Professional Documents
Culture Documents
CSCC - Fire Resistance of Bar-Reinforced Concrete-Filled Steel Hollow Structural Section Columns
CSCC - Fire Resistance of Bar-Reinforced Concrete-Filled Steel Hollow Structural Section Columns
CSCC - Fire Resistance of Bar-Reinforced Concrete-Filled Steel Hollow Structural Section Columns
25
Fire Protection
CANADIAN STEEL CONSTRUCTION COUNCIL 201 Consumers Road, Suite 300
Willowdale, Ontario, M2J 4G8
Algoma Steel Inc. • Dofasco Inc. • Ispat Sidbec Inc. • Stelco Inc.
CSCC Canadian Fasteners Institute • Canadian Institute of Steel Construction • Canadian Sheet Steel Building Institute
Canadian Steel Service Centre Institute • Corrugated Steel Pipe Institute • Canadian Welding Bureau (Associate Member)
97/10
Produced with support from IPSCO Inc.
DESIGN FORMULA AND CURVES 4500
3000
C £ Cmax
where 2500
Cmax, kN
HSS 356 x 6.4
C = axial compressive force due to dead and
0. 90
09
0.0 85
live loads without load factors, kN,
5
0.0 80
0 .0
2000 HSS 324 x 6.4
( )
2
a f c' + 20 D 2.5
Cmax = but shall not exceed 1.7
0. 90 5
09
0. .08 0
R (KL − 1000)
0
5
0 .08
1500
0
HSS 273 x 6.4
0.
08
09
80
CAN/CSA-S16.1, 5 0.0
5
0.0 90
80
a= constant (See Table 1) 500
f c' = specified compressive strength of concrete
in accordance with CSA-A23.3, “Design of
Concrete Structures,” MPa, 0
2000
2500
3000
3500
4000
4500
D= outside diameter of a round column or
outside width of a square column, mm, Effective Length, KL, mm
R= specified fire endurance period, min,
Figure 1: Round hollow steel columns with 30 MPa
KL = effective length of column as defined in
concrete and requiring a 2 h fire endurance period
CAN/CSA-S16.1, mm;
4500
subject to validity limits: HSS 406 x 6.4
f c' 20 MPa to 55 MPa,
4000 HSS 356 2 h Rating
D 165 mm to 410 mm for round columns, x 6.4
f'c = 50 MPa
175 mm to 305 mm for square columns,
longitudinal reinforcement shall be 1.5% to 3500
0.0 0
0.0
5%, with limits on size, number and spacing
95
HSS 32
0.0
9
4 x 6.4 0.0
of bars and ties in accordance with CSA 85
80
3000
A23.3,
25 mm concrete cover to longitudinal
0.0 90
reinforcing bars,
0.0 85
2500
95
Cmax, kN
0.0 0
0.0
3 x 6.4
KL 2000 mm to 4500 mm, and 2000
0. 090
1500
Table 1-Values of a 0.
09
0. 5
08
Aggregate Steel Circular Square 1000 5 0.0
0.0 90
type* reinforcement columns columns 80
2500
3000
3500
4000
4500
Page 2
4500 4500
4000
1 h Rating 4000
1 h Rating
fc' = 30 MPa f'c = 30 MPa
3500 3500
HSS 406 x 6.4
3000 3000
2500 2500
Cmax, kN
Cmax, kN
HSS 356 x 6.4
0
1000 1000 HSS 203 x 203 0 .08
HSS 219 x 0.0
90 0.09 x 6.4 0 .08 5
4.8
0.08 0 5 0.0.075 0
0 .085 0.0 70
0.09 85
5
500 500 0.0
0.085 70
0 0
2000
2500
3000
2000
3500
2500
4000
3000
4500
3500
4000
4500
Effective Length, KL, mm Effective Length, KL, mm
Figure 3: Round hollow steel columns with 30 MPa Figure 5: Square hollow steel columns with 30 MPa
concrete and requiring a 1 h fire endurance period concrete and requiring a 1 h fire endurance period
4500 4500
HSS 32
4 x 6.4
3000 3000
0.
2500 2500 08
0.
Cmax, kN
Cmax, kN
HSS 2 5
08
54 x 25
0.
4 x 8.0
0
07
HSS 2
0.
73 x 6
5
.4
07
0
2000 2000
0.09
5& HSS 2
1500 0.09
0 1500 03 x 2 0.
HSS 2
19 x 4 03 x 6
.4 0. 085
.8 0.0 0. 080
80 0.0 075
70
1000 1000 0.0
85
0.0
95
0.08 0.0
0 70
500 500
0 0
2000
2500
3000
2000
3500
2500
4000
3000
4500
3500
4000
4500
Page 3
columns in general include cross-sectional given on pages 2 and 3 were constructed using the
dimensions, length, concrete strength, and type of proposed formula for a series of round and square
concrete aggregate. A general discussion of hollow steel sections. The following notes apply:
behaviour can be found in Fire Protection Bulletin #21.
The discussion here is limited to the two new Notes to Figures 1 through 6:
parameters introduced in the current study; (1) Cr′ is calculated in accordance with Clause 18.4 of CAN/CSA
S16.1-94 assuming normal-weight concrete, and S/T=0.25
percentage of reinforcing steel and concrete cover where S is the short-term load on the column and T is the total
thickness to the reinforcing bars. load on the column. Confinement effects are ignored by setting
. . [Reference 8]
τ = τ ′ = 10
Three percentages of steel reinforcement, 1.5%, 3%,
(2) HSS designations and dimensions are in accordance with
and 5%, representing low, medium and high levels of
CAN/CSA-G312.3, and are given in the CISC Handbook of
reinforcing were investigated. Although the fire Steel Construction [Reference 9].
resistance increased very little with increasing (3) Two unobstructed vent holes, each not less than 12.7 mm in
percentage of reinforcement, its presence provides diameter shall be provided at opposite ends of the column and
additional containment for the concrete core at at each intermediate floor to vent steam. The holes shall be
located 150 mm from a base plate, cap plate or concrete slab.
elevated temperatures, and substantially increases Pairs of holes should be orientated such that adjacent pairs are
the duration of exposure to fire and the load carrying perpendicular [Reference 10].
capacity of the column when compared to plain
concrete-filled columns. Fire-resistance ratings of up
to 3 hours can be achieved with bar-reinforcing. REFERENCES
1. Chabot, M. and Lie, T.T., “Experimental Studies on the Fire
Two values of cover thickness were investigated, 20
Resistance of Hollow Steel Columns Filled with Bar-Reinforced
mm and 50 mm. The study found that increasing Concrete”, IRC Internal Report No. 628, National Research
concrete cover beyond the minimum has little effect Council of Canada, Institute for Research in Construction,
on fire endurance or load capacity. For simplicity, the Ottawa, Ontario, 1992.
minimum cover thickness has been assumed. 2. Lie, T.T. And Denham, E.M.A., “Factors Effecting the Fire
Resistance of Square Hollow Steel Columns Filled with
Tests [Reference 1] and comparisons with calculated Bar-Reinforced Concrete”, IRC Internal Report No. 650,
fire resistances [Reference 5] showed that the fire National Research Council of Canada, Institute for Research in
resistance remains predictable and without sudden Construction, Ottawa, Ontario, 1993.
failure for loads up to 1.7 times the resistance of the 3. Lie, T.T. And Denham, E.M.A., “Factors Effecting the Fire
unreinforced concrete core, Cr′ , and for effective Resistance of Circular Hollow Steel Columns Filled with
Bar-Reinforced Concrete”, IRC Internal Report No. 651,
column lengths up to 4500 mm. National Research Council of Canada, Institute for Research in
Construction, Ottawa, Ontario, 1993.
At elevated temperatures, the moisture present in the
concrete core turns to steam. A potential bursting 4. Lie, T.T. and Kodur, V.K.R., “Fire Resistance of Steel Columns
Filled with Bar-Reinforced Concrete”, ASCE Journal of
hazard exists if the steam it is not released into the
Structural Engineering, Volume 120, No. 5, January 1996, pp.
atmosphere. To prevent catastrophic failure, vent 30-36.
holes as described in Note 3 must be provided.
5. Lie, T.T., “Fire Resistance of Circular Steel Columns Filled with
Bar-Reinforced Concrete”, ASCE Journal of Structural
Engineering, Volume 120, No. 5, May 1994, pp. 1489-1509.
DESIGN FORMULA
6. Lie, T.T. and Irwin R.J., “Fire Resistance of Rectangular Steel
The current study, as well as the previous study, Columns Filled with Bar-Reinforced Concrete”, ASCE Journal
concluded that the fire-resistance rating of a of Structural Engineering, Volume 121, No. 5, May 1995, pp.
797-805.
bar-reinforced concrete-filled HSS column is primarily
a function of its size, slenderness ratio, concrete 7. Kodur, V.K.R. and Lie, T.T., “Fire Performance of
Concrete-Filled Hollow Steel Columns”, Journal of Fire
strength and type, percentage of reinforcing, and the Protection Engineering, Volume 7, No. 3, 1995, pp. 89-98.
load (unfactored) that it is supporting [Reference 7].
8. Canadian Standards Association, ”Limit States Design of Steel
The design formula, expressed in terms of a restricted Structures”, CAN/CSA-S16.1-94, Rexdale, Ontario, 1994.
column load for a desired fire-resistance rating, is
9. Canadian Institute of Steel Construction, ”Handbook of Steel
given on page 2. The text is patterned after Article Construction”, Sixth Edition, Willowdale, Ontario, 1995.
D-2.6.6. in the 1995 NBCC to convey the approach for
10. Lie, T.T. and Kodur, V.K.R. , “Fire Protection of Hollow Steel
bar-reinforced concrete-filled HSS columns that will Columns Through Concrete Filling”, Proceedings, CSCE
be proposed for the 2001 NBCC. The design curves Annual Conference, Volume 3, 1995, pp. 215-224.
Page 4