SkyAir - Cooling Only - NU (FHC, FH-NU)

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 149

ED24 - 631A

Split System Air Conditioners


SkyAir

NU-V1/Y1 Series

— Cooling Only [50Hz] —


ED24-631A

SkyAir NU Series— Cooling Only [50Hz] — .................................... 1


1. External Appearance...............................................................................2
2. Model Name, Power Supply and Nomenclature .....................................3
2.1 Model Name and Power Supply...............................................................3
2.2 Nomenclature ...........................................................................................4
3. Functions.................................................................................................5
3.1 NU Series .................................................................................................5
4. Specifications ..........................................................................................6
5. Dimensions and Service Space ............................................................12
5.1 Indoor Unit..............................................................................................12
5.2 Wired Remote Controller........................................................................22
5.3 Wireless Remote Controller ...................................................................25
5.4 Outdoor Unit ...........................................................................................26
5.5 Installation Service Space for R26~56NU ..............................................30
6. Piping Diagrams....................................................................................32
7. Wiring Diagrams....................................................................................34
7.1 Indoor Unit..............................................................................................34
7.2 Remote Controller ..................................................................................38
7.3 Outdoor Unit ...........................................................................................40
7.4 Field Wiring ............................................................................................44
8. Electric Characteristics..........................................................................45
8.1 R18~26NUV1 / Y1..................................................................................45
8.2 R36~56NUV1 / Y1..................................................................................46
9. Capacity Tables ....................................................................................47
9.1 Capacity Tables......................................................................................47
9.2 Capacity Correction Factor by the Length of Refrigerant Piping ............51
10.Operation Limit......................................................................................52
11.Fan Performance ..................................................................................53
11.1 FDBG-NU ...............................................................................................53
11.2 FDMG-NU ..............................................................................................54
12.Sound Level ..........................................................................................56
12.1 Overall Sound Level ...............................................................................56
12.2 Octave Band Level .................................................................................58
13.Installation .............................................................................................61
13.1 Indoor Unit..............................................................................................61
13.2 Outdoor Unit .........................................................................................103
14.Accessories.........................................................................................116
14.1 Indoor Unit............................................................................................116
14.2 Outdoor Unit .........................................................................................118
15.Remote Controller ...............................................................................119
15.1 Operation..............................................................................................119
16.Detail Explanation of Options..............................................................124
16.1 Ceiling Mounted Cassette Type (Multi Flow) [FHC] .............................124
16.2 Ceiling Suspended Type [FH] ..............................................................143
16.3 Duct Connection Low Static Pressure Type [FDBG]............................144
16.4 Outdoor Unit .........................................................................................145

Table of Contents i
ED24-631A

ii Table of Contents
ED24-631A

SkyAir NU Series
— Cooling Only [50Hz] —
Model Series
Class 18 21 26 36 42 48 51 56

FHC 18NU 21NU 26NU 36NU 42NU 48NU — —

FH — 21NU 26NU 36NU 42NU 48NU — —


Indoor Unit
FDBG 18NU 21NU 26NU — — — — —

FDMG — — 26NU 36NU 42NU 48NU 51NU 56NU

Outdoor Unit R 18NU 21NU 26NU 36NU 42NU 48NU 51NU 56NU

SkyAir NU Series – Cooling Only – 1


External Appearance ED24-631A

1. External Appearance
Indoor Unit

FHC-NU FH-NU FDBG-NU FDMG-NU

Wired
Remote Controller

BRC1C61 BRC1NU61 KRC47-1 KRC47-2


(for FHC) (for FH) (for FDBG, FDMG) KRC47-4
(for FDBG, FDMG)

Wireless
Remote Controller

BRC7C613W BRC7NU66
(for FHC) (for FH)

Outdoor Unit

R18NU R21NU R26NU

R36NU R42NU R48 · 51NU R56NU

2 SkyAir NU Series – Cooling Only –


ED24-631A Model Name, Power Supply and Nomenclature

2. Model Name, Power Supply and Nomenclature


2.1 Model Name and Power Supply

Indoor Unit Outdoor Unit Power Supply

FHC18NUV1 ∗ R18NUV1 ∗

FHC21NUV1 ∗ R21NUV1 ∗
1 phase 220~240V 50Hz
FHC26NUV1 ∗ R26NUV1 ∗

FHC36NUV1 R36NUV1

FHC26NUV1 ∗ R26NUY1 ∗

FHC36NUV1 R36NUY1
3 phase 380~415V 50Hz
(4 wires)
FHC42NUV1 R42NUY1

FHC48NUV1 R48NUY1

FH21NUV1 ∗ R21NUV1 ∗

FH26NUV1 ∗ R26NUV1 ∗ 1 phase 220~240V 50Hz

FH36NUV1 R36NUV1

FH26NUV1 ∗ R26NUY1 ∗

FH36NUV1 R36NUY1
3 phase 380~415V 50Hz
(4 wires)
FH42NUV1 R42NUY1

FH48NUV1 R48NUY1

FDBG18NUV1 ∗ R18NUV1 ∗

FDBG21NUV1 ∗ R21NUV1 ∗ 1 phase 220~240V 50Hz

FDBG26NUV1 ∗ R26NUV1 ∗

3 phase 380~415V 50Hz


FDBG26NUV1 ∗ R26NUY1 ∗ (4 wires)

FDMG26NUV1 ∗ R26NUV1 ∗
1 phase 220~240V 50Hz
FDMG36NUV1 R36NUV1

FDMG26NUV1 ∗ R26NUY1 ∗

FDMG36NUV1 R36NUY1

FDMG42NUV1 R42NUY1
3 phase 380~415V 50Hz
(4 wires)
FDMG48NUV1 R48NUY1

FDMG51NUV1 R51NUY1

FDMG56NUV1 R56NUY1

Note: 1. ∗ : New Model or Changed Model


2. Power Supply Intake : Outdoor Unit

SkyAir NU Series – Cooling Only – 3


Model Name, Power Supply and Nomenclature ED24-631A

2.2 Nomenclature

Indoor Unit

FDM G 18 NU V1
Power Supply Symbol
V1 : 1 phase 220~240V 50Hz
Indicates Major Design Category
Capacity Indication
DIT Products
FHC : Ceiling Mounted Cassette Type -Multi Flow-
FH : Ceiling Suspended Type
FDB : Duct Connection Low Static Pressure Type
(Cooling Only)
FDM : Duct Connection Middle Static Pressure Type
(Cooling Only)

Outdoor Unit

R 18 NU V1
Power Supply Symbol
V1 : 1 phase 220~240V 50Hz
Y1 : 3 phase 380~415V 50Hz
Indicates Major Design Category
Capacity Indication
Outdoor Unit
R : Cooling Only

4 SkyAir NU Series – Cooling Only –


ED24-631A Functions

3. Functions
3.1 NU Series

FHC-NU
Item Feature Ceiling Mounted Casssete Type (FHC)
Auto swing {
Swing pattern selection {
Switchable fan speed {
Program "Dry" {
Comfort
High ceiling application {
Two selectable Wired type {
thermo-sensors Wireless type —
Timer selector {
Mildew prevention Mold resistant treatment for filter {
Drain water lift-up mechanism {
Pre-charged for up to 10 m { (18~26)
Pre-charged for up to 15 m { (36~48)
Work & servicing
Long-life filter {
Filter sign {
Ceiling soiling prevention {
Auto-restart {
Ultra long-life filter {
Control features
High-efficiency filter {
Fresh air intake kit {
Others PE fin for outdoor unit {

FH-NU
Item Feature Ceiling Suspended Type (FH)
Auto swing {
Switchable fan speed {
Comfort
Program "Dry" {
Timer selector {
Mold resistant treatment for filter {
Mildew prevention
Mildew-proofing drain pan {
Pre-charged for up to 10 m { (21 · 26)
Work & servicing Pre-charged for up to 15 m { (36~48)
Long-life filter {
Control features Auto-restart {
Others PE fin for outdoor unit {

FDBG-NU
Item Feature Duct Connection Low Static Pressure Type (FDBG)
Comfort Switchable fan speed {
Work & servicing Pre-charged for up to 10 m { (18~26)
Control features Auto-restart {
PE fin for outdoor unit {
Others
Adjustable external static pressure {

FDMG-NU
Item Feature Duct Connection Middle Static Pressure Type (FDMG)
Comfort Switchable fan speed {
Pre-charged for up to 10 m { (26)
Work & servicing
Pre-charged for up to 15 m { (36~51)
Control features Auto-restart {
PE fin for outdoor unit {
Others
Adjustable external static pressure {

{ : Functions exist.
— : No Functions

SkyAir NU Series – Cooling Only – 5


Specifications ED24-631A

4. Specifications
FHC (Ceiling Mounted Cassette Type)
Indoor Unit FHC18NUV1 FHC21NUV1 FHC26NUV1
Model V1 R18NUV1 R21NUV1 R26NUV1
Outdoor Unit
Y1 - - R26NUY1
Btu/h 18,100/18,000 21,200/21,000 26,300/26,000
∗1 ∗2 Cooling Capacity (1) / (2) kW 5.3/5.3 6.2/6.2 7.7/7.6
kcal/h 4,580/4,560 5,340/5,290 6,630/6,550
Indoor Unit FHC18NUV1 FHC21NUV1 FHC26NUV1
Dimensions H×W×D mm 230×840×840 230×840×840 230×840×840
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 2×8×1.5 2×8×1.5 2×8×1.5
Face Area m² 0.331 0.331 0.331
Model QTS45B14M QTS45B14M QTS45B14M
Type Turbo Fan
Fan
Motor Output W 45 45 45
Air Flow Rate m³/min (H) 15 (L) 11 (H) 19 (L) 14 (H) 19 (L) 14
Mass (Weight) kg 24 24 24
Liquid mm φ6.4 (Flare) φ6.4 (Flare) φ9.5 (Flare)
Piping Gas mm φ15.9 (Flare) φ15.9 (Flare) φ15.9 (Flare)
Connections
Drain mm I.D.φ25 O.D.φ32 I.D.φ25 O.D.φ32 I.D.φ25 O.D.φ32
Remote Controller Wired BRC1C61 ∗3
(Option) Wireless BRC7C613W
Model BYC125K–W1 BYC125K–W1 BYC125K–W1
Decoration Color White
Panel Dimensions (H×W×D) mm 40×950×950 40×950×950 40×950×950
(Option) Air Filter Resin Net (with Mold Resistant)
Weight kg 5 5 5
V1 R18NUV1 R21NUV1 R26NUV1
Outdoor Unit
Y1 - - R26NUY1
Color Ivory White Ivory
Dimensions H×W×D mm 540×750×270 685×800×300 770×900×320
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 2×22×2.0 2×28×2.0 2×34×2.0
Face Area m² 0.372 0.465 0.634
V1 RC70AV1TRT NH41VMDT NH52VNHT
Model
Y1 - - NH52YDTT
Comp.
Type Hermetically Sealed Rotary Type
Motor Output kW 1.7 2.2 2.5
Model PZ380 PZ430 P47L11S
Type Propeller
Fan
Motor Output W 45 53 90
Air Flow Rate m³/min 27 40 59
V1 42 61 70
Mass (Weight) kg
Y1 - - 69
Liquid mm φ6.4 (Flare) φ6.4 (Flare) φ9.5 (Flare)
Piping
Connections
Gas mm φ15.9 (Flare) φ15.9 (Flare) φ15.9 (Flare)
Drain mm φ18.0 (Hole) φ18.0 (Hole) φ26.0 (Hole)
Thermal Protector for Compressor, Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor.
Safety Devices Outdoor Fan Motor and Indoor Fan Internal Protector of Compressor. Reverse Phase Protector (Y1). Fuse.
Motor. Fuse.
Capacity Step % 100–0 100–0 100–0
Refrigerant Control Capillary Tube
Max. Length m 30 (Equivalent Length 50m) 30 (Equivalent Length 50m) 30 (Equivalent Length 50m)
Ref. Piping
Max. Height Difference m 15 15 20
Model R-22 R-22 R-22
Refrigerant
Charge (Factory Charge) kg 1.20 (Charged for 10m) 1.50 (Charged for 10m) 2.3 (Charged for 10m)
Model Refer to the name plate of compressor.
Ref. Oil
Charge L 0.85 1.20 1.3
Drawing No. C : 4D054418A C : 4D054286A

