CSCC - Fire Resistance of Plain Concrete-Filled Steel Hollow Structural Section Columns
CSCC - Fire Resistance of Plain Concrete-Filled Steel Hollow Structural Section Columns
21
Fire Protection
CANADIAN STEEL CONSTRUCTION COUNCIL 201 Consumers Road, Suite 300
Willowdale, Ontario, M2J 4G8
Algoma Steel Inc. · Dofasco Inc. · Ispat Sidbec Inc. · Stelco Inc.
CSCC Canadian Fasteners Institute · Canadian Institute of Steel Construction · Canadian Sheet Steel Building Institute
Steel Service Centre Institute · Corrugated Steel Pipe Institute · Canadian Welding Bureau (Associate Member)
94/11
DESIGN FORMULA AND CURVES 2500
A concrete-filled column's fire-resistance rating is a function
of its size, slenderness ratio, the concrete strength and type
2 h Rating
f ' = 20 MPa
C
as well as the load it is supporting (without load factors). To
achieve a fire-resistance rating, a load restriction is usually 2000
required. This restricted column load can be calculated in
accordance with the following new Article that will appear in
the 1995 National Building Code of Canada:
Concentrically loaded hollow steel columns that are filled
1500
with plain concrete and are fabricated and erected within the
Cmax , kN
tolerances as stipulated in CAN/CSA-S16.1, “Limit States
Design of Steel Structures" shall be assigned a HSS 406 x 6.4
a=
where HSS 324 x 6.4 0.0
7
C = axial compressive force due to dead and live
HSS 273 x 6.4 a=0
loads without load factors, kN, .08
500
a=0
( )
2 .07
a fc' + 20 D 2.5 a=0.0
Cmax = 8
a=0.0
7
R (KL − 1000)
a=0.08
a=0.07
but shall not exceed the factored compressive resistance of 0
2000
2500
3000
3500
4000
the concrete core,Cr' , in accordance with CAN/CSA-S16.1,
a = constant (See Table 1) Effective Length, KL, mm
'
f = specified compressive strength of concrete in
c Figure 1: Round hollow steel columns with 20 MPa
accordance with CSA-A23.3, “Design of concrete and requiring a 2 h fire endurance period
Concrete Structures,” MPa,
D = outside diameter of a round column or outside 2500
HSS 406
width of a square column, mm, x 6.4
2 h Rating
a=
R = specified fire endurance period, min, f ' = 40 MPa
0.0
C
8
KL = effective length of column as defined in
2000
CAN/CSA-S16.1, mm;
HSS 356 x 6.4
subject to validity limits:
a=
fc'
0.0
20 MPa to 40 MPa,
7
D 140 mm to 410 mm for round columns, HSS 324 x 6.4
140 mm to 305 mm for square columns, 1500
Cmax , kN
R ≤ 120 minutes,
KL 2000 mm to 4000 mm, a=
0.
08
and the hollow steel sections shall be Class 1, 2 or 3 in HSS 273 x
6.4
accordance with CAN/CSA-S16.1. 1000 a=
0.
07
Table 1-Values of a a=
0.0
8
Aggregate Circular Square HSS 219 x 4.
8 a=0
type* columns columns .07
S 0.07 0.06 500
N 0.08 0.07 a=0.0
8
* Type S concrete is made with siliceous coarse aggregate; a=0.08 a=0.07
* Type N concrete is made with carbonate coarse aggregate.
a=0.07
0
For hollow structural sections commonly available in
2000
2500
3000
3500
4000
Page 2
2500 2500
1 h Rating 1 h Rating
f ' = 20 MPa
C f ' = 20 MPa
C
2000 2000
1500 1500
Cmax , kN
Cmax , kN
HSS 406 x 6.4
a=0.07&0.08
2500
3000
3500
4000
2000
2500
3000
3500
4000
Effective Length, KL, mm Effective Length, KL, mm
Figure 3: Round hollow steel columns with 20 MPa Figure 5: Square hollow steel columns with 20 MPa
concrete and requiring a 1 h fire endurance period concrete and requiring a 1 h fire endurance period
2500 2500
HSS 406
x 6.4
a=0.0
1 h Rating 7&0.0
8 1 h Rating
'
f = 40 MPa
C
f ' = 40 MPa
C
2000 2000
HSS 356 x 6.4
Cmax , kN
a=0.0
7&0.0
8
a=
0.
