WATER SUPPLY NOTES: SUBMITTALS:

1. THE SCOPE OF WORK SHALL INCLUDE DETAILED DESIGN,


16. ALL EXTERIOR COLD WATER PIPING SHALL BE INSULATED 1. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR MEP
SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF
WATER SUPPLY SYSTEM AS PER LATEST BAHRAIN EWA WATER WITH 25MM THICK RUBBER INSULATION AND COVERED WITH CONSULTANT APPROVAL.
REGULATIONS AND INTERNATIONAL PLUMBING CODE OR BS ALUMINUM JACKETING.
2. CONTRACTOR SHALL SUBMIT SERVICES COORDINATED DRAWINGS
STANDARDS. IT SHALL INCLUDES BUT NOT LIMITED TO THE
17. UNDERGROUND METAL PIPES,FITTINGS OR VALVES SHALL BE FOR APPROVAL.
FOLLOWING: TAPPING FROM MUNICIPALITY LINE, WATER
METERS, WATER STORAGE TANKS, WATER HEATERS, WATER COATED WITH PROPERLY APPLIED PROTECTION COATING AND
3. CONTRACTOR SHALL SUBMIT COMPLETE LIST OF MATERIAL OF ALL
TRANSFER PUMPS, WATER BOOSTER PUMPS, DISTRIBUTION WRAPPED WITH DENSO TAPE.
ITEMS PROPOSED TO BE USED AND INSTALLED IN THE SCOPE OF
PIPES, FITTINGS, VALVES, INSULATIONS, HANGERS AND
18. ISOLATION VALVES SHALL BE PROVIDED AT THE ENTRANCE OF WORK.
SUPPORTS, EXCAVATION AND BACKFILLING OF RELATED
WORKS, SUPPLY OF MATERIALS/EQUIPMENTS, INSTALLATION, PIPE TO THE TOILETS, PANTRIES OR KITCHENS BEFORE
4. CONTRACTOR SHALL SUBMIT MATERIAL SUBMITTALS FOR THE
TESTING AND COMMISSIONING. INTERNAL PIPES DISTRIBUTION.
FOLLOWING:
19. ISOLATION VALVES SHALL BE PROVIDED ON THE SUPPLY PIPE --- PIPES.
2. THESE DRAWINGS SHOWS THE GENERAL ROUTE OF WATER
TO EACH FIXTURE AND EQUIPMENT. --- PIPE INSULATIONS.
SUPPLY PIPING AND LOCATION OF EQUIPMENT. CONTRACTOR
--- FITTINGS.
SHALL PREPARE DETAILED SHOP DRAWINGS AND
20. PRESSURE REDUCING VALVES SHALL BE PROVIDED FOR EACH --- VALVES.
COORDINATED DRAWINGS. CONTRACTOR SHALL BE
FLOORS HAVING INCOMING WATER PRESSURE EXCEEDING --- WATER HAMMER ARRESTORS.
RESPONSIBLE FOR THE ADDITIONAL FITTINGS, OFFSETS, ETC.
60PSI. --- HANGERS AND SUPPORTS.
NECESSARY TO COMPLETE THE COORDINATED WATER
--- WATER METERS.
SUPPLY WORKS.
21. ALL VALVES SHALL MATCH PIPE SIZE UNLESS OTHERWISE --- WATER HEATERS.
NOTED. --- WATER TANKS.
3. CONTRACTOR SHALL REVIEW THE DESIGN AND MAKE SHOP
--- WATER LEVEL ALARM.
DRAWINGS. CONTRACTOR TO OBTAIN MEP CONSULTANT
22. WATER HAMMER ARRESTOR SHALL BE PROVIDED TO EACH --- PUMPS (ALONG WITH SUPPLIER SELECTION)
APPROVAL AND MAIN CONSULTANT ON SHOP DRAWINGS
TOILET/BATH. --- ADHESIVES AND SEALANTS.
PRIOR TO INSTALLATION OF WATER SUPPLY WORKS AT SITE.
--- FIRE STOP MATERIALS.
23. PIPES, VALVES AND OTHER EQUIPMENTS SHALL BE --- PRIMERS AND PAINTS.
4. CONTRACTOR SHALL CROSS CHECK THE EQUIPMENTS
LABELED/MARKED INDICATING THE AREA SERVED AND FLOW --- LABELING/MARKING MATERIALS.
CAPACITIES OF WATER SUPPLY SYSTEM PRIOR TO
DIRECTION ARROW SHALL BE MARKED. --- TAGGING MATERIAL.
ORDERING/PURCHASING. CONTRACTOR SHALL SUBMIT
MATERIAL SUBMITTAL FOR ALL EQUIPMENTS FOR MEP
5. CONTRACTOR SHALL SUBMIT AS-BUILT DRAWINGS FOR APPROVAL
CONSULTANT APPROVAL BEFORE ORDERING/PURCHASING.
24. ALL WATER FIXTURES SHALL BE AS PER ARCHITECT / MAIN UPON COMPLETION OF THE WORK.
5. CONTRACTOR SHALL COORDINATE WATER SUPPLY SYSTEM CONSULTANT SPECIFICATION. WATER FIXTURES MATERIAL
SUBMITTAL SHALL BE SUBMITTED FOR ARCHITECT APPROVAL. 6. CONTRACTOR SHALL SUBMIT OPERATION AND MAINTENANCE
WITH ALL OTHER TRADES PRIOR TO FABRICATION AND
MANUAL FOR APPROVAL UPON COMPLETION OF THE WORK.
INSTALLATION OF WATER SUPPLY WORKS TO AVOID
CONFLICTS. CONTRACTOR TO SUBMIT COORDINATED
DRAWINGS TO CONSULTANT FOR APPROVAL.