Note: ∗1. The above data are based on the following conditions. Conversion Formulae
Cooling Equivalent Piping Length Hz, Volts
kcal/h=kW×860
Indoor: 27°CDB, 19.5°CWB 50Hz, 220V Btu/h=kW×3412
(1) 7.5m (Horizontal) cfm=m³/min×35.3
Outdoor: 35°CDB, 24°CWB (380V)
Indoor: 27°CDB, 19.0°CWB 50Hz, 220V
(2) 7.5m (Horizontal)
Outdoor: 35°CDB, 24°CWB (380V)
∗2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
∗3. Wire for remote controller : Field supplied.

6 SkyAir NU Series – Cooling Only –


ED24-631A Specifications

FHC (Ceiling Mounted Cassette Type)


Indoor Unit FHC36NUV1 FHC42NUV1 FHC48NUV1
Model V1 R36NUV1 - -
Outdoor Unit
Y1 R36NUY1 R42NUY1 R48NUY1
Btu/h 36,500/36,000 42,700/42,000 49,100/48,000
∗1 ∗2 Cooling Capacity (1) / (2) kW 10.7/10.6 12.5/12.3 14.4/14.1
kcal/h 9,200/9,100 10,800/10,600 12,400/12,100
Indoor Unit FHC36NUV1 FHC42NUV1 FHC48NUV1
Dimensions H×W×D mm 288×840×840 288×840×840 288×840×840
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 2×12×1.5 2×12×1.5 2×12×1.5
Face Area m² 0.497 0.497 0.497
Model QTS45A17M QTS45A17M QTS45A17M
Type Turbo Fan
Fan
Motor Output W 90 90 90
Air Flow Rate m³/min (H) 33 (L) 24 (H) 33 (L) 24 (H) 33 (L) 24
Mass (Weight) kg 28 28 28
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Gas mm φ19.1 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Connections
Drain mm I.D.φ25 O.D.φ32 I.D.φ25 O.D.φ32 I.D.φ25 O.D.φ32
Remote Controller Wired BRC1C61 ∗3
(Option) Wireless BRC7C613W
Model BYC125K–W1 BYC125K–W1 BYC125K–W1
Decoration Color White
Panel Dimensions (H×W×D) mm 40×950×950 40×950×950 40×950×950
(Option) Air Filter Resin Net (with Mold Resistant)
Weight kg 5 5 5
V1 R36NUV1 - -
Outdoor Unit
Y1 R36NUY1 R42NUY1 R48NUY1
Color Ivory
Dimensions H×W×D mm 1,170×900×320 1,170×900×320 1,345×900×320
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 1×52×1.4 1×52×1.4 1×60×1.4
Face Area m² 1.015 1.015 1.172
V1 JT125GA-V1@K - -
Model
Y1 JT125GA-Y1@K JT160GA-Y1@K JT170GA-Y1@K
Comp.
Type Hermetically Sealed Scroll Type
Motor Output kW 3.00 3.75 4.50
Model P47L11S P47L11S×2 P47L11S×2
Type Propeller
Fan
Motor Output W 90 65+90 65+90
Air Flow Rate m³/min 59 92 97
V1 81 - -
Mass (Weight) kg
Y1 79 87 92
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping
Connections
Gas mm φ19.1 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole)
Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. Internal
Safety Devices
Protector of Compressor. Reverse Phase Protector (Y1). Fuse. Thermo Switch (Discharge Pipe).
Capacity Step % 100–0 100–0 100–0
Refrigerant Control Capillary Tube
Max. Length m 30 (Equivalent Length 50m) 30 (Equivalent Length 50m) 30 (Equivalent Length 50m)
Ref. Piping
Max. Height Difference m 20 20 20
Model R-22 R-22 R-22
Refrigerant
Charge (Factory Charge) kg 2.0 (Charged for 15m) 2.4 (Charged for 15m) 2.6 (Charged for 15m)
Model Refer to the name plate of compressor.
Ref. Oil
Charge L 1.4 1.4 1.4
Drawing No. C : 4D052554B

Note: ∗1. The above data are based on the following conditions. Conversion Formulae
Cooling Equivalent Piping Length Hz, Volts
kcal/h=kW×860
Indoor: 27°CDB, 19.5°CWB 50Hz, 220V Btu/h=kW×3412
(1) 7.5m (Horizontal) cfm=m³/min×35.3
Outdoor: 35°CDB, 24°CWB (380V)
Indoor: 27°CDB, 19.0°CWB 50Hz, 220V
(2) 7.5m (Horizontal)
Outdoor: 35°CDB, 24°CWB (380V)
∗2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
∗3. Wire for remote controller : Field supplied.

SkyAir NU Series – Cooling Only – 7


Specifications ED24-631A

FH (Ceiling Suspended Type)


Indoor Unit FH21NUV1 FH26NUV1 FH36NUV1 FH42NUV1 FH48NUV1
Model V1 R21NUV1 R26NUV1 R36NUV1 - -
Outdoor Unit
Y1 - R26NUY1 R36NUY1 R42NUY1 R48NUY1
Btu/h 21,200/21,000 26,300/26,000 36,500/36,000 42,700/42,000 49,100/48,000
∗1 ∗2 Cooling Capacity (1) / (2) kW 6.2/6.2 7.7/7.6 10.7/10.6 12.5/12.3 14.4/14.1
kcal/h 5,340/5,290 6,630/6,550 9,200/9,100 10,800/10,600 12,400/12,100
Indoor Unit FH21NUV1 FH26NUV1 FH36NUV1 FH42NUV1 FH48NUV1
Color White
Dimensions H×W×D mm 195×1,160×680 195×1,160×680 195×1,590×680 195×1,590×680 195×1,590×680
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 3×12×1.75 3×12×1.75 3×12×1.75 3×12×1.75 3×12×1.75
Face Area m² 0.233 0.233 0.341 0.341 0.341
Model 4D12K1AA1 4D12K1AA1 4D12K2AA1 4D12K2AA1 4D12K2AA1
Type Sirocco Fan
Fan
Motor Output W 45 45 70 98 98
Air Flow Rate ∗3 m³/min (H) 22-23 (L) 19-20 (H) 22-23 (L) 19-20 (H) 32-34 (L) 22-24 (H) 38-40 (L) 23-25 (H) 42-44 (L) 24-26
Air Filter Resin Net (with Mold Resistant)
Mass (Weight) kg 26 26 35 35 35
Liquid mm φ6.4 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Gas mm φ15.9 (Flare) φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Connections
Drain mm I.D.φ20 O.D.φ26 I.D.φ20 O.D.φ26 I.D.φ20 O.D.φ26 I.D.φ20 O.D.φ26 I.D.φ20 O.D.φ26
Remote Controller Wired BRC1NU61 ∗4
(Option) Wireless BRC7NU66
V1 R21NUV1 R26NUV1 R36NUV1 - -
Outdoor Unit
Y1 - R26NUY1 R36NUY1 R42NUY1 R48NUY1
Color Ivory White Ivory
Dimensions H×W×D mm 685×800×300 770×900×320 1,170×900×320 1,170×900×320 1,345×900×320
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 2×28×2.0 2×34×2.0 1×52×1.4 1×52×1.4 1×60×1.4
Face Area m² 0.465 0.634 1.015 1.015 1.172
V1 NH41VMDT NH52VNHT JT125GA-V1@K - -
Model
Y1 - NH52YDTT JT125GA-Y1@K JT160GA-Y1@K JT170GA-Y1@K
Comp.
Type Hermetically Sealed Rotary Type Hermetically Sealed Scroll Type
Motor Output kW 2.2 2.5 3.00 3.75 4.50
Model PZ430 P47L11S P47L11S P47L11S×2 P47L11S×2
Type Propeller
Fan
Motor Output W 53 90 90 65+90 65+90
Air Flow Rate m³/min 40 59 59 92 97
V1 61 70 81 - -
Mass (Weight) kg
Y1 - 69 79 87 92
Liquid mm φ6.4 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping
Connections
Gas mm φ15.9 (Flare) φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm φ18.0 (Hole) φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole)
Thermal Protector for Outdoor Fan Motor and Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High
Indoor Fan Motor. Internal Protector of Pressure Switch. Low Pressure Switch. Internal Protector of
Safety Devices
Compressor. Reverse Phase Protector (Y1). Compressor. Reverse Phase Protector (Y1). Fuse. Thermo Switch
Fuse. (Discharge Pipe).
Capacity Step % 100–0 100–0 100–0 100–0 100–0
Refrigerant Control Capillary Tube
30 30 30 30 30
Max. Length m (Equivalent Length 50m) (Equivalent Length 50m) (Equivalent Length 50m) (Equivalent Length 50m) (Equivalent Length 50m)
Ref. Piping
Max. Height Difference m 15 20 20 20 20
Model R-22 R-22 R-22 R-22 R-22
Refrigerant
Charge (Factory Charge) kg 1.50 (Charged for 10m) 2.3 (Charged for 10m) 2.0 (Charged for 15m) 2.4 (Charged for 15m) 2.6 (Charged for 15m)
Model Refer to the name plate of compressor.
Ref. Oil
Charge L 1.20 1.3 1.4 1.4 1.4
Drawing No. C : 4D054275A C : 4D052470B

Note: ∗1. The above data are based on the following conditions. Conversion Formulae
Cooling Equivalent Piping Length Hz, Volts
kcal/h=kW×860
Indoor: 27°CDB, 19.5°CWB 50Hz, 220V Btu/h=kW×3412
(1) 7.5m (Horizontal) cfm=m³/min×35.3
Outdoor: 35°CDB, 24°CWB (380V)
Indoor: 27°CDB, 19.0°CWB 50Hz, 220V
(2) 7.5m (Horizontal)
Outdoor: 35°CDB, 24°CWB (380V)
∗2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
∗3. AFR (Air flow rate) is shown at 220~240V (380~415V).
∗4. Wire for remote controller : Field supplied.

