Professional Documents
Culture Documents
ANALYSIS
ANALYSIS
ANALYSIS
AND
DESIGN COMPUTATION
PROJECT:
LOCATION:
OWNER:
DESIGN AND ANALYSIS PARAMETERS
Design Codes:
National Structural Codes of the Philippines (NSCP) 2015 7TH Edition vol.1, chapter 2.
American Concrete Institute (ACI318M-08), Chapter 9.2
Uniform Building Code (UBC 1997), Vol. 2, Chapter 16
American Society of Civil Engineers 2002 (ASCE-7) 2ND Edition
Design Methodology:
Load Resistance Factor Design (AISC-LFRD)
Design Loads:
Dead Loads
1. Selfweight
150 mm CHB = 2.63 + 0.24 + 0.24 = 3.11 kN/m per meter height
REINFORCED CONCRETE BEAM
LB-1
Input Parameters :
Sup Mid
Standard Specs Moment Capacity Top Bot Shear Capacity
fc' = 21 Mpa Tension Bar, Dt = 2 2 bw = 100 mm fyt = 230
fy = 230 Mpa Tension Bar 2-L, Nb = 0 0 h = 150 mm Av = 2
b₁ = .85 Main Bar dia, D = 12 Sb = 10 mm Stirrups Bar Ø
Es = 200 Gpa Moment, Mu = 3.8 4.0 Cc = 25 mm, Clear Covering
CONDITION ;
Val = 0.65+0.25(Ԑt - Ԑty/0.005 - Ԑty) ρ < ρmin, As is not Adequate for Beam Dim S
Ø = 0.65 , Ԑt ≤ Ԑty if fs > fy, use fy 2-12mmØ
-- -- --
U
Val , Ԑty ˂ Ԑt ˂ 0.005 fs < fy, use fs
0.90 , Ԑt ≥ 0.005 P
Location of d' & dt; Support Midspan P
As1 = π D² Db /4 = 226.19 226.19 O
2L, As2 = π D² Nb /4 = 0.00 0.00
1-12mm
R
y = (As 1 y 1 +As 2 y 2 )/As = 0.00 0.00
d' = Cc + Sb + (D/2) + y = 41.00 41.00 T
dt = h - d' = 109.00 109.00
CHECKING ; Support Midspan
ρ= As / b dt = 0.0208 0.0208 M
ρmin = 1.4 / fy = 0.0061 0.0061 2-12mm
I
ρb = 0.85fc' β1 600/fy(600+fy) = 0.0477 0.0477
Therefore ρ < ρb ρ < ρb D
Tension Steel Yield Yield S
CHECK SHEAR ; Ø = 0.75 P
Vc = 0.17 √fc' bw dt = 8.49 < 0.00 -- -- --
A
Vsmax = 0.67 √fc' bw dt = 33.47 KN 2-12mm
Vs = (Vu/Ø ) - Vc = (8.49) < 33.47 N
Section is Adequate
Av = 2 (π Sb²/4) = 157.1
Vs ≤ 0.33√f'c bw d, d/2
Max S, w/c
or 600mm otherwise
ever is
Vs > 0.33√f'c bw d,
lesser,mm
d/4 or 300mm
BEAM MOMENT CAPACITY @ SUPPORT; Ø = 0.90 BEAM MOMENT CAPACITY @ MIDSPAN; Ø = 0.90
Direct Substitution Direct Substitution
Therfore use, 100x150 with 4-12mmØ @ support and 4-12mmØ @ midspan Main Bars (Grade 33);
10mmØ 2 leg-stirrups: Sp. at 2@50, 0@20 and rest 100 O.C, BOTH ENDS.
REINFORCED CONCRETE COLUMN
SC-1
Des i gn Pa rameters :
Ma i n Ba rs Loc -Z As t
h= 200 mm d' = 25 mm fs 1 = 2 - 175.00 226.19
b= 150 mm Ma i n ba rs = 12 mm Ø fs 2 = 0 - 175.00 0
fc' = 21 Mpa Mux = 3.33 KNm fs 3 = 0 - 175.00 0
fy = 230 Mpa Pu = 12.34 KN fs 4 = 0 - 175.00 0
b₁ = 0.85 Es con = 600 Mpa fs 5 = 2 - 25.00 226.19
Es = 200 Gpa Shea r pa rameters
Therefore use, 200x150mm 4-12mm Ø longitudinal bars (GRADE 33) with 10mm Ø lateral ties space at,
2@50, 0@30mm , and Rest 100mm O.C, BOTH ENDS.