Carrier 58MXA-10SM
Carrier 58MXA-10SM
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 PC 101 Catalog No. 535-80142 Printed in U.S.A. Form 58MXA-10SM Pg 1 9-04 Replaces: 58MXA-9SM
Tab 6a 8a
Downloaded from www.Manualslib.com manuals search engine
→ ELECTRICAL SHOCK AND UNIT DAMAGE
HAZARD
Failure to follow this caution may result in minor personal
injury or damage to furnace.
Label all wires prior to disconnection when servicing con-
trols. Wiring errors can cause improper and dangerous
®
U L T R A H I G H E F F I C I E N
C E
C Y GENERAL
G A S F U R N A N
FILTER
RETAINER
WASHABLE
FILTER
FILTER
SUPPORT
FILTER
RETAINER
WASHABLE FILTER OR
WASHABLE FILTER OR DISPOSABLE MEDIA
DISPOSABLE MEDIA FILTER FILTER IN FILTER CABINET
IN FILTER CABINET A00233
Fig. 4—Filter Installed for Side Inlet
A00232
Fig. 3—Bottom Filter Arrangement
NOTE: If the filter has an airflow direction arrow, the arrow must
ELECTRICAL SHOCK HAZARD point toward the blower.
Failure to follow this warning could result in personal injury To clean or replace filters, proceed as follows:
or death.
Turn off the gas and electrical supplies to the unit before If filter is installed in filter cabinet adjacent to furnace:
performing any maintenance or service. Follow the operating 1. Turn off electrical supply to furnace.
instructions on the label attached to the furnace. 2. Remove filter cabinet door.
The minimum maintenance that should be performed on this 3. Slide filter out of cabinet.
equipment is as follows: 4. If equipped with permanent, washable filter, clean filter by
1. Check and clean or replace air filter each month as needed. spraying cold tap water through filter in opposite direction of
airflow. Rinse filter and let dry. Oiling or coating of the filter
2. Check blower motor and wheel for cleanliness annually. is not recommended.
3. Check electrical connections for tightness and controls for 5. If equipped with factory specified disposable media filter,
proper operation each heating season. Service as necessary. replace only with a factory-authorized filter of the same size.
4. Check for proper condensate drainage. Clean as necessary. 6. Slide filter into cabinet.
5. Check for blockages in combustion-air and vent pipes annu- 7. Replace filter cabinet door.
ally. 8. Turn on electrical supply to furnace.
6. Check burners for cleanliness annually.
3
Downloaded from www.Manualslib.com manuals search engine
If filter is installed in furnace blower compartment: e. Remove bolts holding motor mounts to blower housing and
1. Turn off electrical supply to furnace. slide motor and mounts out of housing. Disconnect capcitor
and ground wire attached to blower housing before remov-
2. Remove main furnace door and blower access panel.
ing motor. Motor mounts need not be removed from motor.
3. Release filter retainer wire. (See Fig. 3 or 4.)
f. Remove blower wheel from housing.
4. Slide filter out of furnace.
5. Furnaces are equipped with permanent, washable filter(s).
Clean filter by spraying cold tap water through filter in
opposite direction of airflow. → UNIT DAMAGE HAZARD
Failure to follow this caution may result in noise or furnace
6. Rinse filter and let dry. Oiling or coating filter is not
component failure.
recommended.
The blower wheel should not be dropped or bent as balance
7. Slide filter into furnace. will be affected.
8. Recapture filter retainer wire.
g. Clean wheel per instructions on degreaser cleaner. Do not
9. Replace blower access panel and main furnace door. get degreaser in the motor.
10. Turn on electrical supply to furnace. 9. Reassemble motor and blower wheel by reversing items 8b
through 8f. Ensure wheel is positioned for proper rotation.
Step 2—Blower Motor and Wheel Maintenance
Tighten set-screw to 140-160 in.-lb torque.
To ensure long life, economy, and high efficiency, clean accumu-
lated dirt and grease from blower wheel and motor annually. 10. Reinstall blower assembly in furnace.
The inducer and blower motors are pre-lubricated and require no 11. Reinstall control box, transformer, and door switch assembly
additional lubrication. These motors can be identified by the on blower shelf.
absence of oil ports on each end of the motor. 12. Reinstall condensate trap and tubing if previously removed.
The following items should be performed by a qualified service a. Reinstall condensate trap in hole in blower shelf.
technician. b. Connect condensate trap drain tubes. See Fig. 8 or tubing
Clean blower motor and wheel as follows: diagram on main furnace door for proper tube location.
1. Turn off electrical supply to furnace. NOTE: Ensure tubes are not kinked or pinched, as this will affect
2. Remove main furnace door and blower access panel. operation.
3. Disconnect blower motor wires from furnace control. (1.) Connect 1 tube (blue or blue and white striped) from
Field thermostat connections may need to be disconnected collector box.
depending on their length and routing. (2.) Connect 1 tube (violet or unmarked) from inducer
4. Remove control box mounting screws and position control housing.
box, transformer, and door switch assembly to right side of (3.) Connect 1 tube (relief port, green or pink) from
furnace casing. collector box.
5. If condensate trap is located in left- or right-hand side of c. Connect field drain to condensate trap.
furnace casing, proceed to item 6, otherwise remove trap and
tubing as described below (See Fig. 8, top left): 13. Reconnect wires.
