Professional Documents
Culture Documents
Volume 04 - Testing of LV Installation
Volume 04 - Testing of LV Installation
QUALITY POLICY
“We at RDSO, Lucknow are committed to maintain and update
transparent standards of services to develop safe, modern and cost
effective railway technology complying with statutory and
regulatory requirements, through excellence in research, designs
and standards by setting quality objectives, commitment to satisfy
applicable requirements and continual improvements of the quality
management system to cater to growing needs, demand and
expectations of passenger and freight traffic on the railways
through periodic review of quality management systems to achieve
continual improvement and customer appreciation. It is
communicated and applied within the organization and making it
available to all the relevant interested parties.”
ii
जितेंद्र ज िंह आई आर ए एम ई
Jitendra Singh IRSME
प्रधान कार्य कारी जनदे शक
Principal Executive Director
FOREWORD
Our motto of preparing these documents under the series “Safety in Electrical Low
Voltage Installations” is to reduce fire cases due to electrical faults and electrocution on
Indian Railways. These publications are based on Indian standards and codes in
simplified and practically implementable manner.
I am sure that this volume-4 along with earlier volumes will be useful for electrical design
and maintenance engineers and technicians for updating their knowledge, improving the
reliability and safety of electrical LV installations as well as precious human lives. This
will be also helpful in reducing the accidents on account of electrical failures.
iii
PREFACE
As per instructions of Railway Board, CAMTECH, Gwalior has done detail study on safety
in low voltage electrical installations by referring various Indian Standards on the subject
and with the help of experts in this domain.
On the basis of various Indian standards, CAMTECH, Gwalior has already prepared &
published three volumes under the series “Safety in Electrical Low Voltage Installations”.
These volumes give basic information about protective earthing, selection and application
of protective devices and various provisions/ requirements for selection of size of
conductors and inspection of LV installations before being put into service.
iv
ACKNOWLEDGEMENT
I would like to express my sincere gratitude to Shri Jitendra Singh, PED/CAMTECH for the continuous
support, guidance & motivation in making of this publication.
I would like to thank Shri Manish Gupta, ED/EEM/Railway Board for his continuous encouragement,
direction, support and guidance during in making of this publication.
My sincere thanks to Shri Vivek Dixit, CEGE/Central Railway for his continuous motivation, guidance,
suggestions, insightful comments, and hard questions which guided us to make this publication simpler
for users to understand.
My sincere thanks to Shri S. Gopa Kumar, Member in various Electro Technical committees of BIS for
his technical guidance and support throughout the process of making this publication. He has helped us
in understanding the Indian and international standards, various concepts of earthing, comments and
clearing our doubts which we faced during the making of this publications.
I thank my team members Shri Bal Chandra Agrawal, SSE, Shri Arvind Chaturvedi, SSE & Smt. Sangeeta
Shrivastava JE/IT for their continuous study, hard work, sincere efforts & dedication to make this
publication.
Himanshu Maheshwari
Dy. Director /Electrical
v
CONTENTS
1 INTRODUCTION..................................................................................................................... 1
1.1 Test Sequence ...................................................................................................................... 1
2 CONTINUITY OF CONDUCTORS (Continuity Resistance measurement) ................................... 2
2.1 Scope of test ......................................................................................................................... 2
2.2 Purpose of test ...................................................................................................................... 2
2.3 Equipment Requirement......................................................................................................... 2
2.4 Pre Test Check ...................................................................................................................... 2
2.5 Test Method .......................................................................................................................... 2
2.5.1 1st Test method ...................................................................................................................... 3
2.5.2 2nd Test method ................................................................................................................... 4
2.6 Result ................................................................................................................................... 4
2.7 Limitation .............................................................................................................................. 5
3 INSULATION RESISTANCE OF THE ELECTRICAL INSTALLATION............................................ 6
3.1 Scope of test ......................................................................................................................... 6
3.2 Purpose of test ...................................................................................................................... 6
3.3 Equipment Requirement......................................................................................................... 6
3.4 Pre-test checks ..................................................................................................................... 6
3.5 Test Method .......................................................................................................................... 7
3.6 Result ................................................................................................................................... 8
4 INSULATION RESISTANCE/ IMPEDANCE OFFLOOR AND WALL .............................................. 9
4.1 Scope of test ......................................................................................................................... 9
4.2 Purpose of test ...................................................................................................................... 9
