Remote Kontrol Kabel & Remote Kontrol Wireless

Operasi & Mendeteksi Kode


Kerusakan

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Operasi remot kontrol
Wired remot kontrol <BRC1A61, 62> LED operasi

Sensor suhu Tombol


ruangan ON/OFF

Tombol pengaturan
swing flap
Tombol timer
ON/OFF Tombol mode
Tombol
Tombol konfirmasi kecepatan fan
timer
Tombol
reset cleaning
Tombol Inspeksi

Tombol waktu timer Tombol pengatur suhu

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Perubahan mode "Inspeksi"

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Operasi remot kontrol
Remot kontrol wireless
<BRC4C151>
Receiver

Buzzer

Indoor unit tipe cassette


BRC4C151
Indikasi lampu operasi
[Lampu operasi]

Indikasi lampu timer


[Lampu timer]

Indikasi lampu
pembersihan filter udara
[Tanda filter]
Remot
Indikasi lampu
defrost/hot Start
Kontrol
[Lampu defrost]

[Depan] [Belakang]

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Operasi remot kontrol
Remot kontrol wireless <BRC4C151>
Tombol ON/OFF
Tombol pengatur suhu
Tombol kecepatan fan

Tombol
pembatalan timer
Tombol
Tombol timer ON/OFF
konfirmasi
timer
Tombol mode
Tombol swing flap
Tombol reset cleaning

Tombol inspeksi

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Operasi remot kontrol
Remot kontrol kabel <BRC1E61>
Tombol Mode

LCD (with backlight)

Tombol UP
Tombol Down
Tombol Right
Tombol Left

LED Operasi
Tombol ON/OFF

Tombol Menu/Enter

Tombol Cancel

Tombol Kecepatan
Fan

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Mendeteksi kode kerusakan

Group kode Kerusakan

I. Indoor :A&C

II. Outdoor : E, F, H, & J

III. Inverter : L & P

IV. System : U

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Mendeteksi kode kerusakan
LED Operasi

Tampilan indoor unit yang


kerusakan telah terdeteksi

UNIT NO. 0

U4
UNIT NO. 0
U4

Tanda Inspeksi

Code Kerusakan

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Mendeteksi kode kerusakan

Kode
Kerusakan

UNIT NO. 0
U4

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Mendeteksi kode kerusakan
Tabel kode kerusakan (Kutipan dari service manual)
Malfunction Malfunction
code
LA Malfunction of power unit
LC Malfunction of transmission between inverter and Control PC board
Outdoor unit P1 Inverter over-ripple protection
P4 Malfunction of inverter radiating fin temperature rise sensor
PJ Malfunction of inverter fan driver matching
U0 Low pressure drop due to refrigerant shortage or electronic expansion valve failure
U1 Reverse phase / Open phase
U2 Power supply insufficient or instantaneous failure
U3 Check operation is not completed
U3 Check operation is not completed
U4
U4 Malfunction of transmission between
Malfunction of indoor and outdoor
transmission betweenunits
indoor and outdoor units
U5 Malfunction of transmission between remote controller and indoor unit
U5 Failure of remote controller PC board or setting during control by remote controller
System U7 Malfunction of transmission between outdoor units
Malfunction of transmission between main and sub remote controllers
U8
(malfunction of sub remote controller)
U9 Malfunction of transmission between indoor unit and outdoor unit in the same system
UA Improper combination of indoor and outdoor units OR indoor units and remote controller
UC Address duplication of central remote controller
UE Malfunction of transmission between central remote controller and indoor unit
UF Refrigerant system not set, incompatible wiring/piping
UH Malfunction of system, refrigerant system address undefined
The system will continue to operate even if one of the malfunction codes shown in the shaded squares is detected.
However, be sure to check and repair it as soon as possible.

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Mendeteksi kode kerusakan
Remot kontrol < BRC4M151W>

1. Tekan tombol TEST dan tampilan akan berubah


menjadi “00”
2. Tekan tombol MODE untuk menunjukan kode ke 1.
3. Tekan tombol SELECT berulangkali (UP / DOWN) jika
Ada bunyi bip 2 kali, menunjukan kode ke 1.
4. Tekan tombol MODE untuk menunjukan kode ke 2.
5. Tekan tombol SELECT berulangkali (UP / DOWN) jika
Ada bunyi bip panjang, menunjukan kode ke 2.
7. Tekan dan tahan tombol ON/OFF selama 5 detik
kode kerusakan dihapus (tampilan “00”).
8. Tekan tombol MODE sekali tampilan kembali keawal.

