Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 3

FLOCULATOR WITH CLARIFIER

1 DATA INPUTS
Diameter of tank = 24.5 Gallons
Depth of water storage = 5.27 m
Capacity of tank = 2483.20 Litres
Capacity of tank = 2.48 m³
Freee board = 0.50 m
Concrete Grade = 25.00 N/mm²
Steel Grade = 550.00 N/mm²
Weight of concrete = 25 kN/m³

2 PERMISSIBLE STRESSES
σct = 1.20 N/mm² for tank walls
= 2.80 N/mm² for dome, ring beam
σcc = 5.00 N/mm²
σst = 150.00 N/mm²
m = 13.00

3 TANK DIMENSIONS
Diameter of circular tank = 24.50 m
= 24.50 m
Shell Thickness of walls = 0.75 m Assumed
Base Slab Thickness = 0.6 m -
4 REINFORCEMENT IN TANK WALLS

Maximum Hoop tension = 0.5 𝑥 Υ 𝑥 𝐻 𝑋 𝐷


= 645.57 kN

Tension reinforcement per metre height of tank wall

Ast = 4303.83 mm²

Using 20mm dia bars on both faces


Spacing = 145.92 mm c/c

Provide 20mm dia bars (at) 125mm c/c on both faces horizontally

5 THICKNESS OF TANK WALL

Assumed thiness of tank wall = 750.00 mm


(0.5 𝑥 Υ 𝑥 𝐻 𝑋 𝐷" " )/(1000 𝑥 𝑡 +(𝑚−1)𝑥𝐴_𝑠𝑡 )
= 1.20

t= 486.33 mm
Provide thickness of tank wall as 550mm
t= 550 mm
6 CURTAILMENT OF REINFORCEMENT IN TANK WALLS

Maximum reinforcement at top of tank walls = 0.30%


Ast = 1650.00 mm²
Using 12mm dia bars on both faces
Spacing = 136.97
Provide 12mm dia bars (at) 125mm c/c on both faces vertically

7 DESIGN OF TANK FLOOR SLAB (SIZE)

Assumed base slab thickness = 600 mm

Weight of water in tank = 24.83 kN


Weight of tank walls = 5574.54 kN
weight ot tank base slab = 7067.94 kN

Total weight = 12667 kN


NSBC as per report = 120 kN/m²
NSBC after soil stabilization = 120 kN/m²
Area required = 105.56 m²

Diameter of tank required = 11.60 m

Diameter of tank provided = 26.60 m

Provide Ast-min = 0.30%

Ast = 1800 mm²

Spacing of 16mm diameter bars = 112 mm c/c

Provide 16mm dia bars (at) 100 c/c in both directions at top and at bottom

You might also like