8 SkyAir NU Series – Cooling Only –


ED24-631A Specifications

FDBG (Duct Connection Low Static Pressure Type)


Indoor Unit FDBG18NUV1 FDBG21NUV1 FDBG26NUV1
Model V1 R18NUV1 R21NUV1 R26NUV1
Outdoor Unit
Y1 - - R26NUY1
Btu/h 18,100/18,000 21,200/21,000 26,300/26,000
∗1 ∗2 Cooling Capacity (1) / (2) kW 5.3/5.3 6.2/6.2 7.7/7.6
kcal/h 4,580/4,560 5,340/5,290 6,630/6,550
Indoor Unit FDBG18NUV1 FDBG21NUV1 FDBG26NUV1
Dimensions H×W×D mm 260×900×580 260×1,300×580 260×1,300×580
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 3×10×1.75 3×10×1.75 3×10×1.75
Face Area m² 0.189 0.231 0.231
Type Sirocco Fan
Fan Motor Output W 45 65 65
Air Flow Rate ∗3 m³/min (H) 13 (L) 11 (H) 18 (L) 15 (H) 18 (L) 15
Mass (Weight) kg 23 31 31
Liquid mm φ6.4 (Flare) φ6.4 (Flare) φ9.5 (Flare)
Piping Gas mm φ15.9 (Flare) φ15.9 (Flare) φ15.9 (Flare)
Connections
Drain mm 3/4 B (I.D.φ21.6 O.D.φ27.2) 3/4 B (I.D.φ21.6 O.D.φ27.2) 3/4 B (I.D.φ21.6 O.D.φ27.2)
Remote Controller Wired KRC47-1 KRC47-2 KRC47-4 KRC47-1 KRC47-2 KRC47-4 KRC47-1 KRC47-2 KRC47-4
(Option) Wireless - - -
V1 R18NUV1 R21NUV1 R26NUV1
Outdoor Unit
Y1 - - R26NUY1
Color Ivory White Ivory
Dimensions H×W×D mm 540×750×270 685×800×300 770×900×320
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 2×22×2.0 2×28×2.0 2×34×2.0
Face Area m² 0.372 0.465 0.634
V1 RC70AV1TRT NH41VMDT NH52VNHT
Model
Y1 - - NH52YDTT
Comp.
Type Hermetically Sealed Rotary Type
Motor Output kW 1.7 2.2 2.5
Model PZ380 PZ430 P47L11S
Type Propeller
Fan
Motor Output W 45 53 90
Air Flow Rate m³/min 27 40 59
V1 42 61 70
Mass (Weight) kg
Y1 - - 69
Liquid mm φ6.4 (Flare) φ6.4 (Flare) φ9.5 (Flare)
Piping
Connections
Gas mm φ15.9 (Flare) φ15.9 (Flare) φ15.9 (Flare)
Drain mm φ18.0 (Hole) φ18.0 (Hole) φ26.0 (Hole)
Thermal Protector for Compressor, Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor.
Safety Devices Outdoor Fan Motor and Indoor Fan Internal Protector of Compressor. Reverse Phase Protector (Y1). Fuse.
Motor. Fuse.
Capacity Step % 100–0 100–0 100–0
Refrigerant Control Capillary Tube
Max. Length m 30 (Equivalent Length 50m) 30 (Equivalent Length 50m) 30 (Equivalent Length 50m)
Ref. Piping
Max. Height Difference m 15 15 20
Model R-22 R-22 R-22
Refrigerant
Charge (Factory Charge) kg 1.20 (Charged for 10m) 1.50 (Charged for 10m) 2.3 (Charged for 10m)
Model Refer to the name plate of compressor.
Ref. Oil
Charge L 0.85 1.20 1.3
Drawing No. C : 4D054295B C : 4D054288A

Note: ∗1. The above data are based on the following conditions. Conversion Formulae
Cooling Equivalent Piping Length Hz, Volts
kcal/h=kW×860
Indoor: 27°C(81°F)DB, 19.5°C(67°F)WB 50Hz, 220V Btu/h=kW×3412
(1) 7.5m (Horizontal) cfm=m³/min×35.3
Outdoor: 35°C(95°F)DB, 24°C(75°F)WB (380V)
Indoor: 27°C(81°F)DB, 19.0°C(66°F)WB 50Hz, 220V
(2) 7.5m (Horizontal)
Outdoor: 35°C(95°F)DB, 24°C(75°F)WB (380V)
∗2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
∗3. Refer to "11. Fan Performance" in detail.

SkyAir NU Series – Cooling Only – 9


Specifications ED24-631A

FDMG (Duct Connection Middle Static Pressure Type)


Indoor Unit FDMG26NUV1 FDMG36NUV1 FDMG42NUV1
Model V1 R26NUV1 R36NUV1 -
Outdoor Unit
Y1 R26NUY1 R36NUY1 R42NUY1
Btu/h 26,300/26,000 36,500/36,000 42,700/42,000
∗1 ∗2 Cooling Capacity (1) / (2) kW 7.7/7.6 10.7/10.6 12.5/12.3
kcal/h 6,630/6,550 9,200/9,100 10,800/10,600
Indoor Unit FDMG26NUV1 FDMG36NUV1 FDMG42NUV1
Dimensions H×W×D mm 305×1,350×680 305×1,550×680 305×1,550×680
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 3×12×1.75 3×12×1.75 3×12×1.75
Face Area m² 0.290 0.340 0.340
Type Sirocco Fan
Motor Output W 125 225 225
Fan
Air Flow Rate ∗3 m³/min 23 37 42
Rated Ext. Static Pressure ∗3 mmH2O 8.5 9.8 8.0
Mass (Weight) kg 43 52 52
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Connections
Drain mm 3/4 B (I.D.φ21.6 O.D.φ27.2) 3/4 B (I.D.φ21.6 O.D.φ27.2) 3/4 B (I.D.φ21.6 O.D.φ27.2)
Remote Controller Wired KRC47-1 KRC47-2 KRC47-4 KRC47-1 KRC47-2 KRC47-4 KRC47-1 KRC47-2 KRC47-4
(Option) Wireless - - -
V1 R26NUV1 R36NUV1 -
Outdoor Unit
Y1 R26NUY1 R36NUY1 R42NUY1
Color Ivory
Dimensions H×W×D mm 770×900×320 1,170×900×320 1,170×900×320
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 2×34×2.0 1×52×1.4 1×52×1.4
Face Area m² 0.634 1.015 1.015
V1 NH52VNHT JT125GA-V1@K -
Model
Y1 NH52YDTT JT125GA-Y1@K JT160GA-Y1@K
Comp.
Type Hermetically Sealed Rotary Type Hermetically Sealed Scroll Type
Motor Output kW 2.5 3.00 3.75
Model P47L11S P47L11S P47L11S×2
Type Propeller
Fan
Motor Output W 90 90 65+90
Air Flow Rate m³/min 59 59 92
V1 70 81 -
Mass (Weight) kg
Y1 69 79 87
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping
Connections
Gas mm φ15.9 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole)
Thermal Protector for Outdoor Fan Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure
Motor and Indoor Fan Motor. Internal Switch. Low Pressure Switch. Internal Protector of Compressor. Reverse Phase
Safety Devices
Protector of Compressor. Reverse Protector (Y1). Fuse. Thermo Switch (Discharge Pipe).
Phase Protector (Y1). Fuse.
Capacity Step % 100–0 100–0 100–0
Refrigerant Control Capillary Tube
Max. Length m 30 (Equivalent Length 50m) 30 (Equivalent Length 50m) 30 (Equivalent Length 50m)
Ref. Piping
Max. Height Difference m 20 20 20
Model R-22 R-22 R-22
Refrigerant
Charge (Factory Charge) kg 2.3 (Charged for 10m) 2.0 (Charged for 15m) 2.4 (Charged for 15m)
Model Refer to the name plate of compressor.
Ref. Oil
Charge L 1.3 1.4 1.4
Drawing No. C : 4D054287A C : 3D052567B

Note: ∗1. The above data are based on the following conditions. Conversion Formulae
Cooling Equivalent Piping Length Hz, Volts
kcal/h=kW×860
Indoor: 27°C(81°F)DB, 19.5°C(67°F)WB 50Hz, 220V Btu/h=kW×3412
(1) 7.5m (Horizontal) cfm=m³/min×35.3
Outdoor: 35°C(95°F)DB, 24°C(75°F)WB (380V)
Indoor: 27°C(81°F)DB, 19.0°C(66°F)WB 50Hz, 220V
(2) 7.5m (Horizontal)
Outdoor: 35°C(95°F)DB, 24°C(75°F)WB (380V)
∗2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
∗3. Refer to "11. Fan Performance" in detail.

