S S DS-300 (H) - 300kilowatt (KW) DoubleStackHighPressure316LStainlessSteelElectricSteamGenerator
S S DS-300 (H) - 300kilowatt (KW) DoubleStackHighPressure316LStainlessSteelElectricSteamGenerator
S S DS-300 (H) - 300kilowatt (KW) DoubleStackHighPressure316LStainlessSteelElectricSteamGenerator
Item # S.S. DS-300 (H), 300 Kilowatt (kW) Double Stack High
Pressure 316L Stainless Steel Electric Steam Generator
Standard Features:
Built by an ASME Certificate holder in accordance with ASME BPVC Section
I - Rules for Construction of Power Boilers ("ASME BPVC Section I"). They also
comply with the requirements outlined in The National Board Synopsis of
Boiler and Pressure Vessel Laws, Rules and Regulations (NB-370) RULES FOR
CONSTRUCTION AND STAMPING section, which for many jurisdictions
include but are not limited to ASME BPVC Section I, ASME CSD-1, ASME B31.1,
and REGISTRATION WITH THE NATIONAL BOARD.
more
Specifications | Amperage | Dimensions | Minimum Clearance | Plumbing Connection Sizes | Included Options |
Options
Specifications
Brands Electro-Steam™
10/13/2023 | Page 2 of 6
208 V
230 V
Alternating Current (AC) 360 V
Voltage1 400 V
480 V
600 V
Phase 3
50 Hz
Frequency
60 Hz
1,035 lb/hr
Steam Capacity2
468.0 kg/hr
124.0 gal/hr
Average Water Consumption3
468.0 L/hr
Amperage
Dimensions
Length 64 in
Width 38 in
Height 63 in
Minimum Clearance
10/13/2023 | Page 4 of 6
Total Width 60 in
Total Height 70 in
Steam Outlet (Shared) 6" Flange (150 psi, 4-Hole) - 2-1/2" pipe connection
1-1/4" NPT (Male) (x2) - Two Black Pipes routed to the floor;
Safety Valves (x2)(Separate)
one from each Safety Valve.
Included Options
Options
1 Electro-Steam™ Double Stack electric steam generators are two (2) electric steam boilers stacked inside
one (1) cabinet. They are plumbed together, but not wired together. Double Stack steam generators require
two (2) or four (4) customer specific high voltage feeds, one (1) per Electrical Box - 150 kW models have two
(2) Electrical Boxes to feed and 200 to 480 kW models have four (4).
2 Calculated values are based off of a 212ºF boiler feed-water temperature. However, it must not exceed
140ºF. Temperatures that range between 60ºF and 140ºF, are approximately 80% to 90% of the calculated
values shown.
3 Calculated values are based off of a 212ºF boiler feed-water temperature. However, it must not exceed
140ºF. Temperatures that range between 60ºF and 140ºF, are approximately 80% to 90% of the calculated
values shown.
4 Calculated values are based off of a 212ºF boiler feed-water temperature. However, it must not exceed
140ºF. Temperatures that range between 60ºF and 140ºF, are approximately 80% to 90% of the calculated
values shown.
5 Wetted Surfaces.
6 Wetted Surfaces.
7 Two (2) Single Service Transformer options are included with each double stack electric steam generator.
These options provide 120 VAC 1Ø, 50/60 Hz for each boiler's controls.
8 A Manual Low Water Reset Button is supplied standard with every steam generator, but it is disabled. If this
Reset Button is required as per your local boiler codes, simply plug the two attached wires into the PC-Board
terminals labeled "Reset"
10/13/2023 | Page 6 of 6