4.3 Equipment Requirement......................................................................................................... 9
4.4 Pre-test checks ..................................................................................................................... 9
4.5 Test method with a.c. voltage .............................................................................................. 10
4.5.1 Type of test electrode .......................................................................................................... 11
5 AUTOMATIC DISCONNECTION OF SUPPLY .......................................................................... 13
5.1 Earth Fault Loop Impedance (Zs) testing .............................................................................. 13
5.1.1 Scope of test ....................................................................................................................... 13
5.1.2 Purpose of test .................................................................................................................... 13
5.1.3 Pre Test Check .................................................................................................................... 14
5.1.4 Method ............................................................................................................................... 14
vi
5.2 Measurement of the resistance of the earth electrode ........................................................... 15
5.2.1 Scope of test ....................................................................................................................... 15
5.2.2 Is measurement of resistance of the earth electrode required? .............................................. 15
5.2.3 Equipment Requirement ....................................................................................................... 16
5.2.4 Method ................................................................................................................................ 16
6 ADDITIONAL PROTECTION .................................................................................................. 23
6.1 Scope of test ....................................................................................................................... 23
6.2 Purpose of test .................................................................................................................... 23
6.2.1 Break (response)& non-actuating time of RCCB ................................................................... 23
6.3 Equipment Requirement ....................................................................................................... 24
6.4 Pre Test Check .................................................................................................................... 24
6.5 Test Method for General type (non delay type) RCCB ........................................................... 24
6.5.1 Through Tester .................................................................................................................... 24
6.5.2 RCCB’s Integral Test Device................................................................................................. 25
6.6 Result.................................................................................................................................. 25
7 POLARITY TEST .................................................................................................................. 26
7.1 Scope of test ....................................................................................................................... 26
7.2 Purpose of test .................................................................................................................... 26
7.3 Equipment Requirement ....................................................................................................... 26
7.4 Method ................................................................................................................................ 26
7.4.1 Low Resistance Ohmmeter in supply OFF condition.............................................................. 26
7.4.2 Live Test ............................................................................................................................. 26
8 PHASE SEQUENCE TEST ..................................................................................................... 27
8.1 Scope of test ....................................................................................................................... 27
8.2 Purpose of test .................................................................................................................... 27
8.3 Equipment Requirement ....................................................................................................... 27
8.4 Method ................................................................................................................................ 27
8.4.1 Through Rotating disc type .................................................................................................. 27
8.4.2 Static Type Phase Sequence Indicator .................................................................................. 27
9 FUNCTIONAL TESTS ............................................................................................................ 29
10 VOLTAGE DROP TESTS ....................................................................................................... 29
10.1 Scope of test ....................................................................................................................... 29
10.2 Purpose of test .................................................................................................................... 29
10.3 Method ................................................................................................................................ 29
vii
10.3.1 Evaluation of voltage drop using diagrams (As per Annex NN of IS 732: 2019) ..................... 29
ANNEXURE -1 FORMAT: REPORT OF VERIFICATION........................................................................ 31
LIST OF FIGURES
Figure 1: CPC Continuity ............................................................................................................... 3
Figure 2: Connections for testing of continuity of protective conductor (Method 1) ......................... 3
