Professional Documents
Culture Documents
Micom P541 and P542: Current Differential Protection
Micom P541 and P542: Current Differential Protection
X 50N/
87 50/51 49
51N
IE sen
IM
Neutral current
from parallel line
(if present)
Differential Ia Ib
current
| I diff |
Ic
Trip
Percentage
bias k2
Percentage
bias k1
Restrain
I S1
I S2 Bias current
| I bias |
| I diff| = | I a + I b + I c |
| I bias| = 0.5 ( |I a| + | I b| + | I c |)
The relay operates when
Multiplexed
TOPOLOGY link
P540 Optical fibers PCM
Differential protection requires the transfer of MUX
current vectors between all ends of the scheme. Other protection
and telecommunication
Figures 3a - 3d show typical configurations. equipment
Figure 3a shows an HV/EHV scheme whereby
either a direct fiber optic, or a multiplexed link P590
Electrical
may be used as the chosen channel. Figure 3b Optical fibers
connections
shows the triangulated connection required in P540 Multiplexed
link
PCM
3-terminal applications. MUX
Transformers
Electrical Multiplexed
P590 P590
interface link
Figure 4 shows a protected line and transformer
Figure 3a Application to 2 terminal lines
“unit”. In such applications the P541 or P542 are
chosen, as these models compensate for the
vector group shift and zero sequence filtering
effects of the in-zone transformer. Second
harmonic restraint is used to stabilize the
protection against magnetizing inrush currents.
P540 P540 Where transformer loads are tapped off the
protected line, it is not essential to install CTs at
P540 the tap. There exists the facility to time grade the
differential protection with downstream relays or
fuses. The internal autoreclose function can be
Figure 3b Upgrade to 3 terminal lines used to implement fuse-saving schemes in the
latter case, improving supply availability.
1550nm single-mode 80
time (s)
Communications supervision
Dependable communications are essential for 1
IEEE-MI
highperformance differential protection. Each
IEEE-VI
active longitudinal channel is independently
US CO2
monitored, and reports error statistics in line with
guidance from ITU-T G.821. US COB
IEEE-EI
0.1
Various means exist to implement “hot-standby” 1 10 100
protection in the event of degraded Current (Multiples of Is)
communications. Dual redundant communications
channels could be considered, whereby there Figure 5 IEC & IEEE/ANSI IDMT
are duplicated links, via diverse communications
paths. In such instances, CH1 and CH2 protection
channels will both be used. Alternatively, back-up
distance or overcurrent elements can be switched
into service (either as permanent parallel main Differential protection calibrated in
protection, or temporary protection only during the differential plane - no compromise
channel outages). on sensitivity
Protection Relays MiCOM P541 and P542 06
Trip and close commands are facilitated from Power system measurements
front panel “hotkeys”, to allow direct CB control
Instantaneous and time integrated voltage, current
without the need to navigate a menu. Other in/
and power measurements are provided. These
out, on/off and enable/disable controls are easily
may be viewed in primary, or secondary values.
programmed.
Autoreclose with check synchronism
The user may select a single, two, three or
four shot autoreclose cycle.
Programmable scheme logic
Powerful graphical logic allows the user to
customize the protection and control functions.
The gate logic includes OR, AND and majority
gate functions, with the ability to invert the inputs
and outputs, and provide feedback. The system is
optimized to ensure that the protection outputs are
not delayed by the PSL operation.
The programmable scheme logic is configured
using the graphical MiCOM S1 PC software, as
shown in Figure 6.
The relay outputs may be configured as latching
(e.g. “Lockout”) or self-reset.
Schneider Electric
35, rue Joseph Monier As standards, specifications and designs change from time to time, please ask for confirmation
CS 30323 of the information given in this publication.
92506 Rueil-Malmaison Cedex, France
Tel: +33 (0) 1 41 29 70 00 This document has been printed
on ecological paper
RCS Nanterre 954 503 439
Capital social 896 313 776 € Publishing: Schneider Electric
www.schneider-electric.com Design: Schneider Electric
Printing:
EnergyAutomation-DS-P542-1749-EN 10-2010