LABORATORY TEST SUMMARY SHEET

Client : Power Grid Company Of Bangladesh Limited (PGCB).


Project : Design, Supply, Installation, Testing & Commissioning Of Rooppur Dhaka (Aminbazar- Kaliakoir) 400kv Double Circuit
Transmission Line On Turnkey Basis (Package-2).
Location : Rooppur - Dhaka.

Borehole No. T-13/0


Sample No. D- 3 D- 15 D- 19 UD-1
Depth (m) 4.5 22.5 28.5 5.55
Natural moisture content, % 32.32
Specific gravity 2.69
Gravel % 0.00 0.00 0.00
Sand % 3.84 78.02 83.34
Grain size
Silt % 77.74
21.98 16.66
Clay % 18.42
qu , (KN/m2) 49.46
Unconfined Strain (%) 11.25
Compression Test Wet Density, (KN/m3) 18.14
Dry Density, (KN/m3) 13.71
Liquid limit 38.00
Atterbarg limit Plastic limit 23.00
Plasticity index 15.00
ø (Degree) 29.00 34.00
Direct Shear Test
c (KN/m2) 0.00 0.00
Initial void ratio, eo
Consolidation Test
Coefficient of Index, Cc