Figure 3: Connections for testing continuity of protective conductor (Method 2) ............................. 4
Figure 4: Insulation test between Line & Neutral ............................................................................ 7
Figure 5: Insulation test between Neutral & Earth ........................................................................... 8
Figure 6: Measurement of Impedance of floor and wall ................................................................ 10
Figure 7: Test Electrode (Type – 1) ............................................................................................. 11
Figure 8: Test Electrode (Type – 2) ............................................................................................. 12
Figure 9: Zs= Ze + R1+R2 ....................................................................................................... 13
Figure 10: Measurement of Fault loop Impedance using Fault Loop Impedance Tester.................... 14
Figure 11: Method of Measurement of Earth Electrode Resistance ................................................. 17
Figure 12: Effect of C location on the earth resistance curve .......................................................... 18
Figure 13: Fall of Potential 61.8 Percent Test ................................................................................. 19
Figure 14: Terminal Tester with CT Clamp ..................................................................................... 20
Figure 15: Fall of Potential - Slope Method .................................................................................... 21
Figure 16: Fall of Potential – 90°/ 180° Test................................................................................... 21
Figure 17: Earth tester................................................................................................................... 21
Figure 18: Earth System with multiple Earth Electrode.................................................................... 22
Figure 19: Rotatic Disc type Phase Sequence Indicator.................................................................. 27
Figure 20: Static phase sequence indicator ................................................................................... 27
Figure 21: Typical phase sequence testing arrangement, using the static indicator ......................... 28
Figure 22: Example of a diagram suitable for the evaluation of the voltage drop .............................. 30
viii
LIST OF TABLES
Table 1: Test Sequence................................................................................................................ 1
Table 2: Specific Conductor Resistance for Copper Wiring at 30°C ............................................... 4
Table 3: Minimum values of insulation resistance (Ref: table 15 of IS 732_2019) ......................... 6
Table 4: Test Sequence for Measurement of Earth Fault/short circuit Loop Impedance by Fault
Loop Impedance Tester ................................................................................................ 15
Table 5: 61.8 Percent Test Probe for Various Grid Sizes ............................................................. 19
Table 6: Example for combined loop resistance for multiple earth electrode................................. 22
Table 7: Limit values of break time and non-actuating time for alternating residual currents (r.m.s.
values) for type AC and A RCCB ................................................................................... 23
Table 8: Limit values of break time for half-wave pulsating residual currents (r.m.s. values) for type
A RCCB ........................................................................................................................ 24
Table 9: Voltage Drop (Ref: Table 47 of IS 732: 2019) ................................................................ 29
ix
ISSUE OF CORRECTION SLIP
The correction slips to be issued in future for this booklet will be numbered as follows:
CAMTECH/EL/2022-23/Vol.04-Testing/1.0/C.S. # XX date---
Where “XX” is the serial number of the concerned correction slip (starting from 01 onwards).
Sr.No. Date of Issue Page No. & Iten No. Modified Remarks
x
DISCLAIMER
It is clarified that the information given in this booklet does not supersede any existing
provisions of Indian Standards (IS) on the subject, related matters, and other existing
provisions laid down by the Railway Board, RDSO. This is not a statuary document and
instructions given are for the purpose of guidance only. If at any point contradiction is
observed, then Indian Standards, regulations issued by Government bodies, Railway
Board/RDSO guidelines shall be referred.
OBJECTIVE OF PUBLICATION
To prepare guidelines which can educate the Indian Railway (IR) engineers and
technicians dealing with low voltage electrical installations and other IR officials about
various provisions given in IS standards pertaining to IS 3043-2018, IS 732:2019.
xi
ABBREVIATION
Abbreviation Full Form
AC Alternating Current
CPC Circuit of Protective Conductors
DB Distribution Board
DC Direct Current
EE Earth Electrode
FELV Functional Extra Low Voltage
FOP Fall of Potential
IEC International Electro-technical Commission
IEEE Institute of Electrical and Electronics Engineers
IR Insulation Resistance
IS Indian Standard
MCB Miniature Circuit Breaker
MCCB Molded Current Circuit Breaker
xii
SAFETY IN ELECTRICAL LOW VOLTAGE INSTALLATIONS
1 INTRODUCTION
(Ref: - Para 6.2 of IS 732:2019)
Every new installation or changes (addition or alteration) in an existing installation shall be verified
during erection and on completion, before being put into service. Initial verification shall include
comparison of the results with relevant criteria to confirm that the requirements have been met.
For any addition or alteration to an existing installation, it shall be verified that the addition or
alteration complies with IS 732: 2019 and does not impair the safety of the existing installation.
Inspection shall precede testing and shall normally be done prior to energizing the installation and
Vol.3 “INSPECTION OF ELECTRICAL LV INSTALLATIONS” already published by this office, which
covers “Inspection” in details with check-sheet.
Measuring instruments, monitoring devices and methods shall be chosen in accordance with the
relevant parts of IEC 61557. If other measuring equipment is used, it shall provide no less degree
of performance and safety.