10 SkyAir NU Series – Cooling Only –


ED24-631A Specifications

FDMG (Duct Connection Middle Static Pressure Type)


Indoor Unit FDMG48NUV1 FDMG51NUV1 FDMG56NUV1
Model
Outdoor Unit R48NUY1 R51NUY1 R56NUY1
Btu/h 49,100/48,000 52,200/51,000 57,000/56,000
∗1 ∗2 Cooling Capacity (1) / (2) kW 14.4/14.1 15.3/15.0 16.7/16.4
kcal/h 12,400/12,100 13,200/12,900 14,400/14,100
Indoor Unit FDMG48NUV1 FDMG51NUV1 FDMG56NUV1
Dimensions H×W×D mm 305×1,550×680 305×1,900×680 305×1,900×680
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 3×12×1.75 3×12×1.75 3×12×1.75
Face Area m² 0.340 0.428 0.428
Type Sirocco Fan
Motor Output W 225 225 225
Fan
Air Flow Rate ∗3 m³/min 42 42 42
Rated Ext. Static Pressure ∗3 mmH2O 8.0 9.8 9.8
Mass (Weight) kg 52 58 58
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping Gas mm φ19.1 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Connections
Drain mm 3/4 B (I.D.φ21.6 O.D.φ27.2) 3/4 B (I.D.φ21.6 O.D.φ27.2) 3/4 B (I.D.φ21.6 O.D.φ27.2)
Remote Controller Wired KRC47-1 KRC47-2 KRC47-4 KRC47-1 KRC47-2 KRC47-4 KRC47-1 KRC47-2 KRC47-4
(Option) Wireless - - -
Outdoor Unit R48NUY1 R51NUY1 R56NUY1
Color Ivory
Dimensions H×W×D mm 1,345×900×320 1,345×900×320 1,345×880×370
Type Cross Fin Coil
Coil Row×Stages×Fin Pitch 1×60×1.4 1×60×1.4 2×60×2.0
Face Area m² 1.172 1.172 1.088
Model JT170GA-Y1@K JT170GA-Y1@K JT200B-YE
Comp. Type Hermetically Sealed Scroll Type
Motor Output kW 4.50 4.50 4.50
Model P47L11S×2 P47L11S×2 P45J11S×2
Type Propeller
Fan
Motor Output W 65+90 65+90 64+56
Air Flow Rate m³/min 97 97 101
Mass (Weight) kg 92 93 114
Liquid mm φ9.5 (Flare) φ9.5 (Flare) φ9.5 (Flare)
Piping
Connections
Gas mm φ19.1 (Flare) φ19.1 (Flare) φ19.1 (Flare)
Drain mm φ26.0 (Hole) φ26.0 (Hole) φ26.0 (Hole)
Thermal Protector for Outdoor Fan Motor and Indoor Fan Motor. High Pressure Switch. Low Pressure Switch. Internal
Safety Devices
Protector of Compressor. Reverse Phase Protector (Y1). Fuse. Thermo Switch (Discharge Pipe).
Capacity Step % 100–0 100–0 100–0
Refrigerant Control Capillary Tube
Max. Length m 30 (Equivalent Length 50m) 30 (Equivalent Length 50m) 50 (Equivalent Length 70m)
Ref. Piping
Max. Height Difference m 20 20 30
Model R-22 R-22 R-22
Refrigerant
Charge (Factory Charge) kg 2.6 (Charged for 15m) 2.7 (Charged for 15m) 2.8 (Charged for 5m)
Model Refer to the name plate of compressor.
Ref. Oil
Charge L 1.4 1.4 1.6
Drawing No. C : 3D052567B

Note: ∗1. The above data are based on the following conditions. Conversion Formulae
Cooling Equivalent Piping Length Hz, Volts
kcal/h=kW×860
Indoor: 27°C(81°F)DB, 19.5°C(67°F)WB 50Hz, 220V Btu/h=kW×3412
(1) 7.5m (Horizontal) cfm=m³/min×35.3
Outdoor: 35°C(95°F)DB, 24°C(75°F)WB (380V)
Indoor: 27°C(81°F)DB, 19.0°C(66°F)WB 50Hz, 220V
(2) 7.5m (Horizontal)
Outdoor: 35°C(95°F)DB, 24°C(75°F)WB (380V)
∗2. Capacities are net, including a deduction for cooling for indoor fan motor heat.
∗3. Refer to "11. Fan Performance" in detail.

SkyAir NU Series – Cooling Only – 11


Dimensions and Service Space ED24-631A

5. Dimensions and Service Space


5.1 Indoor Unit
5.1.1 FHC (Ceiling Mounted Cassette Type)

FHC18NU + BYC125K-W1
FHC21NU + BYC125K-W1
Unit (mm)

4. When the temperature and humidity in the ceiling exceed 30˚C and RH 80%
or the fresh air is inducted into the ceiling or the unit continues 24 hour
operation, an additional insulation (thickness 10mm or more of glasswool or
polyethylene form) is required.
C : 3D054367

FHC26NU + BYC125K-W1
Unit (mm)

4. When the temperature and humidity in the ceiling exceed 30˚C and RH 80%
or the fresh air is inducted into the ceiling or the unit continues 24 hour
operation, an additional insulation (thickness 10mm or more of glasswool or
polyethylene form) is required.

C : 3D054368

12 SkyAir NU Series – Cooling Only –


ED24-631A Dimensions and Service Space

FHC36NU + BYC125K-W1
FHC42NU + BYC125K-W1
FHC48NU + BYC125K-W1

Unit (mm)

4. When the temperature and humidity in the ceiling exceed 30˚C and RH 80%
or the fresh air is inducted into the ceiling or the unit continues 24 hour
operation, an additional insulation (thickness 10mm or more of glasswool or
polyethylene form) is required.
C : 3D052528

5.1.2 FHC with High-Efficiency Filter

KAFP556D80 · 557D80 for FHC18~26NU


Note:When other optional kit is installed, refer to the installation Unit (mm)
drawing of its optional kit.
290

6 Drain pipe connection


5 Gas pipe connection
4 Liquid pipe connection
3 High efficiency filter
2 Decoration panel
1 Indoor unit
Number Name Description
JC : 3D032975C

SkyAir NU Series – Cooling Only – 13


Dimensions and Service Space ED24-631A

KAFP556D160 · 557D160 for FHC36~48NU


Note:When other optional kit is installed, refer to the installation Unit (mm)
drawing of its optional kit.

6 Drain pipe connection


5 Gas pipe connection
4 Liquid pipe connection
3 High efficiency filter
2 Decoration panel
1 Indoor unit
Number Name Description
J : 3D032976C

5.1.3 FHC with Fresh Air Intake Kit (Without T Joint, Duct Fan)

KDDP55D160 for FHC18~26NU


Service Access Panel :
450×450mm or more Unit (mm)
Refer to Note 2

Refrigerant
Piping

View Note 4
Service Access Panel :
450×450mm or more
Refer to Note 2

Installation Service Access Panel

Connection Chamber (Right)


Note:1.When installing this kit, Service Access Panel is necessary. How to connect Chamber 4
(It is necessary when servicing.) Independently(Refer to Note 5,6)
2.Either one of Service Access Panel must be installed.
3.Field construction.
4.In case of using wireless remote controller kit, this part 5 Connection chamber(Left)
will be the infrared receiver. 4 Connection chamber(Right)
5.When both side intakes can not be ensured due to the 3 Suction chamber
obstacles, one side intake is acceptable. 2 Decoration panel
6.When installing the wireless infrared reciever to the unit, Indoor unit
1
air inlet must be on the right side as shown.
Number Name Description
JC : 3D032981D

14 SkyAir NU Series – Cooling Only –


ED24-631A Dimensions and Service Space

KDDP55D160 for FHC36~48NU


Service Access Panel :
450×450mm or more
Unit (mm)
Refer to Note 2

Refrigerant
Piping

Service Access Panel : View Note 4


450×450mm or more
Refer to Note 2
Installation Service Access Panel

Connection Chamber (Right)


How to connect Chamber 4
Independently(Refer to Note 5,6)

Note:1.When installing this kit, Service Access Panel is


necessary. (It is necessary when servicing.)
2.Either one of Service Access Panel must be installed.
3.Field construction.
4.In case of using wireless remote controller kit, this part
will be the infrared receiver. 5 Connecting chamber(Left)
5.When both side intakes can not be ensured due to the 4 Connecting chamber(Right)
obstacles, one side intake is acceptable. 3 Suction chamber
6.When installing the wireless infrared reciever to the unit, 2 Decoration panel
air inlet must be on the right side as shown. 1 Indoor unit
Number Name Description
JC : 3D032984D

5.1.4 FHC with Fresh Air Intake Kit (With T Joint, Without Duct Fan)

KDDP55D160K for FHC18~26NU


Service Access Panel :
450×450mm or more Unit (mm)
Refer to Note 2 Flexible Duct
(Accessory)

Service Access Panel :


450×450mm or more Suction Duct (K-KFD9A)
Refer to Note 2 Optional (Accessory)
Installation Service Access Panel T Joint
Plate Band (Accessory) (Accessory)

Connecting Chamber (Right)


How to connect Chamber 4
Independently(Refer to Note 5)
5 Connecting chamber(Left)
Note:1.When installing this kit, inspection hatch is necessary.
(It is necessary when servicing.) 4 Connecting chamber(Right)
2.Either one of inspection hatch must be installed. 3 Suction chamber
3.Field construction. 2 Decoration panel
4.This kit does not take together with Wireless Remoto Controller kit. 1 Indoor unit
5.When both side intakes can not be ensured due to the Number Name Description
obstacles, one side intake is acceptable.

JC : 3D032987D

SkyAir NU Series – Cooling Only – 15


Dimensions and Service Space ED24-631A

KDDP55D160K for FHC36~48NU


Service Access Panel :
450×450mm or more Unit (mm)
Refer to Note 2 Flexible Duct
(Accessory)

Service Access Panel :


450×450mm or more
Refer to Note 2 Suction Duct (K-KFD9A)
Installation Service Access Panel Optional (Accessory)
Plate Band (Accessory) T Joint
(Accessory)

Connecting Chamber (Right)


How to connect Chamber 4
Independently(Refer to Note 5)
5 Connecting chamber(Left)
Note:1.When installing this kit, inspection hatch is necessary. 4 Connecting chamber(Right)
(It is necessary when servicing.) 3 Suction chamber
2.Either one of inspection hatch must be installed.
2 Decoration panel
3.Field construction.
1 Indoor unit
4.This kit does not take together with Wireless Remoto Controller kit.
5.When both side intakes can not be ensured due to the Number Name Description
obstacles, one side intake is acceptable.

