Professional Documents
Culture Documents
Multipressure Systems
Multipressure Systems
MULTIPRESSURE SYSTEMS
A multipressure system is a refrigeration system that has two or more ``low-side” pressure.
The low-side pressure is the pressure of the refrigerant between the expansion valve and the intake of
the compressor. A multipressure system is distinguished from the single-stage system which has but one
low-side pressure.
A saving in power required by a refrigeration system results if flash gas that develops when liquid
refrigerant expands is removed and recompressed before complete expansion. When saturated liquid
expands through an expansion valve, the percentage of vapor progressively increases. The expansion
process shown in the P-h diagram takes place from 1-2. The state point, as the expansion proceeds,
moves into a region of greater percentage of vapor.
The end point of the expansion, 2, could have been achieved by interrupting the expansion at 3
and separating the liquid and vapor phases, which are 4 and 6. The expansion could then continue by
expanding the liquid at 4 and the vapor at 6 to the final pressure, giving 5 and 7 respectively. The
combination of refrigerant at states 5 & 7 gives point 2.
Inspection of the expansion from 6 to7 confirms that it is wasteful. The refrigerant at 7 can do
no refrigerating and work will be required to compress the vapor back to the pressure it had at 6. Why
not perform part of the expansion, separate the liquid from vapor, continue expanding the liquid, and
recompress the vapor without further expansion? The equipment to achieve this separation is called the
flash tank shown. The expansion from 2 to 3 takes place through a float valve. The valve serves the
further purpose of maintaining a constant level in the flash tank. To recompress the vapor at 6, a
compressor must be available with a suction pressure at 6. Thus two compressors are needed in the
system.
B) Intercooling
Intercooling between two stages of compression reduces the work of compression per pound
(or kg) of vapor.
Intercooling in two- stage compression of air Intercooling of refrigerant in two- stage compression
Methods of Intercooling
The optimum pressure of intercooling can be approximately determined by using the formula:
1
𝑝𝑖 = (𝑝𝑠 𝑝𝑑 )2
Where 𝑝𝑖 = 𝑖𝑛𝑡𝑒𝑟𝑐𝑜𝑜𝑙𝑒𝑟 𝑝𝑟𝑒𝑠𝑠𝑢𝑟𝑒
Example: Calculate the power required by the two compressors in an ammonia system which serves a
25-ton evaporator at -30 F. The system uses two-stage compression with intercooling and removal of
flash gas. The condensing temperature is 90 F. The system is as shown above.
Solution:
INTERCOOLER
Problem. A refrigerant -22 system is arranged as shown below. Condensing pressure is 1.5 MPa,
intermediate pressure is 0.5 MPa, and evaporating pressure is 0.2 MPa. The following temperatures are
known: t1 = 35 C, t3 = 5 C, t5 = -20 C, and t7 = 5 C. Assume isentropic compression and frictionless flow.
Calculate the coefficient of performance.
Solution:
Problem. A refrigerant-22 economizer cycle is arranged as shown. Assume isentropic compression and
frictionless flow. State 5 is compressed isentropically to state 6 which mixes with state 7 at the same
pressure to form state 8. This refrigerant is then compressed isentropically to state 9. Known data are: t1
= 90 F, t3 = 20 F, t5 = 0 F. (a) Calculate the coefficient of performance for this cycle (b) Compute the
coefficient of performance for this cycle when the mass flow rate at state 7 is reduced to zero. (c)
Comment on the difference between the results obtained in parts (a) and (b).
Solution: