SY8330 Technical Specification for

Full automatic three phase energy meter test system (16positions)


The bench according with the standard of IEC 60736:1982, IEC 62053, and IEC 61036.

1. TEST FUNCTION (BOTH FOR MECHANICAL & ELECTRONIC ENERGY METERS):


a) Warm up
b) Basic error test
c) Standard deviation (S) in error test
d) Repeatable error test
e) Latent test (no load test)/automatic/manual operation with seek mark automatically
f) Initial test (starting test)/automatic/manual operation with seek mark automatically
g) Phase rotation test
h) Unbalance voltage test
i) Unbalance current test
j) Voltage influence test
k) Frequency influence test
l) Deviation test for 24 hours
*m) DC injection
*n) Demand error test
*o) Clock error test
*p) Auto calibrate internal clock by using GPS
*q) Harmonic test
*r) Burden test
*s) RS485 / RS232 / optical communication port test
*t) Neutral current function test
*u) Equipment ICT (insulations current transformer) for close link (I-P link) testing
*v) Equipment MOXA card for high communication speed
Note: “*” means optional function.

2. SPECIFICATION OF SOURCE:
a) 19” rack
b) Frequency Generator
c) Voltage amplifiers
d) Current amplifiers
e) Phase position adjuster
f) Harmonic injection unit

3. FREQUENCY GENERATOR:
a) Range from 45Hz to 65Hz in steps of 0.01Hz
b) Provision for superimposition of harmonics for the range of 2nd to 21st harmonics
2-21 sub-harmonic wave contents < 40%
3, 5, 7 sub-harmonic wave coupling, total content < 40%
Phase angle control (odd sub-harmonic wave)
Wave group control (sub-harmonic wave)

4. VOLTAGE AMPLIFIER:
a) Not less than 400VA
b) Electronic protection against O/L and Short Circuit
c) Efficiency better than 85%
d) Resolution of amplitude < 0.05% of the range limit value
e) Accuracy of amplitude < 0.05% of the range limit value
f) Stability < 0.05% / 8 hour at 50Hz
g) Provision for super position of harmonics in the range of 2nd to 21st harmonic
h) Test voltage range 0-300V (phase to neutral), 0-520V (phase to phase) with the range of
60V/120V/240V (480V is optional)
i) No load reaction
j) Malfunctioning be indicated by acoustic & optic signal
k) LCD backlit be provided for voltage display

5. CURRENT AMPLIFIER:
a) Not less than 1500VA
b) Electronic protection against O/L and Short Circuit
c) Efficiency better than 85%
d) Resolution of amplitude < 0.05% of the range limit value
e) Accuracy of amplitude < 0.05% of the range limit value
f) Stability < 0.05% / 8 hour at 50Hz
g) Provision for super position of harmonics in the range of 2 nd to 21st harmonic
h) Test current range 1mA to 120A with the range of 100, 50, 20, 10, 5, 2, 1, 0.5, 0.2, 0.1, 0.05
Amp, (200A is optional)
i) For the starting current test current range 1mA to 10mA shall be provided
j) No load reaction
k) Malfunctioning be indicated by acoustic & optic signal
l) LCD backlit be provided for current display

6. PHASE POSITION ADJUSTER:


Allow adjustment of output power factor from -1.00 to 1.00 in all 4 quadrants in computer
controlled steps of 0.010

7. HARMONIC INJECTION UNIT:


a) Over the range 2nd to 21st harmonic to the test voltage and test current
b) Magnitude of each harmonic shall be adjustable from 0-40% up to 5th harmonics and 0-10%
for the harmonic 5th of fundamental wave

8. TECHNICAL DATA OF REFERENCE STANDARD METER:


a) Measuring modes: three phase three wire, three phase four wire, one phase two wire active /
reactive mode
b) Frequency range: basic frequency 40-70Hz
c) Voltage range: 40V - 480V phase to neutral
d) Current range: 10mA to 120A (200A is optional)
e) Accuracy: voltage and current 0.05%, active power and energy 0.05%, reactive power and
energy 0.1%
f) Variations within 24h is superior 0.01%
Variations within one year is less then 0.02%