J : 3D032990D

5.1.5 FHC with Panel Spacer

KDBP55H160WA for FHC18~26NU

Unit (mm)

View
of panel spacer
the surface of ceiling
Dimension between
the bottom surface

Thickness
of box and

3 Panel spacer
2 Decoration panel
Note:When other optional kit is installed, refer to the installation 1 Indoor unit
drawing of its optional kit Number Name Description

JC : 3D005390E

16 SkyAir NU Series – Cooling Only –


ED24-631A Dimensions and Service Space

KDBP55H160WA for FHC36~48NU


Unit (mm)

View

of panel spacer
the surface of ceiling
Dimension between
the bottom surface

Thickness
of box and
3 Panel spacer
2 Decoration panel
Note:When other optional kit is installed, refer to the installation 1 Indoor unit
drawing of its optional kit Number Name Description

JC : 3D005391D

5.1.6 FH (Ceiling Suspended Type)

FH21NU
Unit (mm)

3D054277

SkyAir NU Series – Cooling Only – 17


Dimensions and Service Space ED24-631A

FH26NU
Unit (mm)

3D027538F

FH36NU
FH42NU
FH48NU
Unit (mm)

3D052469

18 SkyAir NU Series – Cooling Only –


ED24-631A Dimensions and Service Space

5.1.7 FDBG (Duct Connection Low Static Pressure Type)

FDBG18NU
Unit (mm)

3D048541A

FDBG21NU
Unit (mm)

3D048542A

SkyAir NU Series – Cooling Only – 19


Dimensions and Service Space ED24-631A

FDBG26NU
Unit (mm)

3D048543A

5.1.8 FDMG (Duct Connection Middle Static Pressure Type)

FDMG26NU
Unit (mm)

3D048933B

20 SkyAir NU Series – Cooling Only –


ED24-631A Dimensions and Service Space

FDMG36NU
FDMG42NU
FDMG48NU

Unit (mm)

3D048934B

FDMG51NU
FDMG56NU

Unit (mm)

3D048935B

SkyAir NU Series – Cooling Only – 21


Dimensions and Service Space ED24-631A

5.2 Wired Remote Controller

BRC1C61 (for FHC-NU)


Unit (mm)

3D028952

BRC1NU61 (for FH-NU)


Unit (mm)

3D052351

22 SkyAir NU Series – Cooling Only –


ED24-631A Dimensions and Service Space

KRC47-1 (for FDBG-NU and FDMG-NU)

KRC47-2 (Digital Remote Controller) (for FDBG-NU and FDMG-NU)


KRC47-2 contains the following parts, and they are packed in one carton.
1. Digital Remote Controller

2. Holder

SkyAir NU Series – Cooling Only – 23


Dimensions and Service Space ED24-631A

3. Control Board (Box)

4. Wire Cable
Cable length : 4m
Connecting cable between 1. Digital Remote Controller and 3. Control Board (Box).

KRC47-4 (Digital Remote Controller for Duct Heater Use) (for FDBG-NU and FDMG-NU)
1. Digital Remote Controller

AUTO HEAT
HIGH
MED COOL
LOW

POWER FAN

TEMP + TEMP -

For other parts 2. Holder, 3. Control Board (Box), 4. Wire Cable will be the same as KRC 47-2.
(P0007)

24 SkyAir NU Series – Cooling Only –


ED24-631A Dimensions and Service Space

5.3 Wireless Remote Controller

BRC7C613W (for FHC-NU)


Unit (mm)

3D005912D

BRC7NU66 (for FH-NU)


Unit (mm)

3D052347

SkyAir NU Series – Cooling Only – 25


Dimensions and Service Space ED24-631A

5.4 Outdoor Unit

R18NU
Unit (mm)

3D053564

R21NU
Unit (mm)

3D053561

26 SkyAir NU Series – Cooling Only –


ED24-631A Dimensions and Service Space

R26NU
Unit (mm)

3D054206

R36NU
Unit (mm)

3D052425

SkyAir NU Series – Cooling Only – 27


Dimensions and Service Space ED24-631A

R42NU
Unit (mm)

3D052426

R48NU
R51NU
Unit (mm)

3D052427

28 SkyAir NU Series – Cooling Only –


ED24-631A Dimensions and Service Space

R56NU
Unit (mm)

C : 3D052527

SkyAir NU Series – Cooling Only – 29


Dimensions and Service Space ED24-631A

5.5 Installation Service Space for R26~56NU

3D052620A

30 SkyAir NU Series – Cooling Only –


ED24-631A Dimensions and Service Space

3D052620A

SkyAir NU Series – Cooling Only – 31


Piping Diagrams ED24-631A

6. Piping Diagrams
R18 · 21NU

4D050891B

R26NU

3D053984

32 SkyAir NU Series – Cooling Only –


ED24-631A Piping Diagrams

R36~56NU

3D052278

SkyAir NU Series – Cooling Only – 33


Wiring Diagrams ED24-631A

7. Wiring Diagrams
7.1 Indoor Unit

FHC18NUV1
FHC21NUV1
FHC26NUV1
FHC36NUV1
FHC42NUV1
FHC48NUV1

3D052066A

34 SkyAir NU Series – Cooling Only –


ED24-631A Wiring Diagrams

FH21NUV1
FH26NUV1
FH36NUV1
FH42NUV1
FH48NUV1

3D052046A

SkyAir NU Series – Cooling Only – 35


Wiring Diagrams ED24-631A

FDBG18NUV1
FDBG21NUV1
FDBG26NUV1

3D046565A

36 SkyAir NU Series – Cooling Only –


ED24-631A Wiring Diagrams

FDMG26NUV1
FDMG36NUV1
FDMG42NUV1
FDMG48NUV1
FDMG51NUV1
FDMG56NUV1

3D052109A

SkyAir NU Series – Cooling Only – 37


Wiring Diagrams ED24-631A

7.2 Remote Controller

KRC47-1

CONTROL BOARD

TEMPERATURE

ELECTRONIC
CONTROL

CONTROL
« When select the high ESP,
connect the wire as shown
below.

OFF ON P2 P3 P4

P1 P2 P3 P4 P5 P6
A B C

FDBG
FDMG
D A B C E F
Comp. H M L (ON/OFF) N
(THERMOSTAT) L

FAN « (P0008-631A)

KRC47-2
REMOTE CONTROLLER

THERMISTOR

CONTROL BOARD
P8 P9

« When select the high ESP,


connect the wire as shown
below.

P3 P2 P1

P4 P3 P2 P1 P7 A B C

FDBG
FDMG F E A B C D
N L H M L Comp.
(ON/OFF) (THERMOSTAT)

FAN « (P0009-631A)

38 SkyAir NU Series – Cooling Only –


ED24-631A Wiring Diagrams

KRC47-4

REMOTE CONTROLLER

THERMISTOR

CONTROL BOARD

P8 P9

« When select the high ESP,


connect the wire as shown
below.

P3 P2 P1

P4 P3 P2 P1 P7 P6 A B C

FDBG
FDMG F E A B C D

N L H M L Comp. DUCT HEATER


(ON/OFF) (THERMOSTAT) (FIELD SUPPLIED)

FAN «
(P0010-631A)

SkyAir NU Series – Cooling Only – 39


Wiring Diagrams ED24-631A

7.3 Outdoor Unit

R18NUV1

3D032199B

R21NUV1

3D032200A

40 SkyAir NU Series – Cooling Only –


ED24-631A Wiring Diagrams

R26NUV1

3D053671A

R26NUY1

3D053670A

SkyAir NU Series – Cooling Only – 41


Wiring Diagrams ED24-631A

R36NUV1

3D051564A

R36NUY1

3D051536A

42 SkyAir NU Series – Cooling Only –


ED24-631A Wiring Diagrams

R42NUY1
R48NUY1
R51NUY1

3D051535A

R56NUY1

3D052107

SkyAir NU Series – Cooling Only – 43


Wiring Diagrams ED24-631A

7.4 Field Wiring

C : 4D054220
C : 4D052570

44 SkyAir NU Series – Cooling Only –


ED24-631A Electric Characteristics

8. Electric Characteristics
8.1 R18~26NUV1 / Y1

3D054360A
3D054365A

SkyAir NU Series – Cooling Only – 45


Electric Characteristics ED24-631A

8.2 R36~56NUV1 / Y1

3D052523
3D052524
3D052525
3D052526
3D052573

46 SkyAir NU Series – Cooling Only –


ED24-631A Capacity Tables

9. Capacity Tables
9.1 Capacity Tables

FHC18NUV1 / FDBG18NUV1 + R18NUV1

3D054363A

FHC21NUV1 / FH21NUV1 / FDBG21NUV1 + R21NUV1

3D054364A

SkyAir NU Series – Cooling Only – 47


Capacity Tables ED24-631A

FHC26NUV1 / FH26NUV1 / FDBG26NUV1 / FDMG26NUV1 + R26NUV1


FHC26NUV1 / FH26NUV1 / FDBG26NUV1 / FDMG26NUV1 + R26NUY1

3D054484A

FHC36NUV1 / FH36NUV1 / FDMG36NUV1 + R36NUV1


FHC36NUV1 / FH36NUV1 / FDMG36NUV1 + R36NUY1

3D052745A

48 SkyAir NU Series – Cooling Only –


ED24-631A Capacity Tables

FHC42NUV1 / FH42NUV1 / FDMG42NUV1 + R42NUY1

3D052746A

FHC48NUV1 / FH48NUV1 / FDMG48NUV1 + R48NUY1

3D052747A

SkyAir NU Series – Cooling Only – 49


Capacity Tables ED24-631A

FDMG51NUV1 + R51NUY1

3D052751A

FDMG56NUV1 + R56NUY1

3D052754A

50 SkyAir NU Series – Cooling Only –


ED24-631A Capacity Tables

9.2 Capacity Correction Factor by the Length of Refrigerant Piping


The cooling capacity of the unit has to be corrected in accordance with the length of refrigerant piping.
(The distance between the indoor unit and the outdoor unit)
Reference Data

3D052761A

SkyAir NU Series – Cooling Only – 51


Operation Limit ED24-631A

10. Operation Limit

3D049550B

52 SkyAir NU Series – Cooling Only –


ED24-631A Fan Performance

11. Fan Performance


11.1 FDBG-NU

FDBG18NU

3D048561A

FDBG21NU
FDBG26NU

3D048562A

SkyAir NU Series – Cooling Only – 53


Fan Performance ED24-631A

11.2 FDMG-NU

FDMG26NU

4D049493A

FDMG36NU

4D049488A

54 SkyAir NU Series – Cooling Only –


ED24-631A Fan Performance

FDMG42NU
FDMG48NU

4D049489A

FDMG51NU
FDMG56NU

4D049490A

SkyAir NU Series – Cooling Only – 55


Sound Level ED24-631A

12. Sound Level


12.1 Overall Sound Level
12.1.1 Indoor Unit
dB(A)
220V 240V
Model Measuring Location
H L H L

FHC18NUV1 33 29 35 31

FHC21NUV1 35 30 37 32 FHC-NU

FHC26NUV1 35 30 37 32

FHC36NUV1 42 36 44 38

FHC42NUV1 42 36 44 38 4D054296

FHC48NUV1 42 36 44 38

FH21NUV1 44 40 46 42
FH-NU

FH26NUV1 44 40 46 42

FH36NUV1 46 40 48 42

FH42NUV1 48 42 50 44
4D054245

FH48NUV1 49 43 51 45

FDBG-NU
FDBG18NUV1 41 38 43 40

FDBG21NUV1 43 40 45 42

FDBG26NUV1 43 40 45 42
4D054358

FDMG26NUV1 42 38 43 39

FDMG36NUV1 45 37 46 40 FDMG-NU

FDMG42NUV1 46 37 47 40

FDMG48NUV1 46 37 47 40

FDMG51NUV1 47 37 48 39 4D049441A

FDMG56NUV1 47 37 48 39

Note: Operation sound is measured in an anechoic chamber.


Sound level will vary depending on a range of factors such as the construction (acoustic absorption
coefficient) of the particular room in which the equipment installed.

56 SkyAir NU Series – Cooling Only –


ED24-631A Sound Level

12.1.2 Outdoor Unit


dB(A)
Model 220 V 240 V Measuring Location
R18 · 21NU
R18NUV1 49 50

R21NUV1 54 55

R26NUV1 57 57
4D054355

R26~51NU
R36NUV1 55 56

Model 380 V 415 V

R26NUY1 57 57

R36NUY1 55 56
4D054333

R56NU
R42NUY1 57 58

R48NUY1 59 60

R51NUY1 59 60
4D049423B

R56NUY1 56 58

Note: Operation sound is measured in an anechoic chamber.


Sound level will vary depending on a range of factors such as the construction (acoustic absorption
coefficient) of the particular room in which the equipment installed.

SkyAir NU Series – Cooling Only – 57


Sound Level ED24-631A

12.2 Octave Band Level


12.2.1 Indoor Unit
FHC36NUV1
FHC21NUV1 FHC42NUV1
FHC18NUV1 FHC26NUV1 FHC48NUV1

4D054296 4D054293 4D052541A

FH21NUV1
FH26NUV1 FH36NUV1 FH42NUV1

4D054245 4D052455 4D052456

FH48NUV1 Note:
220V
240V

4D052458

58 SkyAir NU Series – Cooling Only –


ED24-631A Sound Level

FDBG21NUV1
FDBG18NUV1 FDBG26NUV1 FDMG26NUV1

4D054358 4D054357A 4D049441A

FDMG42NUV1 FDMG51NUV1
FDMG36NUV1 FDMG48NUV1 FDMG56NUV1

4D049427B 4D049431B 4D049433B

Note:
220V
240V

SkyAir NU Series – Cooling Only – 59


Sound Level ED24-631A

12.2.2 Outdoor Unit


R26NUV1
R18NUV1 R21NUV1 R26NUY1

4D054355 4D054356 4D054333

R36NUV1 R48NUY1
R36NUY1 R42NUY1 R51NUY1

4D052428 4D052429 4D052430

R56NUY1 Note:
V1 : 220V, Y1 : 380V
V1 : 240V, Y1 : 415V

4D049423B

60 SkyAir NU Series – Cooling Only –


ED24-631A Installation

13. Installation
13.1 Indoor Unit
13.1.1 FHC-NUV1

Names and functions of parts

k j

a i
R42 48
h
f
e g
d e

b
d
c
e f
R18 21 26 36

a Indoor unit i Drain pipe


b Outdoor unit Air inlet
j
c Remote controller The built-in air filter removes dust and dirt.
d Inlet air Drain pumping out device(built-in)
e Discharged air k Drains water removed from the room
f Air outlet during cooling.
g Air flow flap (at air outlet) Ground wire
l Wire to ground from the outdoor unit
h Refrigerant piping, connection
electric wire to prevent electrical shocks.

3PN07217-2A

SkyAir NU Series – Cooling Only – 61


Installation ED24-631A

3PN07218-2B-5

62 SkyAir NU Series – Cooling Only –


ED24-631A Installation

3PN07218-2B-6

SkyAir NU Series – Cooling Only – 63


Installation ED24-631A

3PN07218-2B-7

64 SkyAir NU Series – Cooling Only –


ED24-631A Installation

3PN07218-2B-8

SkyAir NU Series – Cooling Only – 65


Installation ED24-631A

3PN07218-2B-9

66 SkyAir NU Series – Cooling Only –


ED24-631A Installation

3PN07218-2B-10

SkyAir NU Series – Cooling Only – 67


Installation ED24-631A

3PN07218-2B-11

68 SkyAir NU Series – Cooling Only –


ED24-631A Installation

3PN07218-2B-12

SkyAir NU Series – Cooling Only – 69


Installation ED24-631A

3PN07218-2B-13

70 SkyAir NU Series – Cooling Only –


ED24-631A Installation

C : 3PN07218-2B-14

SkyAir NU Series – Cooling Only – 71


Installation ED24-631A

3PN07218-2B-15

72 SkyAir NU Series – Cooling Only –


ED24-631A Installation

3PN07218-2B-16

SkyAir NU Series – Cooling Only – 73


Installation ED24-631A

3PN07218-2B-17

74 SkyAir NU Series – Cooling Only –


ED24-631A Installation

3PN07218-2B-18

SkyAir NU Series – Cooling Only – 75


Installation ED24-631A

3PN07218-2B-19

76 SkyAir NU Series – Cooling Only –


ED24-631A Installation

3PN07218-2B-20

SkyAir NU Series – Cooling Only – 77


Installation ED24-631A

3PN07218-2B-21

78 SkyAir NU Series – Cooling Only –


ED24-631A Installation

3PN07218-2B-22

SkyAir NU Series – Cooling Only – 79


Installation ED24-631A

3PN07218-2B-23

80 SkyAir NU Series – Cooling Only –


ED24-631A Installation

13.1.2 FH-NUV1
Names and functions of parts

k
f a
e
e
i

d h
d

j
b
d

c e

a Indoor unit
b Outdoor unit
c Remote controller
d Inlet air
e Discharged air
f Air outlet
g Air flow flap (at air outlet)
h Refrigerant piping, connection electric wire
i Drain pipe
j Air inlet
The built-in air filter removes dust and dirt.
Ground wire
k
Wire to ground from the outdoor unit to prevent electrical shocks.
3PN07087-1A

SkyAir NU Series – Cooling Only – 81


Installation ED24-631A

1PN07240B

82 SkyAir NU Series – Cooling Only –


ED24-631A Installation

1PN07240B

SkyAir NU Series – Cooling Only – 83


Installation ED24-631A

1PN07240B

84 SkyAir NU Series – Cooling Only –


ED24-631A Installation

1PN07240B

SkyAir NU Series – Cooling Only – 85


Installation ED24-631A

1PN07240B

86 SkyAir NU Series – Cooling Only –


ED24-631A Installation

1PN07240B

SkyAir NU Series – Cooling Only – 87


Installation ED24-631A

1PN07241A

88 SkyAir NU Series – Cooling Only –


ED24-631A Installation

1PN07241A

SkyAir NU Series – Cooling Only – 89


Installation ED24-631A

1PN07241A

90 SkyAir NU Series – Cooling Only –


ED24-631A Installation

1PN07241A

SkyAir NU Series – Cooling Only – 91


Installation ED24-631A

1PN07241A

92 SkyAir NU Series – Cooling Only –


ED24-631A Installation

13.1.3 FDBG-NUV1

1PN07524

SkyAir NU Series – Cooling Only – 93


Installation ED24-631A

1PN07524

94 SkyAir NU Series – Cooling Only –


ED24-631A Installation

1PN07524

SkyAir NU Series – Cooling Only – 95


Installation ED24-631A

1PN07524

96 SkyAir NU Series – Cooling Only –


ED24-631A Installation

1PN07524

SkyAir NU Series – Cooling Only – 97


Installation ED24-631A

13.1.4 FDMG-NUV1

1PN06319D

98 SkyAir NU Series – Cooling Only –


ED24-631A Installation

1PN06319D

SkyAir NU Series – Cooling Only – 99


Installation ED24-631A

1PN06319D

100 SkyAir NU Series – Cooling Only –


ED24-631A Installation

1PN06319D

SkyAir NU Series – Cooling Only – 101


Installation ED24-631A

1PN06319D

102 SkyAir NU Series – Cooling Only –


ED24-631A Installation

13.2 Outdoor Unit


13.2.1 R18 · 21NUV1

1PN07605

SkyAir NU Series – Cooling Only – 103


Installation ED24-631A

1PN07605

104 SkyAir NU Series – Cooling Only –


ED24-631A Installation

1PN07605

SkyAir NU Series – Cooling Only – 105


Installation ED24-631A

1PN07605

106 SkyAir NU Series – Cooling Only –


ED24-631A Installation

1PN07605

SkyAir NU Series – Cooling Only – 107


Installation ED24-631A

13.2.2 R26~56NUV1/Y1

1PN07127A

1PN07128B

108 SkyAir NU Series – Cooling Only –


ED24-631A Installation

1PN07128B

SkyAir NU Series – Cooling Only – 109


Installation ED24-631A

1PN07128B

110 SkyAir NU Series – Cooling Only –


ED24-631A Installation

1PN07128B

SkyAir NU Series – Cooling Only – 111


Installation ED24-631A

1PN07128B

112 SkyAir NU Series – Cooling Only –


ED24-631A Installation

1PN07128B

SkyAir NU Series – Cooling Only – 113


Installation ED24-631A

1PN07128B

114 SkyAir NU Series – Cooling Only –


ED24-631A Installation

1PN07128B

SkyAir NU Series – Cooling Only – 115


Accessories ED24-631A

14. Accessories
14.1 Indoor Unit
14.1.1 FHC-NU

Standard
Accessories

3PN07218-2B-3

Optional
Accessories Kit Name
Name of Option Remark
FHC18~26NU FHC36~48NU
Decoration Panel BYC125K–W1
Sealing Member of Air Discharge Outlet KDBHJ55K160
Panel Spacer KDBP55H160WA
Fresh Air Intake Kit ∗3 Chamber Type Without T Joint KDDP55D160
With T Joint KDDP55D160K
Direct Installation Type KDDJ55X160
Chamber Connection Kit ∗4 KKSJ55K160
High–Efficiency Filter (Colorimetric Method 65%) KAFP556D80 KAFP556D160
(Colorimetric Method 90%) KAFP557D80 KAFP557D160
Replacement High–Efficiency (Colorimetric Method 65%) KAFP552H80 KAFP552H160
Filter
(Colorimetric Method 90%) KAFP553H80 KAFP553H160
High–Efficiency Filter Chamber KDDFP55D160
Replacement Long–Life Filter Resin Net (Gravimetric Method 50%) KAFJ551K160
Ultra Long–Life Filter KAFP55D160
Replacement Ultra Long–Life Filter KAFJ55K160H
Branch Duct Chamber KDJ55K80 KDJ55K160
Remote Controller Wired Type ∗2 BRC1C61
Wireless Type BRC7C613W
Wired LCD Remote Controller with Weekly Schedule Timer BRC1D61
Central Remote Controller DCS302CA61
Unified ON/OFF Controller DCS301BA61
Schedule Timer DST301BA61
intelligent Touch Controller DCS601C51
Adaptor for Wiring (Interlock for Fresh Air Intake Fan) ∗1 KRP1B57
Wiring Adaptor for Electrical Appendices ∗1 KRP4A53
Interface Adaptor for SkyAir Series DTA102A52
Installation Box for Adaptor PCB KRP1B98
C : 3D054362
C : 3D052565
Note: ∗1. Installation box for adaptor PCB (KRP1B98) is necessary.
∗2. Wire for remote controller : Field supplied.
∗3. Refer to the Option Handbook for the detail.
∗4. When using the filter (High–Efficiency Filter or Ultra Long–Life Filter) and the Fresh Air Intake Kit together, this kit is necessary.

116 SkyAir NU Series – Cooling Only –


ED24-631A Accessories

14.1.2 FH-NU

Standard
Accessories

1PN07240B

Optional
Accessories
Kit Name
Name of Option Remark
FH21 · 26NU FH36~48NU
Replacement Long–Life Filter KAFJ501D80 KAFJ501D160
L–Type Piping Kit For Upward Direction KHFJ5F80 KHFJ5F160
Remote Controller Wired Type ∗1 BRC1NU61
Wireless Type BRC7NU66
3D054225
3D052467
Note: ∗1. Wire for remote controller : Field supplied.

14.1.3 FDBG-NU

Standard
Accessories

1PN07524

Optional
Accessories
Kit Name
Name of Option Remark
FDBG18NU FDBG21 · 26NU
Remote Controller with 3 Minutes Timer KRC47-1
Digital Remote Controller with 3 Minutes Timer KRC47-2
Digital Remote Controller
With Switch for Duct Heater KRC47-4
with 3 Minutes Timer
Suction Grille KDGF19A45 KDGF19A71
Drain Pan Cover KKD19A1
4D048550A

Note: ∗1. If you use local remote controller, 3 minutes timer is necessary for the recycling guard of compressor.
∗2. Central controls using with VRV controller are available on request. Please consult DAIKIN.

SkyAir NU Series – Cooling Only – 117


Accessories ED24-631A

14.1.4 FDMG-NU

Standard
Accessories

1PN06319D

Optional
Accessories
Kit Name
Name of Option Remark
FDMG26~56NU
Remote Controller with 3 Minutes Timer KRC47-1
Digital Remote Controller with 3 Minutes Timer KRC47-2
Digital Remote Controller
With Switch for Duct Heater KRC47-4
with 3 Minutes Timer
4D054400
4D052569

Note: ∗1. If you use local remote controller, 3 minutes timer is necessary for the recycling guard of compressor.
∗2. Central controls using with VRV controller are available on request. Please consult DAIKIN.

14.2 Outdoor Unit


14.2.1 R-NU

Optional
Accessories Kit Name
Name of Option
R18NU R21NU R26~56NU
Drain Piping Kit - KIS95 -
Central Drain Plug - - KKPJ5F180
4D052475B

118 SkyAir NU Series – Cooling Only –


ED24-631A Remote Controller

15. Remote Controller


15.1 Operation
15.1.1 Wired Remote Controller : BRC1C61 (for FHC)
5 4 2 1

3
7 9
11
6
10
8 12
13 20
19

18

15 14 16 17 21

3PN07217-2A

SkyAir NU Series – Cooling Only – 119


Remote Controller ED24-631A

15.1.2 Wired Remote Controller : BRC1NU61 (for FH)

3PN07204-2

120 SkyAir NU Series – Cooling Only –


ED24-631A Remote Controller

15.1.3 Wireless Remote Controller : BRC7C613W (for FHC)

Fig.1 Fig.2

C : 3PA63363-4P

SkyAir NU Series – Cooling Only – 121


Remote Controller ED24-631A

15.1.4 Wireless Remote Controller : BRC7NU66 (for FH)

FIgure 1

3PN07204-1-4

122 SkyAir NU Series – Cooling Only –


ED24-631A Remote Controller

FIgure 2 (Explanation of Receiver)

3PN07204-1-5

SkyAir NU Series – Cooling Only – 123


Detail Explanation of Options ED24-631A

16. Detail Explanation of Options


16.1 Ceiling Mounted Cassette Type (Multi Flow) [FHC]
16.1.1 BYC125K–W1S — Decoration Panel

BEFORE INSTALLATION
PRECAUTIONS
• Refer also to the installation manual attached to the indoor unit.
ACCESSORIES
• Installation manual.

NOTE TO INSTALLER
Be sure to instruct the customer how to properly operate the system showing him/her the attached operation manual.

PREPARATION OF DECORATION PANEL


<<For this unit, you are able to select air flow directions. To discharge air in 2 or 3 directions, it is necessary to purchase optional
blocking pad kit.>>
HANDLING OF DECORATION PANELS
• Never place the panel facing down nor lean it against a wall nor leave it on a projecting object.
• Never touch or put pressure on the swing flap.
(The swing flap may malfunction.)
(1) Remove the suction grille from the decoration panel. 2) Detach the suction grille from the decoration panel by lifting the
1) Push the suction grille lever inward and lift up the lever side. grille up approximately 45 degrees. (Refer to Fig. 2.)
(Refer to Fig. 1.)

45˚

Lever

Fig. 1

(2) Remove the service cover on the corner. Fig. 2


Slide the service cover outward to remove. (Refer to Fig. 3.)

Fig. 3

124 SkyAir NU Series – Cooling Only –


ED24-631A Detail Explanation of Options

INSTALLATION OF THE DECORATION PANEL TO THE


INDOOR UNIT BODY
<<Refer to the installation manual attached to the indoor unit for the installation of the indoor unit.>>
(1) Set the decoration panel to the indoor unit body by matching the position of the swing flap motor of the decoration panel to the
piping position of the indoor unit as shown in Fig. 4.
(2) Install the decoration panel.
1) Temporarily install the decoration panel to the indoor unit by hanging the latch on the opposite side of the swing flap motor of
the decoration panel to the hook of the indoor unit body. (2 positions)
2) Temporarily hang the remaining 2 latches to the hooks on the sides of the indoor unit.
(Be careful not to let the swing motor lead wire get caught in the sealing material.)
3) Screw all 4 hexagon head screws located right beneath the latches in approximately 5 mm. (Panel will rise.)
4) Adjust the decoration panel by turning it to the arrowed direction in Fig. 4 so that the ceiling opening is completely covered.
5) Tighten the screws until the thickness of the sealing material between the decoration panel and the indoor unit body reduces
to 5–8 mm.
Indoor unit Sealing material

Ceiling material
5 ~ 8 mm

Decoration panel
Air outlet Hook

Latch 1)

2)
Piping position

2)

Swing flap motor

3)

4)

Fig. 4

PRECAUTIONS Air leak


• Improper screwing of the screws may cause the troubles shown in
Fig. 5. Screw properly.
Air leak from ceiling

Contamination Dew formation, dew dripping

Fig. 5

SkyAir NU Series – Cooling Only – 125


Detail Explanation of Options ED24-631A

• If gap is still left between the ceiling and the decoration panel after screwing
the screws, readjust the indoor unit body height. (Refer to Fig. 6.) Adjustment of the indoor unit body height from the
holes in the corner of the decoration panel is
possible if the indoor unit is kept leveled and the
drain piping, etc. is unaffected.

No gaps is allowed.

Fig. 6

(3) Wiring of the decoration panel (Refer to Fig. 7.)


6) Connect the connectors for swing flap motor lead wire
installed on the decoration panel.

If connectors are not connected, the malfunction


display (A7) appears on the remote controller.
Connect the connectors properly.

Make sure that the swing flap motor lead wire is


not caught between the indoor unit and the
decoration panel.

6)
Indoor Decoration
unit side panel side

áWiring Instruction Diagramñ


(It differs from the actual state.)
Fig. 7

INSTALLATION OF SUCTION GRILLE AND SERVICE COVER


(1) Install the suction grille.
Install by reversing the procedure shown in “PREPARATION OF DECORATION PANEL”.
It is possible to install the suction grille in 4 directions by turning the suction grille.
Change the direction when adjusting the direction of the suction grille of multiple units or in meeting customers’ demands.
NOTE)
Be careful not to get swing flap motor lead wire get caught when installing the suction grille.
(2) Install the service cover on the corner.
1) Attach the string of the service cover to the pin of the 2) Install the service cover over the decoration panel.
decoration panel as in Fig. 8.

Pin

Install the service cover by


sliding 4 latches to fit into the
holes on the decoration panel.

Fig. 8

126 SkyAir NU Series – Cooling Only –


ED24-631A Detail Explanation of Options

16.1.2 KDBHJ55K160 — Sealing Member of Air Discharge Outlet


Caution
zRefer to the installation manual for both indoor unit and the decoration panel.
zWhen you install other optional kit, it may not be possible to select the 3-way or 2-way air discharge. For details, refer to the
manual for the optional kit or the catalogue.
zContents of Kit Prior to installation make sure you have the complete kit of parts.
Name Sealing material(A) Sealing material(B) Sealing material(C) Sealing material(D)
Quantity 1 piece 1 piece 1 piece 1 piece

Shape
and
marking

Name Insulation for top plate Insulation for side plate Moisture absorber for bell-mouth Moisture absorber for horizontal vane

Quantity 1 piece 1 piece 1 piece 2 pieces 1 piece 2 pieces 1 piece 5 kinds

Shape
and
marking

J : 1P012222B

SkyAir NU Series – Cooling Only – 127


Detail Explanation of Options ED24-631A

3 Installation of the insulation


(1) Installation to the side plate
Adhere insulation for side plate to the side of indoor unit.
26 class 48 class

Put the wire


through the slit of When adhering When adhering
the insulation. insulation, align its edge insulation, align its edge
with the bottom line of with the bottom line of
casing. casing.

