Professional Documents
Culture Documents
Kitchen Shield Kitchen Fire Suppresion System F808
Kitchen Shield Kitchen Fire Suppresion System F808
3. INSTALLATION ..................................................................................................................... 31
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 1
Version 1.5 / Date: 06. March 2014
System Handbook
3.6. Start-up............................................................................................................................................... 51
3.6.1. Pressurizing the sensor tube ..........................................................................................................51
3.6.2. Opening the cylinder valve/s ..........................................................................................................51
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 2
Version 1.5 / Date: 06. March 2014
System Handbook
6. EPILOGUE ............................................................................................................................... 67
7. LIST OF FIGURES.................................................................................................................. 68
Amendment index
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 3
Version 1.5 / Date: 06. March 2014
System Handbook
The installation of an automatic fire extinguishing system is often done with reference to the number of
annual fire incidents in the kitchen.
However protection of people, assets and on-going business activities should be assessed in
establishing the requirements for systems.
How fires start:
Dangerous fat and grease fires or kitchen fires in general can start in a variety of ways, for example:
due to electrical defects on heating elements, units or burners not switched off, overheating of
controls, grease and dirt residues on controls, grease, fat and dirt residues near hot surfaces.
In addition, it is not always possible that personnel are available to fight a fire manually with a fire
extinguisher, for example if a burner has been left on overnight.
Fire detection:
If there are no personal in attendance, an efficient and reliable fire detection system without false
alarms is required. This detector system should also cover a large area and be resistant to soiling, and
it should remain operational in the event of a power outage.
Fire extinguishing:
Fat and grease fires are particularly difficult to fight because of the high ignition temperatures of more
than 350°C and the catastrophic effects if water is used.
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 4
Version 1.5 / Date: 06. March 2014
System Handbook
1.2. General
The terms DANGER, WARNING, ATTENTION denote that non-compliance with the
warnings can cause severe injuries and even fatalities, or that there is the risk of
substantial material damage. All other notices must also be observed in order to prevent
faults and resulting personal injuries and material damage.
Attention:
Do not expose yourself or others to hazards. Carefully read the following safety
instructions before installing, operating or servicing the system equipment, to prevent
accidents, personal injuries and material damage. The fittings and the product itself may
only be used for the intended purposes.
Limits and values listed in these operating instructions must be observed, particularly operating
pressures and ambient temperatures of the system installation. The company Steel Recon Industries
Sdn. Bhd. will accept no liability for damages resulting from improper use or non-compliance with the
instructions in the system handbook.
These operating instructions are intended for all persons installing, operating and servicing the
products and fittings listed below. It is assumed that persons are aware of the general rules and safety
guidelines for handling gases and pressurized units. Furthermore it is assumed that the personnel are
acquainted with handling electrical components.
In case of difficulties with operating the pressure units that cannot be resolved by consulting these
instructions further information must be requested from the manufacturer.
The manufacturer reserves the right to implement technical changes, improvements and amendments,
consult the newest version of this handbook.
The operating instructions must be retained.
All work must be performed by qualified personnel. Qualified personnel must be instructed according
to the operating instructions. Qualified personnel means all persons appropriately qualified in the set-
up, installation, assembly, start-up, operating and servicing as well as maintenance of the product,
including:
Compliance with regional, national and internal regulations and safety standards
Appropriate safety equipment and work apparel
Product training regarding the kitchen extinguishing system (see chapter 6.1.)
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 5
Version 1.5 / Date: 06. March 2014
System Handbook
Extinguishing system:
Kitchen equipment (deep fat fryers, cookers, ovens…) may only be operated
with a properly installed and operational fire extinguishing system!
The working zone of the extinguisher nozzle must not be obstructed, which
would divert or screen the extinguisher spray.
It must be ensured that when the extinguishing system is triggered and
activated the heat source in the kitchen (electrical or gas) is switched off!
Stopping extractor fans is not necessary, but may be implemented at the
system designer’s discretion.
Regular visual inspections of the vessel pressures on the pressure gauges
ensure the system function and operation outside the service intervals.
The extinguishing agent is water-based and is electrically conductive. It must be
ensured that after extinguishing a fire the electrical power supply is only
reconnected after the kitchen equipment has been returned to a proper and
correct functionality.
1.4. References
Ignoring these instructions can cause severe personal injuries and material damage.
The documents listed above complement the information in this documentation, Please ensure that all
documents consulted are current and in the latest version.
The Kitchen Shield kitchen extinguishing system is designed as a permanent pressure extinguishing
system, i.e. the extinguishing agent is stored in a pressurized vessel at an operating pressure of
15bar, with nitrogen acting as the pressure gas. This pressure gas provides the energy to expel the
extinguishing agent, but it also is useful as a compensation for possible leakages.
If a fire occurs in the kitchen the sensor tube which is filled with nitrogen (15bar internal pressure, as in
the pressure vessel) reacts to the heat.
This sensor tube is mounted inside the extractor hood below the grease filter to ensure rapid fire
detection.
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 6
Version 1.5 / Date: 06. March 2014
System Handbook
This extinguishing system is suitable for the fire protection of deep fat fryers, griddles, cookers
and similar kitchen equipment provided they fall within the dimensional installation limits
detailed in the system handbook.
Kitchen equipment may only be operated with a properly installed and operational
extinguishing system! All electronic monitoring devices, where fitted, including
isolation ball valve position, pressure gas volume and system discharge monitoring
should be capable of isolating the electrical and gas supplies to the kitchen equipment
being protected. See section 2.4.9. (Electronic system monitoring). The system in the
kitchen must be visually inspected regularly for its full functionality!
Kitchen Shield - Kitchen fire suppression systems F808 may only be installed by
specialist companies with the required expertise and trained and qualified personnel.
Authorized companies and specialists installing a fire extinguishing system on behalf
of Steel Recon Industries Sdn. Bhd. must have been provided with sufficient training.
