Huawei Data Center Facility Solutions Datasheets
Huawei Data Center Facility Solutions Datasheets
FusionModule2000
Smart Modular Data Center Solution
INTRODUCTION
Huawei FusionModule2000 is a new generation smart modular data center solution,
which dedicated to providing customers with simple, efficient, and reliable data
center solutions.
It's a modular-designed, highly integrated solution which comprises power supply,
cooling, rack & structure, cabling and management system within a module,
meeting the requirements for quick delivery and on-demand deployment.
Furthermore, the Huawei smart module uses the i3 intelligent management to
comprehensively improve the reliability and efficiency of power supply and cooling
system. This significantly improves data center availability and O&M efficiency.
Standard Dual- row
APPLICATION SCENARIOS
• The FusionModule2000 uses an air-cooled cooling system and is mainly applicable
to small- and medium-sized data centers. The solution features simple design and
high building adaptability, lowering the requirements of room height and
reconstruction. It meets the data center deployment requirements of various
sectors such as enterprise headquarters and large branches, bank headquarters
and secondary branches, governments, carriers, education, and healthcare.
FEATURES
Simple
• Modular design, one module one DC, on-demand deployment and flexible
expansion Standard Dual-row Smart Screen
Green Version*
• iCooling intelligent optimization*, reducing the energy consumption of cooling
system by 8% to 15%
• SmartLi Inside* supports Huawei smart lithium batteries deployed in the
module. Compared with traditional lead-acid batteries, footprint is reduced by
70% under the same load and same backup time
• Wet film humidification*: Compared with traditional electrode humidifiers, wet
film humidifiers reduce energy consumption by 95%
• Industry's first air-cooled smart modular DC PUE test and certification, the
annual average PUE is as low as 1.111 @Beijing
Smart
• iManager: Space, Power, Cooling (SPC) visualization, automatic asset
management simplified O&M
• 3D view* clear display of key information and alarms about power distribution
and cooling system, automatic management of assets*, automatic asset
tracking, and no manual counting
• Local 43-inch smart screen * intuitive display of intelligent features,
simplifying O&M
Reliable
• iPower: Visualization of power supply chain, fault auto-locating and auto Simplified Single-row
shutdown for proactive protection
• SmartLi Inside* :Three-layer BMS ensure the reliability of lithium batteries
• Innovative intelligent refrigerant leakage detection prevents cooling capacity
decrease or air conditioner breakdown *Optional Features
FusionModule Series FusionModule2000 Smart Modular Data Center
SPECIFICATIONS
Item Specifications
Single row (with aisle containment) (L×W×H):
L×2400×2410mm;L×1350×2000mm;L×1600×2000mm
Dimensions
Dual row (with aisle containment) (L×W×H): L×3600×2410mm; L×3400×2410mm;
L×3600×2610mm
Cabinets per module Single row≤24 cabinets; dual row: ≤48 cabinets
Power supply 380/400/415VAC, 50/60Hz, 3Ph+N+PE
Micro Module 180kW (with integrated UPS)/ 145kW (with integrated PDC)/ 310kW (with New main way)/
Max IT load per module
310kW (with precision PDC)
Ultra low temperature condition: -40ºC to 45ºC(Need low-temp kit)
Operation condition
T1 condition: -20ºC to 45ºC; T3 condition: -5ºC to 55ºC(Need T3 outdoor unit)
Cable routing Routed in/out through the top of cabinets
Installation Installing on concrete floor or raised floor
2000mm×600/800mm×1200mm; 2000mm×600mm×1100mm;
Dimensions (H×W×D)
2200mm×600/800mm×1200mm
Integrated power Input IT: 160A/250A MCCB; A/C: 160A/250A MCCB (single/dual input)
distribution Rated input current IT: 160A/250A, Air conditioner: 160A/250A
cabinet (UPS Output IT: 2×24×40A/1P; 2×24×63A/1P;2×8×40A/3P;A/C: 40A/3P×8 or 63A/3P×8 ; lighting:
outside) 10A/1P×3
AC SPD 20kA, 8/20μs
Cooling
Smart
Cooling
Smart
Cooling
Smart
IT IT IT IT IT IT IT IT IT IT IT IT IT
