NOTES:
1. THIS DRAWING SHALL READ AND INTERPRET WITH
THE PROJECT DOCUMENTS AND SPECIFICATION
INCONJUNCTION.
OF
CONSENT
TTEN
WRI
THE
THOUT
WI NG
DRAWI
S
THI
SYMBOL DESCRIPTION
GENERAL NOTES :
FROM
SMOKE DETECTOR/SENSOR
1. FIRE ALARM CONTROL PANEL (FACP) SHALL BE UL LISTED MATERIALS.
NED
2. DETECTORS SHALL NOT BE LOCATED IN A DIRECT AIR FLOW NOT SMOKE DETECTOR WITH SOUNDER BASE
Sb
CLOSER THAN 3FT (900mm) FROM AIR SUPPLY DIFFUSER.
OBTAI
3. INSTALLATION OF FIRE ALARM AND DETECTION SYSTEM SHALL BE IN
SMOKE DETECTOR DUCT MOUNTED
ACCORDANCE TO THE NATIONAL FIRE PROTECTION ASSOCIATION NFPA 72
AND NATIONAL ELECTRICAL CODE (NFPA-70) FOR WIRING SYSTEM. ADDRESSABLE SMOKE/HEAT DETECTOR/
S H
BE
R SENSOR COMBINATION
FIRE ALARM SYSTEM WIRING SHALL BE OF CLASS 'A' OR PERFORM IN
4.
COMPLIANCE WITH NFPA 72 REQUIREMENTS FOR CLASS 'A' CIRCUITS HEAT DETECTOR, COMBINATION
H
PART,SHALL
R/F RATE OF RISE AND FIXED TEMPERATURE
WITH A MINIMUM WIRES OF SIZE 2 CORE #16 AWG SHIELDED TYPE "FPLP"
FOR INITIATING DEVICE CIRCUIT LOOP AND 2 CORE #14AWG CABLE TYPE
F MANUAL PULL STATION
"FDLP" FOR NOTIFICATION CIRCUIT UNLESS OTHERWISE NOTED
ON THE DRAWINGS WHERE SPECIFICATION SHOWN A VENDOR
RECOMMENDATION OF CABLE OR WIRES SIZE. LIM LINE ISOLATOR MODULE
REFERENCE DRAWINGS
LOCAL FIRE ALARM CONTROL PANEL
5. ALL TELECOMMUNICATION ROOM OR CLOSET SHALL HAVE PROVISION WITH
LFACP DRAWING CONTROL FOR J.O.10-08426-0003 TD-283594
, ADDRESSABLE TYPE
N
REMOTE LIGHT ALARM INDICATOR MOUNTED ABOVE THE DOOR ENTRANCE.
I
FDAS MISCELLANEOUS DETAILS TA-283610
6. FINAL LOCATION OF DUCT MOUNTED DETECTOR SHALL BE AS PER MAIN FIRE ALARM CONTROL PANEL
FULL,OR
MFACP
HVAC/MECHANICAL RECOMMENDATION AS SHOWN ON THE HVAC , ADDRESSABLE TYPE
DUCTING LAYOUT.
RI
REMOTE ALARM LIGHT, WALL MOUNTED
7. ALL DUCT SMOKE DETECTORS SHALL BE UL268A LISTED.
N
AUDIBLE & VISIBLE ALARM
I
DETECTORS SHALL BE OF UL521 LISTED.
ON
9. FIRE ALARM CONTROL PANEL, INITIATING DEVICES AND ASSOCIATED
VISIBLE ALARM
REPRODUCTI
ELECTRONIC COMPONENTS SHALL BE ALL AN ADDRESSABLE TYPE.
10.MANUAL PULL STATION SHALL BE MOUNTED AT 1220mm ABOVE FINISHED IM INTERFACE MODULE
FLOOR LEVEL TO THE CENTER OF THE BOX.
