burial (m): 1.00
Reference depth (m): 0.5
Conductor size: Above 300 mm2
IA

Table5 Supply

Phases 3 ph
Voltage (V) 400 (ph-ph)
Permissible Voltage Drop (%) 2.5
TR

Length of Run (m) 50


Fault Level (kA) 46

Table6 Protection
Short-circuit Clearing Time (s) 0.1
Device Type MCB
Rating (A) 100 A

Page 1 of 4
Software by Electrotechnik
Cable Pro 2020 (V4.9)
- www.ELEK.com.au
Cable Pro Report 22/3/2021, 19:23

Curve D
Earth Fault Time 0.4 s
Trip Current (A) 3000
Trip Multiplier 30

ON
RCD FALSE

SI
ER
LV
IA
TR

Page 2 of 4
Software by Electrotechnik
Cable Pro 2020 (V4.9)
- www.ELEK.com.au
Cable Pro Report 22/3/2021, 19:23

Table7 Results
Minimum conductor cross-
sectional area (mm2) No. of circuits
Active Conductor 300 5

ON
Neutral Conductor 300 5
Earth Conductor 150 5

Table8 Current-carrying Capacity: FAIL

Current Rating of Circuit-derated (A) 2298.44


Spare Current-carrying Capacity of Circuit (A) -501.56
Overall Derating Factor 0.76

SI
Conductor Operating Temperature (deg.C.) 114.2
Reference (Ambient) Temperature (deg.C.) 40
Tabulated Current-carrying Capacity of Cable (A) 602
Standard TABLE No. Ref. 8
Standard Column No. Ref. 8
ER
Table9 Voltage Drop: PASS

Voltage Drop (V) 5.77


Voltage Drop (%) 1.44
Permissible Voltage Drop (%) 2.5
Maximum Length of Run (m) 86.69
LV

Phase Conductor Resistance (Ohms/km) 0.08


Neutral Conductor Resistance (Ohms/km) 0.07
Resistance Table No. Ref. 34
Resistance Col. No. Ref. @ min. temp. 2
Resistance Col. No. Ref. @ max. temp. 5
Phase Conductor Reactance (Ohms/km) 0.1
Neutral Conductor Reactance (Ohms/km) 0.1
IA

Reactance Table No. Ref. 30


Reactance Col. No. Ref. 7

Table10 Fault Loop Impedance: PASS


TR

Protective Device Impedance, Zmax (Ohms) 0.077


Total Loop Impedance, Zs (Ohms) 0.003827
Upstream (system) Impedance, Zext (Ohms) 0.000765
Internal Conductors Impedance, Z1+Z2 (Ohms) 0.003061
Impedance of Phase Conductors, Z1 (Ohms) 0.001252
Impedance of Return Conductors, Z2 (Ohms) 0.001809

Page 3 of 4
Software by Electrotechnik
Cable Pro 2020 (V4.9)
- www.ELEK.com.au
Cable Pro Report 22/3/2021, 19:23

Table11 Short-circuit Performance - Active Conductors: PASS


Three-phase Short-circuit Current (A) 22136.3
Duration of Short-circuit (s) 0.1
Material, Initial and Final Temperature Constant, K 129.42

ON
Min. Active Size to Withstand Short-circuit (mm2) 54.09

Table12 Short-circuit Performance - Earth Conductors: PASS


Active-to-Earth Short-circuit Current (A) 23324.1
Duration of Short-circuit (s) 0.1
Material, Initial and Final Temperature Constant, K 129.42
Min. Earth Size to Withstand Short-circuit (mm2)

SI
56.99

ER
LV
IA
TR