XPLE/SWA/PVC

Cable size 4c mm Max Load (KW) CB Capacity (A)


10 15 40
16 18 TO 36 60 TO 80
25 37 TO 52 100
35 53 TO 62 125
50 63 TO 80 160
70 81 TO 100 200
95 101 TO 128 225 TO 250
120 UP TO 130 250
150 131 TO 150 300
185 151 TO 175 350
240 176 TO 200 400
300 201 TO 250 500
2 X 150 251 TO 300 600
2 X 240 301 TO 400 800
2 X 300 401 TO 500 1000
3 X 240 501 TO 600 1200
4 X 240 601 TO 800 1600
4 X 300 801 TO 1000 2000

Main CB Ratin (A) MIN NO. of Earth Electodes MIN Size of Earth Electodes
60 TO 100 1 16
200 1 50
300 1 50
400 1 70
500 2 70
600 2 70
800 2 70
1000 2 70
1600 2 70
2000 2 150
2500 2 150

Main CB Rating (A) Room Dimension


1600 TO 2500 3.5 X 3.5
1000 TO 1200 3X3
600 TO 800 2.5 X2.5
400 TO 500 2 X 2.5
200 TO 300 2 X2

MCB Rating (A) Cable Size (mm) Applications


6 1.5 Light (Light Load)
10 2.5 Light (Heavy Load)
16 2.5 Radial (Sockets Outlet only)
20 4 Radial Appliance)
32 4 Ring socket
32 6 Radial (large appliance )
40 10 Radial (large Machinery )