It shall be ensured that only skilled person, competent in verification, is carrying out verification.
Precautions shall be taken to ensure that the verification shall not cause danger to persons or
livestock and shall not cause damage to property and equipment even if the circuit is defective.
Annexur-1 give model forms of schedule that might be used for description and for initial and also
periodic, verification of installations, particularly suitable for domestic installations.
Electrical continuity resistance test shall be made on protective (earth) conductors, including main
and supplementary equipotential bonding conductors, before the supply is connected (or in supply
OFF/isolated condition).
2.2 Purpose of Test
To verify the continuity of all conductors (circuit protective conductors, line & neutral conductor,
earthing conductor including main and supplementary equipotential bonding conductors and to
obtain a measurement of the combined resistance of line and protective conductors at each point
on every circuit. This test verifies that the conductors are electrically sound and correctly
connected.
2.3 Equipment Requirement
The instrument used for this test shall be either a specialized meter called as micro ohm meter or
a measuring instrument capable of generating a no-load voltage of 4 to 24 V (DC or AC) with
short-circuit current not less than 200 mA.
2.6 Result
1. Each measured value should be compared with the relevant value for a particular conductor
length and size. Specific Conductor Resistance for Copper Wiring at 30°C is being given in below
table.
2. If the measured resistance is higher than required, this can be due to poor connection, and
shall be checked.
3. If the measured resistance is lower than required, this can be due to an unknown parallel path
and shall be checked.
2.7 Limitation
For this length of the conductors from the point of the origin of the circuit under measurement to
the point of testing is to be known for comparison.
This test is also known as ‘meggaring’. The measurements shall be carried out with the installation
isolated from the supply. Generally, the insulation measurement is carried out at the origin of the
installation. This measurement is carried out between all combinations of conductors i.e. line,
neutral and the protective conductors(earth).
1. The incoming supply (power) shall be switched OFF and the installation must be
disconnected.
2. Pilot or indicator lamps and capacitors are disconnected from circuits to prevent misleading
test values from being obtained.
4. Ensure all protective conductors are terminated correctly, including the armouring (steel wire
armoured cable ) and sheath of cables.
5. In TN-C-S system, the neutral conductor shall be disconnected from the protective conductor
for measurement purpose.
6. Ensure all circuit breakers are ON (closed) and/ or fuses are in place.
7. All light switches are ON; where two-way and/or intermediate switching is part of the
installation, the switches should be closed alternatively.
8. Where surge protective devices (SPDs) or other equipment are likely to influence the test, or
be damaged, such equipment shall be disconnected before carrying out the insulation
resistance test. Where it is not reasonably practicable to disconnect such equipment (for
example, in case of fixed socket Outlets incorporating an SPD), the test voltage for the
particular circuit may be reduced to 250 V d.c., but the insulation resistance should be
minimum 1 MΩ.
4. Test between Neutral & Earth. Record the values on the Schedule of Test Results.
5. Test between Line & Earth. Record the values on the Schedule of Test Results.
3.6 Result
If test value is less than the value given in table-3 above, then the following action should be taken:
A. The installation may be divided into several circuit groups and the IR of each group shall be
measured. If, for one group of circuits, the measured value is less than that specified in table 3
above, the IR of each circuit of this group shall be measured.
B. Open the individual circuit breakers one at a time when testing the Line to Neutral or Line to Earth
conductors. When each circuit breaker is opened the installation is re-tested.
C. When the IR value returns to an acceptable level, on the re-test, in this way, the faulty circuit
may be located.
D. Insulation resistance values are usually much higher than those mentioned in table 3 above.
When such values show evident differences, further investigation is needed to identify the
reasons.
The resistance is measured between the test electrode and the main protective (earth)
conductor of the installation.
During the execution of electrical work, operating conditions for the worker to be provided that
he is not exposed to the risk of exposure to potentials other than the potential of faulty equipment,
i.e. dangerous electric shock currents. Effective protection ensured by the reduction of floor and
wall conductivity.
Where fault protection is provided by a non-conducting location, the following should be verified:
1. Exposed-conductive-parts should be arranged so that under normal circumstances a
person will not come into simultaneous contact with:
I. Two exposed-conductive-parts or
II. An exposed-conductive-part and any extraneous-conductive-part
2. There must be not any protective conductors in non-conducting location.
3. Any socket-outlets installed in the non-conducting location must not incorporate an
earthing contact.
