EVOS BUILDCON PVT.

LTD TS-FFPS

TECHNICAL SPECIFICATION
FOR
FIRE FIGHTING PROTECTION SYSTEM
INCLUDING
FIRE DETECTION & ALARM SYSTEM

Proposed Residential Building


For Sea Roses.
(G+10)

Architect:
AAKAAR ARCHITECTS,
N2/14, IrcVillage,
Bhubaneswar-751015

MEP CONSULTANT:
DYNAMIC ENGINEERING CONSULTANTS,
Branch Office: HIG-44, Ground Floor, Dharma Vihar, Khandagiri, Bhubaneswar, -
751030 Odisha
Corporate Office: Plot No 112, Ground Floor, Bhagbanpur, Near D N Regallia Mall,
Patrapada, Bhubaneswar, 751019

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 1|Page


EVOS BUILDCON PVT. LTD TS-FFPS
TECHNICAL SPECIFICATION

FIRE FIGHTING SYSTEM

SECTION I: IS CODES AND REFERENCE STANDARDS

SCOPE:

Scope of technical specifications hereinafter laid out shall cover the entire automatic
wet riser hydrant, sprinkler installation and allied works.

A. Codes and reference standards referred to in the Contract shall be understood to


form part of the Contract.

B. Alternative reference standard produced by different standards authorities may be


specified in a section. Standards of any of the specified authorities may be
acceptable; however, materials specified in the section shall be incorporated in the
works from only one of the specified standards authorities to ensure capability in the
performance of the materials.

C. The Contractor shall be responsible for adherence to reference standard requirements


by Sub Contractors and Suppliers.

D. Where edition date is not specified, consider that reference to manufacturers and
published codes, standards and specifications are made to the latest edition (revision
or amendment) approved by the issuing organisation current at the date of
submission of the tender.

E. The specified reference standards are Indian Standard Codes and are intended to
establish the quality of materials and workmanship required for the works.
Reference standards published in other countries may, in the sole judgment of the
Owner/Owner’s Consultant, also be accepted provided that the Contractor furnishes
sufficient data for the Owner/Owner’s Consultant to determine if the quality of
materials and workmanship atleast equals or exceeds all tests prescribed by the
specified reference Indian Standard Codes.

F. Reference standards and specifications are quoted in the specification to establish


minimum standards. Works or quality of performance characteristics that exceeds
these minimum standards will be considered to confirm. Should regulatory
requirements or the Contract conflict with specified reference standards or
specifications, the more stringent in each case shall be adopted.

G. Where reference is made to manufacturer’s directions, institutions or specifications,


they shall include full information on storing, handling, preparing, mixing, installing,
erection, applying or other matters concerning the materials pertinent to their use in
the works and their relationship to materials with which they are incorporated.

H. Obtain copies of codes, applying to the work, manufacturer’s directions and


standards referred to in the Contract within 90 days of signing the Contract.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 2|Page


EVOS BUILDCON PVT. LTD TS-FFPS

I. Submit a copy of each code, reference standard and specifications and


manufacturer’s directions, instructions and specification to the Owner’s authorised
representative.

J. LIST OF CODES (INDIAN STANDARD CODES)

Standard specifications, associations and regulatory bodies are generally referred to


throughout the specifications by their abbreviated designations. The material
workmanship shall be in accordance with the requirement of the appropriate IS code
wherever applicable together with any building regulations or bye-laws governing
the works.

The following list is included for guidance only and the omission of any IS codes
from the list does not relieve the Contractor from compliance therewith. The more
important codes, Standard and Publication applicable to this section are listed
hereinafter in Section II.

End of Section I

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 3|Page


EVOS BUILDCON PVT. LTD TS-FFPS

SECTION II: APPLICABLE CODES OF PRACTICE AND BUREAU OF INDIAN


STANDARDS

Following codes and standards with up-to-date amendments shall be applicable:

1.0 CODES OF PRACTICE

1.1 Codes of practice for fire safety of building (general) IS:1648


fire fighting equipment and its maintenance

1.2 Code of practice for installation and maintenance of internal


fire hydrant and hose reel on premises IS:3844

1.3 Recommendations for providing first aid and fire fighting


arrangements in public buildings IS:2217

1.4 Code of practice for selection, installation and maintenance


of portable first aid fire appliances IS:2190

1.5 National Building Code

2.0 BUREAU OF INDIAN STANDARDS

2.1 Fire hydrant valves (internal and external) IS:5290

2.2 Two way and three-way suction collection head IS:904

2.3 First aid hose-reel for fire fighting IS:884

2.4 High pressure rubber hose IS:5132

2.5 Fire fighting hose (rubber lined woven-jacketed) IS:636 II

2.6 Branch pipes, universal IS:2871

2.7 Branch pipes, short IS:903

3.0 PIPES AND VALVES

3.1 MS tubes up to 150mm nominal bore IS:1239

3.2 MS tubes 200mm nominal bore and above IS:3589

3.3 Cast iron double flanged sluice valves class 1&2 IS:780

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 4|Page


EVOS BUILDCON PVT. LTD TS-FFPS

3.4 Cast iron double flanged non-return valve IS:5312

3.5 Gunmetal valves IS:778

4.0 M.S. FITTINGS

4.1 ERW Butt welding fittings as per ANSI B-16.9 of designated class.

5.0 DESIGN STANDARD AND FIRE CODES

5.1 Rules and regulations of the local fire services authority for obtaining the statutory
permissions for compliance of the installation and for permission for obtaining all
services connection and permanent occupation certificate of the building.

5.2 Codes and standards of the National Fire Protection Association of America (NFPA).

End of Section II

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 5|Page


EVOS BUILDCON PVT. LTD TS-FFPS

SECTION III: GENERAL

1.0 General Requirements

1.1 Fire suppression works specified in the tender shall be executed in accordance with the
rules and regulations of the local fire authority and that of the various IS/BIS codes of
practice and handbooks.

1.2 All materials to be used on this works shall be new of best quality and shall bear Bureau
of Indian Standards valid certification stamped, marked or cast on the material in an
approved manner. Materials manufactured by firm of repute and approved by Project
Manager shall only be used. For bidders reference list of vendors for different items are
enclosed at Section-VIII.

1.3 It is the responsibility of the Contractor to ensure the competence of design to meet the
above requirement.

1.4 Each item of work shall be complete with all such accessories which are required to
complete the item and put it in perfect working condition whether specially mentioned
in the specifications, drawings and/or schedule of quantities or not.

1.5 Quantities in the tender document are based on the tender drawings. Contractors are
invited to highlight any aspects of the Contract document that may need revision or
reconsideration before the work is started. He must furnish details of such
revision/variations if any, to the Project Manager/ Engineer-In-Charge.

1.6 Contractor, who is awarded this work, shall furnish detailed drawings and design
calculations for submission and approval of the Local Fire Authority and shall obtain
approval of the Chief Fire Officer before the start of the work.

2.0 System Design

2.1 Total Fire Protection Provided

Fire suppression system for this complex is based on the concept of “Total Protection”
by the wet riser hydrant and sprinkler system for the entire premises. Provision of heat
and smoke detectors, call boxes and other devices are also incorporated under passive
fire safety measures and are included in next part of this specification under Fire
Detection & alarm System.

2.2 Water Storage & Pump House

2.2.1 A captive water storage tank having water storage capacity of approximately 75 Cum.
has been provided.

2.2.2 The pump house is located near the water tank.

3.0 Hydrant System

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 6|Page


EVOS BUILDCON PVT. LTD TS-FFPS
3.1 All the hydrants are fed from 150mm nominal bore MS pipe wet risers. Connections for
external hydrant mains are also taken from the internal wet risers as shown in the
drawings.

3.2 Isolation valves

Each connection from the wet riser is provided with an isolation valve. All isolation
valves shall be “Rising System Type” to indicate open/closed conditions.

3.3 Hydrant stations

Internal hydrant stations will be located in approved type of fire cabinets. Landing
valve Hose reels, RRL hoses, branch pipes, fire extinguishers and fire-man axe shall be
provided in each hydrants station in approved type hose boxes.

4.0 Sprinkler System

Installation valves are located as shown in the drawings. Except for electrical switch
rooms, power transformers and such specific areas as may be specified, the entire
building is protected with automatic sprinkler system. The sprinklers piping shall be
separate and independent of the hydrant system. Type of sprinklers to be used shall be
as given in specifications, bill of quantities and approved by the Project Manager.

End of Section III

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 7|Page


EVOS BUILDCON PVT. LTD TS-FFPS

SECTION IV: TECHNICAL SPECIFICATIONS FOR FIRE SUPPRESSION WORKS

1. General Requirements

1.1 All materials shall be new of the best quality conforming to the specifications and
subject to the approval of the Project Manager.

1.2 Pipes and fittings shall be fixed truly vertical, horizontal or in slopes as required in a
neat workmanlike manner.

1.3 Pipes shall be fixed in a manner as to provide easy accessibility for maintenance and
shall not cause obstruction in shafts, passages etc.

1.4 Pipes shall be securely fixed to walls and ceilings by suitable clamps at intervals
specified. Only approved type of anchor fasteners shall be used for RCC ceilings and
walls.

1.5 Valves and other appurtenances shall be so located that they are easily accessible for
operations, repairs, and maintenance.

2. Pipe Works

2.1 Pipes

2.1.1 All pipes within and outside the building in exposed location, shafts, buried under
ground or floors shall be MS pipes of following specifications:

a) Pipe 150mm dia and below IS:1239 heavy class

b) Pipe 200mm dia and above IS:3589 (of thickness specified)

2.2 Pipe Fittings

2.2.1 Pipes fittings mean tees, elbows, couplings, flanges, reducers and all such connecting
devices that are required to complete the piping work and make connections with
branch lines in such a manner that the piping system functions in the best manner with
provision to dismount disconnect for repairs and maintenance in its totality.

2.2.2 Screwed fittings shall be of approved type malleable or cast iron with reinforced ring on
all edges of the fittings suitable for screwed.

2.2.3 Forged steel fittings shall be of approved type with “V” groove for welded joints.
Forged steel fittings shall be screwed type only and shall be used for pipes of 50 mm dia
& below. Fabricated fittings shall not be permitted for pipes diameters 50 mm and
below

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 8|Page


EVOS BUILDCON PVT. LTD TS-FFPS
2.2.4 Fabricated fittings 100mm dia or lesser dia. shall not be permitted except under express
and written instruction of the Project Manager/Engineer-in-charge and after settlement
in the variation of rates in the forged and fabricated fitting.

2.2.5 When allowed to be used, fabricated fittings shall be fabricated, welded as approved by
Project Manager. For ‘T’ connection, pipes must be drilled and reamed for ‘Tee’ holes.
Cutting by gas or electrical resistance welding will not be accepted under any
circumstances.

2.3 Jointing

2.3.1 Screwed joints

If directed by the Project Manager/Engineer-in-Charge screwed joints shall be made for


pipes and fittings for diameters upto 50mm Joints for pipes and fittings shall be metal to
metal threaded joints. Teflon tape of appropriate grade and type shall be applied on all
threads. Use of red or white lead will not be permitted under any circumstances.

2.3.2 Welded joints

2.3.2.1 Welded joints will be made after cutting groove and welded with electrical resistance
welding in an approved manner. Burid pipes will be subject to xray test from an
approved agency as per NBC/TAC/NFPA norms at the cost of contractor. Welded MS
Fittings heavy class with V Groove. The welding machine shall be 3 phase – Rectifier or
required current and capacity.

2.3.2.2 All welding shall be carried out in proper manners and should be followed out in
proper manners and should be followed the welding specification. The contractor must
produce the welder’s, fitters, Binder certificate at the time of submission of the tender.

2.3.2.3 All pipe edges shall be bevel finished to a clean edge by an electric grinder. A requisite
gap determined by the thickness of the weld electrode shall be given between the joints
before start the welding work.

2.3.2.4 Welding electrode shall be of approved make of grade and type as suitable for the job.
This shall be approved by the Project/Engineer- In-Charge before start of work.

2.3.2.5 Joint shall be given a first weld in the full width on the full dia of the pipe. Welding
shall be carried out vertically from the surface.

2.3.2.6 After application of the 1st coat of the joint shall be cleaned by electric grinder and then
another layer of welding shall be taking place. The joint shall also be cleaned by
grinding. Similarly, a third weld shall also be applied.

2.3.2.7 All pipe cutting be done by oxyacetylene gas flame cutter only. The cut surface shall be
cleaned by electric grinder before further welding.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 9|Page


EVOS BUILDCON PVT. LTD TS-FFPS
2.3.3 Flanged joints

Flanged joints shall be provided on:

a) Straight runs not exceeding 12-15m on pipelines of 65mm dia and above.

b) Both ends of any fabricated fittings e.g., bends, tees of 65mm dia or larger
diameter.

c) For jointing all types of valves, appurtenances and connections with other type of
pipes to water tanks and other places necessary and required as good for engineering
practice.

d) Flange shall be as per IS with appropriate number of galvanized nuts and bolts,
3mm insertion rubber gasket.

2.3.4 Union joints

Provide approved type of dismountable unions on pipe lines 50mm and below in
similar places as specified for flanges.

2.4 Piping Installation & Support

2.4.1 All pipe clamps and supports shall be fabricated from MS steel sections.

2.4.2 Pipe supports shall be hung by means of expandable anchor fasteners of approved
make and design. The hangers and clamps shall be fastened by means of nuts and
bolts. The size/diameter of the anchor fastener and the clamp shall be suitable to carry
the weight of water filled pipes and dead load normally encountered.

2.4.3 All pipe clamps and supports shall be painted with black synthetic enamel paint (two or
more coats) over a coat of ready mixed primer of red lead.

2.4.4 Piping shall be properly supported on, or suspended from, on stands, clamps, hangers as
specified and as required. The contractor shall adequately design all the brackets,
saddles, anchor, clamps and hangers, and be responsible for their structural stability.

2.4.5 Pipe work and fittings shall be supported by hangers or brackets or brackets so as to
permit free expansion and contraction. All accessories and ancillaries of support system
such as brackets, saddles, clamps, hangers etc. shall be hot dip galvanized after
fabrication. Further to permit free movement of common piping, support shall be form
a common hanger bar, fabricated from galvanized steel sections.

2.4.6 Pipe hangers shall be provided at the following maximum spacing:

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 10 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
Pipe Dia (mm) Hanger Rod Dia (mm) Spacing between Supports
(m)
Up to 25 8 2
32 to 50 8 2.7
80 to 100 10 2.7
125 to 150 12 3.6
200 to 300 16 5.3

The end of the steel rods shall be threaded and not welded to the threaded blot.

3. Excavation

3.1 Excavation for pipelines shall be in open trenches to levels and grades shown on
the drawings or as required at site. Pipelines shall be buried to a minimum depth
of 1 meter or as directed by the Project Manager.

3.2 Wherever required, Contractor shall support all trenches or adjoining structures with
adequate timber supports.

3.3 On completion of testing and pipe protection work, trenches shall be refilled with
excavated earth in 20cms layers and consolidated.

3.4 Contractor shall dispose off all surplus earth within a lead of 50m.

4. Anchor Thrust Block

4.1 Contractor shall provide suitably designed anchor blocks in cement concrete to
encounter excess thrust due to water hammer and high pressure.

4.2 Thrust block shall be provided at all bends and tees and such other location as
determined by the Project Manager/Engineer-In-Charge.

4.3 Exact location, design, size and mix of the concrete block shall be got approved by the
Project Manager.

5.0 Pipe Protection

5.1 Pipe Painting

All pipes above ground and in exposed locations shall be painted with one coat of red
oxide primer and two or more coats of synthetic enamel paint of approved shade and
quality.

5.2 Underground Pipe Protection

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 11 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
Pipes and fittings buried underground shall be provided with one layer of corrosion
protection tape based on coal tar.

5.3 Specifications for protective tape shall conform to requirements of AWWA C203 Section
8. Tape shall incorporate a centre core of 50-micron High Molecular High Density Poly
Ethylene (HM HDPE) film. Additionally, it shall have second centre core of fiberglass
tissue to lend mechanical strength and dimensional stability to the tape. Tape shall have
three layers of coal tar mix interleaved between the centre cores. The tape shall be
provided on both sides on the exterior with thermo fusible HMHDPE film. All the
layers, as described above shall be calendered together to finish it to 4mm thick tape.

6. Valves

6.1 General Requirements

6.1.1 All valves shall carry BIS certification mark and shall be of makes approved by the
Project Manager before they are allowed to be used on work.

6.1.2 Gunmetal ball valves and butterfly valves will be used for branch connections in
sprinkler and hydrant line and as directed by the Project Manager/Engineer-In-Charge.

6.1.3 Butterfly valves will also be used on suction & delivery of pumps, connection to water
tanks and such other locations or as directed by the Project Manager /Engineer-In-
Charge.

6.2 Gunmetal Valves/ Ball Valves

6.2.1 Valves 65mm dia & below shall be heavy gunmetal ball valves conforming to with
female screwed ends and operating levers. Valves shall be of approved make.

6.3 Sluice Valves

6.3.1 Valves 80mm dia and above shall be cast iron double flanged sluice valve with rising
spindle and position indicator. Sluice valve in exposed positions shall be provided with
cap topes for operation with long handle key. Valves shall conform to IS:780 of
appropriate class or as specified.

6.3.1 A Chambers for underground sluice/butterfly valves shall be of brick masonry of size
60x60x75 cm inside or as given in the schedule of quantities. Brick masonary chambers
shall be plastered from inside with 1:4 cement mortar (1 cement: 4 fine sand) and
outside with 1 :4 cement mortar (1 cement: 4 coarse sand). Chamber shall be provided
C.I. manhole frame and cover of size 600x600mm.

6.3.2 Contractor shall provide suitable ‘T’ keys for sluice valves with cap tops.

6.4 Butterfly Valves

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 12 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
6.4.1 Butterfly valves shall be cast iron body conforming to relevant IS specification with
following details:

a) Disc shall be CI heavy duty electroless nickel-plated abrasion resistant.


b) The shaft shall be EN-8 Carbon Steel with low friction nylon bearings.
c) The seat shall be drip tight constructed by bonding resilient elastomer inside a rigid
backing.
d) Built-in flanged rubber seals.
e) Actuator to lever operated for valves above ground and ‘T’ keys operated valves
below ground. Manufacturer’s details on fixing and installation will be followed.

6.5 Non-return Valves

6.5.1 non-return valves will be used at locations to allow flow only in one direction and
prevent flow in the opposite direction.

6.5.2 NRVs shall be cast iron dual plate with cast iron body SS 304 seat, spring and hinge
pins.

6.6 Air Release Valves

6.6.1 Air release valves shall be provided at suitable points in the piping system to enable
expelling entrapped air when filling or allowing intake of air when emptying the
system. Air release valves shall be installed at locations approved by the Project
Manager/ Engineer-In-Charge.

6.6.2 Air release valve shall be 25mm dia, screwed inlet, cast iron or gunmetal, single acting
for pipelines upto 200mm dia.

6.7 Drain Valves

6.7.1 Provide drain valves at low points and other location in the system to enable draining
out of the entire or a part of the systems for repairs and maintenance.

6.7.2 Drain valves shall be of size shown on the drawings and shall be discharged over a
drain with an air-gap of atleast 50mm by means of a pipeline. No system drain shall be
connected directly to a manhole or underground drain out of sight. Pipes for drains
shall be of the same specifications as those used for the main pipelines.

6.7.3 Drain valves shall be of gunmetal or as specified.

6.7.4 Drain sizes shall be as follows:

a) Lines upto 50mm dia 32mm dia


b) Lines 65-100 mm dia 40mm dia

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 13 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
c) Lines 150mm dia 50mm dia

Project Manager/ Engineer-In-Charge may instruct the Contractor to change the size of
the drain if situation at the site so warrants.

6.7.5 SYSTEM DESIGN:

Typical floors shall be designed between 2.5 bar and 3.5 bar. (Pl review & adopt
accordingly)

7.0 Inspection and Testing Valve

7.1 Arrangement for Inspection and testing of the sprinkler system by providing a drain
valve shall also be incorporated for sprinkler system.

8. Pressure Gauge

8.1 Pressure gauge shall be gunmetal bourdon type with gunmetal isolation cock and
copper ‘U’ tube, taping and connecting pipe and nipple. The gauge shall be installed at
appropriate level and height for easy reading in each fire hose cabinet.

8.2 Pressure gauge shall be provided on all sprinkler branch lines near flow switch as
directed by the Project Manager/Engineer-In-Charge.

9. Flow Indicating Switches

9.1 Flow indicating switches shall be provided on branch lines of sprinkler systems as
indicated on drawings, or as directed by the Project Manager/Engineer-In-Charge.

9.2 Flow indicating switches shall be on/off types to generate an electrical signal indicating
its operation status. The switch should be suitable for mounting on a pipeline of the
required diameter and shall be sensitive to actuate on operating of a single sprinkler.
The switch shall contain all accessories and will be installed in an accessible panel or
space over the fire hydrant station or other location which must be shown on the
Contractor’s shop drawing. The flow switch shall be wired to a central annunciation
panel.

10. Fire Hydrant


10.2 Internal Hydrant (Landing Valve)

10.2.1 The assembly of the internal hydrants shall be one or two single headed hydrant valves
conforming to IS:5290. Hydrant valves shall be mounted on 80 or 100 mm dia branch
outlet pipes. The branch outlet will have flanged or welded connection in which the
orifice flanges will be inserted. A 25mm connection to the hose reel and a 15mm welded
socket will be provided to install a 50mm dia pressure gauge, the assembly shall be as
approved by the Project Manager/Engineer-In-Charge.

10.2.2 Instantaneous outlets for fire hydrants shall conform to IS:903 of standard pattern
approved and suitable for fire brigade hoses.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 14 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
10.3 Fire Brigade Connections

10.3.1 Fire brigade connection are provided to enable the local fire brigade to pump water into
the system with the help of its own pumps to meet emergencies due to the failure of the
captive system of the project. It also enables to pump water from other sources into the
Owner’s fire reserve tank for extended operation.

10.3.2 Collecting head shall be installed on a stand post and provided with additional cast iron
sluice valve and NRV at locations to be approved by Project Manager/Engineer-In-
Charge. Provide etched gunmetal label plates visible legend indicating the service
(Fire/Sprinkler). The plates should permanently be fixed to the fire brigade connection.
If necessary and required, the fire brigade connection shall be installed in a glass
enclosure to make it tamper proof.

11.0 Fire Hose

11.1 Each internal and external fire hydrant shall be provided with requisite number of fire
hoses as specified below.

11.2 Fire hoses shall be 15m long, reinforced rubberised, fabric lined conforming to IS:636
type 2 with a pair of gunmetal (one male and one female) instantaneous type coupling
conforming to IS:903. The coupling shall be machine wound to the fire hose with GI
wire.

12.0 Branch Pipe, Nozzle & Fire Axe

12.1 Branch pipe and nozzle shall be of gunmetal with 63mm inlet conforming to IS:903 with
a 16mm dia outlet nozzle.

12.2 Steel fireman’s axe with insulated handle.

13. First Aid Hose Reels

13.1 Each fire hydrant station shall be provided with a first aid hose reel conforming to
IS:884. Each hose reel shall consist of the reel, dust cover for the reel, stop valve, hose
reel tubing, hose guide, fixing brackets and nozzle. All the components of the hose reel
shall conform to relevant Indian Standards.

14. Fire Hose Cabinets

14.1 Fire hose cabinets (FHC) for fire hydrant stations and for external fire hydrant shall be
as per the local fire codes. Hose cabinets shall be fabricated from MS sections and 14-
gauge MS sheet of fully welded construction. Sizes of the FHC shall be as given in the
Schedule Of Quantities.

14.1.2 The FHC will be painted with synthetic enamel paint of approved color on the inside
surface. The outer surface in contact with masonry shall be painted with primer and
finish with two coats of enamel paint of fire red color.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 15 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
14.1.3 The FHC will be provided with steel panel door. The design of the door shall be as per
Architect’s design and as directed by the Project Manager.

14.1.4 The FHC will have the legend “FIRE HOSE” painted prominently.

14.2 External hose cabinet:

The hose cabinet shall be size to accommodate the following.

i) Single / Double headed yard hydrant valve.


ii) Hose pipe (2 length of 15 m)
iii) Branch pipes, nozzles (2 sets)
iv) Fire man’s axe.

14.3 Internal Hydrant Hose cabinet:

The hose cabinet shall be to accommodate the following.

i) Landing valves
ii) Hose pipe
iii) Hose reel
iv) Branch pipes, nozzles (2 sets)
v) Fire man’s axe and hand appliances

15. Fire Hydrant Stations

15.1 Each fire hydrant station shall be located in a fire hose cabinet of size mentioned in the
Schedule of Quantities. Each station shall contain:

a) Single one or two landing valves, assembly with outlet, orifice flanged connection,
pressure gauge and accessories.

b) Required lengths of 15m long RRL hoses with male and female couplings, branch
pipe and nozzle properly mounted in the fire hose cabinet.

c) Fire hose reel with rubber hose and nozzle.

d) Fireman’s insulated axe

e) Space for atleast two fire extinguishers.

f) Electrical signboard with illumination from emergency power supplies on top.

16.0 Installation Control Valve

Each installation shall be provided with a set of installation control valves comprising: -

a) An Alarm Valve.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 16 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
b) A water Motor Alarm & Gong

c) Contractor shall submit his detailed shop drawings showing the exact location, details
of installation of the valve and alarm complete in all respects.

d) Installation valve shall comprise of a cast iron sluice valve with gunmetal trim, pressure
gauge, double seated clapper check valves. Alarm valve with test valve and orifice
assembly and drain pipe with pressure gauge, bye-pass on check valve to regulate
differential pressure and false alarm, turbine water gong including all accessories
necessary and required and as supplied by original equipment manufacturer and
required for full and satisfactory performance of the system.

16.1 Main Stop Valve

These shall be of cast iron body of requisite size. When closed, these will shut off supply
of water to the installation.

A location plate must be fixed on the outside or an external wall, as near to main stop
valve as possible, bearing the following words on raised letter or other approved type
letter.

i) Sprinkler Stop Valve Inside: The word ‘sprinkler stop valve’ shall be in letters of at least
35 mm and the word “INSIDE” at least 25 mm in height. The words shall be painted
white on black back ground.

ii) All stop valves shall be right-handed i.e they shall be constructed that in order to shut
the valve the spindle shall be right to right. There shall be an indicator which will show
whether the valve is open or shut.

17.0 Measurement

17.1 All items to be measured include:

17.1.1 All equipment and accessories supplied by the manufacturer as a part of the original
equipment whether it is described in the tender document or shown on the tender or
Contractor’s approved shop drawing or not, if such equipment and accessories are an
essential and inherent part of the system.

a) Rates quoted deem to include all items described in the schedule of quantities and
the specifications read with Contractor’s approved shop drawings.

17.2 Pipe Work

17.2.1 Mild steel pipes shall be measured per linear meter of the finished length and shall
include all fittings, flanges, welding, jointing, clamps for fixing to walls or hangers,
anchor fasteners and testing complete in all respects.

17.2.2 Pipe coating

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 17 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
Coating of external pipe for pipe protection shall be measured as per the measurement
of the pipe mentioned in the para above.

17.2.3 Pipe Supports

All fabricated structural pipe support systems shall be measured per Kg. weight and
shall include painting and fixing.

217.3 Valves etc.

Gunmetal, cast-iron sluice valves, butterfly valves, check valves, air valves, pressure
gauges, vibration eliminators, suction strainers etc. shall be measured by numbers.

17.4 Inspection & Testing Valve

17.4.1All items in the inspection and testing assembly for testing of sprinkler zones shall be
measured individually under the respective items.

17.4.2 Drain pipe will be paid for length as per para for measurement for pipes.

17. 5 Fire equipment

Fire hydrant, hose reels, fire brigade connections, fire axe, RRL hoses with couplings
shall be measured by number. Orifice flanges shall be considered as a part of landing
valve and no separate payment for the same shall be admissible.

17.6 Fire Cabinets

17.6.1 Fire hose boxes specified shall be measured by number.

End of Section IV

SECTION V: FIRE PUMPS & ALLIED EQUIPMENT

1. Scope of work

1.1 Work under this section consists of furnishing all labour, materials, equipment and
appliances necessary and required to supply install and commission the fire pumps and
accessories as described hereinafter and given in the Schedule of Quantities.

1.2 Without restricting to the generally of the foregoing, the pumps and ancillary
equipment shall include the following:

a) Electrically operated and diesel driven pumps with motors, baseplates and
accessories.

b) Pressure gauges with isolation valves and piping bleed and block valves.

c) M.S. pipes, valves, suction strainers, suction and delivery headers and
accessories.

e) Foundations, vibration eliminator pads and foundation bolts.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 18 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS

2. General requirements

2.1 Pumps shall be installed true to level on suitable concrete foundations. Baseplate shall
be firmly fixed by foundation bolts properly grouted in the concrete foundations. Each
pump will be provided with vibration eliminating pads and appropriate connectors.

2.2. Pumps and motors shall be truly aligned by suitable instruments.

2.3. All pump connections, shall be standard flanged type with appropriate number of bolts.
In case of nonstandard flanges companion flanges shall be provided with the pumps.

2.4. Manufacturer's instructions regarding installation connections and commissioning shall


be followed with respect to all pumps and accessories. All equipment is required to be
erected/tested & commissioned under supervision of OEM representative/Service
Engineer. If specifically, not mentioned in BOQ, hiring charges of service Engineer is
deemed to be included in the erection/installation charges.

2.5 Contractor shall provide necessary test certificates and performance charts with NPSH
requirement of the pumps from the manufacturer. The contractor shall provide facilities
to the Project Manager or his authorized representative for inspection of equipment
during manufacturing and also to witness various tests at the manufactures works
without any cost to Owner.

2.6. Each pump shall be provided with a 150 mm dia. pressure gauge, isolation cock and
connecting piping, bleed and block valve.

2.7 The contractor shall submit with this tender a list of recommended spare parts for two
years of normal operation and quote the price for the same.

3.0 Fire and Jockey Pumps

3.1 Pumping sets shall be single/multi stage horizontal centrifugal single or multi outlet
with cast iron body and bronze dynamically balanced impellers.

Connecting shaft shall be stainless steel with bronze sleeve and grease lubricated
bearings.

3.2 Pumps shall be connected to the drive by means of spacer type love-joy coupling, which
shall be individually balanced dynamically and statically.

3.3 The coupling joins the prime mover with the pump shall be provided with a sheet metal
guard.

3.4 Pumps shall be provided with approved type of mechanical seals.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 19 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
3.5 Pumps shall be capable of delivering not less than 150% of the rated capacity of water at
a head of not less than 65% of the rated head. The shut-off head shall not exceed 120%
of the rated head.

3.6 The pump shall meet the requirements of the tariff advisory committee and unit shall be
design proven in fire protection services.

4.0 Motors for Electric Driven Pumps

4.1 Electrically driven pumps shall be provided with totally enclosed fan cooled induction
motors. For fire pumps, the motors should be rated not to draw starting current more
than 3 times normal running current.

4.2 Motors for fire protection pumps shall be at least equivalent to the horse power required
to drive the pump at 150% of its rated discharge and shall be designed for continuous
full load duty and shall be design proven in similar service.

4.3 Motors for fire pumps shall meet all requirements and specifications of the tariff
advisory committee.

4.4 Motors shall be suitable for 415 volts, 3 Phase,50 cycles A.C supply and shall be
designed for 33o C ambient temperature. Motors shall conform to IS: 325.

4.5 Motors shall be designed for auto start system.

4.6 Motors shall be capable of handling the required starting torque of the pumps.

4.7 Contractor shall provide heating arrangements for the main fire pump motor to ensure
that motor windings shall remain dry.

5.0 Diesel Fire Pump

5.1 Scope
This section covers the details of requirements of the standby fire pump, operated by a
diesel engine.

5.2 General
The diesel pump set shall be suitable for automatic operation complete with necessary
automatic starting gear, for starting on wet battery system and shall be complete with
all accessories. Both engine and pump shall be assembled on a common bed plate,
fabricated from mild steel channel.

5.3 Drive
The pump shall be only direct driven by means of a flexible coupling. Coupling guard
shall also be provided. The speed shall be 1500 RPM as specified in bill of quantities.

5.4 Fire pump

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 20 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
a) The fire pump shall be horizontal split casing centrifugal type. It shall have a
capacity to deliver 2850 lpm as specified, developing adequate head so as to ensure
a minimum pressure of 3 Kg./cm 2 at the highest and the farthest outlet. The
delivery pressure at the pump outlet shall be not less than 7 Kg./cm 2 in any case.
The pump may be single stage or multi stage as specified. The pump shall be
capable of giving a discharge of not less than 150% of the rated discharge at a head
of not less than 65% of the rated head. The shut off head shall be within 120% of the
rated head.

b) The pump casing shall be of cast iron to grade FG 200 to I.S: 210 and parts like
impeller shaft sleeve, wearing-ring etc. shall be of non-corrosive metal like
bronze/brass/gunmetal. The shaft shall be of stainless steel. The pump shall be
provided with mechanical seal.

c) The pump casing shall be designed to withstand 1.5 times the working pressure.

d) Bearings of pump shall be effectively sealed to prevent loss of lubricant or entry of


dust or water.

5.5 Diesel Engine

5.5.1 Environmental conditions - The engine shall be required to operate under the
conditions of environment as specified.

5.5.2 Engine Rating - The engine shall be cold starting type without the necessity of
preliminary heating of the engine cylinders or combustion chamber (for example, by
wicks, cartridge, heater plugs etc). The engine shall be multi cylinder/vertical 4 stroke
cycle, water cooled diesel engine, developing suitable HP at the operating speed
specified to drive the fire pump. Continuous capacity available for the load shall be
exclusive of the power requirement of auxiliaries of the diesel engine, and after
correction for altitude, ambient temperature and humidity for the specified
environmental conditions as mentioned. This shall be at least 20% greater than the
maximum HP required to drive the pump at its duty point. It shall also be capable of
driving the pump at 150% of the rated discharge at 65% of rated head. The engine shall
be capable of continuous non-stop operation for 8 hours and at least 3000 hours of
operation before major overhaul. The engine shall have 10% overload capacity for one
hour in any period of 12 hours continuous run. The engine shall accept full load within
15 seconds from the receipt of signal to start. The diesel engine shall conform to BS
649/IS 1601/IS 10002, all amended upto date.

5.5.3 Engine Accessories - The engine shall be complete with the following accessories: -

(i) Flywheel dynamically balanced.


(ii) Direct coupling for pump and coupling guard.
(iii) Radiator with hoses, fan, water pump, drive arrangement and guard.
(iv) Corrosion Resister
(v) Air cleaner, oil bath type/dry type

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 21 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
(vi) Fuel service tank support, semi-rotary pump and fuel oil filter with
necessary pipe work.

(vii) Pump for lubricating oil and lub. oil filter


(viii) Elect. starting battery (2x12 v)
(ix) Exhaust silencer with necessary pipe work
(x) Governor
(xi) Instrument panel housing all the gauges, including Tachometer, hour
meter and starting switch with key (for manual staring).

(xii) Necessary safety controls


(xiii) Winterisation arrangement, where specified.
(xiv)

5.5.4 Starting system - The starting system shall comprise necessary batteries (2x12 v), 24
volts starter motor of adequate capacity and axle type gear to match with the toothed
ring on the flywheel. By metallic relay protection to protect starting motor from
excessively long cranking runs suitably integrated with engine protection system shall
be included within the scope of the work.

The battery capacity shall be suitable for meeting the needs of the starting system.

The battery capacity shall be adequate for 10 consecutive starts without recharging with
cold engine under full compression.

The scope shall cover all cabling, terminals, initial charging etc.

5.5.5 Exhaust system - The exhaust system shall be complete with silencer suitable for
outdoor installation, and silencer piping including bends and accessories needed to be
taken out of the building as per statutory requirement/instruction of Engineer-in-
Charge. The Contractors are advised to see the drawing and site to asses the length of
exhaust pipe required and its cost & installation included with cost of pump. The total
backpressure shall not exceed the engine manufacturer’s recommendation. The exhaust
piping shall be suitably lagged.

5.5.6 Engine shut down mechanism - This shall be manually operated and shall return
automatically to the starting position after use.

5.5.7 Governing System - The engine shall be provided with an adjustable governor to
control the engine speed within 5% of its rated speed under all conditions of load up to

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 22 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
full load. The governor shall be set to maintain rated pump speed at maximum pump
load.

5.5.8 Engine Instrumentation - Engine instrumentation shall include the following: -

(i) Lub. oil pressure gauge.


(ii) Lub. oil temperature gauge
(iii) Water pressure gauge
(iv) Water temperature gauge
(v) Tachometer
(vi) Hour meter.

The instrumentation panel shall be suitably resident mounted on the engine.

5.5.9 Engine Protection Devices - Following engine protection and automatic shut down
facilities shall be provided: -

(i) Low lub. oil pressure


(ii) High cooling water temp.
(iii) High lub. oil temperature
(iv) Over speed shut down.

5.5.10 Pipe work - All pipe line with fittings and accessories required shall be provided for
fuel oil, lub. oil and exhaust systems, copper piping of adequate sizes shall be used for
lub. oil and fuel oil. M.S. piping will be permitted for exhaust.

5.5.11 Anti Vibration Mounting - Suitable vibration mounting duly approved by Engineer-in-
charge shall be employed for mounting the unit so as to minimize transmission of
vibration to the structure. The isolation efficiency achievable shall be clearly indicated.

5.5.12 Battery Charger - Necessary float and boost charger shall be incorporated in the control
section of the power and control panel, to keep the battery under trim condition.
Voltmeter to indicate the state of charge of the batteries shall be provided.

6. Air vessel

6.1 Provide one air vessel fabricated from 10 mm M.S. plate with dished ends and suitable
supporting legs. Air vessel shall be provided with a 100 mm dia flanged connection
from pump, one 50 mm dia. drain with valve. The vessel shall be 450 mm dia. x 2000
mm high and tested to 15 Kg/Sq.cm. pressure.

6.2 Air vessel shall have the following mountings on it :

a) Manifold of 20 mm dia M.S. pipe at the upper end of the vessel with the seven pressure
operated switches suitable to start main electrical fire hydrant, sprinkler and diesel
engine operated pumps. These pressure switches will start and NOT stop the pumps.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 23 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
There shall be one more pressure switch to start and stop the jockey pump
automatically.

b) 150 mm dia pressure gauge (0-15kg range) with stop cock.

c) 25 mm threaded socket with heavy duty gunmetal pressure release valve with 25mm
gunmetal stop valve. The pressure release valve shall be set to release pressure at 10.5
kg/Sq cm

6.3 The fire pumps shall operate on drop of 1 Kg/Sqcm. pressure in the mains. The pump
operating sequence shall be arranged in a manner to start the pump automatically but
should be stopped manually by starter push buttons only.

6.4 Air Cushion Tank

Every wet riser shall be provided with an air cushion tank at its top most point. The air
cushion shall be provided with an automatic air release cock, 20 mm dia drain pipe,
drain valve and shut off valve.

7. Operating conditions for fire and sprinkler pumps

Fire Service Nos. Cut in Cut Out Remarks


Pump Pressure Pressure
Jockey pump One 6.0Kg/cm2 7.0 Kg/cm2 To auto start and auto stop
on pressure switch on air
vessel.

Main pump One 5.0 Kg/cm2 Push button To auto start on pressure
manual switch on air vessel and
manual off.
Diesel Fire One 3.5 Push button To auto start on pressure
Pump Kg/Cm2 manual switch on air vessel and
manual off.

8. Vibration eliminators

Provide on all suction and delivery lines double flanged reinforced neoprene flexible
pipe connectors. Connectors should be suitable for a working pressure of each pump
and tested to the test pressure given in the relevant head. Length of the connector shall
be as per manufacturer’s details.

9. Cables

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 24 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
9.1. Contractor shall provide all power and control cables from the motor control centre to
various motors.

9.2. Cables shall conform to I.S. 1554 and carry ISI mark.

9.3. Wiring cables shall conform to IS: 694.

9.4. All power and wiring cables shall be aluminum conductor PVC insulated armoured
and PVC sheathed of 1100 volts grade.

9.5. All control cables shall be copper conductor PVC insulated armoured and PVC sheathed
1100 volt grade.

9.6. All cables shall have stranded conductors. The cables shall be in drums as far as
possible and bear manufacturer's name.

9.7. All cable joints shall be made in an approved manner as per standard practice.

10. Cables trays

10.1. Contractor shall provide M.S. slotted cables trays at locations as shown on the drawings
and of sizes as given in the Schedule of Quantities.

10.2. Cable trays shall be supported from the sides of the cable trench/bottom of the slab at
intervals of 60 cms at both ends by welding support rods with insert plates or to
reinforcement bars. Cutting of holes in the slab for exposing of reinforcement bars
and making good the same after welding of support rods shall be included in the
rate of the tray and no separate payment shall be made on this account.

10.3. Cost of clips, bolts, nuts, supports rods and any other materials required to fix the trays
in proper manner shall be included in the rate for trays.

10.4. Cables trays shall be of approved makes.

11. Earthing

All equipment installed by the Contractor shall be suitably earthed by making proper
connection by means of G.I. wires to the main earthing system laid by the electrical
Contractors.

12. Motor control centre

12.1. Switchboard cubicles of approved type shall be fabricated from 14-gauge M.S. sheet
with dust and vermin proof construction. It shall be painted with stove enameled paint
of approved make and shade. It shall be fitted with suitable etched plastic identification
plates for each motor. The cubicle shall comprise of the following:

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 25 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS

a) Incoming main switch fuse unit of required capacity.

b) Isolation switch fuse unit, one for each motor.

c) Fully automatic DOL/Star Delta starters suitable for motor H.P. with push
buttons; one for each motor and on/off indicating neon lamps.

d) Single phasing preventer of appropriate rating for each motor.

e) Panel type ampere meters; one for each motor.

f) Panel type voltmeter on incoming main with rotary selector switch to read
voltage between phase to neutral and phase to phase.

g) Neon phase indicating lamps on the incoming main.

h) Rotary switch for manual or auto operation for each pump.

i) PVC sleeved aluminum bus bars of required capacity.

j) The panel shall be prewired with colour coded wiring. All interconnecting wiring
from incoming main to switch gear, meters and accessories within the switch board
panel.

12.2. All switch gears and accessories shall be of approved make.

12.3. Switchboard cubicles shall be floor or wall mounted type as recommended by


manufacturers.

13. Measurements

13.1 Fire, Sprinkler and jockey pumps shall be measured by numbers and shall include all
items as given in the specifications and schedule of quantities.

13.2 Air vessel, fire alarm, motor control panels, earthing station, sluice valve, non return
valves, vibration eliminators and suction strainer shall be measured by numbers and
shall include all items as given in the Schedule of Quantities and Specifications.

13.3 Pump headers, power cables, earth wire and tape, slotted

cable trays shall be measured per linear meter and shall include all items given in the
specifications and Schedule of Quantities.
END OF SECTION V

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 26 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS

SECTION VI: HAND APPLIANCES

1.0 Scope of Work

1.1 Work under the section shall consists of furnishing all labour, material, appliances and
equipments necessary and required to install fire extinguishing hand appliances.

1.2 Without restricting to the generality of the foregoing the work shall consist of the
following:

Installation of fully charged and tested fire extinguishing hand appliances CO2, Foam,
Dry chemical powder type as required by these specifications and drawings.

2.0 General Requirements

2.1 Fire extinguishers shall conform to the following Indian Standard Specifications and
shall be with ISI approved stamp as revised and amended upto date:-

Description Water-CO2 Mechanical Dry Chemical ABC Store Carbon


Foam Powder Pressure Dioxide CO2
IS Code 940 10240 2171 13849 2878
Model WCO2 MF 9 DP 10 DP (SP) 10 CO2 4.5
Media Water AFFF Dry Powder Dry Powder CO2
(ABC)
Capacity 9 litres 9 litres 10 kg. 10 kg. 4.5 kg.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 27 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
Effective 85% 90 % 85 % 85 % N.A
discharge minimum minimum minimum minimum
Jet length 6m 6 m minimum 6m 6 m minimum
minimum minimum
Discharge 60 to 120 25 to 60 23 to 30 23 to 30 10 to 18
time seconds seconds seconds seconds seconds
Test 30 kgf/sq.cm 30 kgf/sq.cm 30 kgf/sq.cm 30kgf/sq.cm 250
pressure kgf/sq.cm
Gas 40 gms. CO 2 60 gms. CO2 180 gms CO2 N.A N.A
cartridge
Charged 14 kg. 14 kg. approx. 19 kg. 16 kg. approx. 17 kg.
weight approx. approx. approx.
Operation Upright Upright Upright Upright Upright
method

2.2 Fire extinguishers shall be installed as per Indian Standard Code of practice for
selection, installation and maintenance of portable first aid appliances “I.S. 2190-
1979/2010R”.

2.3 Fire Extinguishers shall be installed in readily accessible locations with the appliance
brackets fixed to wall by suitable anchor fasteners.

2.4 Each Extinguisher shall be provided with an inspection card indicating the date of
inspection, testing, change of charge and other relevant data.

2.5 Extinguishers shall be fixed in a true workman like manner truly vertical and at correct
locations.

3. 0 Measurements

Fire extinguishers shall be measured by numbers and shall include installation and all
items necessary and required and for proper installations.

END OF SECTION VI

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 28 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS

SECTION-VII: ADDRESSABLE FIRE ALARM SYSTEM:

1.0 GENERAL

1.1 DESCRIPTION:

This section of the specification includes the furnishing, installation, connection and
testing of the microprocessor controlled, intelligent reporting fire alarm equipment
required to form a complete, operative, coordinated system. It shall include, but not
be limited to, alarm initiating devices, alarm notification appliances, Fire Alarm
Control Panel (FACP), auxiliary control devices, annunciators, and wiring as shown
on the drawings and specified herein.

The fire alarm system shall comply with requirements of NFPA Standard 72 for
Protected Premises Signaling Systems except as modified and supplemented by this
specification. The system shall be electrically supervised and monitor the integrity of all
conductors.

The system and its components shall be Underwriters Laboratories, Inc. listed under the
appropriate UL testing standard as listed herein for fire alarm applications and the
installation shall be in compliance with the UL listing.

1.2 SCOPE:

A new intelligent reporting, microprocessor-controlled fire detection system shall be


installed in accordance to the project specifications and drawings. The BOQ for the Fire
Detection & Alarm System is tentative on & the successful bidder will be required to
design & develop the drawings/documents for complete system as per enclosed
technical specification. The drawings & documents are required to be submitted to
Engineer-In-Charge for approval before proceeding for execution.

1.2.1 Basic Performance:

Alarm, trouble and supervisory signals from all intelligent reporting devices shall be
encoded on NFPA Style 6 (Class A) Signaling Line Circuits (SLC).

Initiation Device Circuits (IDC) shall be wired Class A (NFPA Style D) as part of an
addressable device connected by the SLC Circuit.

Notification Appliance Circuits (NAC) shall be wired Class A (NFPA Style Z) as part of
an addressable device connected by the SLC Circuit.

On Style 6 or 7 (Class A) configurations a single ground fault or open circuit on the


system Signaling Line Circuit shall not cause system malfunction, loss of operating
power or the ability to report an alarm.

Alarm signals arriving at the FACP shall not be lost following a primary power failure
(or outage) until the alarm signal is processed and recorded.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 29 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS

NAC speaker circuits shall be arranged such that there is a minimum of one speaker
circuit per floor of the building or smoke zones whichever is greater.

Audio amplifiers and tone generating equipment shall be electrically supervised for
normal and abnormal conditions.

NAC speaker circuits and control equipment shall be arranged such that loss of any one
(1) speaker circuit will not cause the loss of any other speaker circuit in the system.

Two-way telephone communication circuits shall be supervised for open and short
circuit conditions.

2.0 DRAWINGS & TECHNICAL SUBMITTALS

2.1 General:

Two copies of all submittals shall be submitted to the Architect/Engineer-in-charge for


review.

All references to manufacturer's model numbers and other pertinent information herein
is intended to establish minimum standards of performance, function and quality.
Equivalent compatible UL-listed equipment from other manufacturers may be
substituted for the specified equipment as long as the minimum standards are met.

For equipment other than that specified, the contractor shall supply proof that such
substitute equipment equals or exceeds the features, functions, performance, and
quality of the specified equipment.

2.1.1 Shop Drawings:

Sufficient information, clearly presented, shall be included to determine compliance


with drawings and specifications.

Include manufacturer's name(s), model numbers, ratings, power requirements,


equipment layout, device arrangement, complete wiring point-to-point diagrams, and
conduit layouts.

Show annunciator layout, configurations, and terminations.

2.1.2 Manuals:

Submit simultaneously with the shop drawings, complete operating and maintenance
manuals listing the manufacturer's name(s), including technical data sheets.

Wiring diagrams shall indicate internal wiring for each device and the interconnections
between the items of equipment.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 30 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
Provide a clear and concise description of operation that gives, in detail, the information
required to properly operate the equipment and system.

2.1.3 Software Modifications:

Provide the services of a factory trained and authorized technician to perform all system
software modifications, upgrades or changes. Response time of the technician to the site
shall not exceed 4 hours.

Provide all hardware, software, programming tools and documentation necessary to


modify the fire alarm system on site. Modification includes addition and deletion of
devices, circuits, zones and changes to system operation and custom label changes for
devices or zones. The system structure and software shall place no limit on the type or
extent of software modifications on-site.

2.1.4 Certifications:

Together with the shop drawing submittal, submit a certification from the major
equipment manufacturer indicating that the proposed supervisor of the installation and
the proposed performer of contract maintenance is an authorized representative of the
major equipment manufacturer. Include names and addresses in the certification.

2.1.5 WARRANTY:

All work performed and all material and equipment furnished under this contract shall
be free from defects and shall remain so for a period of at least one (1) year from the
date of acceptance. The full cost of maintenance, labor and materials required to correct
any defect during this one-year period shall be included in the submittal bid.

3.0 APPLICABLE STANDARDS AND SPECIFICATIONS:

3.1 The specifications and standards listed below form a part of this specification. The
system shall fully comply with the latest issue of these standards, if applicable.

A) National Fire Protection Association (NFPA) - USA:

NFPA 13 Sprinkler Systems


NFPA 16 Foam/Water Deluge and Spray Systems
NFPA 17 Dry Chemical Extinguishing Systems
NFPA 17A Wet Chemical Extinguishing Systems
NFPA 2001 Clean Agent Extinguishing Systems
NFPA 72 National Fire Alarm Code
NFPA 76 Telecommunication Facilities
NFPA 318 Clean Room Applications
NFPA 101 Life Safety Code
NFPA 90A Air conditioning & ventilation system

B) Underwriters Laboratories Inc. (UL) - USA:

UL 268 Smoke Detectors for Fire Protective Signaling Systems

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 31 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
UL 864 Control Units for Fire Protective Signaling Systems 9th Edition Listed
UL 268 A Smoke Detectors for Duct Applications
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 38 Manually Actuated Signaling Boxes
UL 346 Water flow Indicators for Fire Protective Signaling Systems
UL 1971 Visual Notification Appliances
UL 228 Door Holders

3.2 NATIONAL BUILDING CODES

3.2.1 DELHI FIRE CODES

The Video Display Terminal (VDT) shall comply with Swedish magnetic emission and
X-radiation guidelines MPR 1990:10.

3.2.2 APPROVALS:

The system shall have proper listing and/or approval from the following nationally
recognized agencies:

UL Underwriters Laboratories Inc (9th Edition)

The fire alarm control panel shall meet UL Standard 864 9 th Edition (Control Units)

The system shall be listed by the national agencies as suitable for extinguishing release
applications. The system shall support release of high- and low-pressure CO2.

4.0 PRODUCTS

4.1 EQUIPMENT AND MATERIAL, GENERAL:

All equipment and components shall be new, and the manufacturer's current model.
The materials, appliances, equipment and devices shall be tested and listed by a
nationally recognized approvals agency for use as part of a protective signaling system,
meeting the National Fire Alarm Code.

All equipment and components shall be installed in strict compliance with


manufacturers' recommendations. Consult the manufacturer's installation manuals for
all wiring diagrams, schematics, physical equipment sizes, etc., before beginning system
installation.

All equipment shall be attached to walls and ceiling/floor assemblies and shall be held
firmly in place (e.g., detectors shall not be supported solely by suspended ceilings).
Fasteners and supports shall be adequate to support the required load.

5.0 CONDUIT AND WIRE:

5.1 Conduit:

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 32 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
Conduit shall be in accordance with The National Electrical Code (NEC), local and state
requirements.

Where required, all wiring shall be installed in conduit or raceway. Conduit fill shall
not exceed 40 percent of interior cross-sectional area where three or more cables are
contained within a single conduit.

Cable must be separated from any open conductors of power, or Class 1 circuits, and
shall not be placed in any conduit, junction box or raceway containing these conductors,
as per NEC Article 760-29.

Wiring for 24-volt DC control, alarm notification, emergency communication and


similar power-limited auxiliary functions may be run in the same conduit as initiating
and signaling line circuits. All circuits shall be provided with transient suppression
devices and the system shall be designed to permit simultaneous operation of all circuits
without interference or loss of signals.

Conduit shall not enter the fire alarm control panel, or any other remotely mounted
control panel equipment or back boxes, except where conduit entry is specified by the
FACP manufacturer.

Conduit shall be 3/4-inch (19.1 mm) minimum.

5.2 Wire:

All fire alarm system wiring shall be new.

Wiring shall be in accordance with local, state and national codes (e.g., NEC Article 760)
and as recommended by the manufacturer of the fire alarm system. Number and size of
conductors shall be as recommended by the fire alarm system manufacturer, but not less
than 1.5 mm² for Initiating Device Circuits and Signaling Line Circuits, and 2.5 mm² for
Notification Appliance Circuits.

All wire and cable shall be listed and/or approved by a recognized testing agency for
use with a protective signaling system.

Wire and cable shall have a fire resistance rating suitable for the installation as indicated
in NFPA 70 (e.g., FPLR).
Wiring used for the multiplex communication circuit (SLC) shall be twisted and
unshielded and support a minimum wiring distance of 12,500 feet. The design of the
system shall permit use of IDC and NAC wiring in the same conduit with the SLC
communication circuit.
All field wiring shall be electrically supervised for open circuit and ground fault.

The fire alarm control panel shall be capable of t-tapping Class B (NFPA Style 4)
Signaling Line Circuits (SLCs). Systems that do not allow or have restrictions in, for
example, the number of t-taps, length of t-taps etc., are not acceptable.
Terminal Boxes, Junction Boxes and Cabinets:

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 33 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
All boxes and cabinets shall be UL listed for their use and purpose.

Initiating circuits shall be arranged to serve like categories (manual, smoke, water flow).
Mixed category circuitry shall not be permitted except on signaling line circuits
connected to intelligent reporting devices.

The fire alarm control panel shall be connected to a separate dedicated branch circuit,
maximum 20 amperes. This circuit shall be labeled at the main power distribution panel
as FIRE ALARM. Fire alarm control panel primary power wiring shall be 4.0 mm². The
control panel cabinet shall be grounded securely to either a cold-water pipe or
grounding rod.

6.0 MAIN FIRE ALARM CONTROL PANEL OR NETWORK NODE:

The main FACP Central Console shall contain a microprocessor based Central
Processing Unit (CPU). The CPU shall communicate with and control the following
types of equipment used to make up the system: intelligent addressable smoke and
thermal (heat) detectors, addressable modules, panel modules including initiating
circuits, control circuits, and notification appliance circuits, local and remote operator
terminals, printers, annunciators, and other system-controlled devices.

6.1. In conjunction with intelligent Loop Control Modules and Loop Expander Modules, the
main FACP shall perform the following functions:

a. Supervise and monitor all intelligent addressable detectors and monitor modules
connected to the system for normal, trouble and alarm conditions.

b. Supervise all initiating signaling and notification circuits throughout the facility
by way of connection to monitor and control modules.

c. Detect the activation of any initiating device and the location of the alarm
condition. Operate all notification appliances and auxiliary devices as
programmed. In the event of CPU failure, all SLC loop modules shall fallback to
degrade mode. Such degrade mode shall treat the corresponding SLC loop
control modules and associated detection devices as conventional two-wire
operation. Any activation of a detector in this mode shall automatically activate
associated Notification Appliance Circuits.

d. Visually and audibly annunciate any trouble, supervisory, security or alarm


condition on operator's terminals, panel display, and annunciators.

1. When a fire alarm condition is detected and reported by one of the


systems initiating devices or appliances, the following functions shall
immediately occur:

a. The system alarm LED shall flash.

b. A local piezo-electric audible device in the control panel shall


sound a distinctive signal.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 34 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
c. The 640-character backlit LCD display shall indicate all
information associated with the fire alarm condition, including
the type of alarm point and its location within the protected
premises.

d. Printing and history storage equipment shall log and print the
event information along with a time and date stamp.

e. All system outputs assigned via preprogrammed equations for a


particular point in alarm shall be executed, and the associated
system outputs (alarm notification appliances and/or relays) shall
be activated.

2. When a trouble condition is detected and reported by one of the systems


initiating devices or appliances, the following functions shall
immediately occur:

a. The system trouble LED shall flash.

b. A local piezo-electric audible device in the control panel shall


sound a distinctive signal.

c. The 640-character backlit LCD display shall indicate all


information associated with the trouble condition, including the
type of trouble point and its location within the protected
premises.

d. Printing and history storage equipment shall log and print the
event information along with a time and date stamp.

e. All system outputs assigned via preprogrammed equations for a


particular point in trouble shall be executed, and the associated
system outputs (trouble notification appliances and/or relays)
shall be activated.

3. When a supervisory condition is detected and reported by one of the


systems initiating devices or appliances, the following functions shall
immediately occur:

a. The system trouble LED shall flash.

b. A local piezo-electric audible device in the control panel shall


sound a distinctive signal.

c. The 640-character backlit LCD display shall indicate all


information associated with the supervisory condition, including
the type of trouble point and its location within the protected
premises.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 35 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
d. Printing and history storage equipment shall log and print the
event information along with a time and date stamp.

e. All system outputs assigned via preprogrammed equations for a


particular point in trouble shall be executed, and the associated
system outputs (notification appliances and/or relays) shall be
activated.

4. When a security alarm condition is detected and reported by one of the


systems initiating devices or appliances, the following functions shall
immediately occur:

a. The system security LED shall flash.

b. A local piezo-electric audible device in the control panel shall


sound a distinctive signal.

c. The 640-character backlit LCD display shall indicate all


information associated with the fire alarm condition, including
the type of alarm point and its location within the protected
premises.

d. Printing and history storage equipment shall log and print the
event information along with a time and date stamp.

e. All system outputs assigned via preprogrammed equations for a


particular point in alarm shall be executed, and the associated
system outputs (alarm notification appliances and/or relays) shall
be activated.

5. When a pre-alarm condition is detected and reported by one of the


systems initiating devices or appliances, the following functions shall
immediately occur:

a. The system pre-alarm LED shall flash.

b. A local piezo-electric audible device in the control panel shall


sound a distinctive signal.

c. The 640-character backlit LCD display shall indicate all


information associated with the fire alarm condition, including
the type of alarm point and its location within the protected
premises.

d. Printing and history storage equipment shall log and print the
event information along with a time and date stamp.

e. All system outputs assigned via preprogrammed equations for a


particular point in alarm shall be executed, and the associated

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 36 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
system outputs (alarm notification appliances and/or relays) shall
be activated.

7.0 Operator Control

1. Acknowledge Switch:

a. Activation of the control panel acknowledge switch in response to new


alarms and/or troubles shall silence the local panel piezo electric signal
and change the alarm and trouble LEDs from flashing mode to steady-
ON mode. If multiple alarm or trouble conditions exist, depression of this
switch shall advance the LCD display to the next alarm or trouble
condition. In addition, the FACP shall support Block Acknowledge to
allow multiple trouble conditions to be acknowledged with a single
depression of this switch.

b. Depression of the Acknowledge switch shall also silence all remote


annunciator piezo sounders.

8.0 Signal Silence Switch:

Depression of the Signal Silence switch shall cause all programmed alarm notification
appliances and relays to return to the normal condition. The selection of notification
circuits and relays that are silence able by this switch shall be fully field programmable
within the confines of all applicable standards. The FACP software shall include silence
inhibit and auto-silence timers.

1. Drill Switch:

Depression of the Drill switch shall activate all programmed notification


appliance circuits. The drill function shall latch until the panel is silenced or
reset.

2. System Reset Switch:

Depression of the System Reset switch shall cause all electronically latched
initiating devices to return to their normal condition. Initiating devices shall re-
report if active. Active notification appliance circuits shall not silence upon
Reset. Systems that de-activate and subsequently re-activate notification
appliance circuits shall not be considered equal. All programmed Control-By-
Event equations shall be re-evaluated after the reset sequence is complete if the
initiating condition has cleared. Non-latching trouble conditions shall not clear
and re-report upon reset.

3. Lamp Test:

The Lamp Test switch shall activate all local system LEDs, light each segment of
the liquid crystal display and display the panel software revision for service
personal.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 37 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS

4. Scroll Display Keys:

There shall be Scroll Display keys for FIRE ALARM, SECURITY,


SUPERVISORY, TROUBLE, and OTHER EVENTS. Depression of the Scroll
Display key shall display the next event in the selected queue allowing the
operator to view events by type.

5. Print Screen:

Depression of the PRINT SCREEN switch shall send the information currently
displayed on the 640-character display to the printer.

9.0 System Capacity and General Operation

1. The control panel shall be capable of expansion via up to 10 SLC modules. Each
module shall support a maximum of 318 analog/addressable devices for a
maximum system capacity of 3180 points. The system shall be capable of 3072
annunciation points per system regardless of the number of addressable devices.

2. The Fire Alarm Control Panel shall include a full featured operator interface
control and annunciation panel that shall include a backlit 640-character liquid
crystal display, individual, color coded system status LEDs, and a QWERTY
style alphanumeric keypad for the field programming and control of the fire
alarm system. Said LCD shall also support graphic bit maps capable of
displaying the company name and logo of either the owner or installing
company.

3. All programming or editing of the existing program in the system shall be


achieved without special equipment and without interrupting the alarm
monitoring functions of the fire alarm control panel.

10.0 The FACP shall be able to provide the following software and hardware features:

10.1 a. Pre-signal and Positive Alarm Sequence: The system shall provide means to
cause alarm signals to only sound in specific areas with a delay of the alarm
from 60 to up to 180 seconds after start of alarm processing. In addition, a
Positive Alarm Sequence selection shall be available that allows a 15-second time
period for acknowledging an alarm signal from a fire detection/initiating device.
If the alarm is not acknowledged within 15 seconds, all local and remote outputs
shall automatically activate immediately.

b. Smoke Detector Pre-alarm Indication at Control Panel: To obtain early warning


of incipient or potential fire conditions, the system shall support a
programmable option to determine system response to real-time detector
sensing values above the programmed setting. Two levels of Pre-alarm
indication shall be available at the control panel: alert and action.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 38 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS

c. Alert: It shall be possible to set individual smoke detectors for pre-programmed


pre-alarm thresholds. If the individual threshold is reached, the pre-alarm
condition shall be activated.

d. Action: If programmed for action, and the detector reaches a level exceeding the
pre-programmed level, the control panel shall indicate an action condition.
Sounder bases installed with either heat or smoke detectors shall automatically
activate on action Pre-Alarm level, with general evacuation on alarm level.

e. The system shall support a detector response time to meet world annunciation
requirements of less than 3 seconds.

f. Device Blink Control: Means shall be provided to turn off detector/module LED
strobes for special areas.

g. NFPA 72 Smoke Detector Sensitivity Test: The system shall provide an


automatic smoke detector test function that meets the requirements of NFPA 72.

h. Programmable Trouble Reminder: The system shall provide means to


automatically initiate a reminder that troubles exist in the system. The reminder
will appear on the system display and (if enabled) will sound a piezo alarm.

i. On-line or Off-line programming: The system shall provide means to allow


panel programming either through an off-line software utility program away
from the panel or while connected and on-line. The system shall also support
upload and download of programmed database and panel executive system
program to a Personal Computer/laptop.

j. History Events: The panel shall maintain a history file of the last 4000 events,
each with a time and date stamp. History events shall include all alarms,
troubles, operator actions, and programming entries. The control panels shall
also maintain a 1000 event Alarm History buffer, which consists of the 1000 most
recent alarm events from the 4000-event history file.

k. Smoke Control Modes: The system shall provide means to perform FSCS mode
Smoke Control to meet NFPA-92A and 90B and HVAC mode to meet NFPA
90A.

l. The system shall provide means for all SLC devices on any SLC loop to be auto
programmed into the system by specific address. The system shall recognize
specific device type ID’s and associate that ID with the corresponding address of
the device.

m. Drill: The system shall support means to activate all silence-able fire output
circuits in the event of a practice evacuation or “drill”. If enabled for local
control, the front panel switch shall be held for a minimum of 2 seconds prior to
activating the drill function

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 39 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
n. Passwords and Users: The system shall support two password levels, master and
user. Up to 9 user passwords shall be available, each of which may be assigned
access to the programming change menus, the alter status menus, or both. Only
the master password shall allow access to password change screens.

o. Block Acknowledge: The system shall support a block Acknowledge for Trouble
Conditions

p. Sensitivity Adjust: The system shall provide Automatic Detector Sensitivity


Adjust based on Occupancy schedules including a Holiday list of up to 15 days.

r. Environmental Drift Control: The system shall provide means for setting
Environmental Drift Compensation by device. When a detector accumulates
dust in the chamber and reaches an unacceptable level but yet still below the
allowed limit, the control panel shall indicate a maintenance alert warning.
When the detector accumulates dust in the chamber above the allowed limit, the
control panel shall indicate a maintenance urgent warning.

s. Custom Action Messages: The system shall provide means to enter up to 100
custom action messages of up to 160 characters each. It shall be possible to
assign any of the 100 messages to any point.

t. Print Functions: The system shall provide means to obtain a variety of reports
listing all event, alarm, trouble, supervisory, or security history. Additional
reports shall be available for point activation for the last Walk Test performed,
detector maintenance report containing the detector maintenance status of each
installed addressable detector, all network parameters, all panel settings
including broad cast time, event ordering, and block acknowledge, panel timer
values for Auto Silence, Silence Inhibit, AC Fail Delay time and if enabled,
Proprietary Reminder, and Remote Reminder timers, supervision settings for
power supply and printers, all programmed logic equations, all custom action
messages, all non-fire and output activations (if pre-programmed for logging) all
active points filtered by alarms only, troubles only, supervisory alarms, pre-
alarms, disabled points and activated points, all installed points filtered by SLC
points, panel circuits, logic zones, annunciators, releasing zones, special zones,
and trouble zones.

u. Local Mode: If communication is lost to the central processor the system shall
provide added survivability through the intelligent loop control modules.
Inputs from devices connected to the SLC and loop control modules shall
activate outputs on the same loop when the inputs and outputs have been set
with point programming to participate in local mode or when the type codes are
of the same type: that is, an input with a fire alarm type code shall activate an
output with a fire alarm type code.

v. Resound based on type for security or supervisory: The system shall indicate a
Security alarm when a monitor module point programmed with a security Type
Code activates. If silenced alarms exist, a Security alarm will resound the panel
sounder. The system shall indicate a Supervisory alarm when a monitor module

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 40 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
point programmed with a supervisory Type Code activates. If there are silenced
alarms, a Supervisory alarm will resound the panel sounder.

w. Read status preview - enabled and disabled points: Prior to re-enabling points,
the system shall inform the user that a disabled device is in the alarm state. This
shall provide notice that the device must be reset before the device is enabled
thereby avoiding activation of the notification circuits.

x. Custom Graphics: When fitted with an LCD display, the panel shall permit
uploading of a custom bit-mapped graphic to the display screen. Graphic shall
display when all systems are normal.

y. Multi-Detector and Cooperating Detectors: The system shall provide means to


link one detector to up to two detectors at other addresses on the same loop in
cooperative multi-detector sensing. There shall be no requirement for sequential
addresses on the detectors and the alarm event shall be a result or product of all
cooperating detectors chamber readings.

z. Tracking/Latching Duct: The system shall support both tracking and latching
duct detectors.

aa. ACTIVE EVENT: The system shall provide a Type ID called FIRE CONTROL
for purposes of air-handling shutdown, which shall be intended to override
normal operating automatic functions. Activation of a FIRE CONTROL point
shall cause the control panel to (1) initiate the monitor module Control-by-Event,
(2) send a message to the panel display, history buffer, installed printer and
annunciators, (3) shall not light an indicator at the control panel, (4) Shall display
ACTIVE on the LCD as well a display a FIRE CONTROL Type Code and other
information specific to the device.

bb. NON-FIRE Alarm Module Reporting: A point with a type ID of NON-FIRE shall
be available for use for energy management or other non-fire situations. NON-
FIRE point operation shall not affect control panel operation nor shall it display a
message at the panel LDC. Activation of a NON-FIRE point shall activate
control by event logic but shall not cause any indication on the control panel.

cc. Security Monitor Points: The system shall provide means to monitor any point
as a type security.

dd. One-Man Walk Test: The system shall provide both a basic and advanced walk
test for testing the entire fire alarm system. The basic walk test shall allow a
single operator to run audible tests on the panel. All logic equation automation
shall be suspended during the test and while annunciators can be enabled for the
test, all shall default to the disabled state. During an advanced walk test, field-
supplied output point programming will react to input stimuli such as CBE and
logic equations. When points are activated in advanced test mode, each
initiating event shall latch the input. The advanced test shall be audible and
shall be used for pull station verification, magnet activated tests on input
devices, input and output device and wiring operation/verification.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 41 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS

ee. Control By Event Functions: CBE software functions shall provide means to
program a variety of output responses based on various initiating events. The
control panel shall operate CBE through lists of zones. A zone shall become
listed when it is added to a point’s zone map through point programming. Each
input point such as detector, monitor module or panel circuit module shall
support listing of up to 10 zones into its programmed zone map.

ff. Permitted zone types shall be general zone, releasing zone and special zone.
Each output point (control module, panel circuit module) can support a list of up
to 10 zones including general zone, logic zone, releasing zone and trouble zone.
It shall be possible for output points to be assigned to list general alarm. Non-
Alarm or Supervisory points shall not activate the general alarm zone.

gg. 1000 General Zones: The system shall support up to 1000 general purpose
software zones for linking inputs to outputs. When an input device activates,
any general zone programmed into that device’s zone map will be active and
any output device that has an active general zone in its map will be active. It
shall also be possible to use general zone as arguments in logic equations.

hh. 1000 Logic Equations: The system shall support up to 1000 logic equations for
AND, OR, NOT, ONLY1, ANYX, XZONE or RANGE operators that allow
conditional I/O linking. When any logic equation becomes true, all output
points mapped to the logic zone shall activate.

ii. 10 trouble equations per device: The system shall provide support for up to 10
trouble equations for each device, which shall permit programming parameters
to be altered, based on specific fault conditions. If the trouble equation becomes
true, all output points mapped to the trouble zone shall activate.

jj. Control-By-Time: A time-based logic function shall be available to delay an


action for a specific period of time based upon a logic input with tracking
feature. A latched version shall also be available. Another version of this shall
permit activation on specific days of the week or year with ability to set and
restore based on a 24-hour time schedule on any day of the week or year.

kk. Multiple agents releasing zones: The system shall support up to 10 releasing
zones to protect against 10 independent hazards. Releasing zones shall provide
up to three cross-zone with four abort options to satisfy any local jurisdiction
requirements.

ll. Alarm Verification, by device, with timer and tally: The system shall provide a
user-defined global software timer function that can be set for a specific detector
or indicating panel module input. The timer function shall delay an alarm signal
for a user-specified time period and the control panel shall ignore the alarm
verification timer if another alarm is detected during the verification period. It
shall also be possible to set a maximum verification count between 0 and 20 with
the “0” setting producing no alarm verification. When the counter exceeds the
threshold value entered, a trouble shall be generated to the panel.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 42 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS

10.2 Central Processing Unit

10.2.1. The Central Processing Unit shall communicate with, monitor, and control all other
modules within the control panel. Removal, disconnection or failure of any control
panel module shall be detected and reported to the system display by the Central
Processing Unit.

10.2.2. The Central Processing Unit shall contain and execute all control-by-event (including
Boolean functions including but not limited to AND, OR, NOT, ANYx, and
CROSSZONE) programs for specific action to be taken if an alarm condition is detected
by the system. Such control-by-event programs shall be held in non-volatile
programmable memory, and shall not be lost with system primary and secondary
power failure.

10.2.3. The Central Processing Unit shall also provide a real-time clock for time annotation, to
the second, of all system events. The time-of-day and date shall not be lost if system
primary and secondary power supplies fail.

10.2.4 The CPU shall be capable of being programmed on site without requiring the use of any
external programming equipment. Systems that require the use of external
programmers or change of EPROMs are not acceptable.

10.2.5 Consistent with UL864 standards, the CPU and associated equipment are to be
protected so that voltage surges or line transients will not affect them.

10.2.6 Each peripheral device connected to the CPU shall be continuously scanned for proper
operation. Data transmissions between the CPU and peripheral devices shall be reliable
and error free. The transmission scheme used shall employ dual transmission or other
equivalent error checking techniques.

10.2.7 The CPU shall provide an EIA-232 interface between the fire alarm control panel and
the UL Listed Electronic Data Processing (EDP) peripherals.

10.2.8 The CPU shall provide two EIA-485 ports for the serial connection to annunciation and
control subsystem components.

10.2.9 The EIA-232 serial output circuit shall be optically isolated to assure protection from
earth ground.

10.2.10 The CPU shall provide one high-speed serial connection for support of network
communication modules.

10.2.11 The CPU shall provide double pole relays for FIRE ALARM, SYSTEM TROUBLE,
SUPERVISORY, and SECURITY. The SUPERVISORY and SECURITY relays shall
provide selection for additional FIRE ALARM contacts.

10.3 Display

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 43 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
10.3.1 The system display shall provide all the controls and indicators used by the system
operator and may also be used to program all system operational parameters.

10.3.2 The display assembly shall contain, and display as required, custom alphanumeric
labels for all intelligent detectors, addressable modules, and software zones.

10.3.3 The system display shall provide a 640-character backlit alphanumeric Liquid Crystal
Display (LCD). It shall also provide ten Light-Emitting-Diodes (LEDs), that indicate the
status of the following system parameters: AC POWER, FIRE ALARM, PREALARM,
SECURITY, SUPERVISORY, SYSTEM TROUBLE, OTHER EVENT, SIGNALS
SILENCED, POINT DISABLED, and CPU FAILURE.

10.3.4 The system display shall provide a QWERTY style keypad with control capability to
command all system functions, entry of any alphabetic or numeric information, and
field programming. Two different password levels with up to ten (one Master and nine
User) passwords shall be accessible through the display interface assembly to prevent
unauthorized system control or programming.

10.3.5 The system display shall include the following operator control switches:
ACKNOWLEDGE, SIGNAL SILENCE, RESET, DRILL, and LAMP TEST. Additionally,
the display interface shall allow scrolling of events by event type including, FIRE
ALARM, SECURITY, SUPERVISORY, TROUBLE, and OTHER EVENTS. A PRINT
SCREEN button shall be provided for printing the event currently displayed on the 640-
character LCD.

10.4 Loop (Signaling Line Circuit) Control Module:

10.4.1 The Loop Control Module shall monitor and control a minimum of 318 intelligent
addressable devices. This includes 159 intelligent detectors (Photoelectric, Thermal etc.)
and 159 monitor or control modules.

10.4.2 The Loop Control Module shall contain its own microprocessor and shall be capable of
operating in a local/degrade mode (any addressable device input shall be capable of
activating any or all addressable device outputs) in the unlikely event of a failure in the
main CPU.

10.4.3 The Loop Control Module shall provide power and communicate with all intelligent
addressable detectors and modules on a single pair of wires. This SLC Loop shall be
capable of operating as a NFPA Style 6 (Class B) circuit.

10.4.4 The SLC interface board shall be able to drive an NFPA Style 6 twisted shielded circuit
up to 12,500 feet in length. The SLC Interface shall also be capable of driving an NFPA
Style 6, no twist, no shield circuit up to 3,000 feet in length. In addition, SLC wiring
shall meet the listing requirements for it to exit the building or structure. "T"-tapping
shall be allowed in either case.

10.4.5 The SLC interface board shall receive analog or digital information from all intelligent
detectors and shall process this information to determine whether normal, alarm, or
trouble conditions exist for that particular device. Each SLC Loop shall be isolated and

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 44 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
equipped to annunciate an Earth Fault condition. The SLC interface board software
shall include software to automatically maintain the detector's desired sensitivity level
by adjusting for the effects of environmental factors, including the accumulation of dust
in each detector. The analog information may also be used for automatic detector testing
and the automatic determination of detector maintenance requirements.

