GROUP B: (Cables and Related Accessories)
Supply, installation, testing & commissioning of of
following sizes HT(11KV) armored XLPE cable through
air tight underground duct bank, all electrical contacts
shall be of brass copper connected through connector
or soldering (no twisting shall be allowed) and cables
shell be manufactured and tested according to
B1
relevant IEC/BDS/BS/VDE standards and as per
detailed specification mentioned in Annexure-A. The
work shell be carried out as per
direction/approval/acceptance of the Engineer. In
underground portion there must not be any cable
joint.
Cable manufacturer(s) must have valid type test
certificate (within last seven years) from
internationally accredited laboratory (like CPRI, KEMA
etc.) accepted / approved by the Engineer In Charge.
(a) 3C X 150 sqmm cable Mtr 850
Supply and fixing of loop cable of this following sizes:
Cable manufacturer(s) must have valid type test
B2 certificate (within last seven years) from
internationally accredited laboratory (like CPRI, KEMA
etc.) accepted / approved by the Engineer In Charge.
From transformer to LT switchgear
(without ECC & conduit )
1C - 4 x 630 sqmm ( NYY ) Mtr 120

1
Point of Completion
Country Qnty Completion as Schedule
Item Unit of Total
Description of the Item of Of units Unit Price per Schedule Offered as per
No Measurement Price
Origin Required of Schedule of
Requirement Requirement
1 2 3 4 5 6 7= (5*6) 8 9
Supply and fixing of loop cable of this following sizes:
Cable manufacturer(s) must have valid type test
certificate (within last seven years) from
internationally accredited laboratory (like CPRI, KEMA
etc.) accepted / approved by the Engineer In Charge.
From LT switchgear to PFI plant
(without neutral, ECC and conduit)
1C - 3 x 630 sqmm (NYY) Mtr 100
Supply, installation, testing & commissioning of the
following PVC insulated & sheathed cable (NYY) /
(XLPE) insulated & PVC sheathed cable (2XY) with PVC
insulated Green / Yellow bi-color ECC wire (BYA)
connecting at both ends, through PVC pipe &
accessories in the following manner. All electrical
contacts shall be of brass / copper connected through
B3
connector or soldering (no twisting shall be allowed)
and cables shall be manufactured and tested
according to IEC / BS / VDE standards along with
relevant BDS standard as per detailed specification
mentioned in Annexure-1. The work shall be carried
out as per direction & approval of the Engineer In
Charge.
In kutcha ground through uPVC pipe by cutting 45.70
cm width x 91.40 cm depth trench with necessary
brick or tile protection and mending the damages
good by refilling trench with proper compaction;
In pucca floor through uPVC pipe by cutting 45.70 cm
width x 91.40 cm depth trench of necessary size and