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Mendeteksi kode kerusakan

1. Tekan TEST masuk kepencarian kode kerusakan


6
3,5 2. Tekan MODE masuk ke pencarian pada kode pertama
3. Tekan UP/DOWN cari dikode pertama jika ada bunyi bip
3,5
2 kali menunjukan kode ke 1. lakukan langkah ke 4
4. Tekan MODE masuk kepencarian pada kode ke 2
5. Tekan UP/DOWN cari dikode ke 2 jika ada bunyi bip
panjang, menunjukan kode ke 2

2,4 “Jika terdapat satu kali bunyi bip yang panjang”


Tampilan menununjukkan kode kerusakan
6. Tekan dan tahan ON/OFF selama 5 detik
kode kerusakan dihapus.
1

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Operasi remot kontrol
Remot kontrol < ARC455A, ARC452A, ARC433B, ARC423A, ARC417A>

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Mendeteksi kode kerusakan
Remot kontrol < ARC455A, ARC452A, ARC433B, ARC423A, ARC417A>

Tombol CANCEL

1. Tekan dan tahan tombol CANCEL 5 detik,


tampilan akan berubah menjadi “00”
2. Tekan tombol CANCEL berulang sampai
mendapatkan bunyi bip panjang, tampilan
akan menunjukan kode kerusakan

RESET,
Tekan & tahan tombol CANCEL 5 detik
kode kerusakan dihapus.

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Mendeteksi kode kerusakan
Remot kontrol < ARC455A, ARC452A, ARC433B, ARC423A, ARC417A>

Tekan ke 3 tombol
secara bersamaan

1. Tekan tombol TEMP. Cari dikode pertama jika


ada bunyi bip 2 kali, menunjukan kode ke 1.
2. Tekan tombol MODE. Masuk ke pencarian kode
ke dua
3. Tekan tombol TEMP. Cari dikode kedua jika
mendapatkan bunyi bip panjang, menunjukan
kode kerusakan

RESET,
Tekan & tahan tombol ON/OFF 5 detik kode
kerusakan dihapus.

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Remot kontrol < ARC480A23>

1. Tekan tombol OFF dan TEMP bersamaan waktu dan


tampilan akan berubah menjadi “SC”
2. Tekan tombol FAN dan tampilan berubah menjadi “00”
3. Tekan tombol TEMP (UP / DOWN) cari dikode pertama
jika ada bunyi bip 2 kali menunjukan kode ke 1.
lakukan langkah ke 4.
4. Tekan tombol FAN masuk kepencarian pada kode ke 2.
5. Tekan tombol TEMP (UP / DOWN) cari dikode ke 2 jika
ada bunyi bip panjang, menunjukan kode ke 2.
5. Tekan dan tahan tombol OFF selama 5 detik
kode kerusakan dihapus (tampilan “00”).
6. Tekan dan tahan tombol FAN selama 5 detik
tampilan kembali keawal.

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Operasi remot kontrol
Remot kontrol <BRC1NU64>

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Operasi remot kontrol
Remot kontrol <FVPGR-N, FVGR-N>

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Operasi remot kontrol
Remot kontrol <FVPGR-N, FVGR-N>

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Tampilan kode kerusakan
Kode kerusakan Kerusakan yang terjadi
A0 Proteksi eksternal perangkat aktif

A1 PCB indoor bermasalah

A3 Sistem drain bermasalah

A5 Frezee up Proteksi aktif

A6 Fan motor bermasalah


Unit Indoor

A7 motor swing flap bermasalah

A9 Electronic expanstion valve bermasalah

AF Drain level di atas limit

AJ Setting kapasitas bermasalah (PCB indoor)

C4 Thermistor (R2T) pipa liquid bermasalah

C5 Thermistor (R3T) pipa gas bermasalah

C9 Thermistor (R1T) inlet udara bermasalah

CA Thermistor discharge udara bermasalah

CC Sensor humidity bermasalah

CJ Sensor thermostat dalam RC bermasalah

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Tampilan kode kerusakan
Kode kerusakan Kerusakan yang terjadi
E0 Keamanan perangkat aktif

E1 PCB outdoor bermasalah

E3 High pressure switch aktif (HPS)

E4 Low pressure switch aktif (LPS)

E5 Kompresor inverter over heat


Unit Outdoor

E6 Kompresor STD macet atau over current

E7 Motor fan outdoor bermasalah

E8 Kompresor inverter over current

E9 Electronic expansion valve bermasalah

F3 Temp. pipa discharge tidak normal

F6 HPS tidak normala / kelebihan refrigerant

H3 High pressure switch bermasalah (HPS)

H4 low pressure switch bermasalah (LPS)

H7 Signal motor fan outdoor bermasalah

H8 Kompresor input (CT) bermasalah

H9 Thermistor udara (R1T) outdoor bermasalah

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Tampilan kode kerusakan
Kode kerusakan Kerusakan yang terjadi

J1 Pressure sensor bermasalah

J2 Current sensor kompressor bermasalah

J3 Thermistor pipa discharge (R31 ~ 33T) bermasalah

J5 Thermistor pipa suction (R2T) bermasalah


Unit Outdoor

J6 Thermistor heat exchanger (R4T) bermasalah

J7 Thermistor pipa liquid (R6T) refrigerant circuit

J8 Thermistor pipa liquid (R7T) refrigerant circuit

J9 Thermistor pipe gas (R5T) bermasalah

JA High pressure sensor bermasalah

JC Low pressure sensor bermasalah

JH Thermistor oli bermasalah

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Tampilan kode kerusakan
Kode kerusakan Kerusakan yang terjadi

