Professional Documents
Culture Documents
Pres MSA 2
Pres MSA 2
© MSA 2021
Agenda
• Installation Pre-work
• Summary
© MSA 2021
Installation Pre-Work
• Complete Hazard Operability (HAZOP) Study
Identify flammable & toxic risks & release scenarios
• Define High Risk Flammable/Toxic Zones
Optimal detection technologies for each hazard
• Complete FGFD Coverage Mapping study
Define coverage and install locations
• Define Hazardous Area(s) Classification
• Define Environmental and Site Challenges
• Define Instrument Installation Requirements
© MSA 2021
Hazard Area Classification
© MSA 2021
Classes & Divisions
© MSA 2021
Combustible Gas Groups
© MSA 2021
Code Compliance Requirements
© MSA 2021
Environmental Challenges
• Arctic cold
Operating temperature rating requirements specified
• Tropical humidity and monsoon rainfall
Ingress Protection (IP) rating requirements specified
• Presence of corrosive vapors, liquids and gases
Material of construction requirements specified
• Poor earth ground connectivity
Offshore platforms
Arctic settings – permafrost
Corrosive soils with high moisture or salt content, high temperatures
© MSA 2021
Jobsite Challenges
© MSA 2021
Installation Best Practices
• Electrical
Grounding
Power Supplies
Cabling – New & Existing
• Mechanical
Site Inspection/Walk-thru
Conduit, Seals, Breathers & Drains
Instrument Installation
• Final Inspection & Documentation
© MSA 2021
Grounding
© MSA 2021
Power Supplies
• Always ensure supply is properly sized for your system power load
Must support full power load from completely cold start
Newer detectors use 32-bit microprocessors, heaters etc.
• Proper battery back-up sizing calculations are required for deluge
FM-approved automatic extinguishing release systems require battery
backup to support 24 hours in normal mode and 5 minutes in full alarm
© MSA 2021
Cabling Requirements
© MSA 2021
14
Electrical Installation Summary
© MSA 2021
15
Onsite Installation Walk-Through
© MSA 2021
Conduit Seals
• NEC 501.15 requires that seal fittings filled with approved compound
be installed in conduits entering explosion proof enclosures
Exception: Approved instruments with specific labeling stating
“conduit seal not required”
© MSA 2021
Conduit Seals
FGFD Instrument Conduit Seal Requirements Per NFPA 70 - National Electric Code Article 501
Instrument
Hazardous Instrument "Conduit Seal"
Hazardous Location "Conduit Seal" Requirement
(Classified) Location Marking
Marking
Class I, Division 1 Class I, Division 1
within 18" of entry point*
No conduit seal marking present
Class I, Division 2 Class I, Division 1
on instrument
Class I, Division 2 Class I, Division 2 Conduit seal not required
© MSA 2021
Conduit Breathers & Drains
© MSA 2021
Flame Detection Installation Recommendations
© MSA 2021
21
Adjustable Field of View (FoV)
| 22
© MSA 2021
Basic Flame Coverage Techniques
© MSA 2021
23
Hangar Example – Top View
© MSA 2021
Hangar Example – Side View
No under-fuselage
protection
© MSA 2021
Hangar Example – Side View
© MSA 2021
Point Gas Detector Sensor Placement
• Always identify all hazardous gases to be detected and other gases possibly present
• Ensure sensor elevation and placement is appropriate for gas(es) to be detected
• Generally recommended gas sensor placement areas include:
Close to most likely gas leak origin locations, e.g. leak source point
Between leak origin point and known ignition sources
Between leak origin point and populated areas including workers’ breathing zone
Gas leak accumulation areas or confirmed gas leak dispersion paths (close to air outlets, exhausts)
• Generally recommended gas transmitter placement areas include:
Outside of the hazardous area using remote sensor separation kit
Areas of easy access and visibility
• Identify special requirements and challenges
Pipe mount, duct mount kits, remote calibration tubing
High temperature or vibration areas to avoid
Be aware of dilution effects from entrances or fresh air vents
Recommend to use remote sensor separation kits for difficult access locations and ease of calibration
© MSA 2021
Point Gas Detection Installation Requirements
• Ensure solid mounting structure is used for all
detection instruments Remote J-Box & XIR+ 1 Remote J-Box & XIR+ 2
Point Infrared Gas Detectors - Electrochemical Toxic Catalytic Bead Combustible Gas
Horizontal Detectors - Vertical Detectors - Vertical
© MSA 2021
29
Fixed Gas Detector Mounting – Special Applications
© MSA 2021
30
Final Inspections
© MSA 2021
Summary
© MSA 2021