Professional Documents
Culture Documents
Relay Settings - DANHIM
Relay Settings - DANHIM
FOR INFORMATION
Date Representative
End Customer:
Table of Contents
1 GENERAL.............................................................................................................................. 3
1.1 Settings to be checked by the grid ................................................................................................... 3
1.2 Settings to be checked during commissioning ............................................................................... 3
2 TECHNICAL DATA .................................................................................................................. 4
3 GENERATOR PROTECTION RELAY (GPR) ............................................................................... 6
3.1 Generator Differential- 87G ................................................................................................................ 6
3.2 Voltage protection- 27/59 ................................................................................................................... 7
3.3 Generator Over / Under Frequency Protection - 81O/U .................................................................. 8
3.4 Negative Phase Sequence- 46 ........................................................................................................... 9
3.5 Stator Earth Fault 95%- 59N ............................................................................................................. 10
3.6 Stator Earth Fault 100%- 27GN ........................................................................................................ 10
3.7 Reverse Power- 32R .......................................................................................................................... 12
3.8 Generator Overcurrent protection- 50/51 ....................................................................................... 13
3.9 Breaker Failure- 50BF ....................................................................................................................... 14
3.10 Voltage Restrained Overcurrent- 51V ............................................................................................. 15
3.11 Over fluxing (24) ................................................................................................................................ 15
3.12 Inadvertent Energization (Dead Machine) 51/27: ........................................................................... 16
3.13 Field Failure 40: ................................................................................................................................. 17
3.14 Pole Slipping 78: ............................................................................................................................... 17
4 TRANSFORMER PROTECTION RELAY (TPR) .......................................................................... 18
4.1 Transformer Protection - 87T ........................................................................................................... 18
4.2 Transformer Restricted Earth fault protection- 64REF ................................................................. 19
4.3 Transformer Over Current- 50/51..................................................................................................... 20
4.4 Over fluxing- 24 ................................................................................................................................. 21
4.5 Circuit Breaker Failure- 50BF........................................................................................................... 22
5 LINE PROTECTION RELAY – ................................................................................................. 23
5.1 Directional/Non-Directional Overcurrent & Earth Fault Protection (3ph.) – 67/50 & 50/67N .. 23
5.2 Under voltage Protection- 27 ........................................................................................................... 24
5.3 Over Voltage Protection- 59 ............................................................................................................. 25
5.4 Breaker Failure- 50BF ....................................................................................................................... 25
1 GENERAL
This document provides information about the protective scheme for the generator, generator-
transformer, auxiliary transformer protection and line
Please note that documentation with detailed descriptions of the various protection systems are pro-
vided in separate relay document of relays.
Please note:
The calculated relay settings are based on different input data sheets available during the workout
from generator data sheet, transformer data sheet and single line diagram.
In case of any equipment modification or change of various electrical characteristics this document
has to be revised.
Generally the calculation of the settings is done according to our best knowledge and conscience. As
mentioned before the relay settings depend on various data given by several suppliers and by the cli-
ent as well. We can’t accept any responsibility in case of wrong given information.
Some protection settings (e.g. frequency, voltage) have to be checked and approved also from the
power grid. All settings mentioned in this document refer to the secondary values (relay values).
2 TECHNICAL DATA
Generator:
Gen-Transformer:
Current Transformer
Voltage transformer
Note:
1) Settings of some of the protection function may change if change in input data observed.
2) Settings of some of the function will be finalized during commissioning stage.
The function includes a saturation detection of the connected CT’s. Saturation phenomena can hap-
pen during high current through faults with short circuit currents which contain a high content of DC-
displacement current.
When the internal logic of the differential protection function detects a saturated current transformer,
the bias characteristic is changed to the saturated curve. The saturated curve can be set with different
bias slopes than the unsaturated curve. Therefore see the bias characteristic below. A specified high
set stage is also implemented. When the differential current overreaches the high set value the satu-
ration detection is not active any more. In this case it can be assumed that the fault is in the generator
winding.
Trip Matrix
Stage – 1 (52G_Unit Breaker) Trip, Excitation Trip, Turbine Trip (Machine
Shutdown), 86G
Stage – 1 (52G_Unit Breaker) Trip, Excitation Trip, Turbine Trip (Machine
Shutdown), 86G
The overvoltage function protects the generator, the main transformer against electrical field
stresses. The function is provided with 2 stages whereby stage 1 has a lower setting value and a larg-
er time delay to cater for voltage regulator response time in case of full load rejections and stage 2 is
provided with a higher voltage setting above load rejection conditions and minimum time delay.
Trip Matrix
Stage- 1&2 (52G_Unit Breaker) Trip, Excitation Trip, 86GZ
Note: Settings will be finalized at site during commissioning as per the Fluctuation in grid.
Trip Matrix
52G, 86GZ Non-Urgent Relay and Excitation
Trip Matrix
52G, 86GZ Non-Urgent Relay and Excitation
The stator earth fault function will protect the major part (95%) of the generator winding and all other
parts of the 6.3kV system (all parts galvanically connected to the generator) against earth faults.
The function measures the displacement voltage with the open delta winding at the generator lead
out.
The digital system only considers the nominal frequency. Any other harmonics will be repressed by fil-
tering.
The setting values of this function are below:
(11kV/1.732)x(220V/11kV)
=127.0 V
63.5 V
= 6.35 V
With a setting value of 𝑈 = 6.35𝑉, the protection range
of the generator winding will be 95%.
Operate time 1.0 s For a fast clearance of the earth fault a time delay of 1.0
delay s is set
Trip Matrix
52G, 86G-Urgent Relay and Excitation
Trip Matrix
52G, 86G-Urgent Relay and Excitation
Group – 1 Power:
Name Setting Value Address
Operating Mode Generating 31.20
Powe 1 Function Reverse 31.24
-P >1 Settings 6.82 31.28
Power1 Time Delay 4.00 S 31.34
Power1 DO Timer 0S 31.38
P1 Pole dead Inh. Enabled 31.3C
Power2 Function Disabled 31.40
S2> CT Source IA – 2, IB – 2, IC – 2, 31.61
S2>1 Status Disabled. 31.62
Start value current 3.36 A The secondary current to the relay at maximum load is
Stage - 2 0.84A
The overcurrent stage is set to 400% of rated genera-
tor current
𝐼 = 400% ∗ 𝐼 , = 4.0 ∗ 0.84𝐴 = 3.4𝐴
Trip Matrix
Stage – 1 (52G_Unit Breaker) Trip, Excitation Trip, Turbine Trip
(Machine Shutdown), 86G
Stage – 1 (52G_Unit Breaker) Trip, Excitation Trip, Turbine Trip
(Machine Shutdown), 86G
The GCB position criterion is evaluating the position signal of the CB. When the GCB-off signal is not
received, or the GCB-on signal will not disappear in the set time, the function is tripping also the high-
er level circuit breaker.
The function also includes also a monitoring function for the CBF-start signal. If the signal is to long
active an error message will be sent to the control system.
The input variables are the 3-phase current-transformer signal, Current L123, and the 3-phase volt-
age-transformer signal Voltage L123, where in both cases the amplitude of the fundamental wave,
H1, is selected for detection.
The function can be used for phase voltages and for phase-to phase voltages.
Trip Matrix
52G, 86G-Urgent Relay and Excitation
GROUP – 1 VOLTS/HZ
Name Setting Value Address
V/HZ Alarm Status Enable 3D.01
V/HZ>1 Status Enable 3D.10
V/HZ>1 Trip Function DT 3D.13
V/HZ>1 Trip Set 2.45 3D.16
V/HZ>1 Delay 3.00 S 3D.1A
V/HZ>2 Status Enable 3D.20
V/HZ>2 Trip Set 2.70 3D.25
V/HZ>2 Delay 1.00 S 3D.2A
V/HZ>3 Status Disable 3D.30
V/HZ>3 Status Disable 3D.40
TRIP MATRIX
52G, 86G-Urgent Relay and Excitation
TRIP MATRIX
52G, 86G-Urgent Relay and Excitation
TRIP MATRIX
52G, 86G-Urgent Relay and Excitation
Trip Matrix
Stage – 1 (52G_Unit Breaker) Trip, Excitation Trip, Turbine Trip (Machine Shutdown),
86G
The function includes a saturation detection of the connected CT’s. Saturation phenomena can hap-
pen during high current through faults with short circuit currents which contain a high content of DC-
displacement current.
When the internal logic of the differential protection function detects a saturated current transformer,
the bias characteristic is changed to the saturated curve. The saturated curve can be set with differ-
ent bias slopes than the unsaturated curve. Therefore see the bias characteristic below. A specified
high set stage is also implemented. When the differential current overreaches the high set value the
saturation detection is not active any more. In this case it can be assumed that the fault is in the
transformer winding.
Further is the transformer differential function equipped with a 2nd and 5th harmonic blocking. This
blocking is necessary during switching an unloaded transformer to the grid. During this switching an
inrush current appears and this current can cause the differential protection to trip inadvertent. The
inrush current has quite high magnitudes of 2nd and 5th harmonics. The differential function detects
this harmonics and can block the operation of the differential function.
𝐼 1053
𝐼 , = = = 0.88𝐴
𝐶𝑇 1200⁄1𝐴
The differential current setting is chosen to be 20% of the
rated relay current, i.e.
𝐼 = 20%𝐼 = 0.20 ∗ 0.88𝐴 = 0.18𝐴
This setting value correspond to a generator differential
current of
𝐼 0.18
∗ 100% = ∗ 100% = 0.20%
𝐼 , 0.88
TRI MATRIX 52T2 & 52T1, 86T-Urgent Relay
Where V and VN are the actual voltage and rated voltage and F and FN the actual frequency and rat-
ed frequency respectively.
The GCB position criterion is evaluating the position signal of the CB. When the GCB-off signal is not
received, or the GCB-on signal will not disappear in the set time, the function is tripping also the high-
er level circuit breaker.
The function also includes also a monitoring function for the CBF-start signal. If the signal is to long
active an error message will be sent to the control system.
The relay setting for stage-1 is 110% of lines relay secondary current.
1.10x0.76= 0.825 A≈0.83A
For stage 2, the setting is chosen to be 120% of the line secondary current.
1.20x 0.76= 0.912 A ≈0.93A
The relay setting for stage-1 is 20% of lines relay secondary current.
0.20x 0.76= 0.16 A
For stage 2, the setting is chosen to be 50% of the line secondary current.
0.40x 0.76= 0.30 A
V27-2 = 82%VNominal
Setting:
Parameter Setting Value
Operate Value (U1<) 96.8 V
Time Delay (TU1<) 2.0 sec
Operate Value (U1<<) 90.0 V
Time Delay (TU1<<) 1.0 sec
Trip Matrix
Alarm & Trip
Setting:
Parameter Setting Value
Operate Value (U1>) 123.2 V
Time Delay (TU1>) 1 Sec
Operate Value (U1>>) 126.5 V
Time Delay (TU1>>) 0.5 Sec
U1 > (>) Reset 0.98
Trip Matrix
52L & 86L
Setting:
Setting Value
FCT breaker fail ON
I>BF 0.1
Ip- RETRIP YES
T1-1pole 0.00sec
T1-3pole 0.00sec
T2 0.15sec
T3-BkrDefective 0.00sec
Trip BkrDefect No
Chk BRK CONTACT Yes
End Flt. Stage OFF
T-Endfault 2.00 sec
PoleDiscrepancy OFF
T-PoleDiscrep. 2.00 sec
Trip Matrix
Tripping To surrounding breakers