Download as pdf or txt
Download as pdf or txt
You are on page 1of 14

DOMESTIC RANGE

NEWS: DOMESTIC FANS — 2019

■ BATHROOM EXTRACT FANS SOLUTIONS


A PANEL BAÑO CRISTAL MURO CRISTAL

Low noise level Low noise level Low noise level Low noise level Low noise level
Temporized Temporized Temporized Windows use Window and wall
DC Mate aluminum finishing Sensors included uses

■ IN-LINE DUCT FANS


T AW MINI TUB IN NOVO

Low noise level Low noise level Low noise level Low noise level
Temporized In-line Avialable with high pressure

■ ECONOMICAL KITCHEN SOLUTIONS


CHEF

Kitchen
Low noise level

We manufacture innovative solutions


INDUSTRIAL RANGE
NEWS: AXIAL FANS — 2019

■ AXIALS WALL FANS 50Hz 60Hz

AXIAL WINDER AXIAL AXIAL SOLID BASIC ROTEX

AXIAN WINDER AXIAN AXIAN SOLID AXIAN POWER AXIAL BOX

IN F300
F400

■ IN-LINE DUCT CYLINDRICAL CASED FANS 50Hz 60Hz

AXITUB WINDER AXITUB AXITUB SOLID AXITUB POWER AXITRANS

IN F300 IN F300
F400 F400

■ IN-LINE DUCT AXIAL BOX FANS 50Hz 60Hz

AXI BOX WINDER AXI BOX AXI BOX SOLID

IN F300 IN F300
F400 F400

■ ROOF MOUNTED FANS 50Hz 60Hz

AXITEJ WINDER AXITEJ AXITEJ BS


INDUSTRIAL RANGE
NEWS: AXIAL FANS — 2019

■ JET FANS 50Hz 60Hz

JET WINDER JET PIROS JET SOLID

IN F300 IN F300
F400 F400

■ PORTABLE UNIT 50Hz 60Hz

PORTATIL

We manufacture innovative solutions


INDUSTRIAL RANGE
NEWS: CENTRIFUGAL FANS — 2019

■ CENTRIFUGAL DIRECT DRIVEN FANS 50Hz 60Hz

BP CAL CAL PP

■ DIRECT DRIVEN CABINET FANS 50Hz 60Hz

BP BOX BP TWIN BOX LINE E BOX LINE Q BOX LINE Q I

IN

F400

■ IN-LINE DUCT FORWARD CURVED DIRECT DRIVEN FANS 50Hz 60Hz

MBC MBR MBK TUB

■ BELT DRIVEN ACUSTIC CABINET FANS 50Hz 60Hz

BPT BOX / S TWIN BPT BOX BPT BOX R BTP BOX COMPACT HT

OUT

F400

■ ROOF FORWARD CURVED DIRECT DRIVEN FANS 50Hz 60Hz

CRE CRE-V CF CF-S

OUT

F400
PRESSURIZATION
KIT
Staircases - Lobbies - Corridors
■ Definition
The purpose of a DIFFERENTIAL PRESSURE SYSTEM is the protection of people and firefighting teams. Therefore design of
the project must be done according to regulations and validated by the empowered authorities.
The standards that determine the conditions of fire protection for the evacuation areas (staircases, lobbies and corridors)
according to the typology of the building are the following:

BUILDING TYPOLOGY SPANISH REGULATIONS EUROPEAN STANDARD

Housing and tertiary CTE DB SI 3 Part 5


EN 12101-6:2006
Industry RSCIEI Annex II Part 6

■ General characteristics

KIT - AXI BOX VARIABLE FREQUENCY DRIVE


● Galvanized steel casing with insulated panel thermo acoustic inner class M1. ● Selectable V/F control.
● Thermoplastic impellers reinforced with fiberglass. Variable pitch according to ● Advanced PID Process Control.
MNS (Multiflow Novovent System) to improve performance. ● Simple PLC and multi-pass 16 speed control.
● Three-phase motors. Class F insulation. Degree of protection IP55 . ● Communication RS485 Modbus RTU.
● Automatic energy saving and kWh meter.
● Inputs: 4/5 digitals, 2 analog and 1 pulses.
● Outputs: 2 relay, 2 analog and 1 transistor.

KIT - AXI BOX WINDER DIFFERENTIAL PRESSURE SENSOR


● Galvanized steel casing with insulated panel thermo acoustic inner class M1. ● ABS housing IP 54.
Insulation sandwich 50 mm thickness, rock wool density of 70 kg/m3 . ● Working temperature: -10 ºC / +50 ºC
● Aluminum impellers with MNS (Multiflow Novovent System) and SNC (Serrated ● Admissible Environmental Humidity: 0 — 95%

Novovent Concept) improving performance and reducing sound.


● Three-phase motors. Class F insulation. Degree of protection IP55 .