4. The resistance of insulating floors and walls to the main protective conductor of the
installation should be tested at not less than three points on each relevant surface, one of
which should be approximately 1 m from any extraneous-conductive part. e.g. pipes, in the
location.
At least three measurements shall be made in the same location, one of these measurements
being approximately 1mtr from any accessible extraneous- conductive-part in the location. The
other two measurements shall be made at greater distances. The measurement of
resistance/impedance of insulating floors and walls is carried out with the system voltage to
earth at nominal frequency.
Test to be made before the application of the surface treatment (varnishes, paints and similar
products).
Measurement of impedance or resistance of insulating floors and walls shall be carried out with
the system voltage to earth and nominal frequency, or with a lower voltage of the same nominal
frequency combined with a measurement of insulation resistance.
By measurement with lower a.c. voltages (minimum 25 V) and additionally by an IR tester using
a minimum test voltage 500 V (d.c.) for nominal system voltages not exceeding 500 V and a
minimum test voltage 1000 V (d.c.) for nominal system voltages above 500 V.
For safety reasons, when measuring voltages above 50 V, the maximum output current shall be
limited to 3.5 mA.
The measurement is to be carried out between the measurement electrode and the protective
(earth) conductor, which is only accessible outside of the tested nonconductive room.
Current is fed through an ammeter to the test- electrode from the output of the voltage source
or from the phase conductor.
The voltage UX at the electrode is measured by means of a voltmeter with internal resistance
of at least 1 MΩ towards PE.
The impedance of the floor insulation will then be:
𝑈𝑥
𝑍𝑥 =
𝐼
The measurement for ascertaining the impedance shall be carried out at as many points as
deemed necessary, selected at random, with a minimum of three.
The floors and walls are considered to be non-conducting where the measured resistances are
at least 50 kΩ (where the system voltage to earth does not exceed500 V).
If insulation has been applied to the extraneous-conductive-parts, within the location, during
construction its insulation resistance must be tested. A test voltage of 2 kV ac rms is applied,
with a flash insulation tester and any leakage current is measured, which should not be more
than 1 mA. This test is applied on completion of the standard 500 V insulation resistance test.
A TN System
Fault protection (indirect contact) in a TN system is provided by automatic disconnection of
supply and to ensure its effectiveness the following components need to be verified:
i The measured value of the earth fault loop impedance (Zs) to confirm it meets the
required standard.
ii Confirm by visual inspection whether the MCCB/MCB, which are provided, have suitable
short-time or instantaneous tripping setting i.e. type and rated current. Pl refer vol-
2“Selection and Application of LV Protective Devices” for more details.
iii Electrical testing of installed RCCBs to confirm, they meet required the disconnection
times.
B TT System
The effectiveness of automatic disconnection of supply in TT system is verified in a similar
manner as for a TN system, however the measured value of Zs is replaced with RA, which is
the combined resistance of the earth electrode and the protective conductor connecting it to
the exposed-conductive-parts of an installation.
Where
Zs= The fault loop impedance in ohms (Ω)
Ia = The current in amperes (A) causing the automatic operation of the
disconnecting device within the time as per table 1 given in para 1.1.1.2 in
vol-3.
Uo = The nominal a.c. or d.c. line to earth voltage in volts (V).
On the basis of above fault loop impedance is required to be measured and Uo which is
nominal voltage (known). Now Ia may be calculated and shall be compared with MCCB/MCB
characteristics to trip within specified time as per table-1 of IS 732:2019.
5.1.2.2 TT System
(Ref: Para 4.2.11.5.3 of IS 732: 2019)
Where a residual current protective device (RCCB) is used for fault protection, the following
conditions shall be fulfilled:
RA× IΔn ≤ 50 V
Where
RA = The sum of the resistance (in Ω) of the earth electrode and the protective conductor
for the exposed conductive-parts, and
IΔn= The rated residual operating current of the RCCB
5.1.4 Method
5.2.2.1 TT System
In TT systems, provision of RCCB is mandatory for earth fault protection. Where an RCCB is
used, the circuit should also be protected by an overcurrent protective device. Earth fault loop
impedance is generally high in TT system and fault current will not be sufficient to operate the
overcurrent protection device in case of earth faults and then RCCB will take care of earth
faults. RCCB is suitable for both earth fault & earth leakage.