Dated training records with full names of the participants must be kept and submitted
to Steel Recon Industries Sdn. Bhd. on request.
The installer of the extinguishing system is responsible for the approval of the
installed system.
The manufacturer and/or the installer of the fire extinguishing system must deliver a
technical documentation and system-specific operating instructions regarding the
appropriate and required safety installation at the time of commissioning of the
system.
In addition, the operating instructions to the individual components (see section 1.4.) complementing
the information in this documentation must be observed.
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 7
Version 1.5 / Date: 06. March 2014
System Handbook
Check the system for its functionality in regular intervals and before starting daily work!
This includes the inspection of the vessel pressure on the pressure gauges and
checking the ball valves in the ILP valve.
Lever open –
System
operational
Never sever the sensor hose as this would trigger the extinguishing process!
The ball valve of the extinguishing system must never be shut by the operator as this
would prevent any extinguishing action!
The operator of the system must be instructed on the functions of the fire extinguishing
system; especially the instructions for actions in case of a fire or a fault must be
handed over in writing in the documentation and the service records.
As part of the general supervisory obligation the system operator is required to perform
safety training for the respective staff including instructions on the operation of the
extinguishing system.
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 8
Version 1.5 / Date: 06. March 2014
System Handbook
The dimensions and numbers listed above are the system limits and must be observed!
They were confirmed by several trial installations and the approval tests. Within these
limits a comprehensive and safe extinguishing effect may be expected. In case
individual or several limits are exceeded, a protection of persons or assets cannot be
warranted.
The correct layout and dimensioning is critical for obtaining maximum system
efficiency. Any deviations have a substantial effect on the efficiency of the system.
Therefore the layout of kitchen fire extinguishing systems may only be performed by
personnel trained by Steel Recon Industries Sdn. Bhd. For further specifications and
instruction to individual components please consult the respective operating
instructions. Any subsequent structural changes to the object to be protected require
an adaptation of the fire extinguishing system.
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 9
Version 1.5 / Date: 06. March 2014
System Handbook
Within these limits a safe and comprehensive extinguishing effect can be expected.
Should individual or several limits be exceeded a protection of persons or material
assets cannot be warranted.
*The maximum length of the sensor tube on the ILP valve (10m) corresponds to the
length of the tap line and longest continuous line section. An addition of T junctions
and branches may not result in a total length of 11m being exceeded!
For further limits and notices consult the operating instructions for the ILP valve, the sensor tube and
the electronic monitoring components listed in section 1.4.
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 10
Version 1.5 / Date: 06. March 2014
System Handbook
There are three system variants (sizes) available, characterizing mainly by the size of the installation
to be protected and the number of items of cooking equipment to be protected.
In case of installation requirements where one or several values exceed the system
limits specified above, consult Steel Recon Industries Sdn. Bhd.; it may be possible to
achieve the protection level by installing two separate extinguishing systems.
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 11
Version 1.5 / Date: 06. March 2014
System Handbook
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 12
Version 1.5 / Date: 06. March 2014
System Handbook
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 16
Version 1.5 / Date: 06. March 2014
System Handbook
Number and size of vessels (bottles) depend on the system variant chosen and must
be adjusted accordingly!
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 17
Version 1.5 / Date: 06. March 2014
System Handbook
Part number Total Ext. agent volume Dip tube type Dip tube
press. vessel volume length
FEC004-MS-6LT-JA 7.14 litres 6 litres FEC701-PS-6LT-JA 411,5mm
FEC004-MS-9LT-JA 10.86 litres 9 litres FEC701-PS-9LT-JA 446,5mm
FEC004-MS-6LT-KS 7.1 litres 6 litres FEC701-PS-6LT-KS 414mm
FEC004-MS-9LT-KS 11.4 litres 9 litres FEC701-PS-9LT-KS 503mm
During triggering no debris may enter the extinguisher lines and the nozzles.
Cleanliness is of utmost importance, because otherwise nozzles may be
blocked and fail. The dip tube strainer alone does not absolutely prevent soiling,
but will reduce the risk.
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 18
Version 1.5 / Date: 06. March 2014
System Handbook
Compensation bore
Fig. 11 – Compensation bore
2.4.1.3. Leakage
Leakage is any unintended loss of gas or liquid in a technical system and can result in a failure of
the entire technical system. Tightness, in a technical sense, means “no leakage according to the
technical application”, so tightness is a relative term. Because there can be diffusion of gases
through various materials there is no such thing as absolute tightness of components. Requiring
tightness therefore always depends on the respective specified conditions. The tightness of an
entire system depends on the material properties as well as the quality of the construction (sealing
quality, tolerances, temperatures, pressures, gases, etc.).
The Kitchen Shield kitchen extinguishing system has been dimensioned and developed so that the
gas leakages during the service intervals will not result in system failures. This is achieved by a
100% functional and tightness test of the valve components. However, errors in handling and
operation as well as a faulty installation may result in undesired leakages.
In order to ensure a long-term functionality regular visual inspections before commencing work are
indispensable; electronic monitoring of the operational state (contact pressure gauges etc.) can
increase the system safety.
This is the volume of the pressure gas inside the pressure vessel above the extinguishing
agent.
L= Sensor tube
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 19
Version 1.5 / Date: 06. March 2014
System Handbook
In case of excessive leakage the pressure gas buffer will shrink and the extinguishing effect
will be reduced because there will not be sufficient extinguishing pressure. To prevent this,
regular servicing is essential. In addition, we recommend installing electronic pressure guards
(contact gauges) to monitor the pressure levels and to sound an alert signal in case of a drop
of pressure below a minimum.
2.4.1.5. Permeation
Permeation is the technical term describing gas diffusion through plastics and seals (in
general it occurs in all materials). This permeation will result in a long term leakage of gas.
This leakage depends on parameters such as operating temperature and choice of materials.