06
HSS 254 x
254 x 8.0
HSS 273 x
6.4
1000 1000
a=0.0
7&0.0
8
HSS 203 a=
HSS 219 x 4. x 203 x 6. 0.0
8 4 7
a=0
500 500 .06
a=0
.08
a=0.0 a=0.07
7
a=0.06
0 0
2000
2500
3000
3500
4000
2000
2500
3000
3500
4000
Page 3
CAN/CSA-S16.1 [Reference 14] by multiplying the 3. Flemington, R.A., Fire Protection of Hollow Structural Sections,
resistance of the core (Cr' ) by an amplifier (τ ' ). Technical Bulletin 21, Stelco Inc., Hamilton, Ontario, 1980.
4. Granjean, G., Grimault, J.P. and Petit, L., Détermination de la
As the temperature increases, the column begins to
durée au feu des profils creux remplis de Béton, Rapport final,
lose part of its strength because the steel's resistance Commission des communautés européennes, Recherche
reduces. However, the steel temperature rises more technique acier, Luxembourg, 1981.
slowly than that of a column without any concrete fill 5. Kordina, E.H.K. and Klingsch, W., Brandverhalten von
because of the heat sink effect of the concrete core. Stahlstützen im Verbund mit Beton und von massiven
This is referred to as a capacitive method of fire Stahlstützen ohne Beton, Teil 1: Bericht, Institut für Baustoffe,
protection. Massivbau und Brandschulz Lerstuhl für Massivbau,
Technische Universität Braunschweig, West Germany, 1983.
Lie et al found that slender columns lose their load
carrying capacity faster than do stocky columns. The 6. Design Manual for SHS Concrete filled Columns, British Steel
Corporation, Corby Technical Centre, U.K., 1984.
capacity of slender square columns can drop to well
below the resistance of the concrete core alone, Cr' . 7. Kruppa, J., Méthode de Prévision par le calcul du
comportement au feu des poteaux mixtes ( Acier + Béton ),
Although stocky round columns can maintain their
Construction métallique, No. 3, 1988.
strength above Cr' (highest test load recorded = 165
. Cr'
[Reference 10]), occasions of sudden failure were 8. Twilt, L., Design Charts for the Fire Resistance of Concrete
Filled HSS Columns under Centric Loading, TNO Institute for
observed in the test programme. Lie et al therefore
Building Materials and Structures, Netherlands, 1988.
restricted the loads for all columns to no greater than
Cr' , among other restrictions (see Page 2), to ensure a 9. Klingsch, W. and Wittbecker, F. W., Fire Resistance of Hollow
Section Composite Columns of Small Cross Sections,
desirable and predictable behaviour. The beneficial
Bergische Universität, Wuppertal, West Germany, 1988.
confinement effect is also ignored by setting τ ' = 1.
10. Lie, T. T. and Chabot, M., Experimental Studies on the Fire
Note 1: Resistance of Hollow Steel Columns Filled with Plain Concrete,
IRC Internal Report No.611, Institute for Research in
In accordance with Clause 18.4 of CAN/CSA S16.1,
Construction, National Research Council of Canada, Ottawa,
Cr' = 0.85φCf c' Ac λ−c2 [ 1+ 0.25λ−c4 − 0.5λ−c2 ] Jan. 1992.
KL f ' 11. Lie, T. T. and Chabot, M., A Method to Predict the Fire
In which λc = c
Resistance of Circular Concrete Filled Hollow Steel Columns,
rc π Ec 2
Note 2:
In the curves on the preceding pages, and in accordance with
CAN/CSA-G312.3, "Metric Dimensions for Structural Steel Shapes
and Hollow Structural Sections", HSS 406 x 6.4 (for example)
designates a round steel hollow structural section of 406 mm
nominal outside diameter and 6.4 mm wall thickness, whereas HSS
305 x 305 x 8.0 designates a square hollow structural section of 305
mm nominal outside width and 8.0 mm wall thickness.
REFERENCES
1. Lie, T. T. and Stringer, D. C., Calculation of the Fire Resistance
of Steel Hollow Structural Section Columns Filled with Plain
Concrete, Canadian Journal of Civil Engineering, Volume 21,
No. 3, June 1994.
2. Lie, T. T., and Stringer, D. C., Assessment of the Fire
Resistance of Steel Hollow Structural Section Columns Filled
with Plain Concrete, IRC Internal Report No. 644, May 1993.
Page 4