520AID01 CS en

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

RTU520 product line

Analog input 520AID01


Connections and settings

Application, characteristics and technical data have to be taken


from the hardware data sheet: Parameter name Default Parameter location

520AID01 data sheet 1KGT 150 866 Aquisition mode Integrated AMI, MFI - PDP parameters
threshold su-
pervision
Operation Aquisition mode:
– Integrated threshold supervision
The 520AID01 module records up to 6 analog measured values. – absolute threshold supervision
– periodic update
The module is available in two versions (rubrics): – Integrated threshold + periodic update
– R0001: Current measurement version
– R0002: Voltage measurement version
For additional information on these configuration parameters in
RTUtil500 refer to RTU500 series function description - part 5:
SCADA functions .
Processing functions
Scan cycle and line frequency interferance suppression
The module 520AID01 is able to process the following types of
signals:
Beside the information about the configured measuring range
– Analog measured values (AMI)
the information about the line frequency is required for the A/D-
– Measured floating point information (MFI)
conversion. The scan cycle time is determined by the AC line
frequency:
The micro-controller on the module processes all time critical
tasks of the parameterized processing functions. Moreover it
carries out the interactive communication with the RTU I/O bus. Frequency Conversion time per Scan cycle time

All configuration data and processing parameters are loaded by channel (same for all chan-

the communication unit via the RTU I/O bus. nels)

60 Hz 50 ms 400 ms
The analog input unit can execute the following processing
50 Hz 60 ms 480 ms
functions on the measured values:
– Scan cycle and line frequency interference suppression 16.7 Hz 200 ms 1600 ms

– Zero value supervision and switching detection


– Smoothing The scan frequency is independent from the number of config-
– Threshold value monitoring on absolute value or with accu- ured channels. The synchronization of the scan cycle with the
mulation line frequency is used to increase the line frequency interference
– Periodic transmission and background cycles suppression of the DC input signal.

Parameter name Default Parameter location Parameter name Default Parameter location

Zero range ±0.25 % AMI, MFI – PDP parameters Line frequency 50 Hz AMI, MFI – PDP parameters

value range: ±0.1... ±5 % value range: 50 Hz, 60 Hz, 16.7 Hz


Zero value supervision forces low input signals in the configured range to 0% Depending in the line frequency the scan cycle of the analog input is determined.
Parameter has to be the same for all channels of the analog input module.

Parameter name Default Parameter location

Smoothing factor disabled AMI, MFI - PDP parameters

value range: 2, 4, 8, 16, 32, 64, 128 or disabled


Unstable input signals can be smoothed to prevent too many value transmissions
Settings The LED ERR indicates module errors or I/O bus errors:
– module runs initialization procedure
Input signal range – module is performing a cold or warm start
– module has detected a memory error (RAM or PROM)
All input signal ranges of the 520AID01 R0001 and R0002 are – micro-controller is faulty
selected by the RTU configuration. – no dialog via the I/O bus for at least 2 minutes. The module
is not polled by the CMU.
Following measurement ranges can be configured for – A/D converter faulty
520AID01 R0001:
– ± 2.5 mA
– ± 5 mA Connections
– ± 10 mA
– ± 20 mA I/O bus connection

Following measurement ranges can be configured for The module is connected to the RTU I/O bus via the connectors
520AID01 R0002: X1 and X2.
– ± 1 V DC
– ± 10 V DC ADVICE

To prevent damage on the connected modules de-energize


In addition for the 520AID01 R0002 jumper S1 selects the in-
the system before plugging or unplugging the I/O bus con-
put range:
nectors.
– S1 at Position 1-2: input range ± 1 V DC
– S1 at Position 2-3: input range ± 10 V DC
ADVICE
Parameter name Default Parameter location
To prevent unintended disconnection of the I/O bus connec-
Input signal range 20 mA AMI / MFI – PDP parameters tors end stops (e. g. BAM3 1SNK900001R0000) shall be
used at both ends of the I/O assembly.
select the required input range according to the analog input module variant

Input signal type bipolar AMI / MFI – PDP parameters


Process connections
input signal types:
– bipolar (e. g. ±20 mA) The process signals will be connected to the terminals X3 (see
– unipolar (e. g. 0... 20 mA) Fig. 2 and Fig. 4). The input channels are not potential isolated
– live zero (e. g. 4... 20 mA) from the internal power supply.
Adjust zero value for live ze- deactivated AMI / MFI – PDP parameters
ro signal
Automatic calibration
only valid for live zero values
– deactivated: 4... 20 mA -> 0... 100%
Two internal measuring channels of the 520AID01 are performing
– activated: 4... 20 mA -> -100... 100%
an automatic zero calibration at each cycle. The A/D converter
uses the result as a rating factor.

Signaling An on-site calibration of the A/D converter is not necessary. The


520AID01 is calibrated for all channels and measuring ranges at
LED ERR the factory.

The module monitors and checks the own functionality as well


as the dialog via the I/O bus. Detected errors are indicated by the
red LED ERR on the front plate and transmitted via the I/O bus to
the communication unit (CMU). Additional diagnostic messages
are available using the Web-Server on the CMU.

2 | 1KGT 150 867 V001 1 - Analog input 520AID01


Figure 1: 520AID01
R0001 Front plate Figure 2: 520AID01 R0001 Label

Figure 3: 520AID01
R0002 Front plate
Figure 4: 520AID01 R0002 Label

6 5
1

3
4
2

Figure 7: RTU520 DIN rail mounting - step 3


Figure 6: RTU520 DIN rail mounting - step 2
Figure 5: RTU520 DIN rail mounting - step 1
1 Insert upper edge into DIN rail and 3 + 4: 5 + 6:
push downwards Shift one module connector into the oth- Mount end stops at the left and right
2 Push lower edge towards DIN rail er starting from right to left side
and snap in the module

Analog input 520AID01 - 1KGT 150 867 V001 1 | 3


+ I06
X3-11

ERR

Resistor network
Protection
ADC
A
Micro -
controller

- I06
X3-12

...
Multiplexer
RTU I/O bus

RAM
Input circuit

+ I03
Signal- X3-5

conditioning - I03
X3-6
Flash
+ I02
X3-3
Signal-
conditioning - I02
X3-4
D
IOC
+ I01
Signal- X3-1
conditioning - I01
X3-2

Figure 8: 520AID01 connection diagram

4 | 1KGT 150 867 V001 1 - Analog input 520AID01


ABB AG Note:
Power Systems Division The specifications, data, design or other information contained in this document
P.O. Box 10 03 51 (the “Brochure”) - together: the “Information” - shall only be for information pur-

68128 Mannheim, Germany poses and shall in no respect be binding. The Brochure does not claim to be ex-
haustive. Technical data in the Information are only approximate figures. We re-

www.abb.com/substationautomation serve the right at any time to make technical changes or modify the contents of
this document without prior notice. The user shall be solely responsible for the
use of any application example or information described within this document.
The described examples and solutions are examples only and do not represent
any comprehensive or complete solution. The user shall determine at its sole
discretion, or as the case may be, customize, program or add value to the ABB
products including software by creating solutions for the end customer and to
assess whether and to what extent the products are suitable and need to be ad-
justed or customized.

This product is designed to be connected to and to communicate information


and data via a network interface. It is the users sole responsibility to provide and
continuously ensure a secure connection between the product and users or end
customers network or any other network (as the case may be). The user shall es-
tablish and maintain any appropriate measures (such as but not limited to the in-
stallation of firewalls, application of authentication measures, encryption of da-
ta, installation of anti-virus programs, etc) to protect the product, the network,
its system and the interface against any kind of security breaches, unauthorized
access, interference, intrusion, leakage and/or theft of data or information. ABB
AG is not liable for any damages and/or losses related to such security breaches,
any unauthorized access, interference, intrusion, leakage and/or theft of data or
information.

ABB AG shall be under no warranty whatsoever whether express or implied and


assumes no responsibility for the information contained in this document or for
any errors that may appear in this document. ABB AG's liability under or in con-
nection with this Brochure or the files included within the Brochure, irrespective
of the legal ground towards any person or entity, to which the Brochure has been
made available, in view of any damages including costs or losses shall be exclud-
ed. In particular ABB AG shall in no event be liable for any indirect, consequen-
tial or special damages, such as – but not limited to – loss of profit, loss of pro-
duction, loss of revenue, loss of data, loss of use, loss of earnings, cost of cap-
ital or cost connected with an interruption of business or operation, third party
claims. The exclusion of liability shall not apply in the case of intention or gross
negligence. The present declaration shall be governed by and construed in ac-
cordance with the laws of Switzerland under exclusion of its conflict of laws rules
and of the Vienna Convention on the International Sale of Goods (CISG).

ABB AG reserves all rights in particular copyrights and other intellectual property
rights. Any reproduction, disclosure to third parties or utilization of its contents -
in whole or in part - is not permitted without the prior written consent of ABB AG.

© Copyright ABB 2014


All rights reserved

Analog input 520AID01 - 1KGT 150 867 V001 1 | 5