10.5 Enclosures:

10.5.1 The control panel shall be housed in a UL-listed cabinet suitable for surface or semi-
flush mounting. The cabinet and front shall be corrosion protected, given a rust-resistant
prime coat, and manufacturer's standard finish.

10.5.2 The back box and door shall be constructed of 2mm thickness CRCA steel with
provisions for electrical conduit connections into the sides and top.

10.5.3 The door shall provide a key lock and shall include a glass or other transparent opening
for viewing of all indicators. For convenience, the door may be site configured for either
right- or left-hand hinging.

10.5.4 The control unit shall be modular in structure for ease of installation, maintenance, and
future expansion.

10.6 Power Supply:

10.6.1 The Addressable Main Power Supply shall operate on 240 V AC, 50Hz, and shall
provide all necessary power for the FACP.

10.6.2 The Addressable Main Power Supply shall provide sufficient power to the CPU, using a
switching 24 VDC regulator and shall incorporate a battery charger for 24 hours of
standby power using dual-rate charging techniques for fast battery recharge.

10.6.3 The Addressable Main Power Supply shall provide a battery charger for 24 hours of
standby using dual-rate charging techniques for fast battery recharge. The supply shall
be capable of charging batteries ranging in capacity from 25-200 amp-hours within a 48-
hour period.

10.6.4 The Addressable Main Power Supply shall provide a very low frequency sweep earth
detect circuit, capable of detecting earth faults.

10.6.5 The Addressable Main Power Supply shall be power-limited as per 1995 UL864
requirements.

10.7 Universal Digital Alarm Communicator Transmitter (UDACT).

The UDACT is an interface for communicating digital information between a fire alarm
control panel and an UL-Listed central station.

10.7.1 The UDACT shall be compact in size, mounting in a standard module position of the
fire alarm control cabinet. Optionally, the UDACT shall have the ability for remote

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 45 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
mounting, up to 6,000 feet from the fire alarm control panel. The wire connections
between the UDACT and the control panel shall be supervised with one pair for power
and one pair for multiplexed communication of overall system status. Systems that
utilize relay contact closures are not acceptable.

10.7.2 The UDACT shall include connections for dual telephone lines (with voltage detect), per
UL/NFPA/FCC requirements. It shall include the ability for split reporting of panel
events up to three different telephone numbers.

10.7.3 The UDACT shall be completely field programmable from a built-in keypad and 4-
character red, seven segment display.

10.7.4 The UDACT shall be capable of transmitting events in at least 15 different formats. This
ensures compatibility with existing and future transmission formats.

10.7.5 Communication shall include vital system status such as:

- Independent Zone (Alarm, trouble, non-alarm, supervisory)


- Independent Addressable Device Status
- AC (Mains) Power Loss
- Low Battery and Earth Fault
- System Off Normal
- 12- and 24-Hour Test Signal
- Abnormal Test Signal (per UL requirements)
- EIA-485 Communications Failure
- Phone Line Failure

10.7.6 The UDACT shall support independent zone/point reporting when used in the Contact
ID format. In this format the UDACT shall support transmission of up to 2,040 points.
This enables the central station to have exact details concerning the origin of the fire or
response emergency.

11.0 Stand Alone Voice Evacuation Control Panel

11.1 A stand alone Voice Evacuation Control Panel shall be available from the same
manufacturer of the main fire alarm system.

11.2 This Voice Control Panel shall work stand alone or as a slave to the Main Control Panel.

11.3 Shall have as minimum requirements:

a. Integral 25 Watt, 25 Vrms audio amplifier.

b. Speaker circuit that can be wired both Class A and B.

c. Integral Digital Message Generator with a capacity of up to 60 seconds. The


Digital Message Generator shall be capable of primary and secondary messages
(30 seconds each). These messages shall field programmable without the use of
additional equipment.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 46 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS

d. Built in alert tone generators with steady, slow woop, high/low and chime tone
field programmable.

e. Integral Diagnostic LEDs for Power, System Trouble, Message Generator


Trouble, Tone Generator Trouble, and Alarm.

The Voice Control Panel shall be fully supervised including microphone, amplifier
output, message generator, speaker wiring, and tone generators.

Speaker outputs shall be fully power-limited.

12.0 Auxiliary Field Power Supply - Addressable

12.1 The auxiliary addressable power supply is a remote 24 VDC power supply used to
power Notification Devices and field devices that require regulated 24VDC power. The
power supply shall also include and charge backup batteries.

12.2 The addressable power supply for the fire alarm system shall provide up a minimum of
6.0 amps of 24-volt DC regulated power for Notification Appliance Circuit (NAC)
power or 5 amps of 24 volt DC general power. The power supply shall have an
additional .5 amp of 24 VDC auxiliary powers for use within the same cabinet as the
power supply. It shall include an integral charger designed to charge 7.0 - 25.0-amp
hour batteries.

12.3 The addressable power supply shall provide four individually addressable Notification
Appliance Circuits that may be configured as two Class "A" and two Class "B" or four
Class "B" only circuits. All circuits shall be power-limited per UL 864 requirements.

12.4 The addressable power supply shall provide built-in synchronization for certain
Notification Appliances on each circuit without the need for additional synchronization
modules. The power supply's output circuits shall be individually selected for
synchronization. A single addressable power supply shall be capable of supporting both
synchronized and non-synchronized Notification Devices at the same time.

12.5 The addressable power supply shall operate on 240 VAC, 50Hz.

12.6 The interface to the power supply from the Fire Alarm Control Panel (FACP) shall be
via the Signaling Line Circuit (SLC) or other multiplexed means. Power supplies that do
not use an intelligent interface are not suitable substitutes. The required wiring from
the FACP to the addressable power supply shall be a single unshielded twisted pair
wire.

12.7 The addressable power supply shall supervise for battery charging failure, AC power
loss, power brownout, battery failure, NAC loss, and optional ground fault detection. In

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 47 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
the event of a trouble condition, the addressable power supply shall report the incident
and the applicable address to the FACP via the SLC.

12.8 The addressable power supply shall have an AC Power Loss Delay option. If this option
is utilized and the addressable power supply experiences an AC power loss, reporting
of the incident to the FACP will be delayed. A delay time of eight or sixteen hours shall
be Dip-switch selected.

12.9 The addressable power supply shall have an option for Canadian Trouble Reporting
and this option shall be Dip-switch selectable.

12.10 The addressable power supply mounts in either the FACP back box or it's own
dedicated surface mounted back box with cover.

12.11 Each of the power supply's four output circuits shall be DIP-switch selected for
Notification Appliance Circuit or General Purpose 24 VDC power. Any output circuit
shall be able to provide up to 2.5 amps of 24 VDC power.

12.12 The addressable power supply's output circuits shall be individually supervised when
they are selected to be either a Notification Appliance Circuit when wired Class "A" or
by the use of and end-of-line resistor. When the power supply's output circuit is selected
as General 24VDC power, the circuit shall be individually supervised when an end-of-
line relay is used.

12.13 When selected for Notification Appliance Circuits, the output circuits shall be
individually DIP-switch selectable for Steady, March Time, Dual Stage or Temporal.

12.14 When selected as a Notification Appliance Circuit, the output circuits of the addressable
power supply shall have the option to be coded by the use of a universal zone coder.

12.15 The addressable power supply shall interface and synchronize with other power
supplies of the same type. The required wiring to interface multiple addressable power
supplies shall be a single unshielded, twisted pair wire.

12.16 An individual or multiple interfaced addressable power supplies shall have the option
to use an external charger for battery charging. Interfaced power supplies shall have the
option to share backup battery power.

13.0 Field Charging Power Supply: The FCPS is a device designed for use as either a remote
24-volt power supply or to power Notification Appliances and provide synchronization
signals to visual strobe devices.

13.1 The FCPS shall be available in two models offering either up to 6.0 amps (4.0 amps
continuous) or 8.0 amps (6.0 amps continuous) of regulated 24-volt power. It shall
include an integral charger designed to charge 7.0-amp hour batteries and to support
60-hour standby.

13.2 The Field Charging Power Supply shall have two input triggers. The input trigger shall
be a Notification Appliance Circuit (from the fire alarm control panel) or a relay. Four

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 48 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
outputs (two Style Y or Z and two style Y) shall be available for connection to the
Notification devices.

13.3 The FCPS shall include an attractive surface mount back box.

13.4 The Field Charging Power Supply shall include the ability to delay the AC fail delay per
NFPA requirements.

13.5 The FCPS include power limited circuitry, AS per 1995 UL standards.

14.0 System Circuit Supervision:

14.1 The FACP shall supervise all circuits to intelligent devices, annunciators and
conventional peripherals and annunciate loss of communications with these devices.
The CPU shall continuously scan above devices for proper system operation and upon
loss of response from a device shall sound an audible trouble, indicate that device or
devices are not responding and print the information in the history buffer and on a
printer.

14.2 Sprinkler system valves, standpipe control valves, PIV and main gate valves shall be
supervised for off-normal position.

15.0 Field Wiring Terminal Blocks:

All wiring terminal blocks shall be the plug-in/removable type and shall be capable of
terminating up to 1.5 mm² wire. Terminal blocks that are permanently fixed to the PC
board are not acceptable.

15.1 Printer

15.1.1 Printers shall be of the automatic type, printing code, time, date, location, category, and
condition.

15.1.2 The printer shall provide hard-copy printout of all changes in status of the system and
shall time-stamp such printouts with the current time-of-day and date. The printer shall
be standard carriage with 80-characters per line and shall use standard pin-feed paper.
The printer shall be enclosed in a separate cabinet suitable for placement on a desktop
or table and UL, ULC listed for use with the NFS-3030. The printer shall communicate
with the control using an interface complying with Electrical Industries Association
standard EIA-232D. The printer power shall be 120 VAC @ 60 Hz.

15.1.3 Thermal printers are not acceptable.

15.1.4 The system shall have a strip printer capable of being mounted directly in the main
FACP enclosure. Alarms shall be printed in easy-to-read RED, other messages, such as a
trouble, shall be printed in BLACK. This printer shall receive power from the system
power supply and shall operate via battery backup if AC mains are lost. The strip
printer shall be UL 864 listed.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 49 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
16.0 Transponders (Remotely Located Control Panels): (Repeater Panel)

16.1 Transponders shall be listed under UL category UOJZ as an independent, local fire
alarm control unit as well as being listed as a critical component in a multiplex fire
alarm system. Transponders shall be located where shown on the plans.

The transponder shall serve as the interface between conventional initiating fire devices,
controlled signaling devices, and the FACP. The supervised multiplex communication
port shall be an integral part of the transponder.

16.2 Each Transponder shall be powered from a local Power Supply, and shall provide all
power necessary for its own operation, including standby power.

16.3 Transponders shall be used to house batteries and power supplies to allow a true
distributed processing and amplification.

16.4 Each transponder shall have the following indicators and operator Controls:

a. Alarm Acknowledge/Signal Silence/Reset Switch


b. Power LED
c. System alarm LED
d. System trouble LED
e. Local piezoelectric signal
f. Red alarm per Initiating Device Circuit
g. Green on/off LED per notification appliance circuit or relay

16.5 Each transponder will be capable of expansion of up to 24 field circuits of the following
types in any mix:

16.6 a. Initiating Device Circuits (IDC): IDCs may be added to the transponder in
groups of 8 Style B (Class B), or 4 Style D (Class A) circuits. Each circuit shall be
capable of monitoring up to 30 compatible 2-wire smoke detectors, and/or any
number of contact type initiating devices.

b. Auxiliary Control Relay Outputs: Auxiliary relay outputs may be added to the
transponder in groups of eight individually controlled single Form-C circuits.
Alternately, the eight independent relays may be configured as four dual Form-
C. All relay contacts shall be rated 2 A @ 30 VDC.

c. Notification Appliance Circuits: Notification Appliance Circuit outputs may be


added to the transponder in groups of 8 Class B (Style Y), or 4 Class A (Style Z)
circuits. Each circuit shall be capable of being configured as a Telephone, Horn,
Strobe or Speaker Circuit.

17.0 Remote Transmissions:

17.1 Provide local energy or polarity reversal or trip circuits as required.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 50 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
17.2 The system shall be capable of operating a polarity reversal or local energy or fire alarm
transmitter for automatically transmitting fire information to the fire department.

17.3 Provide capability and equipment for transmission of zone alarm and trouble signals to
remote operator's terminals, system printers and annunciators.

17.4 Transmitters shall be compatible with the systems and equipment they are connected to
such as timing, operation and other required features.

17.5 System Expansion: Design the main FACP and transponders so that the system can be
expanded in the future (to include the addition of twenty percent more circuits or
zones) without disruption or replacement of the existing control panel. This shall
include hardware capacity, software capacity and cabinet space.

18.0 Field Programming

18.1 The system shall be programmable, configurable and expandable in the field without
the need for special tools, laptop computers, or other electronic interface equipment.
There shall be no firmware changes required to field modify the system time, point
information, equations, or annunciator programming/information.

18.2 It shall be possible to program through the standard FACP keyboard all system
functions.

18.3 All field defined programs shall be stored in non-volatile memory.

18.4 Two levels of password protection shall be provided in addition to a key-lock cabinet.
One level shall be used for status level changes such as point/zone disable or manual
on/off commands (Building Manager). A second (higher-level) shall be used for actual
change of the life safety program (installer). These passwords shall be five (5) digits at a
minimum. Upon entry of an invalid password for the third time within a one-minute
time period an encrypted number shall be displayed. This number can be used as a
reference for determining a forgotten password.

18.5 The system programming shall be "backed" up on a CD Drive or Pen Drive utilizing an
upload/download program. This system back-up disk shall be completed and given in
duplicate to the building owner and/or operator upon completion of the final
inspection. The program that performs this function shall be "non-proprietary", in that,
it shall be possible to forward it to the building owner/operator upon his or her request.

The installer's field programming and hardware shall be functionally tested on a


computer against known parameters/norms which are established by the FACP
manufacturer. A software program shall test Input-to-Output correlations, device Type
ID associations, point associations, time equations, etc. This test shall be performed on
an IBM-compatible PC with a verification software package. A report shall be
generated of the test results and two copies turned in to the engineer(s) on record.

It shall be the responsibility of the equipment supplier /installer to ensure that all
equipment supplied will fit in locations designated on plans and in the specifications.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 51 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS

19.0 Specific System Operations

19.1 Smoke Detector Sensitivity Adjust: Means shall be provided for adjusting the sensitivity
of any or all analog intelligent smoke detectors in the system from the system keypad or
from the keyboard of the video terminal. Sensitivity range shall be within the allowed
UL window.

19.2 Alarm Verification: Each of the Intelligent Addressable Smoke Detectors in the system
may be independently selected and enabled to be an alarm verified detector. The alarm
verification function shall be programmable from 5 to 50 seconds and each detector shall
be able to be selected for verification during the field programming of the system or any
time after system turn-on. Alarm verification shall not require any additional hardware
to be added to the control panel. The FACP shall keep a count of the number of times
that each detector has entered the verification cycle. These counters may be displayed
and reset by the proper operator commands.

19.3 System Point Operations:

a. Any addressable device in the system shall have the capability to be enabled or
disabled through the system keypad or video terminal.

b. System output points shall be capable of being turned on or off from the system
keypad or the video terminal.

19.4 Point Read: The system shall be able to display the following point status diagnostic
functions without the need for peripheral equipment. Each point shall be annunciated
for the parameters listed:

a. Device Status.
b. Device Type.
c. Custom Device Label.
d. Software Zone Label.
e. Device Zone Assignments.
f. Analog Detector Sensitivity.
g. All Program Parameters.

19.5 System Status Reports: Upon command from an operator of the system, a status report
will be generated and printed, listing all system statuses:

19.6 System History Recording and Reporting: The fire alarm control panel shall contain a
history buffer that will be capable of storing up to 4000 system events. Each of these
events will be stored, with time and date stamp, until an operator requests that the
contents be either displayed or printed. The contents of the history buffer may be
manually reviewed, one event at a time, and the actual number of activations may also
be displayed and or printed.

The history buffer shall use non-volatile memory. Systems that use volatile memory for
history storage are not acceptable.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 52 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
19.7 Automatic Detector Maintenance Alert: The fire alarm control panel shall automatically
interrogate each intelligent system detector and shall analyze the detector responses
over a period of time.

If any intelligent detector in the system responds with a reading that is below or above
normal limits, then the system will enter the trouble mode, and the particular Intelligent
Detector will be annunciated on the system display, and printed on the optional system
printer. This feature shall in no way inhibit the receipt of alarm conditions in the system,
nor shall it require any special hardware, special tools or computer expertise to perform.

19.8 The system shall include the ability (programmable) to indicate a "pre-alarm" condition.
This will be used to alert maintenance personal when a detector is at 80% of its alarm
threshold in a 60 second period.

20.0 Network Control Annunciator

A network control annunciator shall be provided to display all system intelligent points.
The NCA shall be capable of displaying all information for all 200,000 possible points on
the network. Network display devices, which are only capable of displaying a subset of
network points, shall not be suitable substitutes.

The NCA shall include a minimum of 640 characters, backlit by a long-life, solid-state
LCD display. It shall also include a full QWERTY style keypad with tactile feel.
Additionally, the network display shall include ten soft-keys for screen navigation and
the ability to scroll events by type. i.e. Fire Alarm, Supervisory Alarm, Trouble, etc.

The network control annunciator shall have the ability to display up to eight events in
order of priority and time of occurrence. Counters shall be provided to indicate the
total number of events by type.

The NCA shall mount in any of the network node fire alarm control panels. Optionally,
the network display may mount in a backbox designed for this use. The network shall
support a minimum of 103 network control annunciators (not to exceed total node
capacity) and shall connect to the network over either a wire or fiber interface.

The network control annunciator shall have an event history buffer capable of storing a
minimum of 1000 events in non-volatile memory. Additionally, the NCA shall have a
fire alarm history buffer capable of storing a minimum of 200 events in non-volatile
memory. Systems that do not protect fire alarm events from being overwritten by other
events are not suitable substitutes.

The NCA shall include two optically isolated, 9600 baud, industry standard EIA-232
ports for UL864 listed printers and CRT's. These peripheral devices shall print or
display network activity.

The network control annunciator shall include control switches for system wide control
of Acknowledge, Signal Silence, System Reset, Drill, and local Lamp Test. A mechanical
means by which the controls switches are "locked out", such as a key, shall be available.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 53 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
The NCA shall include long life LEDs to display Power, Fire Alarm, Pre-Alarm, Security
Alarm, System Trouble, Supervisory, Signals Silenced, Disabled Points, Other (non-fire)
Events, and CPU Failure.

The network control annunciator shall include a Master password and up to nine User
passwords. Each password shall be up to eight alpha-numeric characters in length. The
Master password shall be authorized to access the programming and alter status menus.
Each User password may have different levels of authorization assigned by the Master
password.

The NCA shall allow editing of labels for all points within the network; control on/off
of outputs; enable/disable of all network points; alter detector sensitivity; clear detector
verification counters for any analog addressable detector within the network; clear any
history log within the network; change the Time/Date settings; initiate a Walk Test.

The network control annunciator shall support an optional Windows TM based


program utility. This utility shall allow the user create an NCA database,
upload/download an NCA database, and download an upgrade to the NCA executive.
To ensure program validity, this utility shall check stored databases for errors. A
compare function shall be included to identify differences between databases.

For time keeping purposes the NCA shall include a time-of-day clock.

Each NCA shall support up to 32 additional 80-character remote display annunciators


for displaying network activity. These "Terminal Mode" displays will mimic the activity
appearing on the corresponding NCA.

21.0 Digital Voice Command Center

The Digital Voice Command Center located with the FACP, shall contain all equipment
required for all audio control, emergency telephone system control, signaling and
supervisory functions. This shall include speaker zone indication and control, telephone
circuit indication and control, digital voice units, microphone and main telephone
handset.

Function: The Voice Command Center equipment shall perform the following
functions:

Operate as a supervised multi-channel emergency voice communication system.

Operate as a two-way emergency telephone system control center.

Audibly and visually annunciate the active or trouble condition of every speaker circuit
and emergency telephone circuit.

Audibly and visually annunciate any trouble condition for digital tone and voice units
required for normal operation of the system.

Provide all-call Emergency Paging activities through activation of a single control


switch.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 54 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS

As required, provide vectored paging control to specific audio zones via dedicated
control switches.

Provide a factory recorded “library” of voice messages and tones in standard WAV. File
format, which may be edited and saved on a PC running a current Windows®
operating system.

Provide a software utility capable of off-line programming for the VCC operation and
the audio message files. This utility shall support the creation of new programs as well
as editing and saving existing program files. Uploading or downloading the VCC shall
not inhibit the emergency operation of other nodes on the fire alarm network.

Support an optional mode of operation with four analog audio outputs capable of being
used with UL 864 fire-listed analog audio amplifiers and SCL controlled switching.

The Digital Voice Command shall be modular in construction, and shall be capable of
being field programmable without requiring the return of any components to the
manufacturer and without requiring use of any external computers or other
programming equipment.

The Digital Voice Command and associated equipment shall be protected against
unusually high voltage surges or line transients.

22.0 Audio Amplifiers

22.1 The Audio Amplifiers will provide Audio Power (@70 Volts RMS) for distribution to
speaker circuits.

Multiple audio amplifiers may be mounted in a single enclosure, either to supply


incremental audio power, or to function as an automatically switched backup
amplifier(s).

The audio amplifier shall include an integral power supply, and shall provide built-in
LED indicators for the following conditions:

Earth Fault on DAP A (Digital Audio Port A)


Earth Fault on DAP B (Digital Audio Port B)
Audio Amplifier Failure Detected
Trouble
Active Alarm Bus input
Audio Detected on Aux Input A
Audio Detected on Aux Input B
Audio Detected on Fire Fighter’s Telephone Riser
Receiving Audio from digital audio riser
Short circuit on speaker circuit 1
Short circuit on speaker circuit 2
Short circuit on speaker circuit 3
Short circuit on speaker circuit 4
Data Transmitted on DAP A

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 55 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
Data Received on DAP A
Data Transmitted on DAP B
Data Received on DAP B
Board failure
Active fiber optic media connection on port A (fiber optic media applications)
Active fiber optic media connection on port B (fiber optic media applications)
Power supply Earth Fault
Power supply 5V present
Power supply conditions – Brownout, High Battery, Low Battery, Charger Trouble
The audio amplifier shall provide the following built-in controls:
Amplifier Address Selection Switches
Signal Silence of communication loss annunciation
Reset
Level adjustment for background music
Enable/Disable for Earth Fault detection on DAP A
Enable/Disable for Earth Fault detection on DAP A
Switch for 2-wire/4-wire FFT riser

Adjustment of the correct audio level for the amplifier shall not require any special tools
or test equipment.

Includes audio input and amplified output supervision, back up input, and automatic
switch over function, (if primary amplifier should fail).

System shall be capable of backing up digital amplifiers.

23.0 Audio Message Generator (Prerecorded Voice)/Speaker Control:

Each initiating zone or intelligent device shall interface with an emergency voice
communication system capable of transmitting a prerecorded voice message to all
speakers in the building.

Actuation of any alarm initiating device shall cause a prerecorded message to sound
over the speakers. The message shall be repeated four (4) times. Pre- and post-message
tones shall be supported.

A built-in microphone shall be provided to allow paging through speaker circuits.

24.0 Speakers:

All speakers shall operate on 70 VRMS or with field selectable output taps from 0.5 to
2.0 Watts.

Speakers in corridors and public spaces shall produce a nominal sound output of 84
dBA at 10 feet (3m).

Frequency response shall be a minimum of 400 HZ to 4000 HZ.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 56 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
The back of each speaker shall be sealed to protect the speaker cone from damage and
dust.

25.0 System paging from emergency telephone circuits shall be supported.

The audio message generator shall have the following indicators and controls to allow
for proper operator understanding and control:

LED Indicators:
Lamp Test
Trouble
Off-Line Trouble
Microphone Trouble
Phone Trouble
Busy/Wait
Page Inhibited
Pre/Post Announcement Tone

Controls with associated LED Indicators:


Speaker Switches/Indicators

The speaker circuit control switches/indicators shall include visual indication of active
and trouble status for each speaker circuit in the system.

The speaker circuit control panel shall include switches to manually activate or
deactivate each speaker circuit in the system.

26.0 Fire Fighters Telephone System

The emergency telephone circuit control panel shall include visual indication of active
and trouble status for each telephone circuit in the system.

The telephone circuit control panel shall include switches to manually activate or
deactivate each telephone circuit in the system.

27.0 Water flow Operation

An alarm from a water flow detection device shall activate the appropriate alarm
message on the main panel display, turn on all programmed notification appliance
circuits and shall not be affected by the signal silence switch.

27.1 Supervisory Operation

An alarm from a supervisory device shall cause the appropriate indication on the
system display, light a common supervisory LED, but will not cause the system to enter
the trouble mode.

27.2 Signal Silence Operation

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 57 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
The FACP shall have the ability to program each output circuit (notification, relay,
speaker etc) to deactivate upon depression of the signal silence switch.

28.0 Sprinkler and Standpipe Valve Supervisory Switches:

Each sprinkler system water supply control valve riser, zone control valve, and
standpipe system riser control valve shall be equipped with a supervisory switch.
Standpipe hose valves, and test and drain valves shall not be equipped with
supervisory switches.

PIV (post indicator valve) or main gate valves shall be equipped with a supervisory
switch.

The switch shall be mounted so as not to interfere with the normal operation of the
valve and adjusted to operate within two revolutions toward the closed position of the
valve control, or when the stem has moved no more than one-fifth of the distance from
its normal position.

The supervisory switch shall be contained in a weatherproof aluminum housing, which


shall provide a 3/4-inch (19 mm) conduit entrance and incorporate the necessary
facilities for attachment to the valves.

The switch housing shall be finished in red baked enamel.

The entire installed assembly shall be tampering proof and arranged to cause a switch
operation if the housing cover is removed, or if the unit is removed from its mounting.

Valve supervisory switches shall be provided and connected under this section and
installed by mechanical contractor.

29.0 Non-Alarm Input Operation


Any addressable initiating device in the system may be used as a non-alarm input to
monitor normally open contact type devices. Non-alarm functions are a lower priority
than fire alarm initiating devices.

Combo Zone

A special type code shall be available to allow water flow and supervisory devices to
share a common addressable module. Water flow devices shall be wired in parallel,
supervisory devices in series.

30.0 SYSTEM COMPONENTS:

30.1 Printer

The printer shall provide hard-copy printout of all changes in status of the system and
shall time-stamp such printouts with the current time-of-day and date. The printer shall
be standard carriage with 80-characters per line and shall use standard pin-feed paper.
The printer shall be enclosed in a separate cabinet suitable for placement on a desktop
or table. The printer shall communicate with the control panel using an interface

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 58 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
complying with Electrical Industries Association standard EIA-232D. Power to the
printer shall be 240 VAC @ 50 Hz.

The system shall have a strip printer capable of being mounted directly in the main
FACP enclosure. Alarms shall be printed in easy-to-read RED, other messages, such as a
trouble, shall be printed in BLACK. This printer shall receive power from the system
power supply and shall operate via battery back-up if AC mains are lost. The strip
printer shall be UL 864 listed.

30.2 Video Display Terminal

The Video Display Terminal shall provide a visual display and an audible alert of all
changes in status of the system and shall annotate such displays with the current time-
of-day and date.

The Video Display Terminal shall be enclosed in a cabinet suitable for placement on a
desktop or table.

A detachable keyboard shall be provided that may be used for programming, testing,
and control of the system. Individual keys shall be provided on the keyboard for the
ACKNOWLEDGE, RESET, LAMP TEST, SYSTEM TEST, and SIGNAL SILENCE
functions of the control panel.

The video display terminal shall include a count of all alarms and troubles in the
system, as well as a count of all alarms and trouble requiring acknowledgment. These
counts shall be continuously displayed during all FACP operations.

31.0 SYSTEM COMPONENTS - ADDRESSABLE DEVICES

Addressable Devices - General

Addressable devices shall use simple to install and maintain decade, decimal address
switches. Devices shall be capable of being set to an address in a range of 001 to 159.

Addressable devices, which use a binary-coded address setting method, such as a DIP-
switch, are not an allowable substitute.

Detectors shall be intelligent (analog) and addressable, and shall connect with two wires
to the fire alarm control panel Signaling Line Circuits.

Addressable smoke and thermal detectors shall provide dual alarm and power/polling
LEDs. Both LEDs shall flash green under normal conditions, indicating that the detector
is operational and in regular communication with the control panel, and both LEDs
shall be placed into steady red illumination by the control panel, indicating that an
alarm condition has been detected. If required, the LED flash shall have the ability to be
removed from the system program. An output connection shall also be provided in the
base to connect an external remote alarm LED.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 59 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
The fire alarm control panel shall permit detector sensitivity adjustment through field
programming of the system. The panel on a time-of-day basis shall automatically adjust
sensitivity.

Using software in the FACP, detectors shall automatically compensate for dust
accumulation and other slow environmental changes that may affect their performance.
The detectors shall be listed by UL as meeting the calibrated sensitivity test
requirements of NFPA Standard 72, Chapter 7.

The detectors shall be ceiling-mount and shall include a separate twist-lock base with
tamper proof feature. Bases shall include a sounder base with a built-in (local) sounder
rated at 85 DBA minimum, a relay base and an isolator base designed for Style 7
applications.

The detectors shall provide a test means whereby they will simulate an alarm condition
and report that condition to the control panel. Such a test may be initiated at the
detector itself (by activating a magnetic switch) or initiated remotely on command from
the control panel.

Detectors shall also store an internal identifying type code that the control panel shall
use to identify the type of device.

Detectors will operate in an analog fashion, where the detector simply measures its
designed environment variable and transmits an analog value to the FACP based on
real-time measured values. The FACP software, not the detector, shall make the
alarm/normal decision, thereby allowing the sensitivity of each detector to be set in the
FACP program and allowing the system operator to view the current analog value of
each detector.

Addressable devices shall store an internal identifying code that the control panel shall
use to identify the type of device.

A magnetic test switch shall be provided to test detectors and modules. Detectors shall
report an indication of an analog value reaching 100% of the alarm threshold.

Addressable modules shall mount in a 4-inch square (101.6 mm square), 2-1/8 inch (54
mm) deep electrical box. An optional surface mount Lexan enclosure shall be available.

32.0 Programmable Electronic Exit Point Directional Sounders:

Electronic sounders shall operate on 24 VDC nominal.

Electronic sounders shall be field programmable without the use of special tools, at a
sound level of at least 90 dBA measured at 10 feet from the device.

Shall be flush or surface mounted as shown on plans.