The components of the Kitchen Shield product range have all been optimized in the respect of
the gas losses, albeit 100% gas tightness is technically impossible.
Discharge line
Trigger
ILP valve
Sensor tube
Pressure and
agent cylinder
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 20
Version 1.5 / Date: 06. March 2014
System Handbook
Each extinguishing agent cylinder requires a cylinder valve. If in a system there is more
than one valve the valves must be connected so that they can be triggered
simultaneously. See the respective information in chapter 3: Installation. In any system,
always the same valves (variants/types) must be used!
Using the kitchen is strictly prohibited if and as long as the extinguishing system has
been shut down or is out of service for any reason!
For this purpose suitable electronic monitors for the position of the ball valve, of the
gas volume and the system activation are available which will shut down the kitchen in
case of an extinguishing system failure.
If during servicing the ball valve is shut down, it must be ensured that the valve will be
reopened later. Otherwise the extinguishing system is out of service and not available
in the case of a fire. By employing of the electronic lever position monitoring this risk
can be excluded. If the valve is closed the fault alert signal is given out.
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 21
Version 1.5 / Date: 06. March 2014
System Handbook
It combines the perfect extinguishing properties of a foam agent with an optimized biological
tolerance. It is biodegradable to more than 99% and is therefore not classified as hazardous
waste. In addition, after having been expelled the residues can be used as a cleaning agent,
because it has excellent cleaning and degreasing properties.
The specified extinguishing agent volumes listed in the table above must be
observed under all conditions in order to ensure the proper extinguishing effect
of the system. The water-concentrate ratio is 10:1 (10% of agent concentrate).
For instruction on mixing and filling the extinguishing agent consult chapter
“Installation”. The water to be used is of drinking water quality!
Due to the limited shelf life of the extinguishing agent it must be replaced
according to the instructions in the service instructions! (See chapter 4.2.,
“Service intervals”).
At temperatures below 0°C the extinguishing agent may freeze!
2.4.4. Kitchen Shield Sensor tube for automatic fire detection (SPS-KS001-100-BK)
In Kitchen Shield kitchen fire extinguishing system the standard fire detection device is the
Kitchen Shield sensor tube (SPS-KS001-100-BK). A customized marking of this tube is
possible. Kitchen Shield sensor tubes consist of high-tech plastic and were developed
especially for the installation and application in automatic fire extinguishing systems.
The prescribed operating pressure is applied to the sensor tube after the proper installation.
Due to thermal material properties and the inner over-pressure the sensor tube will burst when
touched by a flame or subjected to an excessive heat increase, and so it functions as a
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 22
Version 1.5 / Date: 06. March 2014
System Handbook
When using gas kitchen appliances it must be ensured that the hot exhaust
gases and flames cannot reach the sensor tube, as otherwise there is the risk of
false alarms due to the high temperatures. Therefore please fit gas burners with
a cover or consult Steel Recon Industries and/or test the proper function in
advance.
The maximum length according to the description of the system limits included
in chapters 2.1 and 2.2 may not be exceeded. If, for example, the installation of a
manual trigger would require an extension of the sensor hose an additional
electromagnetic trigger must be used and a manual electrical actuation needs to
be implemented.
For further information on the sensor tube as well as the resistance tables and temperature graphs
consult the operating instructions FiWaGuard Sensor tube – Accessories (SPS-KS001-100-BK).
Specifications
Permeability: 10-4 mbar l / sec (Helium)
Dimensions: Ø6 x 1mm (inner Ø - 4mm)
Recommended bending radius: 150mm (min. 100mm)
Part number: SPS-KS001-100-BK
Marking
Only when using Kitchen Shield multi-layer tube a rapid and efficient fire detection
without the risk of false alarms is possible. Additionally the respective installation and
operating instructions must be observed. For further information (e.g. medium
resistance) please consult the respective operating instructions to the Kitchen Shield
sensor tube. Because of the aggressive kitchen environment (temperatures, steam,
detergents …) the sensor tube must be replaced in intervals according to chapter 4.2
(Service intervals).
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 23
Version 1.5 / Date: 06. March 2014
System Handbook
Fig. 16 - Multiblock
To actuate the manual trigger pull the safety pin and press the red strike knob!
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 24
Version 1.5 / Date: 06. March 2014
System Handbook
The electromagnetic trigger should not be operated in connection with smoke, fire or
similar alarm devices.
For further information and instructions to the triggers please consult the respective operating
instructions to the Kitchen Shield Sensor tube – Accessories!
Monitoring options for leakages and the lever settings and positions indicate the
functionality and operational state of the system and reduce the risk of system
malfunction. Optical and acoustic signals may also be used to alert problems
and call for an inspection by authorized personnel!
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 25
Version 1.5 / Date: 06. March 2014
System Handbook
This is used to switch off the equipment when the extinguishing system is actuated. The
signals can be used to cut the energy supply and, for example, switch off the extractor fan.
The heat source can be stopped, as well as the extraction, but this is, however, not
compulsory. A ventilation left running can move any smoke or exhaust gases to the
outside. The decision on this option is with the system designer when implementing
customer requirements.
If the system functionality needs to be ensured on a long-term basis monitoring any leakage is
indispensable. If due to leakage the system pressure drops below a critical minimum (<11bar)
an early warning signal is issued through a contact pressure gauge.
If during servicing the ball valve is shut down, it must be ensured that the valve will be
reopened later. Otherwise the extinguishing system remains deactivated and will not
function in case of a fire.
By electronically monitoring of the lever position this risk can be minimized. If the valve
is shut a fault signal is issued.
For other specifications and operating instructions refer to the operating instructions Kitchen
Shield ILP valve (SPS-KS002-402).
For switching capacities, installation notes and further information please refer to respective operating
instructions for the Kitchen Shield Leakage and pressure monitoring.
The components listed above can also be installed and used in conjunction to provide an optimized
system monitoring.
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 26
Version 1.5 / Date: 06. March 2014
System Handbook
It is essential to observe the specified number of nozzles and their arrangement and
alignment, according to chapter 3 “Installation”. Also important is the correct selection
of nozzle variants and the correct location in the extinguishing system!
The nozzles are protected against the intrusion of dirt and grease by protection caps.
However, the nozzles must be kept absolutely clear of dirt and obstructions during
installation. When the system is activated, the protection caps are blown off and must
not dangle in the extinguishing agent spray! The nozzles must be selected according to
the local circumstances (hood length) and aligned accordingly (see installation
instructions, chapter 3).
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 27
Version 1.5 / Date: 06. March 2014
System Handbook
Pipes, tubing and fittings must comply with the specifications listed above and must
only be installed in an undamaged and clean state and deburred!
Any processing (bending, cutting) must only be performed using suitable tools (pipe
bending tool with a radius of min. 20mm and pipe cutters)!
Keeping within system limits listed in chapters 2.1 and 2.2 is compulsory.
Only if these specifications are complied with and the components listed there
are used can a proper and safe function of the system be ensured.
2.5. Accessories
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 28
Version 1.5 / Date: 06. March 2014
System Handbook
The FiWaGuard Mini DHP is used to provide pressurized gas during installation and servicing,
because the sensor tube must be filled before opening the ILP valve from the end-of-line or
through suitable connections. In addition the pressurization of the extinguishing agent vessel
and the leakage test of the extinguishing line can be checked with this valve. Filling the
pressure gas cartridge is described in the respective operating instructions.
The Mini DHP is essential for a safe and functional filling of the tube, and it is
used to check the extinguishing line for leaks. Using other than the specified
suitable means can result in malfunctions and other dangers. Please always
observe the instructions in the operating manual of the Mini DHP valve!
Only if these specifications are complied with and the listed components are
used the system can function safely.
Discharge line
Actuator
ILP valve
Sensor tube
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 29
Version 1.5 / Date: 06. March 2014
System Handbook
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 30
Version 1.5 / Date: 06. March 2014
System Handbook
It is especially important that there is no dirt added to the mixture, because this
may cause the nozzles to fail.
It is also important to mix the concentrate into the water in the correct ratio (10%
concentrate in 90% water). Use only water of drinking water quality.
The volumes of the extinguishing agents per vessel must be filled precisely,
because this will ensure a functioning ratio of extinguishing agent to pressure
gas volume. When filling the vessel ensure that no dirt is introduced into the
vessel or the extinguishing agent!
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 31
Version 1.5 / Date: 06. March 2014
System Handbook
The assembly is done by screwing the dip tube into the dip tube connection of the ILP valve all
the way to the stop with a torque of 5Nm. Gluing is not necessary. Mounting the strainer at the
bottom end will strain dirt and pollutants and thereby protect the nozzles against blocking. This
strainer is a standard accessory mounted on the respective Kitchen Shield dip tubes.
For filling instructions please refer to the operating instructions to the ILP valve in
chapter 11 (Filling vessels with Kitchen Shield ILP valves).
The pressure gas bottle must be filled through the tube connection on top of the
ILP valve. For this purpose the Mini DHP (F161) can be used.
For filling the pressurized gas cartridge on the Mini DHP refer to the operating
instruction for the Mini DHP.
The visual inspections using soap water and the pressure drop test are very
imprecise and will only detect larger leakages. Therefore, a regular pressure
check after installation and commissioning is indispensable (in this case
electronic monitoring of the pressure drop using a contact gauge is suitable).
Any detected leakages must be immediately rectified!
All residues of the leakage test substances must be rinsed off completely with
clear water to prevent any corrosion. As a rule no aggressive substances may
be used.
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 32
Version 1.5 / Date: 06. March 2014
System Handbook
Use only suitable mounting means or brackets for the pressurized gas vessel
and keep the vessel in the correct position!
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 33
Version 1.5 / Date: 06. March 2014
System Handbook
tube brackets
300 300
In kitchens with gas appliances it is important to ensure hot exhaust gases and
flames cannot reach the sensor tube directly, otherwise there is the risk of false
alarms through increased temperatures. Use shields over gas burners and, if
necessary, consult Steel Recon Industries Sdn. Bhd. and/or test the
functionality in advance.
For joining sensor tubes use only SRI tube fittings, which are tested and
approved for the special application regarding their function, leakage and
operation. If there is no actuator mounted on the end of the sensor line (manual
or electromagnetic trigger), the end must be terminated with an End-of-line
adapter or plug.
The maximum specified sensor tube length may not be exceeded. Unnecessary
use of fittings increases the leakage risk. For information on handling the
sensor tube refer to operation instruction manual of the sensor tube.
As a rule use only tube fittings and components from the Kitchen Shield
product range, see the respective product list in the operating instructions
Kitchen Shield Sensor tube – Accessories (F102).
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 34
Version 1.5 / Date: 06. March 2014
System Handbook
Attention:
The reaction time increases with the distance between the fire source and the sensor tube.
If the sensor tube is covered by other components the reaction time is increased again or it
will react only when the fire has spread much further.
Gas flames from cookers and their exhaust gases may not come into direct contact
with the sensor tube. Gas flames must be covered to affect the tube only indirectly, if
necessary check the installation before commissioning.
The same applies if the tube is routing near heat sources.
The tube should be routed so that it cannot be damaged during the use of the kitchen
(filter replacement, cleaning, etc.).
Observe the mounting instructions to prevent a random movement of the tube ends after a
burst.
Do not lay the tube over sharp edges (use bulkhead fittings or rubber bushings), avoid
buckling and kinks.
To ensure an improved burst behaviour the sensor tube should not be mounted flush on
surfaces, use suitable mounting fixtures.
Use only Kitchen Shield tube fittings (see operating instructions of sensor tube).
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 35
Version 1.5 / Date: 06. March 2014
System Handbook
The tube should be fitted below the extractor plenum, around the filter panels. The bend radius
must not be less than 100mm, because otherwise the tube may kink or buckle (see below)!
The sensor tube should be layed as closely as possible to the filter panels
without obstructing these when they are replaced (e.g. for cleaning purposes).
The distance to the danger zone should be as small as possible, to ensure a rapid
detection (especially if the extractors are mounted very high). Do not mount the
hose directly and flush against the panels as this can influence the bursting
behaviour (Dimension R, see below).
Tubing should be installed across the filter panel rows. To ensure a best possible detection the
sensor tube should be routed approx. 100-200mm above and diagonally across the panels
(Dimension L) (see below).
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 36
Version 1.5 / Date: 06. March 2014
System Handbook
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 37
Version 1.5 / Date: 06. March 2014
System Handbook
T fitting (SPS-KS008-TFT-XX)
Keep within the system lengths for the extinguishing line specified in chapter
2.2 (system lengths for the extinguishing pipe system). The specifications for
the pipes and fittings are listed in chapter 2.4.11 (pipes and fittings) and must be
complied with. Workmanship must be clean and tidy and no soiling of the pipes
and tubes is permissible.
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 38
Version 1.5 / Date: 06. March 2014
System Handbook
The extinguishing line must be routed inside the extractor plenum, according to the sketches
and explanations in sections 3.5.4 (Nozzle positioning / alignment) and 3.5.2 (Extinguishing
line laying scheme).
The extinguishing line must be mounted so that the system limits regarding the
nozzle spacing and the distance to the surface to be protected are not exceeded
(chapters 2.1 and 2.2). In some cases nozzle extension may be necessary (3.5.5).
Before installing the pipe sections, ensure that these are clean and without
chips or burrs. Any soiling may block the nozzles and render them
dysfunctional. Use only tubes and pipes according to the specifications and
keep within the maximum lengths!
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 39
Version 1.5 / Date: 06. March 2014
System Handbook
The system variant F8082000 has a special feature in that both vessel valves are connected to a
single extinguisher line, with the two exit feed lines joined by a T fitting.
The lengths of the individual exit feed lines may not be longer than 300mm (stretched out), and both
branches must be symmetrical, i.e. the length from the T fitting and the position including bends and
angles as well as fittings must be identical.
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 40
Version 1.5 / Date: 06. March 2014
System Handbook
In the largest system variant with 2 x 9 litres of extinguishing agent each ILP valve must be connected
to a separate extinguisher line, the number of nozzles (six in all) is distributed over two lines (2 x 3
nozzles).
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 41
Version 1.5 / Date: 06. March 2014
System Handbook
Please follow the fitting manufacturer instructions regarding the torque and
assembly procedures.
Use only fittings meeting the specifications and do not exceed maximum
number!
It is compulsory not to exceed the system limits as specified in chapters 2.1 and
2.2, including height of the nozzles above the surface to be protected (900 –
1350mm).
Because inside the extractor plenum dirt and grease can accumulate (in the filters and
above) it is indispensable to cover the area above the filter panels (see figure).
In order to protect the duct from flames a single nozzle is placed in the centre of the duct
cross-section, just above the top edge of the hood (see figure).
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 42
Version 1.5 / Date: 06. March 2014
System Handbook
The fryer protection nozzles are mounted inside and beneath the front of the extractor
hood and pointed slightly to the rear of the worktop. This will prevent the flames from
striking outwards when the extinguisher is triggered. The nozzles are pointed directly to
the centre of the oil surface (see figure).
Dimension Description Value
D1 Depth ½ x total fryer basin depth
D2 Distance nozzle fryer centre max. 600mm
E1 Width ½ x total fryer basin width
O Alignment angle resulting from A and D2
Depends on the arrangement of the kitchen
H Nozzle spacing equipment*
A Distance nozzle surface 900 – 1350mm
*an overlapping of the spray cones is only possible within a distance (H) of maximum 700mm!
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 43
Version 1.5 / Date: 06. March 2014
System Handbook
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 44
Version 1.5 / Date: 06. March 2014
System Handbook
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 45
Version 1.5 / Date: 06. March 2014
System Handbook
The laser pointer is fitted into a G1/4” adapter and can be screwed onto the nozzle
fitting (chapter 3.5.5). Tighten the pointer in the fitting by hand, it must not be loose.
Order the tool with the part number F0060019.
Procedure
1) Switch on the laser pointer (red button inside the fitting thread). Do not look
into the laser beam!
2) Screw on the laser pointer (hand-tight, check for tightness).
The laser will now point the direction of the spray axis.
3) Align all nozzles according to the specifications in chapter 3.5.4
Battery replacement
1) Carefully unscrew the laser lens counter-clockwise
- see part 1 in sketch
2) Replace batteries
- check for correct polarity
- use only battery type LR44 (2 pc.)
3) Replace lens by screwing on clockwise
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 46
Version 1.5 / Date: 06. March 2014
System Handbook
Ensure that all adapters and fittings meet the specifications listed in chapter
2.4.11. Mounting shall be in accordance to the fitting manufacturer instructions.
The mounting torque and dimensions according to the drawings must be
observed for a correct function of the nozzles. Use only a flat seal because
residues from sealing tape and glue may obstruct or block the nozzle.
Nozzle extensions
In the circumstances where the
distance of the nozzle to the
surface to be protected is too
high, e.g. if the extractor hood is
mounted too high, the nozzle can
be extended by means of a tube
section Ø10x1mm (same as the
extinguishing line) by up to
150mm.
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 47
Version 1.5 / Date: 06. March 2014
System Handbook
Protection cap
Nozzles are fitted with a protection cap to prevent the intrusion of dirt and grease and the
blocking of the nozzles.
The cap is designed so that it will be blown off at the slightest pressure. A safety rope made of
stainless steel will prevent the cap from falling into the hot oil which would result in oil
splashes.
The safety rope must be fastened in a manner that the blowing off of the cap is not
prevented. It must also be ensured that the cap does not dangle in the
extinguishing spray after blowing off. The cap must always be in place to ensure
the protection effect.
3.5.6. Leakage test of the extinguisher line (checking the pipe fittings)
Replacing nozzles
After installing the extinguisher line and mounting the nozzles the tightness of the system must
be checked. For this purpose the nozzles are dismantled. One of the nozzle fittings is
connected to a pressure gauge plug (F0060017) and all others with a blind plug (F0060016).
The mounting torque is the same as for the nozzles.
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 48
Version 1.5 / Date: 06. March 2014
System Handbook
No leakage detected!
Remove the pressure gauge from the line and vent the system. Remove the adapter with the
hose fitting for the Mini DHP and replace all plugs on the nozzle fittings with the extinguisher
nozzles. (Take care not to change the nozzle positions and alignments!)
The system may not be started without a prior leakage test, because this test
also serves to check the fittings and connections (for tightness and mounting).
Leakages in the system can prevent a successful extinguishing.
Read the second pressure value only after at least 30 minutes after taking the
first reading. The Mini DHP must be closed before taking the readings as it
could otherwise compensate any leakages.
All pipes must be fitted with mounts every 500mm, and the distance between the mount and
the last nozzle must be no more than 100mm (the last nozzle may not dangle unsupported).
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 49
Version 1.5 / Date: 06. March 2014
System Handbook
Dimension Description
P Spacing of mounts max. 500mm
Q Distance to the last nozzle max. 100mm
The installation engineer is responsible for installing the correct and purposeful
mounting elements according to the instructions and specifications in this
handbook. Please consult the pipe and mountings as well as fittings
manufacturers for additional information on the mounting elements.
The manual triggers must be located in a position easy to reach (in an emergency), and the
person actuating the trigger must not be endangered (in the case of fire), e.g. by flaring up of
flames when extinguishing commences. It is recommended to place the triggers near the
emergency exits, but please observe the maximum system limits, because the actuator is
mounted at the end or in the sensor line).
Unsuitable location
A mounting near the extinguishing agent vessel is recommended, outside and beyond the
worktop and units to be protected (points X)
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 50
Version 1.5 / Date: 06. March 2014
System Handbook
When mounting the actuator near the worktop it can be mounted on the
extractor hood if this is in a suitable height. As a rule it should be located where
in case of actuation there can be no contact with flames, even when the
extinguishing process starts, which may cause flaring up and out of flames. In
addition, the manual triggers must never be covered or obstructed, and remain
in full visibility.
If a safe mounting is not possible due to the local circumstances, an electronic actuator should
be installed. This can be placed at a greater distance to the kitchen (triggering from outside
the danger zone) and in several locations, without increasing the risk of leakages (see
chapters 2.4.8 and 3.7.1).
For further details on the connection of the extinguishing line please check the operating
instructions of the ILP valve.
3.6. Start-up
Due to the construction design a separate pressurization from the line end is
necessary. Before that the ILP valve may not be opened!
Please refer to the ILP valve operating instructions for details on the pressurization, in chapter
14 (Pressurization of the Kitchen Shield Sensor tube at the Kitchen Shield End-of-Line).
The pressurization is also possible through the respective connections at the actuators and at
the adapter for the signal generator (see the operating instructions Kitchen Shield Sensor tube
and accessories, where you will also find details for the handling of tube fittings, filling
adapters and tools).
The sensor tube must be pressurized with an operational pressure of 15bar (+/-0.25) at 15°C,
in order to ensure a faultless system function! Use only pure nitrogen as pressure gas!
For pressurization use only the FiWaGuard Mini DHP valve (F161).
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 51
Version 1.5 / Date: 06. March 2014
System Handbook
Signal generator
o Section 3. (Kitchen Shield signal generator)
Contact gauge (with one or two switching points)
o Section 7. (Contact gauge)
Installation notes:
The contact gauge with one switch contact (SPS-KS006-51-NO or SPS-KS006-51-
NC) is used only for monitoring the operation pressure on the pressurized gas vessel
and is therefore mounted on the gauge connection of the ILP valve (in replacement of
the analogue gauge)
For details on the position monitoring of the ball valve on the ILP please refer to the instruction
manual Kitchen Shield ILP section 18. (Technical data of the electrical monitoring).
Monitoring for leakage using the contact pressure gauge is only possible when
the vessel valves are open and there is contact between the pressure vessel and
the sensor tube.
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 52
Version 1.5 / Date: 06. March 2014
System Handbook
After completion of the installation the following points should be checked again:
Have the nozzles been aligned correctly and are there any obstructions to the spray?
If after an objective inspection no fault or error is visible and if the inspection record according to
section 4.3 (Service records) has been filled in, the system can be approved for kitchen use.
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 53
Version 1.5 / Date: 06. March 2014
System Handbook
After all cleaning work check whether the entire system is depressurized. Do
not remove any components before checking this point!
Should there still be pressure in the system it must be shut down completely.
Proceed according to section 13 (Start-up / shut-down of the extinguishing system) and
section 15 (Dismantling the Kitchen Shield Sensor tube) in the instruction manual of the ILP!
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 54
Version 1.5 / Date: 06. March 2014
System Handbook
Do not use aggressive substances for cleaning as these could damage the
materials! All components must be cleaned of extinguishing agent, grease and
dirt residues and then be rinsed with water. After drying they can be reinstalled.
The pressure vessel must be replaced and disposed of after max. 8 years!
The heavily diluted extinguishing agent can be disposed of in the waste water
system, but check the regional and national waste management regulations,
because especially oil and grease residues should not enter the water or nature.