Aisle Containment
cabinet
Battery
cabinet
Battery
UPS
Integrated
Cooling
Smart
Cooling
Smart
IT IT IT IT IT IT IT IT IT IT IT
30 25kW×2
40 25kW×3
60 35kW×3
150 65kW×4
180 65kW×5
FusionModule Series FusionModule2000 Smart Modular Data Center
UPS Outside the Module(Precision PDC ) UPS Outside the Module(Smart Busway)
Cooling
Smart
Cooling
Smart
Cooling
Smart
Cooling
Smart
Cooling
Smart
Cooling
Smart
IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT
R24-140kW R24-140kW
(aisle) (aisle)
Cooling
Smart
Cooling
Smart
Cooling
Smart
Cooling
Smart
Cooling
Smart
Cooling
Smart
PDC
Precision
IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT IT
R24 Typical Layout of Dual-Row (Precision PDC) R24 Typical Layout of Dual-Row (Smart Busway)
30 35kW×2
40 25kW×3
Integrated PDC/ Integrated PDC/
60 Precision Power 35kW×3
PDC/Smart Distribution Box
90 35kW×4
Busway
120 46kW×4
145 65kW×4
Introduction
The PowerPod integrates the full-power link between the medium-
voltage transformer and the load feeder,it provides a MW-level
integrated power supply, distribution, and backup solution for
large-scale data centers. The integrated design and high-density
components are integrated to reduce the footprint of the power
system. Prefabrication, reduce engineering, reduce the delivery
complexity and shorten the deployment duration. The iPower
intelligent feature implements visualized management and
predictive maintenance of the entire chain, ensuring system
security.
Scenarios
• Indoor power supply and distribution system of the data center
in traditional building.
Green
• Full-link convergence, Footprint reduces 40%+
• Power link efficiency is up to 95.6% (97.8% Smart Online Mode)
Smart·Reliable
Specifications
Scenario FusionPower6000 for IT only (Indoor) FusionPower6000 for IT & Motive(Indoor)
Transformer
3Ph+PE, 10kV AC 50/60Hz
Power input
Transformer
3Ph+N+PE, 380 V AC/400 V AC/415 V AC, 50 Hz/60 Hz
Power output
Default bus tie switch: Default when left-in and right-out layout; not configured when right-in and
Main input switch left-out layout
Main input: 4000A/3P Main input: 3200A/3P Main input: 4000A/3P Main input: 3200A/3P
/Bus tie switch
Bus tie: 2500A/4P Bus tie: 2000A/4P Bus tie: 2500A/4P Bus tie: 2000A/4P
0 to 5 modules can be configured
Power supply SVG/APF SVG 100kVar/module
and distribution
APF 100A/module
UPS5000-H- UPS5000-H-500kVA UPS5000-H-600kVA UPS5000-H-500kVA
UPS for IT
600kVA*4PCS *4PCS *3PCS *3PCS
UPS5000-H-500kVA UPS5000-H-400kVA
UPS for Motive / /
*1PCS *1PCS
Maintenance
4000A/3P 3200A/3P+800A/3P 2500A/3P+800A/3P
bypass switch
2*400A/3P+160A/3P+ 400A/3P+250A/3P+ 800A/3P+160A/3P+ 800A/3P+160A/3P+
Utility power
Feeder for Motive
100A/3P 160A/3P+100A/3P 100A/3P 100A/3P
The feeder cabinet is configured based on project requirements. The maximum capacity of a
single feeder cabinet is as follows:
UPS Feeder for IT
250A 3P * 18; Or 400A 3P * 7; Or 630A 3P * 7;
Power monitoring
Monitoring ECC for centralized management
system
External
dimensions (H x
W x D)(not 2475×9600×1500 2475×9600×1500 2475×10200×1500 2475×10200×1500
includes the
Structure feeder cabinet)
• Directly install on the ground
Installation mode
• Assemble and install on the base onsite
Operating
0℃~+40℃
temperature
Storage
–40℃~+70℃
temperature
Environmental
Ambient humidity ≤ 95% RH (non-condensing)
requirements
Application
Class A environment
environment
0–4000 m. When the altitude is greater than 1000 m, the power is derated according to the
Altitude
industry standard.
UPS5000-H Series
(400-1600 kVA) 3P4W
Introduction
UPS5000-H is Huawei‘s medium and large-scale uninterruptible power
supply system with advanced 100kVA/3U hot swappable power
modules. The system achieves 1 MW,1 rack, effectively saves footprint
and installation time. System efficiency is up to 97%. Intelligent iPower
improves system reliability and simplifies operation and maintenance
for customers. The S-ECO(Super ECO) mode achieves not only 99.1%
efficiency and optimal power quality but also 0ms mode transferring.