KIT - BTP BOX EMERGENCY SWITCH


● Galvanized steel casing with insulated panel thermo acoustic inner class M1. ● Housing IP 65.
Insulation sandwich 20 mm thickness, rock wool density of 70 kg/m3 .
● Galvanized steel DWDI impeller. Belt driven.
● Three-phase motors. Class F insulation. Degree of protection IP55
PRESSURIZATION
KIT
Calculation example
CLASS D
■ CALCULATION EXAMPLE according to UNE EN 12101-6: 2006 criteria.*
HOTEL - GROUND FLOOR + 6 and 3 EVACUATION STAIRCASES

■ BUILDING DATA:

RESIDENTIAL OF PUBLIC
BUILDING USE SYSTEM CLASS CLASS D
USE

FLOORS PB+6 OPENED DOORS 2 (by staircase)

EVACUATION HEIGHT 18m


CLOSED DOORS 8 (by staircase)
EVACUATION TYPE DESCENDENT
AIR VELOCITY 0.75 m/s
STAIRCASES TYPE 3 PROTECTED

LOBBIES TYPE NOT PROTECTED PRESSURE DIFFERENCE 50 Pa

LIFT TYPE NO PROTECTED

■ PRESSURIZATION SYSTEM CLASS: CLASS D

“For means of escape. Sleeping risk”

CAPTION
1 Opened door
2 Closed door
3 Air release path

Airflow criterion Preassure difference- Preassure difference criterion


criterion (All closed doors)

■ STAIRCASES TIPOLOGY:

EP_I → Protected staircase I with non pressurized lobby EP_III → Protected staircase III without lobby

EP_II → Protected staircase II with non pressurized lobby

CAPTION CAPTION
1 Staircase 1 Staircase
2 Lobby 2 Lobby
3 Accommodation 3 Accommodation
4 Supply air 4 Supply air
5 Leakage path through doors 5 Leakage path through doors
6 Air release path from buil- 6 Air release path from buil-
ding ding
P Shows pressurized space P Shows pressurized space

*Example based on Spanish adaptation of European Standard EN 12101-6:2006.


■ CALCULATION EXAMPLE according to UNE EN 12101-6: 2006 criteria.*

■ METHOD 1 - AIRFLOW CRITERION

PROTECTED STAIRCASES EP_I, EP_II y EP_III

Staircases data: Pressurization system data:

STAIRCASE NAME DOOR NAME DOOR AREA [m2] SYSTEM CLASS CLASS D

P1A 3.2 OPENED DOORS 2 (by staircase)


EP_I
P2A 1.6
CROSS AIR VELOCITY 0.75 m/s
P1B 3.2
EP_II
P2B 1.6

P1C 1.6
EP_III
P2C 1.6

Equations: Where:

OPENED DOOR AIRFLOW → QPA i = V x SPA i x PA i


AIRFLOW BY STAIRCASE → QPA i Airflow for same area opened doors.
QTPA = Σ QPA i
SECURIZED AIRFLOW Q1 = QTPA x 1,15 V Cross air velocity.

SPA i Opened door area.

PA i Number of opened doors.


Calculation example for staircase EP_I:

→ QPA_P1A = 0.75 x 3.2 x 1 x 3600 = 8640 m3/h Requested airflow with opened doors.
QTPA
QPA_P2A = 0.75 x 1.6 x 1 x 3600 = 4320 m3/h

Q1 Total air supply rate including leakage from


air supply ducting (+15%).
→ QTPA/EP_I = 8640 + 4320 = 12960 m3/h

→ Q1/EP_I = 12960 x 1,15 = 14904 m3/h

Results:

STAIRCASE FLOW WITH OPENED DOOR [m3/h] QTPA [m3/h] Q1 [m3/h]

8640
EP_I 12960 14904 (*)
4320

8640
EP_II 12960 14904
4320

4320
EP_III 8640 9936
4320

(*) 15% included for ductwork


losses

*Example based on Spanish adaptation of European Standard EN 12101-6:2006.


■ CALCULATION EXAMPLE according to UNE EN 12101-6: 2006 criteria.*

■ METHOD 2 - PRESSURE DIFFERENCE CRITERION

PROTECTED STAIRCASES EP_I, EP_II y EP_III


Staircases data: Pressurization system data:

PRESSURE
LEAKAGE AREA SYSTEM CLASS CLASS D
DOOR TYPE DIFFERENTIAL
[m2]
[Pa]
Single-leaf opening inside aa CLOSED DOORS 8 (by staircase)
50 0.01
pressurized space

Single-leaf opening outside the PRESSURE DIFFERENCE 50 Pa


50 0.02
pressurized space

Double-leaf 50 0.03

Lift landing door 50 0.06

Equations: Where:

AIRFLOW LEAKAGE WITH CLO- QPC_i = 0.83 x Σ AfPC i x P1/2 QPCi Air leakage rate through closed doors.
SED DOORS →
AIRFLOW FOR STAIRCASE → QTPC = Σ QPC i AfPC i Area for leaks according to doors type.
SECURIZED AIRFLOW FOR → Q2 = QTPC x 1,5
P Pressure difference.