L0 Sistem Inverter bermasalah

L1 PCB Inverter bermasalah

L4 Temperatur fin radiasi inverter bermasalah

L5 Arus inverter naik tiba-tiba (DC)

L6
Inverter

Arus inverter naik tiba-tiba (AC)

L8 Kompresor inverter kelebihan arus

L9 Startup kompresor inverter bermasalah

LA Power transistor bermasalah

LC Transmisi control & PCB inverter bermasalah

P1 Voltase tidak seimbang, (phase putus)

P4 Sensor temperatur fin bermasalah

PJ Capacity setting outdoor bermasalah

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Tampilan kode kerusakan
Kode kerusakan Kerusakan yang terjadi

U0 Kekurangan refrigerant

U1 Phase bermasalah atau phase terbuka

U2 Voltase kurang tiba-tiba

U3 Belum dilakukan dilakukan cek operasi

U4 Transmisi antara unit indoor & outdoor terganggu

U5 Transmisi antara RC & unit indoor terganggu


Sistem

U6 Transmisi anatara unit indoor terganggu

U7 Transmisi antara unit outdoor terganggu

U8 Transmisi antara remote kontrol terganggu

U9 Transmisi antara unit indoor & outdoor dalam sistem yang sama bermasalah

UA Jumlah unit indoor terlalu banyak

UC Seting alamat centralized salah

UE Transmisi antara indoor dan centralize bermasalah

MC Alamat indoor double

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Wiring diagram indoor unit inverter
FTKC25/35NVM, FTKC25/35NVM

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Wiring diagram outdoor unit inverter
RKC25/35NVM

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Wiring diagram indoor unit non inverter
FTM25/35JV14

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Wiring diagram outdoor unit non inverter
RM25/35JV14

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Wiring diagram indoor unit SkyAir Inverter
FCQ100LUV1 / FCQ125LUV1 / FCQ140LUV1

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Wiring diagram outdoor unit SkyAir inverter
RZR100LUY1 / RZR125LUY1 / RZR140LUY1

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Wiring diagram indoor unit SkyAir non Inverter
FCNQ13MV1(4) / FCNQ18MV1(4) / FCNQ21MV1(4) / FCNQ26MV1

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Wiring diagram outdoor unit SkyAir non Inverter
RNQ26MY1(4)

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Nilai tahanan thermistor terhadap temperatur

X12A (R2T)

Indoor PCB

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Nilai tahanan thermistor terhadap temperatur

Indoor Unit Thermistor Air Suction R1T


Thermistor Liquid pipe R2T
Thermistor Gas pipe R3T

Outdoor Unit Thermistor Outdoor air R1T


Thermistor Coil pipe R2T
Thermistor Discharge pipe R3T
Thermistor Suction pipe R4T
Thermistor Receiver gas pipe R5T

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Nilai tahanan thermistor terhadap temperatur
Indoor : R1T, R2T, & R3T. Outdoor : R1T, R2T, R4T, & R5T

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Nilai tahanan thermistor terhadap temperatur
Outdoor : R31T (Thermistor discharge)

© PT. DAIKIN AIRICONDITIONING INDONESIA. Daikin Training


WBT JP0036-1
Cara mengukur nilai tahanan thermistor
[Metode Inspeksi] (1) Mengukur resistansi (2) Temp. didapat  (3) Cek perbedaannya dengan temperatur lingkungan.

(1) Mengukur nilai resistansi (2) Cari temperatur berdasarkan pengukuran


nilai resistansi
Konektor Tabel termistor temperatur-resistansi (Satuan: kΩ)

Termistor udara outdoor Temp. A B C


-4 81.08 78.97 1002.5
Tester -2 73.01 71.14 898.6
0 65.84 64.17 806.5
Nilai resistansi
2 59.43 57.94 724.8
Lepaskan konektor thermistor dari PCB dan ukur + 4 53.71 52.38 652.2
resistansi dengan tester
-
6 48.61 47.42 587.6
8 44.05 42.98 530.1
(3) Membandingkan dengan termometer 10 39.96 39.01 478.8
12 46.02 35.45 432.9

Termistor udara outdoor Temp.


14 20˚C. 33.02 32.25 392.0
16 30.06 Nilai resistansi
29.37 yang terukur
355.325kΩ
18 27.41 26.78 322.4
Tidak masalah 20 25.01 24.45 292.9
jika terukur 22 22.85 22.35 266.3
20˚C. 24 20.9 20.45 242.5
Temp.
lingkungan 26 19.14 18.73 221.0
Termometer 28 17.54 17.17 201.6
A: Outdoor air, heat exchanger, pipa suction
Jika tidak sesuai, ganti termistor Catatan B: Fin panas radiasi