Where an RCCB is used for fault protection, the following conditions shall be fulfilled:
Where
RA = the sum of the resistance (in Ω) of the earth electrode and the protective (earth)
conductor to the exposed conductive-parts, and Where RA is not known, it may be replaced by
Zs.
In the case of 30mA RCCB is provided, during earth faults, even if earth electrode resistance
is higher i.e. upto 1666 Ohm, RCCB will be trip in required time.
50 𝑉
𝑅𝐴 = = 1666 Ω
30 𝑚𝐴
If we are measuring the earth fault loop impedance, then measurement of earth
electrode resistance has no relevance other than record purpose.
5.2.2.2 TN system
Earth electrode resistance is not the primary path of earth fault loop in TN system and the
metallic return path act as a primary path offering lower resistance for flow of maximum current
during faults. Accordingly, measurement of earth electrode resistance is less relevance in TN
system and earth fault loop impedance decides the automatic disconnection of supply.
On the basis of above it may be concluded that after measuring fault loop impedance in above
systems (TT & TN) to check the effectiveness of protection system, Earth electrode resistance
measurement is of less relevance other than record keeping.
Earth electrode resistance tester is normally a battery operated 3 or 4 terminal instrument with
current and potential spikes.
i One coil type instrument: Used to test systems with just one earth electrode.
ii Two coil type instrument: Used to test systems with more than one electrode.
iii Test Instrument: Earth Electrode Tester, either a stake less type or a probe type.
5.2.4 Method
(Ref: Para 41of IS3043: 2018)
𝑉
𝑅=
𝐼
Where;
R = resistance of the test electrode in ohms,
V = reading of the voltmeter in Volts, and
I = reading of the ammeter in amperes
Minimum Distance for C: Consider below Figure, which shows the effect of earth shells overlap
between the test electrode and current electrode C on the value of resistance. In Figure 12-A,
current electrode C is so close to the test electrode that the both earth shells are overlapping. Then
potential electrode (B) is positioned at 61.8 percent of the distance between the test electrode and
the current probe (C). The value of resistance will be affected due to shells overlapping of test
electrode & current electrode at that point. The value of resistance will be increases continuously
due to shell overlapping of current electrode C.
In Figure 12-B, current electrode C is placed farther away from the test electrode. Then effect of
shells overlapping of test electrode & current electrode are nil at 61.8 percent of the distance
between the test electrode and the current electrode (C). The value of earth resistance is very
close to the actual earth resistance at that position. The value of resistance will be same near the
61.8 percent location.
For an Individual test electrode, which is in the form of rod, pipe or plate, the auxiliary current
electrode C shall be placed at least 30 m away from it and the auxiliary potential electrode B
midway between them.
• The 61.8 percent test is the recommended test procedure for small earth electrode systems
where the electrical center of the earth system is known, particularly ground mounted
distribution substations and pole mounted transformers.
• In this method the value of measured resistance will be equal to the true value when the
voltage probe (P) is positioned at 61.8 percent of the distance between the test electrode
(A)and the current probe (C).
A 50 m separation between the earth grid and the current probe (C) may be used and is usually
adequate for smaller earth systems. If the earth electrode system (Multiple electrode) is of
medium size containing rods, then these distances should be increased for correct
measurement of earthing system resistance as per the table given below.
Table 5: 61.8 Percent Test Probe for Various Grid Sizes (Table 17 of IS 3043:2018)
Test Procedure
• In 4 Terminal Earth Tester the Current Terminal (C1) and Potential Terminal (P1) together
with a short jumper on the earth tester and connect it to earthing Test electrode(A) under
test.
• Drive another Current Electrode (C) into the earth at suitable distance as explained above
and connect to C2 Terminal of earth tester.
• Drive another potential Electrode (P) into the earth at 61.8 percent of the distance between
the test electrode (A)and the current probe (C)and connect to Earth Tester on P2.