9. DISPLAY AT PC & REFERENCE STANDARD METER:


a) True RMS value of voltage & current input
b) Phase angle between voltage and current
c) Power factor
d) Active, reactive & Apparent power
e) Frequency

10. INSULATE CURRENT TRANSFORMER:


a) Current range: 0.01A… 120A. (200A is optional)
b) Maximum transmission power: Max. 50VA. (100VA at 200A )
c) Transformation ratio error: < 0.01%
d) Angular Error: < 0.3min
e) Active power error: < 0.10% (PF=0.5C~1~0.5L)

11. GPS CLOCK (OPTIONAL):


a) Accuracy: <100nS (Absolute), 40nS (1 Sigma)
b) Output: 1 pulse per second

12. BURDEN TESTING INSTRUMENT (OPTIONAL):


a) Voltage circuit burden test range: Input voltage 50V - 264V
Input current: 5mA - 600mA
Input power factor: 0.25L - 1.0 - 0.25C
b) Current circuit burden test range: Input voltage: 30mV - 3V
Input current: 1A - 120A
Input power factor: 0.25L - 1.0 - 0.25C
c) Function: Appearance power (VA), active power (Watt) for voltage circuit
Appearance power (VA), active power (Watt) for current circuit
d) Accuracy: class 3

13. SPECIFICATION FOR PC AND SOFTWARE:


a) User interface to operate the system
b) Supervision and control of the test procedure
c) Supervision and display of the test current and voltage
d) Indication of errors of the meters to test
e) Evaluation and report of the test results
f) Manual testing, semiautomatic and automatic testing facility
g) The same configuration but with different meter constants energy meter can be tested at one
time.
h) It shall have facility to interrupt the testing restart it again
i) Password facility for each main and sub-option
j) Selection facility of different curve
k) Print out facility with desired header
l) Easy to transfer data to excel files
m) In other language is available (easy to be translated into French, German, Spanish, Arabic,
Vietnamese, etc).
n) ………..

14. DIGITAL PROCESS UNIT:


a) 20 input for scanning head pulses
b) 1 input for reference impulses
c) 1 interface for connection with PC
d) Control output for Dosage Operation (Dial Test)
e) Error display per measuring position
f) Error display range: -99.999% - +99.999%

15. KEYBOARD:
a) Together with signal source
b) Shortcut key:
Current load key: Imax, 600%, 400%, 300%, 200%, 100%, 50%, 20%, 10%, 5%, 2%, 1%
Power factor key: 0.5L, 0.8L, 1.0, 0.8C, 0.5C
Creep test key
Starting test key
c) Number key: 0 - 9

16. SCANNING HEAD:


a) Photoelectric sampler can realize three-dimensional adjustment. It can sample the turntable
signal of rotary electric meters and the stroboscopic signal of electronic electric meters. The
photoelectric head also has the function of auto-turning
b) Total 20 sensors. 1 photoelectric scanning head for each position
c) Suitable for reading the marking from the disc of Ferraris wheel meters without opening the
cover of the meter
d) Suitable for reading the pulse output of electronic meters
e) Must be able to measure LED pulse output of frequency up to 200Hz

17. METER MOUNTING RACK:


a) Suitable design, good figure. The frame for meters and the body frame are fully made by
special aluminum alloy. The table board is composed of fireproofing and heat-proof fiber
materials. The whole device is in soft color and good figure.
b) High level of autoimmunization. When checking the electric meters, you only need hang the
meters manual and adjust the photoelectric sample and setup the parameters correctly, then
all of the checking items (including warm-up, dormant test, startup test, standard wide range
measurement, basic error measurement) will be controlled by PC automatically and fulfill at
once time. The checking program can be designed according to the national standard or
user-defined.
c) Consist of a frame for mounting of sensor heads, display devices and meters
d) Shall additionally have emergency stop switch

18. QUICK CONNECTOR:

a) Made by aluminum alloy, pins can be adjusted in 2 ways ( right-left, front-back)

b) Up to 120A by screws tightened

c) Up to 60A by spring touch

d) Concentric or excentric type quick connector