Power Module: 100kVA/3U
Application Scenarios
• Data centers in headquarter or disaster recovery data centers
• Internet data centers
• Large cloud computing data centers
Smart
• iPower pre-warnings for key components by AI method
• Source share of main and battery achieves intelligent peak shaving,
eliminating the reconstruction of grid.
UPS5000-H- UPS5000-H-1600kVA
Reliable 1200kVA
• Redundant architecture eliminates single point of failure
• S-ECO mode: non-interruptible mode transferring.
FusionPower UPS5000-H-(400-1600kVA)
Specifications
Model UPS5000-H-300k
Rack capacity 300kVA
Capacity
Module number 2-6 (100k power module derating to 50kVA)
Input wiring 3PH+N+PE
Rated voltage 200/208/210Vac
Voltage range 138-260Vac (100% load: 170-260V)
Mains input
Frequency range 40-70Hz
Total harmonic distortion THDi<3% for 100% linear load
Input power factor 0.99
Input wiring 3PH+N+PE
Bypass input Rated voltage 200/208/210Vac
Input frequency 50/60±6Hz
180-600Vdc (the number of VRLA can be selected from 15 to 50; 20 batteries rated, no
Rated voltage battery neutral, support odd battery number);
512Vdc(Huawei SmartLi)
Maximum charge capacity
Battery Single power module: 15%, 30A
and current
Battery category Huawei SmartLi, VRLA
Battery sharing Support (VRLA)
Output wiring 3PH+N+PE
Voltage 200/208/210Vac±1%
Frequency Tracking the bypass input (normal mode); 50/60hz±0.05% (battery mode)
Output
THDv THDv<2% for linear load
Inverter: 100%<load≤110% for 60 minutes, then transfer to bypass mode; 110%<
Overload capacity load≤125% for 10 minutes, then transfer to bypass mode; 125%<load≤150% for 1 minute,
then transfer to bypass mode
Output power factor 1
Efficiency Up to 94.5%
System
Source share mode Support main input and battery joint operating
Parallel 2
Operating temperature 0-40ºc
Storage temperature -40-70ºc
Environment
Relative humidity 0%-95% (no condensing)
Operating altitude 0-2000m. Above 2000m, derating based on EN/IEC 62040-3
Weight 800kg
H*W*D(mm) 2000*800*1000
Others Standards: EN/IEC 62040-1, EN/IEC 62040-2, EN/IEC 62040-3
Standards and certifications
Certifications: CE; CB; RoHS, REACH, WEEE, etc.
Communications ports and Communications ports: dry contacts, RS485, FE
protocol Communications protocol: web, Modbus and SNMP
Note: Tier4 or Tier3 levels specified in TI942 are required, that two UPSs form a dual bus or a UPS and utility form dual bus for i mportant systems related to
major economy or public safety, such as civil aviation management centers, financial liquidation centers and trading centers, etc.
Specifications
Model UPS5000-H-400/500/600k UPS5000-H-800k UPS5000-H-1200k UPS5000-H-1600k
Rack capacity 400/500/600kVA 800kVA 1200kVA 1600kVA
Capacity
Module number 2-4/2-5/2-6 2-8 2-12 2-16
Input wiring 3PH+N+PE
Rated voltage 380/400/415Vac
Voltage range 138-485Vac (100% load: 323-485V)
Mains input
Frequency range 40-70Hz
Normal mode: THDi<3% for 100% linear load
Total harmonic distortion
S-ECO mode: THDi<3% for 100% linear load
Input power factor Normal mode: 0.99; S-ECO mode: 0.99
Input wiring 3PH+N+PE
Bypass input Rated voltage 380/400/415Vac
Input frequency 50/60±6Hz
360-600Vdc (the number of VRLA can be selected from 30 to 50; 40 batteries rated, no battery
Rated voltage neutral, support odd battery number);
512Vdc(huawei SmartLi)
Maximum charge capacity and
Battery Single power module: 15%, 30A
current
Battery category Huawei SmartLi, VRLA
Battery sharing Support (VRLA)
Output wiring 3PH+N+PE
Voltage 380/400/415Vac±1%
Frequency Tracking the bypass input (normal mode); 50/60hz±0.05% (battery mode)
Output
THDv THDv<1% for linear load
Inverter: 100%<load≤110% for 60 minutes, then transfer to bypass mode; 110%<load≤125%
Overload capacity for 10 minutes, then transfer to bypass mode; 125%<load≤150% for 1 minute, then transfer to
bypass mode
Output power factor 1
Normal mode: up to 97%
Efficiency
System S-ECO mode: up to 99%
Source share mode Support main input and battery joint operating
Parallel 4 4 4 2
Operating temperature 0-40ºc
Storage temperature -40-70ºc
Environment
Relative humidity 0%-95% (no condensing)
Operating altitude 0-2000m. Above 2000m, derating based on EN/IEC 62040-3
Weight 580kg/690kg/800kg 1300kg 1600kg 2300kg
H*W*D(mm) 2000*800*1000 2000*1600*1000 2200*1600*1000 2200*2400*1000
Others Standards: EN/IEC 62040-1, EN/IEC 62040-2, EN/IEC 62040-3
Standards and certifications
Certifications: CE; CB; rohs, REACH, WEEE, etc.