Take the Reading of Earth Resistance value. This is the actual resistance value of the Test
electrode(A). To confirm the accuracy of the first reading the potential probe should be moved
to the 50 percent and 70 percent positions and additional readings to be taken.
Look up the value of PPT/CP corresponding to the µ from table 5 of IEEE Std 81-2012.
Since CP (distance to the current probe) is already known, calculate a new PP T (distance
of the potential probe) as follows:
𝑷𝑷𝑻
𝑷𝑷𝑻 =
𝑪𝑷 × 𝑪𝑷
Now measure the earth resistance by placing the potential probe at this new distance PP T.
This measurement is known as the “true” resistance.
Repeat the whole process for a larger value of CP. If the “true” resistance decreases
appreciably as CP is increased, it is necessary to increase the distance of CP still further.
After making a number of tests and plotting the “true” resistance, the curve will begin to
show less of a decrease and will indicate more stable readings. It is at this point the
resistance of the earthing system is noted.
• This method effectively analysis a loop resistance measurement briefly explained below:
Suppose an earth system consist of multiple earth electrodes as shown in above figure. The
clamp-on ground tester is clamped around one of the earth electrodes and then it measures the
resistance of the entire loop.
The remaining earth electrodes are all connected in parallel and earth electrode being measured
is in series. If the clamp-on tester is clamped around R6, the measurement of the resistance of
the entire loop shown by clamp on tester will be as shown below:
Table 6:Example for combined loop resistance for multiple earth electrode
R6 R1 R2toR5 RLoop
10 Ω 10 Ω 10 Ω 12 Ω
10 Ω 100 Ω 10 Ω 12.44 Ω
100 Ω 10 Ω 10 Ω 102 Ω
Note: If we take 60 electrodes each having, resistance from R1 to R60 is 10 Ω. Where the
test electrode is on R60.Then the loop resistance measured with tester will be 10.17
Ω.
• From the above table it is clear that the measurement of the loop resistance is relatively close
to the resistance of the earth electrode being tested. The more electrodes or ground paths
in the system the nearer the measurement gets to the actual electrode under test’s true
resistance. The clamp-on earth tester can easily indicate a poor electrode whether there are
a few parallel paths in series with the measured value, or many parallel paths present.
• Based on above discussion it can be concluded that this method will give user an
approximate idea about earth resistance value of the particular electrode and the same can
be compared to the standard value of earth electrode resistance.
Limitation
• Clamp-on earth tester measurement is a measurement of the resistance of the entire loop.
There must be a loop resistance to measure i.e. there must be a series- parallel resistance
path.
6 ADDITIONAL PROTECTION
6.1 Scope of Test
RCCB detects any imbalance of current in three phase or single phase circuit. Any imbalance in
this context means that the sum of the circuit current does not equal to zero. This situation will be
interpreted by the RCCB as an earth leakage/fault, between either a neutral or a phase conductor
and earth. The leakage current causing the RCCB to trip is symbolized as:IΔn
Residual current devices can be categorized as:
Maximum values of break time for half-wave pulsating residual currents (r.m.s. values) for type A
RCCB are given in
Table 8: Limit values of break time for half-wave pulsating residual currents (r.m.s. values) for
type A RCCB (Ref: Table2 of IS 12640 (Part 1) : 2016)
Fault Current(mA) General Type
30mA 100mA 300mA Maximum break-time
1.4 In 42 140 420 300ms
2.8 In 84 280 840 150ms
3.5 In 105 -- -- 40ms
7 In -- 700 2100 40ms
An RCCB tester or a Multifunction tester can perform the tests for single phase and three phase
RCCBs by measuring the tripping time.
6.5 Test Method for General type (non delay type) RCCB
6.6 Result
i. If during testing of any RCCB, if it trips during the 50 per cent test. Consider the possibility
that there is a small earth leakage on the circuit or system. Switch all circuits OFF and test
RCCB on the load side at 50 per cent. If it still trips, the RCCB may be defective and should
be replaced.
ii. If it does not trip, turn each circuit ON one at a time, carrying out a 50 per cent test each
time a circuit has been turned ON. When the RCCB trips, switch OFF all circuits except the
last one which was switched ON. Test again. If the RCCB trips, carry out an insulation test
on this circuit as it probably has a low insulation resistance. If the RCCB does not trip it
could be an accumulation of earth leakage from several circuits and they should all be tested
for insulation resistance.
