Professional Documents
Culture Documents
ELEPRA3 Assessment 2
ELEPRA3 Assessment 2
ELEPRA3 Assessment 2
Experiment 1
Simulated first in these experiments are the three operating states comprising no-load,
matching and short-circuit for the two-line lengths of 150 and 300 km. Two multimeterscan
be used to simultaneously measure all voltages and currents as well as active, reactive, and
apparent powers at both line ends. The feed transformer's voltage at the start of the line is to
be increased in steps to the specified value in each case.
In this process, make sure that the maximum permissible values of the voltage (400 Vbetween two
outer conductors’ phases) and current (2.5 A during short circuit) are not exceeded anywhere. Set
up the circuit as illustrated next.
No-load
Disconnect the resistive load to study operating response under no-load.
For both line lengths, set the voltage to the nominal value (380 V) at the beginning ofthe line.
The
outer conductors are designated L1 , L2 and L3 , the neutral conductor N. Measure the variables
indicated in the table (the powers always comprise three-phase values, i.e. total powerlevels):
Line length of 150 km:
Compare the measurement results with the calculated values (all calculations are carried
out for single phases on the basis of the associated phasor diagram).
To determine the voltage rise at the line's open end, it is best to use the voltage measured there
to calculate the voltage at the line's start. The calculations shown nextapply according to Figure
1.5.
Experiment 2: Matching [20]
Figure 1.12: Experiment circuit for measurements with purely resistive loads
To study the response during matching, the resistive load is decreased from its maximum
value until attainment of the power levels specified in the table below. In thecase of both line
lengths, the nominal voltage (380 V) is to be set at the start of the lineand maintained at this
value through readjustment wherever necessary. The variables indicated next are to be
measured.
For a line length of 150 km:
What can be said about the sign of the reactive power fed into the line?
The equation P = U2Δ ²/ R or R = U2Δ ²/ P is used to calculate the corresponding loadresistance which
also represents the characteristic impedance (U2Δ is the line-to-linevoltage across the load).
Evaluate the line resistances.
For a line length of 150 km: R = ZW = 493 Ohm
Finally, the measured values are used to determine the efficiency during matching forboth line
lengths:
Efficiency η150 = (P2 / P1) = 75%
Most important case in practice is a supply for mixed resistive-inductive loads. Investigated
beforehand, however, is the line response in the case of purely capacitiveand inductive loads.
All the tests are conducted again at the nominal voltage of 380 V. All experiments hereare
conducted with a line length of 150 km.
For measurements with capacitive loads, assemble the circuit as shown next.
Connect the capacitor in star configuration, and set the voltage at the start of the line toa
constant
value of 340 V; perform any readjustment necessary to avoid excess voltages at theend of the
line.
Enter the values of the specified parameters in the table below. The power levels againcomprise
total values.
Capacitance 2µF 4 µF 6 µF 8 µF
Voltage L1-L2(Line end) in V 405 408 418 430
Current L1 (at line end) in A 0.16 0.31 0.46 0.63
Reactive Power ( at line start) in VAR 34 71 112 156
Current L1 (at Line start) in A 0.31 0.45 0.61 0.78
Active Power (at line start) in W 0 1 1 2
Reactive Power (at line start) in VAR 63 97 134 172
Figure 1.14: Experiment circuit for measurements with purely inductive loads
L= 3.2 H 2.8 H 2.4 H 2.0 H
Voltage L1 - L2 (line end)in V 374 372 369 365
Current L1(at line end) in A 0.2 0.23 0.27 0.32
Reactive power (at line end) in var 43 49 57 67
Current L1 (at line start) in A 0.07 0.1 0.14 0.19
Active power (at line start) in W 6 7 8 9
Reactive power (at line start) in var 14 21 29 40
5.1 A two wire dc ring distributor is fed at point a with a voltage of 240 V. Loads
of 75 A, 160 A and 125 A are tapped from the distributor at points b, c and d
respectively. The resistance (including the lead and return) of section ab is 0.04
E=2.2∟9°kV
distribution system. Assume that the feeder between the substation abd a is
disconnected, and then use Thevenin’s theorem to calculate the voltage at each
load point.
Thevenin’s theorem states any linear circuit containing several voltages and resistances can be replaced by
one single voltage in series with a single resistance connected across the load. Circuit was simplified and all
calculations proved the theorem true and thus the experiment was deemed a success.