6. INSTALLATION OF ALL WATER SUPPLY WORKS SHALL BE AS


PER MANUFACTURER RECOMMENDATIONS AND RELATED
CODES.

7. WATER SUPPLY SYSTEM SHALL BE INSPECTED, TESTED AND


APPROVED PRIOR TO CONCEALING OR COVERING.

8. ABOVEGROUND WATER TANKS SHALL BE OF WHITE COLOR.


SHADE SHALL BE PROVIDED ABOVE THE TANKS TO AVOID
DIRECT SUN RAYS. SHADE DETAILS SHALL BE SUBMITTED TO
ARCHITECT FOR APPROVAL.

9. UNDERGROUND WATER TANKS,ABOVEGROUND WATER TANK


WITH 10 CU.M CAPACITY OR MORE AND ROOF WATER TANK
WITH 10 CU.M CAPACITY OR MORE SHALL BE PROVIDED WITH
AUDIBLE AND VISUAL ALARM THAT SHALL BE ACTIVATED WHEN
SCHEDULE OF MATERIALS
WATER LEVEL REACHES 50MM BELOW WATER TANK INLET.THE
ALARM SHALL BE LOCATED CLOSE TO THE TANK AND IN ITEM SPECS MAKE
RECEPTION OR IN SECURITY/GUARD ROOM. UNDERGROUND COLD WATER PIPES PPR-80 BANNINGER OR EQUAL
& FITTINGS
10. WATER HEATER SHALL BE GLASS LINED, CATHODIC
ABOVEGROUND COLD WATER PIPES PPR-80 FOR ABOVE CEILING PIPES
PROTECTED AND EQUIPPED WITH RELIEF VALVE. BANNINGER OR EQUAL
& FITTINGS PEX PIPES FOR INSIDE WALL PIPING TO FIXTURES
11. PIPING NETWORK SHALL BE HYDRAULICALLY TESTED FOR 24 ABOVEGROUND HOT WATER PIPES PPR-80 FOR ABOVE CEILING PIPES
BANNINGER OR EQUAL
HOURS BEFORE USE . & FITTINGS PEX PIPES FOR INSIDE WALL PIPING TO FIXTURES

12. ALL EXTERNAL WATER PIPES (EXPOSED TO SUN) SHALL BE VALVES KITZ OR EQUAL
PROVIDED WITH SLEEVES, SHADE OR INSULATION. HANGERS & SUPPORTS DIAMOND SUPPORTS OR EQUAL
ABOVE GROUND WATER STORAGE MARJAN TANKS OR EQUAL
TANKS
13. ALL PIPE PENETRATIONS IN WALLS AND/OR SLABS SHALL BE
ELECTRIC WATER HEATER A. O. SMITH OR EQUAL
PROVIDED WITH SLEEVES OF MINIMUM ONE PIPE SIZE LARGER.
TRANSFER PUMP GRUNDFOS, LOWARA OR EQUAL
14. ALL PIPE PENETRATIONS IN WALLS AND/OR SLABS SHALL BE BOOSTER PUMP GRUNDFOS, LOWARA OR EQUAL
SEALED WITH APPROVED FIRE STOP MATERIAL.

GENERAL NOTE WATER SUPPLY


15. ALL HOT WATER PIPING SHALL BE INSULATED WITH 25MM
THICK FIBERGLASS INSULATION.