(2) Installation to the top plate (3) Adhere the moisture absorber for horizontal vane to the
Adhere insulation for top plate , to the top of the indoor unit. edge of the horizontal vane of air outlet (Fig. 2).
(Choose the same color as panel.)
Horizontal vane

Moisture absorber
for horizontal vane
Fig. 2
Align it with the upper edge of horizontal vane.

Horizontal
vane
Fig. 1 Moisture absorber
for horizontal vane

(4) Adhere the moisture absorber in accordance with the


reference surface without wrinkles. (Fig. 4)
Adhere the moisture absorber in accordance with the
reference line . (Fig. 5)
Reference surface

Swing connector
Adhere it from the edge of (Fig. 3)
Swing motor
switch box.
reference
Sticking

Switch box

Bellmouth

Sticking reference

Fig. 4 Fig. 5
JC : 1P012222B

128 SkyAir NU Series – Cooling Only –


ED24-631A Detail Explanation of Options

16.1.3 KDBP55H160WA — Panel Spacer


Installation

1P136564E

SkyAir NU Series – Cooling Only – 129


Detail Explanation of Options ED24-631A

1P136564E

130 SkyAir NU Series – Cooling Only –


ED24-631A Detail Explanation of Options

16.1.4 KDDP55D160(K) — Fresh Air Intake Kit (Chamber Type)


Installation

SkyAir FHC18~48NU

18~26NU 240
36~48NU 298

C : 3K011144A

SkyAir NU Series – Cooling Only – 131


Detail Explanation of Options ED24-631A

3K011144A

132 SkyAir NU Series – Cooling Only –


ED24-631A Detail Explanation of Options

SkyAir NU Series – Cooling Only – 133


Detail Explanation of Options ED24-631A

16.1.5 KDDJ55X160 — Fresh Air Intake Kit (Direct Installation Type)


The fresh air is taken into the unit by the indoor unit fan or duct fan, which is field supplied. The location of fresh air intake port will be
changeable by installing the duct fan.
Dimension

J : D3K2175

Installation

2P066796C

134 SkyAir NU Series – Cooling Only –


ED24-631A Detail Explanation of Options

2P066796C

SkyAir NU Series – Cooling Only – 135


Detail Explanation of Options ED24-631A

16.1.6 KAFP556D80 · 160 — High–Efficiency Filter (Including Filter Chamber)


KAFP557D80 · 160 — High–Efficiency Filter (Including Filter Chamber)
Combination table
High–Efficiency Filter (Set) Replacement High–Efficiency Filter High–Efficiency Filter Chamber
KAFP556D80 KAFP552H80
KAFP557D80 KAFP553H80
KDDFP55D160
KAFP556D160 KAFP552H160
KAFP557D160 KAFP553H160
16.1.7 KAFP552H80 · 160 — Replacement High–Efficiency Filter
KAFP553H80 · 160 — Replacement High–Efficiency Filter
Specifications
Replacement High–Efficiency Filter KAFP552H80 KAFP552H160 KAFP553H80 KAFP553H160
High–Efficiency Filter Chamber KDDFP55D160
Collecting Efficiency (%) 65% (NBS Colorimetric method) 90% (NBS Colorimetric method)
Initial Pressure Loss (Pa) 34 or less
Final Pressure Loss (Pa) 98 or less
Filter Non–woven Fabric of Synthetic Fiber Non–woven Fabric of Synthetic Fiber
Life (h) 2,500 h (Dust Concentration 0.15 mg / m3) 1,800 h (Dust Concentration 0.15 mg / m3)
Models to be Applied 18~26NU 36~48NU 18~26NU 36~48NU
Precaution at use
1. The high–efficiency filter, and the other filter can not be installed together.
2. The unit should be operated with 4-way discharge when the high–efficiency filter is installed.
It can not be applied to the high ceiling room.
3. Field setting by remote controller is necessary when the high–efficiency filter is installed.

Dimension
560
560

10 540 -20 10
AA

Model AA
KAFP552H80, KAFP553H80 25
KAFP552H160, KAFP553H160 45
J : D3K04256A

16.1.8 KRP1B98 — Installation Box for Adaptor PCB


Dimension Model No.
KRP1B98
Item
Applicable Model FHC18~48NU
KRP1B57
Adaptor for Wiring
KRP4A53

D3K2169

136 SkyAir NU Series – Cooling Only –


ED24-631A Detail Explanation of Options

16.1.9 KDDFP55D160 — High–Efficiency Filter Chamber


Installation

SkyAir FHC18~26NU

SkyAir FHC36~48NU

C : 3K011148B

SkyAir NU Series – Cooling Only – 137


Detail Explanation of Options ED24-631A

3K011148B

138 SkyAir NU Series – Cooling Only –


ED24-631A Detail Explanation of Options

16.1.10 KAFJ551K160 — Replacement Long–Life Filter for Decoration Panel


Specifications
Collecting Efficiency (%) 65 (Gravity Method)
Initial Pressure Loss (Pa) 8 or less
Final Pressure Loss (Pa) 49 or less
Filter Mildew–Proof Resin Net
Number of Sheets Included 1
Life (h) 2,500 h (Dust Concentration 0.15 mg / m3)
Models to Be Applied 18~48NU
J : D3K2170C

16.1.11 KAFP55D160, KAFJ55K160H (Replacement) — Ultra Long–Life Filter


(Including Filter Chamber)
Specifications
Ultra Long–Life Filter KAFP55D160 Precaution at use
Replacement Ultra Long–Life Filter KAFJ55K160H 1. The Ultra long–life filter, and other filter can not be installed
High–Efficiency Filter Chamber KDDFP55D160 together.
Collecting Efficiency (%) 50 (Gravity Method) 2. Field setting by remote controller is necessary when the Ultra
Initial Pressure Loss (Pa) 8 or less
long –life filter is installed.
Refer to the installation manual of Ultra long–life filter for
Final Pressure Loss (Pa) 49 or less
setting.
Filter Mildew–Proof Resin Net 3. Filter cleaning period can not be displayed on the monitor when
5,000 h the Ultra long–life filter is installed.
Life (h)
(Dust Concentration 0.3 mg / m3)
Refer to the left table and clean (with water) the filter
Models to Be Applied 18~48NU periodically.
J : D3K2174A

Installation Iocation Filter Cleaning Period

Dirty Area Every 5,000 hrs

Not Dirty Area Every 10,000 hrs

SkyAir NU Series – Cooling Only – 139


Detail Explanation of Options ED24-631A

16.1.12 KKSJ55K160 — Chamber Connection Kit


Dimension

J : D3K2186

Installation

3P089651C

140 SkyAir NU Series – Cooling Only –


ED24-631A Detail Explanation of Options

16.1.13 KDJ55K80 · 160 — Branch Duct Chamber


Installation

SkyAir NU Series – Cooling Only – 141


Detail Explanation of Options ED24-631A

142 SkyAir NU Series – Cooling Only –


ED24-631A Detail Explanation of Options

16.2 Ceiling Suspended Type [FH]


16.2.1 KAFJ501D80 · 160 — Replacement Long–Life Filter
Specifications
Model
KAFJ501D56 KAFJ501D80 KAFJ501D112 KAFJ501D160
Item
Effective Life, Average Efficiency 2,500 hours (at Dust Particle Concentration of 0.15 mg/m3 ), 45% (by Weight Method)
Initial Pressure Loss (Pa) 10 or less
Final Pressure Loss (Pa) 59 or less
Filter Materials Mold Prevention Resin Net Mold Prevention Resin Net
Nos. Required 2 pieces 3 pieces
Applicable Model - 21 · 26NU - 36~48NU
J : D3K3074A

16.2.2 KHFJ5F80 · 160 — L–Type Piping Kit


Application purpose
This kit must be bent inside the unit as shown below, when the refrigerant piping is carried out in a ceiling
space. This L shape kit is an optional accessory which has been developed for improving the work of the
processing on site.

Model
Item KHFJ5F50 KHFJ5F60 KHFJ5F80 KHFJ5F160

Applicable Model - - 21 · 26NU 36~48NU

KHFJ5F50~160 Installation

SkyAir NU Series – Cooling Only – 143


Detail Explanation of Options ED24-631A

16.3 Duct Connection Low Static Pressure Type [FDBG]


16.3.1 KKD19A1—Drain Pan Cover
Installation

FDBG18·21·26NUV1

C : 1P067376A

144 SkyAir NU Series – Cooling Only –


ED24-631A Detail Explanation of Options

16.4 Outdoor Unit


16.4.1 KIS95 — Drain Piping Kit
Use this plug to connect a drain hose to an outdoor unit.

„ Outlook
KIS95

KIS95
Drain piping
(With Y joint)
„ Drain hose connection dia φ16ID. plug (3 pcs.)

Note: 1. This is the joint for attaching a vinyl hose (field supplied).
This is used between the drain hole which is on the bottom plate of outdoor unit and vinyl hose.
2. Drain water accumulate to the bottom of outdoor unit it depends on the situation of operation. But it is
necessary to connect drain hose not to be spread the drain water over the neighbors, when it is installed
on the wall.
3. The position of holes are unfit to connect with outdoor units in some models.
In this case, use it without Y joint.

16.4.2 KKPJ5F180 — Central Drain Plug

SkyAir NU Series – Cooling Only – 145


Warning Daikin Industries, Ltd.’s products are manufactured for export to numerous countries throughout the
world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a
particular country. Prior to purchase, please therefore confirm with your local authorized importer,
distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for
use, in the region where the product will be used. This statement does not purport to exclude, restrict
or modify the application of any local legislation.
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorized parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any inquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided.

About ISO9001 About ISO 14001


ISO 9001 is a plant certification system ISO 14001 is the standard defined by the
defined by the International Organization International Organization for Standardization
for Standardization (ISO) relating to (ISO) relating to environmental management
quality assurance. ISO 9001 certification systems. Our group has been acknowledged
covers quality assurance aspects related by an internationally accredited compliance
to the “design, development, organisation as having an appropriate
manufacture, installation, and programme of environmental protection
supplementary service” of products procedures and activities to meet the
JMI-0107 JQA-1452 manufactured at the plant. EC99J2044 JQA-E-90108 requirements of ISO 14001.

Dealer
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global/
c All rights reserved

Specifications, designs and other content appearing in this brochure are current as of July 2006 but subject to change without notice. Printed on 100% recycled paper with soy ink.

ED24-631A
Printed in Japan 08/2006 K FS