Communications ports and Communications ports: dry contacts, RS485, FE
protocol Communications protocol: web, Modbus and SNMP
Note: Tier4 or Tier3 levels specified in TI942 are required, that two UPSs form a dual bus or a UPS and utility form dual bus for i mportant systems related to major
economy or public safety, such as civil aviation management centers, financial liquidation centers and trading centers, etc.
Specifications
Model UPS5000-H-800k
Rack capacity 800kVA
Capacity
Module number 2-8
Input wiring 3PH+N+PE
Rated voltage 480Vac
Voltage range 192-528Vac (100% load: 384-528V)
Mains input
Frequency range 40-70Hz
Total harmonic distortion THDi<3% for 100% linear load
Input power factor 0.99
Input wiring 3PH+N+PE
Bypass input Rated voltage 480Vac
Input frequency 50/60±6Hz
360-600Vdc (the number of VRLA can be selected from 30 to 50; 40 batteries rated, no
Rated voltage battery neutral, support odd battery number);
512Vdc(huawei SmartLi)
Maximum charge capacity
Battery Single power module: 15%, 30A
and current
Battery category Huawei SmartLi, VRLA
Battery sharing Support (VRLA)
Output wiring 3PH+N+PE
Voltage 480Vac±1%
Frequency Tracking the bypass input (normal mode); 50/60hz±0.05% (battery mode)
Output
THDv THDv<1% for linear load
Inverter: 100%<load≤110% for 60 minutes, then transfer to bypass mode; 110%<
Overload capacity load≤125% for 10 minutes, then transfer to bypass mode; 125%<load≤150% for 1
minute, then transfer to bypass mode
Output power factor 1
Efficiency Up to 97%
System
Source share mode Support main input and battery source share
Parallel 1
Operating temperature 0-40℃
Storage temperature -40-70℃
Environment
Relative humidity 0%-95% (no condensing)
Operating altitude 0-2000m. Above 2000m, derating based on EN/IEC 62040-3
Weight 1300kg
H*W*D(mm) 2000*1600*1000
Others Standards: EN/IEC 62040-1, EN/IEC 62040-2, EN/IEC 62040-3
Standards and certifications
Certifications: CE; CB; rohs, REACH, WEEE, etc.
Communications ports and Communications ports: dry contacts, RS485, FE
protocol Communications protocol: web, Modbus and SNMP
Note: Tier4 or Tier3 levels specified in TI942 are required, that two UPSs form a dual bus or a UPS and utility form dual bus for i mportant systems related to major
economy or public safety, such as civil aviation management centers, financial liquidation centers and trading centers, etc.
INTRODUCTION
Indirect evaporative cooling is a free cooling solution applied in data centers. Huawei
FusionCol8000-E indirect evaporative cooling product is prefabricated with DX cooling and
key functional components. In addition, the solution implements convergence of cooling ,
power and AI energy efficiency optimization, helping to build a new-generation simple, green,
smart, and reliable cooling solution.
FusionCol8000-E260H4
WORKING PRINCIPLES
The air-to-air heat exchanger uses external cold air and water spray evaporation to
dissipate heat for the data center.
Exhaust air to
outdoor
Return air from
data center
Switching points
Dry bulb>16℃
are automatically
Spray Mode and wet ON ON OFF
switched based
bulb≤19℃
on load changes.