4.1.6. Re-commission
Re-commission the system by following the instructions in chapter 3 (Installation).
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 55
Version 1.5 / Date: 06. March 2014
System Handbook
Any problems identified during servicing or maintenance work, during operation or in any
other event are to be recorded and communicated to the company Steel Recon Industries
Sdn. Bhd. Upon receipt of the records we will deal with the problem and provide solutions,
either by adapting the documentation or changing individual system components.
In order to ensure the long-term functionality of the system the operational state of the
extinguishing system must be inspected once per year by qualified service personnel, see
section 4.2.2 (Inspection of operational states). This inspection must also be performed on
a daily basis before commencing daily use by the operator of the system (in case there is
no electronic system monitoring installed).
First of all, the pressure gas volume must be checked, and if necessary be replenished
with nitrogen to 15bar (+/-0.25).
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 56
Version 1.5 / Date: 06. March 2014
System Handbook
Use only the Mini DHP (F161) or a similar device with a filling pressure of
15bar (nitrogen). In addition, components such as the sensor tube, nozzles,
nozzle caps, mounting elements must be checked for wear and tear, aging
and other damages, and if necessary be replaced.
Every two years the wear and tear parts must be replaced as a matter of routine. This
includes the sensor tube and the mounting elements made of plastic and of course, other
defective components!
Also, replace the extinguishing agent and re-pressurize the system!
Before dismantling the sensor tube and replacing the extinguishing agent the
entire system must be shut down!
Please proceed as described in the operating instructions of ILP valve section
13 (Start-up / shut down of the extinguishing system) and section 15
(Dismantling the Kitchen Shield Sensor tube)!
During the general maintenance and in addition to the normal servicing work the
extinguishing agent is replaced, including the dip tube and its strainer. The entire
depressurized system is to be checked for damage and wear and tear; affected
components must be replaced!
First of all, the entire system must be shut down, to depressurize the
components. Please proceed as described in the operating instructions of ILP
valve section 13 (Start-up / shut down of the extinguishing system) and section
15 (Dismantling the Kitchen Shield Sensor tube)!
The procedure for replacing the extinguishing agent includes the disposal of the old agent
and rinsing the pressure vessel.
After no more than eight years the pressure vessel and the valves must be
replaced!
The new installation of the components and mixing of the extinguishing agent are
described in 3 (Installation).
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 57
Version 1.5 / Date: 06. March 2014
System Handbook
The operational system pressure and also the pressure gas volume can be checked by
the pressure gauge. Target pressure: 15bar (+/-0.25)
Depending on the system design there are standard pressure gauges available for system
pressure monitoring. These are located at the end-of-line adapter, on the various
actuators and also on the ILP valve (if no contact gauge is installed). The pressure should
be checked with a suitable pressure sensor or more precise pressure gauge with switch
contacts.
If contact gauges with switch contacts are fitted the operation pressure can be easily
checked, the precision of these instruments is sufficient.
If the pressure is too low follow the instructions in section 4.2.1.2 to remedy the situation.
Check the protection caps to verify their proper position and for damage. They should not
be soiled or sticky.
Unscrew the extinguishing nozzles and inspect for soiling or damage, if necessary clean
or replace them.
The surface of the hose may not have any cracks, dents or other damage, such as kinks
or constrictions, these must be remedied immediately.
The tube should be fitted properly in the risk zone and not be covered up, as described in
section 3.4 (Installation of the sensor tube).
The mounting and fastening elements for the sensor tube, pipes and pressure vessels
may not be damaged or bent. There must be no slack, all elements must be securely
mounted and fixed.
Retighten the connectors and check for tightness, see chapter 3.5 (Laying the
extinguishing line / nozzle alignment).
The nozzle alignment must match the details in section 3.5 (Installation of the
extinguishing discharge line / nozzle alignment) or must be adjusted.
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 58
Version 1.5 / Date: 06. March 2014
System Handbook
When replacing components proceed as for a new installation, see section 3 (Installation).
4.2.5. Re-commissioning
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 59
Version 1.5 / Date: 06. March 2014
System Handbook
For a new installation and any maintenance and service work records must be kept, containing the
following details:
Other features
Replaced components
Other features
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 60
Version 1.5 / Date: 06. March 2014
System Handbook
Replaced components
Other features
Replaced components
Other features
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 61
Version 1.5 / Date: 06. March 2014
System Handbook
Replaced components
Other features
These records must be retained by the installation company for auditing purposes and submitted to
the manufacturer Steel Recon Industries Sdn. Bhd. on request.
In addition, reports on any problems or issues encountered must be kept, with the following details:
Problems
o False alarms
o Assembly, installation problems
o Maintenance, service problems
o Insufficient product training
o Customer complaints
o Criticism, improvement suggestions
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 62
Version 1.5 / Date: 06. March 2014
System Handbook
The extinguishing system is installed to minimize the hazards in case of a fire. The objective is to fight
the fire right from the start, to prevent the spreading of a fire and to extinguish it.
This is only possible with a fully functional system, for which a correct and diligent installation, regular
servicing and maintenance and of course an activation of the system are essential!
Kitchen equipment may only be operated with a properly installed and operational
extinguishing system! For this, electronic monitoring of the settings of the ball
valve, the pressure gas volume and the system actuation is available so that the
affected kitchen equipment can be switched off if the system should fail. See
section 2.4.9. (Electronic system monitoring).
Open ball valves (shut-off valves to the sensor tube) only if the vessel has been properly fastened, the
Kitchen Shield sensor tube has been connected with the ILP, the extinguishing line has been
connected and the Kitchen Shield sensor tube has been correctly pressurized! Any unintentional
actuation of the ball valves will actuate the system with the risk of injuries!
Before any starting or repairs on a fire extinguishing system the material, pressure and temperature
must be checked against the details in these operating instructions.
Never assume that the pressure vessel is empty. Always treat it as if it were charged and
pressurized.
