Rru-1 - Ul 924 Remote Relay Unit: Ilumin

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Technical Data iLumin

RRU-1 – UL 924 Remote Relay Unit

Catalog# Prepared by Overview


Project Date
The The Remote Relay Unit (RRU-1) is available in 120 VAC and 277
Comments Type
VAC input voltage configurations. The RRU-1 is designed to force
all outputs in the lighting control panel to an emergency scene
regardless of the control panel’s programmed output status. This
allows the override of outputs during loss of normal (grid) power to
allow an alternate power source to drive the lighting loads (Once
the RRU-1 senses the normal power returning, the control panel will
return to the normal programmed operating mode).

Features
UL 924 Listed Accessory
Detects loss of normal power and automatically sends signal to
lighting control panel
RRU-1 – UL 924 Remote Relay Unit
July 2015

Features Wiring Diagram


General UL 924 Listed
Electrical Data Connects to normal power for monitoring
Ethernet link

Mechanical Data Architectural Dimming System must be fed


Switch Switch
DMX- DMX+ OV Shield
Input 1 Input 2
from alternate power

L
L

L
For Emergency panel configurations, ensure
Compatibility SC-UN, SC-FT, SC-RP, SC-RPB the Source Controller is fed from an emergency
power source.
DMX
Standards UL Approved Contact
closure The RRU-1 needs to provide a dry contact
UL 924 Listed maintained closure to the Switch Input 1 or
Switch Input 2 terminal on the Source Controller
RS485- RS485+ OV Shield +12V CAN-H DRAIN CAN-L DV input card.
(red) (white) (gray) (blue) (black)

Emergency actions can be programmed from


the Source Controller on board user interface.
RS485
Operation iCAN

The RRU-1 provides a Normally Closed (N/C) dry contact closure to


the Source Controller panel when normal (grid) power is lost. This Switch Switch
contact closure performs an override of all outputs in the enclosure Input 1 Input 2
to an emergency scene. This override condition takes priority over iLumin Contact inputs
any output commands from the system controller and will remain in
effect until the contact closure from the RRU-1 is opened.
To override On:
Connect dry contact from RRU-1 to Switch Input 1 or
Installation Switch Input 2.

When contact closes all relays/dimmers are forced


The RRU-1 can be installed next to the Source Controller. to an emergency scene. Contact of the RRU-1 will close
when normal power is lost.
Red (14 AWG)

NC Black
(14 AWG)
C
SPST Relay

Neutral = White Hot 120 VAC = Black


(16 AWG) Hot 277 VAC = Orange
To Normal Power Source
(16 AWG)
To Normal Power Circuit

Ordering
This is an accessory with the SC-UN, SC-FT, SC-RP, SC-RPB Source
Controllers. When ordering, specify the RRU-1 as a separate system
accessory.
Catalog # Descriptoin Rating
RRU-1-120V UL924 Remote Relay Unit 120 VAC
RRU-1-277V UL924 Remote Relay Unit 277 VAC

Note: Note: for 347 VAC Applications please see Model LRM-347

Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com

Eaton
Lighting systems
203 Cooper Circle
Peachtree City, GA 30269
www.eaton.com/lightingsystems

© 2015 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA