K-Factor Transformers
K-Factor transformers are designed to reduce the heating
effects of harmonic currents created by loads like those
shown in Chart A. The K-Factor rating is an index of the trans-
former’s ability to withstand harmonic content while operating
within the temperature limits of its insulating system. SolaHD
K-Factor transformers have UL ratings of K-4, K-13, and
K-20.
Features
• Energy Efficient Compliant to DOE 2016 1
• Conductors to carry harmonics of a K-rated load
without exceeding insulation temperature ratings
• UL 1561 Listed up to K-20 rated protection
• Rated temperature rise of 150°C, 220°C insulation
• Shielded for quality power
Chart A: Typical Load K-Factors
• Basic design takes “stray losses” into account and
functions within safe operating temperatures Load K-Factor
• Core and coil design engineered to manage the zero Electric discharge lighting............................................................... K-4
sequence flux caused by triplen harmonics UPS with optional input filter........................................................... K-4
Welders.......................................................................................... K-4
• Provides 100% rated current without overheating the Induction heating equipment.......................................................... K-4
windings or saturating the core PLCs and solid state controls......................................................... K-4
Telecommunications equipment (e.g.. PBX).................................. K-13
UPS without input filtering............................................................. K-13
Accessories and Optional Design Styles Multiwire receptacle circuits in general care areas of
health care facilities and classrooms of schools, etc..................... K-13
• Wall mounting brackets (500 lbs maximum) (Item WB1C) Multi-wire receptacle circuits supplying inspection or
• Weather Shields (UL Listed/NEMA Type 3R) testing equipment on an assembly or production line................... K-13
Mainframe computer loads........................................................... K-20
• Totally enclosed non-ventilated designs (TENV) (Non UL) *
Solid state motor drives (variable speed drives)............................. K-20
• Low temperature rise units available
REPRINTED WITH PERMISSION FROM EDI MAGAZINE
• Open core and coil designs (UL Recognized)
• Copper Wound designs
• Alternate voltages
* Not all optional designs are UL Listed. Contact Technical Services.
1. DOE 2016 refers to Department of Energy CFR (Code of Federal Regulations) title 10, part 431.196).
Notes:
1. Weather shields (set of two) must be ordered separately.
2. Design Styles and Electrical Connections can be found at the end of the Ventilated Distribution Transformers section.
1 2
240 x 480 Volt Primary, 120/208/240/277 Volt Primary,
120/240 Volt Secondary 120/240 Volt Secondary
Taps: 2, 2½% FCAN; 4, 2½% FCBN Taps: None
H1 H2 H1 H2
7 5 3 1 2 4 6 8 5 3 1 2 4 6
SHIELD
SHIELD
X1 X3 X2 X4 X1 X3 X2 X4
Connect
Connect Primary Voltage Interconnect
Primary Voltage Interconnect Lines To
Lines To
277 1 to 2 H1 & H2
504 1 to 2 H1 & H2
240 3 to 4 H1 & H2
492 2 to 3 H1 & H2
208 5 to 6 H1 & H2
480 3 to 4 H1 & H2
H1 to 4
120 H1 & H2
468 4 to 5 H1 & H2 H2 to 3
456 5 to 6 H1 & H2 Secondary Connect
Interconnect
444 6 to 7 H1 & H2 Voltage Lines To
252 H1 to 2 H2 to 1 H1 & H2 X2 to X3
120-0-120 X1-X2-X4
X2 to
240 H1 to 4 H2 to 3 H1 & H2
X1 to X3
120 X1 & X4
228 H1 to 6 H2 to 5 H1 & H2 X2 to X4
216 H1 to 8 H2 to 7 H1 & H2 ES12 Series
Secondary Connect
Interconnect
Voltage Lines To
240 X2 to X3 X1 & X4
120-0-120 X2 to X3 X2 to X1-X2-X4
120 X1 to X3 X2 to X4 X1 & X4
ES5 Series
Design Style
W D
Style 1 - Ventilated
5 6
Taps: 2, 2½% FCAN; 4, 2½% FCBN Taps: 2, 2½% FCAN; 4, 2½% FCBN
H1 H2 H3 H1 H2 H3
SHIELD * SHIELD *
X0 X1 X2 X3 X6 X1 X2 X3
X2 H2 X2
H2
X1 X0
H1 H3 X1 X3
H1 H3 X3
X6
@ Tap Voltage X1, X2, X3 X0- X1, X2, X3 @ Tap Voltage X1, X2, X3 X6-X1, X6-X3
1 504 1 504
2 492 2 492
3 480 3 480
4 468 208 120 4 468 240 120
5 456 5 456
6 444 6 444
7 432 7 432
E2 and 3H Series E5 Series
* Shield available in electrostatically shielded units only. * Shield available in electrostatically shielded units only.
H2 X2 X2 X2
H2 H2
X1 X0 X1 X0 X1 X0
H1 H3 X3 H1 H3 X3 H1 H3 X3
Primary H1-H2-H3 Secondary Voltage Primary H1-H2-H3 Secondary Voltage Primary H1-H2-H3 Secondary Voltage
@ Tap Voltage X1, X2, X3 X0- X1, X2, X3 @ Tap Voltage X1, X2, X3 X0- X1, X2, X3 @ Tap Voltage X1, X2, X3 X0- X1, X2, X3
1 504 1 504 1 218
2 492 2 492 2 213
3 480 3 480 3 208
4 468 380 220 4 468 480 277 4 203 208 120
5 456 5 456 5 198
6 444 6 444 6 192
7 432 7 432 7 187
E79 Series E81 Series E3 Series
X1 X3 H3 H1 H3 X3 X1 X3 H3
Primary X1-X2-X3 Secondary Voltage Primary H1-H2-H3 Secondary Voltage Primary X1-X2-X3 Secondary Voltage
@ Tap Voltage H1-H2-H3 H0-H1, H2, H3 @ Tap Voltage X1, X2, X3 X0- X1, X2, X3 @ Tap Voltage H1, H2, H3 H0- H1, H2, H3
1 218 1 252 1 252