QTPC Total identified leakage from the pressu-


rized space with the doors closed.
Calculation example for staircase EP_I:
Q2 Total air supply rate required with all doors
→ QPC_PB =0.83 x (0.02 x 50 1/2 + 0.03 x 50 1/2 ) x 3600 = 1056 m3/h closed (+50%)

→ QTPC/EP_I = (1056 + 423 + 432 + 423 + 423 + 423 + 423) = 3592 m3/h
→ Q2/EP_I = 3592 x 1,5 = 5388 m3/h

Results table for staircase EP_I:

FLOOR TYPE DOOR SINGLE-LEAF


LEAKAGE
DOUBLE-LEAF
LEAKAGE AIR LEAKA- QTPC Q2
AREA [m2] AREA [m2] GE RATE [m3/h] [m3/h]

GF OUTWARDS 1 0,02 1 0,03 1056


Floor 1 OUTWARDS 1 0,02 0 0 423
Floor 2 OUTWARDS 1 0,02 0 0 423
Floor 3 OUTWARDS 1 0,02 0 0 423 3592 5388 m3/h
Floor 4 OUTWARDS 1 0,02 0 0 423
(*)
Floor 5 OUTWARDS 1 0,02 0 0 423
Floor 6 OUTWARDS 1 0,02 0 0 423

(*) 50% Included


Final results:

SECURIZED AIRFLOW +50%


STAIRCASE AIRFLOW [m3/h]
[m3/h]

EP_I 3592 5388

EP_II 3592 5388

EP_III 3592 5388

*Example based on Spanish adaptation of European Standard EN 12101-6:2006.


■ CALCULATION EXAMPLE according to UNE EN 12101-6: 2006 criteria.*

■ DEFINITION OF AIRFLOW TO BE CONSIDERED:

COMPARE THE AIRFLOWS CALCULATED WITH METHOD 1 & METHOD 2

METHOD 1 METHOD 2
STAIRCASE NAME
Q1 [m3/h] Q2 [m3/h]

EP_I 14904 5388

EP_II 14904 5388

EP_III 9936 5388

→ THE SELECTED FLOW FOR EACH STAIRCASE IS THE HIGHER BETWEEN THE TWO METHODS OF CALCULATION

METHOD 1
STAIRCASE NAME
Q1 [m3/h]
EP_I 14904

EP_II 14904

EP_III 9936

■ SELECTION OF THE PRESSURIZATION KIT


Selection is done considering a pressure loss of 250 Pa in the ventilation installation.

METHOD 1 SELECTED
STAIRCASE AVAILABLE PRESSURE [Pa] FAN UNIT
Q1 [m3/h] PRESSURIZATION KIT
EP_I 14904 250 KSW-6 AXI BOX WINDER

EP_II 14904 250 KSW-6 AXI BOX WINDER

EP_III 9936 250 KSBPT-6 BPT BOX

KIT - AXI BOX WINDER KIT - BPT BOX


KSW-6 KSBPT-6

*Example based on Spanish adaptation of European Standard EN 12101-6:2006.


PRESSURIZATION
KIT
Design recommendations according to
UNE EN 12101-6:2006 standard.
■ How to apply the UNE EN 12101-6:2006* standard.
1. Determine the USE of the BUILDING (residential housing, administrative, teaching, commercial, public
concurrency, public residential, hospital, parking, other tertiary or industrial uses).
2. Determine by means of the tables of the relevant fire regulations whether it is a PROTECTED, ESPE-
CIALLY PROTECTED evacuation element and whether an EMERGENCY LIFT is requested.
3. The CLASSIFICATION OF THE PRESSURIZATION SYSTEM shall be agreed with the EMPOWERED AU-
THORITIES.

SYSTEM CLASS DEFINITION

A For means of escape. Defend in place.

B For means of escape and firefighting.

C For means of escape by simultaneous evacuation.

D For means of escape. Sleeping risk.

E For means of escape by phased evacuation.

F Firefighting system and means of escape.

■ Design criteria for air supply


1. Each pressurized evacuation route must have its own independent air supply.
2. Depending on the height of evacuation [he]:
■ he ≤ 11m → One air supply location is enough.
■ he > 11m → Supply air every 3 floors
3. The supply air points should be located at a distance d ≥ 3 m from the exit doors.
4. Drive fans must have 2 stages : normal and enhanced.
5. In case there is only 1 way of evacuation, installation of a back-up fan is mandatory.