Shall produce broad band directional sound to guide occupants to safe exists even in
complete darkness.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 60 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS

Strobe lights shall meet the requirements of the ADA, UL Standard 1971, be fully
synchronized, and shall meet the following criteria:

The maximum pulse duration shall be 2/10 of one second.

Strobe intensity shall meet the requirements of UL 1971.

The flash rate shall meet the requirements of UL 1971.


Field Wiring Terminal Blocks

For ease of service all panel I/O wiring terminal blocks shall be removable, plug-in
types and have sufficient capacity for 1.5 mm² to 4.0 mm² wire. Terminal blocks that are
permanently fixed are not acceptable.

33.0 Addressable Manual Fire Alarm Box (manual station)

Addressable manual fire alarm boxes shall, on command from the control panel, send
data to the panel representing the state of the manual switch and the addressable
communication module status. They shall use a key operated test-reset lock, and shall
be designed so that after actual emergency operation, they cannot be restored to normal
use except by the use of a key.

All operated stations shall have a positive, visual indication of operation and utilize a
key type reset.

Manual fire alarm boxes shall be constructed of Lexan with clearly visible operating
instructions provided on the cover. The word FIRE shall appear on the front of the
stations in raised letters, 1.75 inches (44 mm) or larger.

34.0 Intelligent Multi-Co-Operative Sensing Type Photoelectric Smoke Detector

The detectors shall use the photoelectric (light-scattering) principal to measure smoke
density and shall be in position to work in advance multi–Co-Operative Sensing, on
command from the control panel, send data to the panel representing the analog level of
smoke density.

35.0 Intelligent Thermal Detectors

Thermal detectors shall be intelligent addressable devices rated at 135 degrees


Fahrenheit (58 degrees Celsius) and have a rate-of-rise element rated at 15 degrees F (9.4
degrees C) per minute. It shall connect via two wires to the fire alarm control panel
signaling line circuit.

36.0 Intelligent Laser Photo Smoke Detector

36.1 The intelligent laser photo smoke detector shall be a spot type detector that incorporates
an extremely bright laser diode and an integral lens that focuses the light beam to a very

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 61 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
small volume near a receiving photo sensor. The scattering of smoke particles shall
activate the photo sensor.

36.2. The laser detector shall have conductive plastic so that dust accumulation is reduced
significantly.

36.3. The intelligent laser photo detector shall have nine sensitivity levels and be sensitive to a
minimum obscuration of 0.03 percent per foot.

36.4. The laser detector shall not require expensive conduit, special fittings or PVC pipe.

36.5. The intelligent laser photo detector shall support standard, relay, isolator and sounder
detector bases.

36.6. The laser photo detector shall not require other cleaning requirements than those listed
in NFPA 72. Replacement, refurbishment or specialized cleaning of the detector head
shall not be required.

36.7. The laser photo detector shall include two bicolor LEDs that flash green in normal
operation and turn on steady red in alarm.

37.0 Intelligent Multi Criteria Acclimating Detector

37.1 The intelligent multi criteria Acclimate detector shall be an addressable device that is
designed to monitor a minimum of photoelectric and thermal technologies in a single
sensing device. The design shall include the ability to adapt to its environment by
utilizing a built-in microprocessor to determine its environment and choose the
appropriate sensing settings. The detector design shall allow a wide sensitivity
window, no less than 1 to 4% per foot obscuration. This detector shall utilize advanced
electronics that react to slow smoldering fires and thermal properties all within a single
sensing device.
37.2 The microprocessor design shall be capable of selecting the appropriate sensitivity levels
based on the environment type it is in (office, manufacturing, kitchen etc.) and then
have the ability to automatically change the setting as the environment changes (as
walls are moved or as the occupancy changes).

37.3 The intelligent multi criteria detection device shall include the ability to combine the
signal of the thermal sensor with the signal of the photoelectric signal in an effort to
react hastily in the event of a fire situation. It shall also include the inherent ability to
distinguish between a fire condition and a false alarm condition by examining the
characteristics of the thermal and smoke sensing chambers and comparing them to a
database of actual fire and deceptive phenomena.

38.0 Intelligent Duct Smoke Detector


38.1 The smoke detector housing shall accommodate either an intelligent ionization detector
or an intelligent photoelectric detector, of that provides continuous analog monitoring
and alarm verification from the panel.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 62 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
38.2 When sufficient smoke is sensed, an alarm signal is initiated at the FACP, and
appropriate action taken to change over air handling systems to help prevent the rapid
distribution of toxic smoke and fire gases throughout the areas served by the duct
system.

39.0 Hostile-Area Smoke Detector


39.1 The detector shall be designed to provide early warning smoke detection in
environments where traditional smoke detectors are not practical.
39.2 The detector shall have a filter system to remove particles down to 25 microns.
39.3 This filter system shall remove unwanted airborne particles and water mist. This shall
allow the detector to operate in environments where traditional smoke detectors would
have nuisance alarms.
39.4 The filter system shall consist of 2 filters one of which is field replaceable.
39.5 The filter system shall have an intake fan to draw air and smoke through the filters into
the sensing chamber.
39.6 The filter system shall be supervised so that if the filter is clogged or the fan fails the
control panel reports trouble.
39.7 The filter system shall be powered from 24 VDC separate from the SLC
communications.
39.8 The detector shall utilize a photoelectric sensing chamber.

40.0 Two Wire Detector Monitor Module


40.1 Addressable monitor modules shall be provided to connect one supervised IDC zone of
conventional 2-wire smoke detectors or alarm initiating devices (any N.O. dry contact
device).

40.2 The IDC zone may be wired for Class A or B (Style D or Style B) operation. An LED
shall be provided that shall flash under normal conditions, indicating that the monitor
module is operational and in regular communication with the control panel.

41.0 Addressable Control Module

41.1 Addressable control modules shall be provided to supervise and control the operation
of one conventional NACs of compatible, 24 VDC powered, polarized audio/visual
notification appliances.

41.2. The control module NAC may be wired for Style Z or Style Y (Class A/B) with up to 1
amp of inductive A/V signal, or 2 amps of resistive A/V signal operation.

41.3. Audio/visual power shall be provided by a separate supervised power circuit from the
main fire alarm control panel or from a supervised UL listed remote power supply.

41.4. The control module shall be suitable for pilot duty applications and rated for a
minimum of 0.6 amps at 30 VDC.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 63 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS

42.0 Addressable Relay Module

42.1 Addressable Relay Modules shall be available for HVAC control and other building
functions. The relay shall be forming C and rated for a minimum of 2.0 Amps resistive
or 1.0 Amps inductive. The relay coil shall be magnetically latched to reduce wiring
connection requirements, and to ensure that 100% of all auxiliary relay or NACs may be
energized at the same time on the same pair of wires.

43.0 Isolator Module

43.1 Isolator modules shall be provided to automatically isolate wire-to-wire short circuits on
an SLC Class A or Class B branch. The isolator module shall limit the number of
modules or detectors that may be rendered inoperative by a short circuit fault on the
SLC loop segment or branch. At least one isolator module shall be provided for each
floor or protected zone of the building.

43.2 If a wire-to-wire short occurs, the isolator module shall automatically open-circuit
(disconnect) the SLC. When the short circuit condition is corrected, the isolator module
shall automatically reconnect the isolated section.

43.3 The isolator module shall not require address-setting, and its operations shall be totally
automatic. It shall not be necessary to replace or reset an isolator module after its normal
operation.

43.4 The isolator module shall provide a single LED that shall flash to indicate that the
isolator is operational and shall illuminate steadily to indicate that a short circuit
condition has been detected and isolated.

44.0 BATTERIES:

The battery shall have sufficient capacity to power the fire alarm system for not less
than twenty-four hours plus 5 minutes of alarm upon a normal AC power failure.

The batteries are to be completely maintenance free. No liquids are required. Fluid level
checks for refilling, spills, and leakage shall not be required.

If necessary to meet standby requirements, external battery and charger systems may be
used.

45.0 EXECUTION

45.1 INSTALLATION:

Installation shall be in accordance with the NEC, NFPA 72, local and state codes, as
shown on the drawings, and as recommended by the major equipment manufacturer.

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 64 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
All conduit, junction boxes, conduit supports and hangers shall be concealed in finished
areas and may be exposed in unfinished areas. Smoke detectors shall not be installed
prior to the system programming and test period. If construction is ongoing during this
period, measures shall be taken to protect smoke detectors from contamination and
physical damage.

All fire detection and alarm system devices, control panels and remote annunciators
shall be flush mounted when located in finished areas and may be surface mounted
when located in unfinished areas.

Manual fire alarm boxes shall be suitable for surface mounting or semi-flush mounting
as shown on the plans, and shall be installed not less than 42 inches (1067 mm), nor
more than 48 inches (122 mm) above the finished floor.

45.2 TEST:

The service of a competent, factory-trained engineer or technician authorized by the


manufacturer of the fire alarm equipment shall be provided to technically supervise and
participate during all of the adjustments and tests for the system. All testing shall be in
accordance with NFPA 72, Chapter 7.

Before energizing the cables and wires, check for correct connections and test for short
circuits, ground faults, continuity, and insulation.

Close each sprinkler system flow valve and verify proper supervisory alarm at the
FACP.

Verify activation of all waterflow switches.

Open initiating device circuits and verify that the trouble signal actuates.

Open and short signaling line circuits and verify that the trouble signal actuates.

Open and short notification appliance circuits and verify that trouble signal actuates.

Ground all circuits and verify response of trouble signals.

Check presence and audibility of tone at all alarm notification devices.

Check installation, supervision, and operation of all intelligent smoke detectors using
the walk test.

Each of the alarm conditions that the system is required to detect should be introduced
on the system. Verify the proper receipt and the proper processing of the signal at the
FACP and the correct activation of the control points.

When the system is equipped with optional features, the manufacturer's manual shall
be consulted to determine the proper testing procedures. This is intended to address

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 65 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
such items as verifying controls performed by individually addressed or grouped
devices, sensitivity monitoring, verification functionality and similar.

45.3 FINAL INSPECTION:

At the final inspection, a factory-trained representative of the manufacturer of the major


equipment shall demonstrate that the system functions properly in every respect.

46.0 INSTRUCTION:

Instruction shall be provided as required for operating the system. Hands-on


demonstrations of the operation of all system components and the entire system
including program changes and functions shall be provided.

The contractor and/or the systems manufacturer's representatives shall provide a


typewritten "Sequence of Operation."

END OF SECTION VII

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 66 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS

SECTION-VIII : LIST OF VENDORS FOR VARIOUS ITEMS

S.No Materials IS Brand Manufacturer/Approved


Dealer
1 MS Pipes 1239/3589 TATA Tata steel Limited
JINDAL HISSAR Jindal Tube Co.
JINDAL STAR Jindal gaziabad
2(a) Forged Steel Fittings SS / TRUE True Forge/ SS /
FORGE V.S.Forge
(b) Butt Welded Fittings DRP/True Forge / SS
3. Gunmetal Ball Valves AIP AIP VALVES
SANT Sant Valves.
TBS Thakur Bhai & Son
Zoloto Zoloto Marketing Co.
4. C.I. Double flanged sluice 780 KARTAR Juneja Metals
Valves & check valves
SANT Sant Valves.
Leader Leader Engg. Works,
Jullandur
KIRLOSKAR/IVC KIRLOSKAR/IVC
5. Slim Seal Butterfly Valve AIP AIP Valves
ADVANCE Advance Valve Co.
SANT Sant Valves.

6. Dual/Disk type Non- SANT Sant Valves


Return Valves
ADVANCE Advance Valve Co.
KIRLOSKAR/IVC KIRLOSKAR/IVC
7. Fire Hydrant Valves, 5290 LIFE GUARD United Fire Equipments
Branch pipe & Fire man Pvt. Ltd.
Axe.
PADMINI Padmini Industris Ltd.
NEWAGE Newage Industris
MINIMAX
8. Fire Aid Fire Hose Reels 884 LIFE GUARD United Fire Equipments
Pvt. Ltd.
PADMINI Padmini Industris Ltd.
NEWAGE Newage Industris
MINIMAX
9. CP Hose Pipe 8423 LIFE GUARD United Fire Equipments
Pvt. Ltd.
PADMINI Padmini Industris Ltd.
NEWAGE Newage Industris
MINIMAX
S.No Materials IS Brand Manufacturer/Approved
Dealer

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 67 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
10. Sprinkler Head TYCO
LIFE GUARD
VIKING
HD
SPRAYSAFE
11. Fire Pumps 1520 KIRLOSKER Kirloskar Brothers
MATHER+PLATT Mather+platt

12 Motors IS: 325/ KIRLOSKAR, Kirloskar Brothers, Pune


TAC
SIEMENS Siemens
CROMPTON, CROPTON, NGEF
NGEF
13 Electrical Switch Gear & L&T
ABB

14 CABLES RR
Sable/HAVELS/
KEI
Polycab/CCI

15 Suction Strainer Sant/Jaypee/


kartar
Zoloto

16 Vibration Eliminator Resistoflex Relay Corp. Noida


Connectors
Kanwal
D. Wren Calcutta

17 Single Phasing Preventor Siemems, Minilec


L & T,

18 Pipe coat material PYPKOTE Integrated Water-


Proofing Co. Madras
(Pipe protection) Coaltek Rustech Products (P)
Ltd
Syndicate Enclave,
Dabri
19 Flow switch Tyco
SYSTEM SENSOR
20 Diesel Engine IS : 10000 ASHOK
LEYLAND/
TAC Approved
KIRLOSKAR
/CUMMINS
S.No Materials IS Brand Manufacturer/Approved
Dealer

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 68 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
21 Main control panel Relevant SIEMENS/L&T/TEI
IS/TAC
TRICOLITE
ADVANCE AUTOMATION
ELEGANT CONTROL
DIMOND
RISA CONTROL
22 Fire brigade inlet. 904 PADMINI Padmini Industris Ltd.
NEWAGE Newage Industris
MINIMAX

23 Rubber Hose pipe 444 JYOTI


Kartar
PADMINI
MINIMAX
24 Hose Couplings branch 909 PADMINI Padmini Industris Ltd.
NEWAGE Newage Industris
MINIMAX
25 Pressure Switches TAC INDFOSS/
Denfoss

26 Pressure Gauge 3624(CL- H. GURU/FIEBIG


I)
MINIMAX
27 Battery EXIDE/
PRESTOLITE

28 Fire Extinguisher PADMINI


SAFEX
CEASE FIRE
29 Enamel paint ASIAN
NEROLAC
BERGER

30 Annunciation panel 2189 SAFEWAY


DAKSH

31 Alaram Valve MATTER


&PALET
HD

32 Contactor L& T
SIEMENS

Sl.No Materials IS Brand Manufacturer/Approved


Dealer
33 Tnimbles/Ferrules Dowel

TECHNICAL SPECIFICATION FIRE FIGHTING PROTECTION SYSYEM 69 | P a g e


EVOS BUILDCON PVT. LTD TS-FFPS
Tinned Copper

34 Cable gland. COMMEX


POWER
GRIPWELL
35 Power Capacitor L&T
CROMPTON
ASIAN

36 Measuring Meter L&T/Siemens/


AE

37 MS Conduit Steel
Craft/BEC/AKG

38 Dash Fastener Hilti/Fisher

39 Weld Electrodes Advani/


Esab/Victor

40 Pipe Hangers Chillys/GMGR

NOTE :
01. All approved vendors available under JPDPL are also to be considered as approved make.

02. All makes shall confirm to standard specifications of each items as enclosed with the tender
documents.