SAUDIARAMCO.NO
12.THE FIRE ALARM CONTROL PANEL SHALL BE PROVIDED WITH BATTERY
BACK UP POWER SUPPLY OF MAINTENANCE FREE AND AUTO RE-CHARGE
24 VDC
SYSTEM WITH A RATED CAPACITY TO OPERATE THE SYSTEM IN
QUIESCENT (NON-ALARM CONDITON) LOAD FOR 24 HOURS AND SHALL BE
ABLE TO ALARM NOTIFICATION DEVICES FOR 5 MINUTES AT THE END OF NAC NOTIFICATION APPLIANCE CIRCUIT
OF
14.WHERE ANY WIRING OF FIRE ALARM COMPONENTS AND DEVICES FOUND
TS TAMPER SWITCH
NOT SHOWN ON THE DRAWINGS A VENDOOR INSTRUCTION MANUAL AND
PROPERTY
RECOMMENDATION SHALL BE FOLLOWED FOR SITE AND CONSTRUCTION
ACTIVITIES OF INSTALLATION. WP WEATHER PROOF
15.LINE ISOLATOR MODULE SHALL BE INSTALLED AS PER FAS VENDOR FAS FIRE ALARM SYSTEM
RECOMMENDATION INSTRUCTION MANUAL.
AFF ABOVE FINISH FLOOR LEVEL
16.NOTIFICATION APPLICATION OF SELECTING HORNS SAHLL MEET THE REQUIREMENTS
SOLE
OF UL 464 (AUDIBLE SIGNALLING APPLIANCES) OF LOW FREQUENCY (520Hz) FOR FACP FIRE ALARM CONTROL PANEL
SMOKE SOUNDER BASE WITH SQUARE TONE WITH SOUND PRESSURE OF AT LEAST
75 dB AT THE PILLOW. JBI-O JUNCTION BOX FOR INITIATING
THE
CIRCUIT-OUTGOING
17.WHERE ANY CONDUIT IS NOT SPECIFICALLY MENTIONED ON THE LAYOUT
DRAWINGS, CONTRACTOR SHALL READ THE WIRING OR CABLING JBI-R JUNCTION BOX FOR INITIATING
ARE
CIRCUIT-RETURN
INSTALLATION AS FOLLOWS:
- PVC CONDUITS SHALL BE USED FOR DIRECT BURIED, BELOW GROUND JBN-O JUNCTION BOX FOR NOTIFICATION
N
CIRCUIT-OUTGOING
HEREI
OR EMBEDED IN CONCRETE WALL/FLOOR OR CEILING
- EMT CONDUIT SHALL BE USED FOR INDOOR INSTALLATIONS WITHIN THE BUILDING. JBN-R JUNCTION BOX FOR NOTIFICATION
CIRCUIT-RETURN
- RGS CONDUIT SHALL BE USED FOR OUTDOOR OR EXPOSED INSTALLATION
THAT ARE SUBJECT FOR ANY MECHANICAL DAMAGE.
NED
SCALE: NTS
18.SURGE PROTECTOR DEVICE SHALL BE PROVIDED FOR EACH CIRCUIT
CONTAI
EXITING/ENTERING THE BUILDING.
REVISION VALIDATION
19.SURGE PROTECTOR DEVICE SHALL BE LISTED/UL 1449 AND SHALL BE
THIS REVISION NO. 00 IS COVERED, FOR ALL APPROVAL AND CERTIFICATION
PROVIDED FOR POWER LIMITED CIRCUITS AS PER NFPA-70 ARTICLE 760.32 REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:
ON
10-08426-0003-001
NFORMATI
20.ALL FIRE PROTECTION, DETECTION AND ALARM SYSTEM DEVICES ARE IN DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
(DESIGN AGENCY) REQUIRED (SAUDI ARAMCO)
ACCORDANCE WITH RVL.
ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE
I
00 09/08/22 ISSUED FOR CONSTRUCTION
THE
JOB ORDER/EWO NO.
THIS REVISION IS NOT TO BE USED FOR
10-08426-0003 CONSTRUCTION UNTIL CERTIFIED AND DATED
AND
DRAWING TYPE
NG
RESIDENTIAL & SUPPORT FACILITIES
DRAWI
GOVT.BLDG.POLICE STA.&BARRACKS
S
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.
THI
098 B TA-283609 001 00
.FILE. .DATE .TIME .COMP .BY Saudi Aramco 2615 ENG. (05/05)