Customer: Done By:


General Info

Project: Location:

Ref/Tag: Quantity: 1

Revision: Rev 0 Date:

Required Capacity Required Entering Required Outside Required Air


Temperatures Conditions Conditions
External
Total Sensible Dry Bulb Wet Bulb Ambient Altitude Air Flow Static Pressure

kW kW °C °C °C ft LPS Pa
Input Conditions

90.7 53.3 33.8 23.8 46.00 0.00 2051 462

Required Power Supply Auxiliary Required Options

Voltage Phases Frequency Pre Filter Final Filter Blower Type Heater

Volts Phase Hertz 2'' 15'' kW


400V (4 Wire) 3 60Hz Aluminum Bag Filter Backward Fan N/A

Selected Unit Model


A

Performance @ 46 °C Ambient Physical Data


Total Cooling Capacity 102.15kW
Fan Data Condenser Evaporator Units
Total Sensible Capacity 60.73 kW
Total Power Input 43.3 kW Size 800 400
Quantity 2 1
Air Flow 11,666.5 2,051 LPS
Psychrometric Data Fan Speed 1100 2,201 RPM
Entering (On Coil) Leaving (Off Coil) Coil Data Condenser Evaporator Units

33.8°C 12.2 °C Coil Face Area 51.5 16.0 sqft


Dry Bulb Dry Bulb
Output Performance

23.8 °C 11.5°C Coil Tube Diameter 3/8 3/8 in


Wet Bulb Wet Bulb
Number of Rows 3 8
Fins Per Inch 12 12 FPI
Compressor Data Fins Material Cu Cu

Type Hermetic Scroll


Quantity 2 Electric Heater Filter Data
Capacity N/A 33x20 Inch
Electrical Data FLA Amps 2 Each
Condenser Evaporator Units

380/400-3-60Hz 380/400-3-60Hz
Refrigerant
Power Supply (4 wire) (4 wire)
Refrigerant R410A
Compressor RLA (Each) 37.9/37.9 Amps
Charge Per System 552/513 Oz
Compressor LRA (Each) 196/196 Amps
Fan Motor (Each) 2.7HP 7.5 HP*
Fan Motor Speed 1100 3,450 RPM General Data
Fan Motor FLA* (Each) 3.9 11.9 Amps
Unit MCA 105.0 Amps Drain Connection 3/4''
Unit MOCP 125.0 Amps External Static Pressure Pa 462
FLA tolerance ± 5%