Insulgard (230 VAC) in Enclosure
Insulgard (230 VAC) in Enclosure
Signal
Ch1 4-20 mA interface
+
4-20
Alarm 2 RS - 485 mA
Connector for Flat Cable from
-
Shield
Host
USB
Sensor Interface Board
Ch 2
G B A +5
Flat Cable to
Ch 3 RS485 interface
InsulGard
Ch 4
Alarm
Device
Ch 6
USB
Ch 7
Alarm 1
Warning
Ch 8
Warning relay
Ethernet
Auxiliary sensor Ch 9
Left Right
connection: Ch 10 side side
Status
white 1
Ch 11
black 2 Status relay
3
RTD
red 4
Ch 12
black 5 S
Ch 13
InsulGard's
6 CT
white 7 S1 connectors DIN-Rail Terminals
Ch 14
Ref red
Power
8 S2
GN L
9
Ch 15 white
white 10 green
red 11 +5 H% Ch 16
12 S (Noise) Screw on
black
H% Sw Ref back cover 1 2 3
Gnd
Gnd
Fuse
Humidity sensor
green
Ground Screw
CT - Load sensor
Green
on the panel
Neutral
Ground
Temperature sensor
Phase
Ground screw on enclosure
must be connected to local
ground Power 230VAC
Fuse inside InsulGard:Time-Lag 100mA, 250VAC, 5X20mm type 5ST by BEL Fuse Inc., Catalog # 5ST 100.
Fuse on the panel: Fast Acting 3.0A, 250VAC, 5x20mm type 5MF by Bel Fuse Inc. Catalog # 5MF 3-R (or equivalent).
NOTES:
1) To connect PD sensors to Sensor Interface Board it is necessary to take off InsulGard from the panel. To do
this disconnect flat cable from Sensor Interface Board, disconnect green plug connected to Power input,
disconnect green wire connected to din-rail terminal block # 1. Then disconnect 4 screws and take off
InsulGard. After all connections are done (see next page) install InsulGard in reverse order.
2) Relay "Status" changes its status when InsulGard has AC power and works properly. It returns in the status
shown on the label if InsulGard lost AC power or works not properly (has Error). Relay "Alarm 1" is used for
"Warning" and relay "Alarm 2" for "Alarm". They change their status if partial discharge level exceeds
predefined thresholds.
3) RS485 network (if used) should be connected to inputs A (+) and B (-). Don't use terminals G (insulated
ground) and +5 (insulated +5V).
4) USB port "Device" is used for communication with PC. Port "Host" is not used now.
5) Switch "Sw" must be in position H% to monitor humidity.
6) Please pay special attention for PD sensor connection to Sensor Interface board. InsulGard comes
preconfigured for certain sequence of the PD sensor connection to channels ##1-15. PD sensors must be
connected accordingly. For motor/generator application connect IPDS sensors on phases A, B and C starting
with channel 1 and then connect RTD PD sensors. For switchgear application this sequence is shown in the
Questionnaire you provided to us. Also it can be verified in InsulGard software → "Unit Settings" → "Settings
for Channel" section.
7) www.PartialDischarge.com is changed to www.eaton.com/pd
Connections to InsulGard
Load sensor
Humidity
sensor
Cables from auxiliary sensors Coaxial cables from PD sensors Connections to relays and to
connection connection interfaces
Coaxial cables preparation:
For connection to the relays and interfaces use green plugs on right side of InsulGard:
Plug for 4-20mA Plug for Relays Plug for RS485
NO contact
- B (-)
Common
+
NC contact
A(+)
Stripped length of the wire insulation for all green connectors should be about 6mm (0.24”)
and about 9mm (0.35”) for din-rail terminal blocks.