Local laws and regulations have to be followed, especially with regard to pressure equipment
directives
The operator, and not the manufacturer Steel Recon Industries Sdn. Bhd., is responsible for
the layout and dimensioning of the fire extinguishing system, as well as the suitability of the
fire protection application.
The delivery state of the components complies with the drawings and design at
the time of production. Any changes on any components, will render the
component and system approval null and void.
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 63
Version 1.5 / Date: 06. March 2014
System Handbook
15.5
15.0
14.5
14.0
13.5
13.0
12.5
12.0
0 5 10 15 20 25 30 35 40 45 50 55 60 65
Temperature [°C]
This pressure temperature characteristic curve shows the pressure in the operating temperature range
of the system. A drop in pressure does not necessarily indicate a leakage. Please use this graph to
assess the functionality of the system.
In order to optimize the efficiency of the extinguishing system the heat source
in the kitchen (electricity or gas) must be switched off in case of a fire! For this
use the electronic system monitors available, section 2.4.9 (Electronic system
monitoring). Only this switching off function will ensure the system
functionality, because without switching off the heat source, re-ignition may
occur directly after the oil temperature rises above the self-ignition point again.
The extinguisher nozzles must not be covered, and the spray must be
unobstructed!
The sensor tube must be installed and connected as specified in the section on
the installation, as otherwise the automatic triggering will not operate.
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 64
Version 1.5 / Date: 06. March 2014
System Handbook
2) Composition / components
No specific hazards are known. The product must nevertheless be treated with the same care as other chemicals. When
extinguishing a fire note that inside the foam breathing is not possible.
5) Firefighting measures
Safe handling: Store and handle with the same care as other chemicals. Keep container tightly closed
Fire and explosion protection: No special measures
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 65
Version 1.5 / Date: 06. March 2014
System Handbook
Form: liquid
Colour: brownish
Odour: typical
Melting point: N/A
Boiling point: > 100°C
Ignition point: > 100°C
Density at 20°C: 1.02 g/ml
Water solubility: unlimited in water
pH-Value (g/litre water °C): approx. 7.5
No special characteristics
11) Toxicology
When product is handled with due diligence and care there are no harmful effects known to us.
12) Ecology
When product is handled with due diligence and used for the intended purpose there are no harmful effects known to us.
Biodegradability: easily biodegradable. The surfactants used meet the criteria for a complete aerobic biodegradability in Annex
III, Part A of the Detergents Directive (VO (EC) No. 648/2004 and may therefore be distributed without further restrictions.
Documents certifying this are available only for the responsible authorities in the Member States and will be supplied on a direct
request by a detergent manufacturer.
13) Disposal
14) Transport
16) Miscellaneous
The details in this information sheet correspond with our best knowledge at the time of printing, they are in no way a guarantee
for certain properties and do not constitute a contractual legal relation.
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 66
Version 1.5 / Date: 06. March 2014
System Handbook
For a safe system layout and installation a comprehensive knowledge of the extinguishing system and
its functions is indispensable. Therefore the company Steel Recon Industries Sdn. Bhd. provides a
special product training without which an installation in compliance with the approval is not possible.
The planning and design personnel as well as the installation engineers must undergo special training
for their future tasks. Refresher courses are required at regular intervals (at least every five years).
The General Terms and Conditions of Steel Recon Industries Sdn. Bhd. are available on the web at
www.sri.com.my. On request we will be pleased to mail them to you.
6.3. Contact
No 8, Jalan Subang 7,
Taman Perindustrian Subang,
47610 Subang Jaya,
Selangor Darul Ehsan,
Malaysia.
mailto:spd@sri.com.my
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 67
Version 1.5 / Date: 06. March 2014
System Handbook
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 68
Version 1.5 / Date: 06. March 2014
System Handbook
Standard LPS1223
Issue 2.2
Cert. No. XXXX
and with the additional optional notice “Kitchen extinguishing system approved as per LPS1223, Issue
2.2”.
The suitability, reliability and functionality of the fire extinguishing system “Kitchen Shield – Kitchen fire
suppression (F808)” was tested and approved in fire and extinguishing tests by the Loss Prevention
Certification Board (LPCB) of BRE Global Ltd. according to LPS1223. A copy of the certificate is
available from the system manufacturer Steel Recon Industries Sdn. Bhd. on request.
A Condition for the use of the marking is the listing as an approved manufacturer in the LPCB
Redbook of BRE Global Ltd. (http://www.redbooklive.com) and the authorization of Steel Recon
Industries Sdn. Bhd. For further information and requirements for the use of the “LPCB Certification
Mark” refer to the standards authority documentation in PN103 – Rules and Guidance for use of the
LPCB Certification Marks.
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 69
Version 1.5 / Date: 06. March 2014
System Handbook
In addition, the pressure vessel must be fitted with a visible system label:
Kitchen Shield
Kitchen fire suppression
9 Liter foam agent (10% Premix)
maximum fryer size: 45 Liter
In case
1 of fire:
(when system has not released automatically)
Only trained personnel are allowed to work on the system and its
components.
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 70
Version 1.5 / Date: 06. March 2014
System Handbook
We herewith declare that the pressure equipment described below have been subjected effectually to a
conformity assessment procedure according to: PED directive 97/23/EEG, category I, modules A and may
therefore bear the CE-marking.
Description: F808
Description:
Typ: Kitchen Shield kitchen fire suppression
Type
Artikelnummer: F8081000 / F8082000 / F8083000
Article number:
Datum
Date
Föhren, 15. Oct. 2014 03.09.2013
Steel Recon Industries Sdn. Bhd. – No 8, Jalan Subang 7, Taman Perindustrian Subang, 47610 Subang Jaya, Selangor Darul Ehsan, Malaysia. www.sri.com.my
Technical amendments reserved Page 71
Version 1.5 / Date: 06. March 2014