7 POLARITY TEST
7.4 Method
8.4 Method
If using the inductor, lamp 2 will be brighter than lamp 1 if the phase sequence is correct, while
lamp 1 becomes brighter than lamp 2 when the phases are reversed.
However, using the capacitor tester, lamp 1 will light on while lamp 2 will be off. If the sequence
is incorrect, lamp 2 lights up while lamp 1 remains off.
Connection diagram
Figure 21: Typical phase sequence testing arrangement, using the static indicator
The brighter lamp indicates the phase that follows B (the capacitor terminal of the indicator) that
means the phase sequence is BRY i.e. RYB.
9 FUNCTIONAL TESTS
Major assemblies in LV installation such as switchgear and control-gear, drives, controls and
interlocks, shall be subjected to a test of their function to verify that they are properly mounted,
adjusted and installed in accordance with the relevant requirements of IS 732: 2019 standard.
Protective devices shall be submitted to a test of their function, as necessary, to check that they
are properly installed and adjusted
10.3 Method
The voltage drop may be evaluated by the following method:
i. By using diagrams similar to the one shown as an example in Annexure NN of IS
732:2019.
ii. By measuring the circuit impedance.
10.3.1 Evaluation of voltage drop using diagrams (As per Annex NN of IS 732: 2019)
The voltage drops due to a change in the length of the PVC insulated cable can be evaluated
by using the below diagrams.
The figure below is only giving guidance regarding change in voltage drop due to
increasing/decreasing length of Three-phase PVC insulated copper wiring/cabling.
The current carrying capacity of wires/cables in the given diagram is an assumed value and
limited to a value considering voltage drop of 4%.
Calculation of voltage drop with example already given in Para 4.5.2 of vol-2“Selection and
Application of LV Protective Devices”
Figure 22: Example of a diagram suitable for the evaluation of the voltage drop
NOTES
1. By enquiry (manufacturer, name plate or technical doc.)
2. By measurement or calculation
3. Enter C if complies or NC if does not comply
4. Complete test where appropriate shall be performed including touch voltage and tripping time a trated current
5. Enter appropriate function code (see opposite)
6. Only to be completed if the distribution board is not connected directly to the origin of the installation
7. Only required where supplementary equipotential bonding has been installed in accordance with 413.1.3.6
8. Record connected load where readily identifiable
REFERENCES
4. IIEEE wiring regulation 17th edition Guidance Note 3: Inspection & Testing
NOTE
………………………………………………………………………………………………………………
………………………………………………………………………………………………………………
………………………………………………………………………………………………………………
………………………………………………………………………………………………………………
………………………………………………………………………………………………………………
………………………………………………………………………………………………………………
………………………………………………………………………………………………………………
………………………………………………………………………………………………………………
………………………………………………………………………………………………………………
………………………………………………………………………………………………………………
………………………………………………………………………………………………………………
………………………………………………………………………………………………………………
………………………………………………………………………………………………………………
………………………………………………………………………………………………………………
………………………………………………………………………………………………………………
………………………………………………………………………………………………………………
………………………………………………………………………………………………………………
………………………………………………………………………………………………………………
………………………………………………………………………………………………………………
………………………………………………………………………………………………………………
………………………………………………………………………………………………………………
………………………………………………………………………………………………………………
………………………………………………………………………………………………………………
34
SAFETY IN ELECTRICAL LOW VOLTAGE INSTALLATIONS
CONTACT US
CAMTECH is continuing its efforts in the documentation and up-gradation of information on maintenance practices
of electrical assets. Over the years a large number of publications on electrical assets have been prepared in the
form of handbooks, pockets books, pamphlets and video films, etc. These publications have been uploaded on
the internet as well as rail net.
1. On internet visit:www.rdso.indianrailways.gov.in
Go to Directorates CAMTECH Other important links Publications for download Electrical Engineering
INDIAN RAILWAYS
CENTRE FOR ADVANCED MAINTENANCE TECHNOLOGY
Maharajpura, Gwalior, M.P. 474 005
36