Load Schedule

You might also like

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 2

Ckt no P AT AF KAIC LOAD DESCRIPTION VA VOLT

1 2 15 50 10 21 LIGTHING OUTLET-1 2100 230


2 2 15 50 10 14 LIGTHING OUTLET-2 1400 230
3 2 15 50 10 17 LIGTHING OUTLET-3 1700 230
4 2 15 50 10 20 LIGTHING OUTLET-4 2000 230
5 2 20 50 10 9 CONVIENCE OUTLET -1 1620 230
6 2 20 50 10 13 CONVIENCE OUTLET -2 2340 230
7 2 30 50 10 1 REF 1000 230
8 2 30 50 10 1 RANGE 3000 230
9 2 30 50 10 1 WATER HEATER-1 3000 230
10 2 30 50 10 1 WATER HEATER-2 3000 230
11 2 30 50 10 1 WATER HEATER-3 3000 230
12 2 30 50 10 2 HP ACU-1 2760 230
13 2 30 50 10 1.5 HP ACU-2 2300 230
14 2 30 50 10 1 HP ACU-3 1840 230
15 2 20 50 10 SPARE 1500 230
16 2 20 50 10 SPARE 1500 230
Total Connected Load, IFL 34060
Demand Factor 85%
Total Demand Current
Size of Wire: Size of Circuit Breaker
IFL = 148.09+0.25*12= 151.09 Amps IFL =
at 85% demand factor = 128.42 Amps at 85% demand factor
Use: 2- 38sq.mm THHN Cu wire+ 1- 14 sqmm TW grnd in 40 mm RSC Use: 125AT/200AF, 2
A SIZE OF WIRE CONDUIT
9.13 2-2.0 sqmm THHN Cu 20mm Ø PVC
6.09 2-2.0 sqmm THHN Cu 20mm Ø PVC
7.39 2-2.0 sqmm THHN Cu 20mm Ø PVC
8.70 2-2.0 sqmm THHN Cu 20mm Ø PVC
7.04 2-3.5 sqmm THHN Cu 20mm Ø PVC
10.17 2-3.5 sqmm THHN Cu 20mm Ø PVC
4.35 3-5.5 sqmm THHN Cu 20mm Ø PVC
13.04 3-5.5 sqmm THHN Cu 20mm Ø PVC
13.04 3-5.5 sqmm THHN Cu 20mm Ø PVC
13.04 3-5.5 sqmm THHN Cu 20mm Ø PVC
13.04 3-5.5 sqmm THHN Cu 20mm Ø PVC
12.00 3-5.5 sqmm THHN Cu 20mm Ø PVC
10.00 3-5.5 sqmm THHN Cu 20mm Ø PVC
8.00 3-5.5 sqmm THHN Cu 20mm Ø PVC
6.52 STUB UP IN 20mm Ø PVC
6.52 STUB UP IN 20mm Ø PVC
148.09
0.85
125.87
Size of Circuit Breaker Protection:
148.09+1.5*12= 166.09 Amps
at 85% demand factor = 141.17 Amps
Use: 125AT/200AF, 2P, Bolt-On Type CB