Hybrid
wet bulb>19℃ ON ON ON
Mode
APPLICATION SCENARIO
• ISP
• Carrier IDC
• Cloud data center
01 Side installation
02 Rooftop installation
03 Indoor installation
Exhaust pipe
Simple 50%
• Integrated all-in-one system. Optional Less TTM
components humidifier, 2-in-1 damper for
fireproof and block, saving 50% TTM. 15%
• Integrated cooling-power architecture, Less footprint of power
supply system
reducing footprint by removal of UPS.
• Modular fan driver module, maintained in one 1 min
minutes. Maintenance on modular
fan driver
Green 0.15
• High efficiency polymer air-air heat Low CLF by free cooling
exchanger and spray system for optimized
free cooling. CLF=0.115@London 6%
• EC fan: Separated architecture, improving Higher fan efficiency
air volume by 45% and efficiency by 6%
• Wet-film humidifier : 0 power consumption
0
Humidification power
Smart 15 min
Fault diagnosis
• Automatic fault diagnosis in 15 minutes.
• iCooling optimization technology helps to 8%
reduce CLF by accurate response to IT load. Lower CLF by iCooling
Reliable
• Dual power supply & No compressor restart 0 fluctuation
and 0 temperature fluctuation during power During power switch
switch. <5%
• Operating harmonic THDi<5% THDi
• Spray water pipe equipped with ultraviolet
sterilization, sterilization rate up to 99.99% 99.99%
• Indoor air is completely isolated from out Ultraviolet sterilization
door free cooling sources, preventing
affecting indoor environment.
0
Air pollution from outdoor
SIMPLE
240 days
120 days
02 Integration of cooling&power, no need for UPS, simplified power distribution link, 12% less
CAPEX, 18% less footprint
VS
12% less CAPEX,18% less footprint
Main control module hot swap maintenance Fan driver module hot swap maintenance
GREEN
01 High efficiency polymer heat exchange core. Full utilization of free cooling source.
CLF≤0.115@London
02 High-efficiency EC fan: separated architecture, improving air volume by 45% and efficiency
by 6% compared with a common EC fan.
AeroTube blade
SMART
RELIABLE
Antifreeze protection mode is enabled Minimum speed of fan Inclined heat exchanger
temperature lower than 5 ℃ set to 15% Downwind drainage
Compressor and EC fan run continuously without shutting down during power switch, complying with continuous
cooling requirements of Tier IV.
KEY COMPONENTS
Polymer heat exchange core
High-efficiency EC fan
• A self-developed high-speed fan is used, which features large air volume, high
static pressure, high reliability, and a long service life;
• The fan is separated from the drive. Its efficiency is improved by more than 6%
compared with a common EC fan;
• The direct drive that the fan adopts has higher transmission efficiency than the
belt drive, which reduces belt replacement and routine checks.
Water pump
• A horizontal three-stage centrifugal pump is used, which features high pump lift,
small size, high reliability, and long service life;
• The water pump is made of new lubrication sealing material. Wear parts such as
water pump spindle seal and seal ring do not need to be maintained in the life
cycle;
• The N+1 redundancy design ensures cooling supply.
• The main control module and fan drive module support hot swap maintenance,
which avoids the impact of traditional fan shutdown and maintenance on the
equipment room environment, greatly saving the O&M time;
• The fan drive is separated from the fan, improving the system reliability.
Display module
• The 7-inch TFT touch screen is used to provide a human-machine interface for
query, setting, monitoring and maintenance;
• Displays the temperature and humidity curve for 30 days, enabling O&M
personnel to view the unit running status on site.
TECHNICAL SPECIFICATIONS
Model FusionCol8000-E260
Water pipe connection Spray water drainage DN40, G 1-1/2in internal thread
Remarks:
• Cooling performance condition: Indoor return air DB 38℃, indoor supply air DB 25℃. Outdoor air DB 35℃, outdoor air WB≤27℃.
• It is recommended to select the cooling capacity based on the extreme climate in 20 years.
TECHNICAL SPECIFICATIONS
Model FusionCol8000-E260
Remarks:
• Cooling performance condition: Indoor return air DB 38℃, indoor supply air DB 25℃. Outdoor air DB 35℃, outdoor air WB≤27℃.
• It is recommended to select the cooling capacity based on the extreme climate in 20 years.
Copyright © 2022 Huawei Digital Power Technologies Co., Ltd. All rights reserved.