Refer to furnace wiring diagram, and connect thermostat leads
a. Disconnect field drain connection from condensate trap. if previously disconnected. (See Fig. 15.)
b. Disconnect drain and relief port tubes from condensate
NOTE: Refer to Table 1 for motor speed lead reconnection if
trap.
leads were not identified before disconnection.
c. Remove condensate trap from blower shelf.
6. Remove screws securing blower assembly to blower shelf and
slide blower assembly out of furnace.
UNIT DAMAGE HAZARD
7. Clean blower wheel and motor by using a vacuum with soft
Failure to adjust the heating speed may shorten heat ex-
brush attachment. Be careful not to disturb balance weights
changer life.
(clips) on blower wheel vanes. Do not bend wheel or blades as
Heating speed selection MUST be adjusted to provide proper
balance will be affected.
temperature rise as specified on the rating plate. Failure to
8. If greasy residue is present on blower wheel, remove wheel adjust the heating speed may shorten heat exchanger life.
from the blower housing and wash it with an appropriate
degreaser. To remove wheel:
a. Mark blower wheel location on shaft before disassembly to
ensure proper reassembly.
Table 1—Speed Selection
b. Loosen setscrew holding blower wheel on motor shaft. FACTORY
COLOR SPEED
ATTACHED TO
NOTE: Mark blower mounting arms and blower housing so each Black High Cool
arm is positioned at the same hole location during reassembly. Yellow (When Present) Medium High Spare
c. Mark blower wheel orientation and cutoff plate location to Blue Medium Low Heat
ensure proper reassembly. Red Low Fan
White Common Com
d. Remove screws securing cutoff plate and remove cutoff
plate from housing.
4
Downloaded from www.Manualslib.com manuals search engine
CELL
PANEL
ELECTRICAL SHOCK HAZARD
MANIFOLD
Failure to follow this warning could result in personal injury MOUNTING
or death. SCREW
Blower access door switch opens 115-v power to furnace
control. No component operation can occur. Caution must be
taken when manually closing this switch for service purposes.
5
Downloaded from www.Manualslib.com manuals search engine
NOTE: Inspect combustion-air intake housing. If foamed gasket
was removed, check for any damage. If gasket is damaged in any
→ ELECTRICAL SHOCK AND UNIT DAMAGE way, it must be repaired. To repair, remove damaged gasket
HAZARD section, apply sealant releasing agent such as PAM cooking spray
Failure to follow this caution may result in minor personal or equivalent (must not contain corn or canola oil, aromatic or
injury or furnace component damage. halogenated hydrocarbons or inadequate seal may occur) to burner
Label all wires prior to disconnection when servicing con- box and apply a small bead of G.E. RTV 162, G.E. RTV 6702, or
trols. Wiring errors can cause improper and dangerous Dow-Corning RTV 738 sealant to edge of combustion-air intake
operation. housing. (See Fig. 7.)
3. Disconnect wires or connectors to flame rollout switch, gas
valve, igniter, and flame sensor.
4. Disconnect combustion-air intake pipe from intake housing.
5. Remove the pressure switch tube from intake housing.
6. Remove screws attaching intake housing to burner box, and RTV
rotate intake housing away from burner box for removal.
7. Using backup wrench, disconnect gas supply pipe from gas
valve. PAM
PLUG
COLLECTOR BOX
CAP DRAIN TUBE (BLUE) CAP
PLUGGED END
COLLECTOR BOX DRAIN TUBE
COLLECTOR BOX DRAIN (BLUE)
COLLECTOR BOX TUBE
TUBE (GREEN) (BLUE & WHITE STRIPED) COLLECTOR BOX TUBE
(PINK)
COLLECTOR BOX DRAIN TUBE PLUG
(BLUE & WHITE STRIPED) COLLECTOR BOX TUBE
INDUCER HOUSING DRAIN (GREEN)
COLLECTOR BOX TUBE (VIOLET)
EXTENSION TUBE COLLECTOR BOX EXTENSION TUBE
BURNER ENCLOSURE PRESSURE
COLLECTOR BOX REFERENCE TUBE ASSEMBLY
CONDENSATE TRAP EXTENSION TUBE
DRAIN TUBE COUPLING CONDENSATE TRAP
BURNER ENCLOSURE PRESSURE COLLECTOR BOX
REFERENCE TUBE ASSEMBLY TUBE (PINK) DRAIN TUBES ROUTED IN COLLECTOR BOX
FRONT OF GAS VALVE EXTENSION DRAIN TUBE
INDUCER HOUSING DRAIN TUBE (VIOLET) GAS VALVE
A00308
;;
;;
5. Remove igniter assembly.
fuse to blow. If fuse replacement is required, use ONLY a fuse of
identical size (3-amp). The control LED will flash status code 24
when fuse needs to be replaced.
→ BURN HAZARD BURNER FLAME
Failure to follow this caution may result in minor personal BURNER
injury.
Allow igniter to cool before removal. Normal operating
temperatures exceed 2000°F.
A93081
9
Downloaded from www.Manualslib.com manuals search engine
FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING
NOTE 2
W C R G Y THERMOSTAT
FIVE WIRE TERMINALS FIELD-SUPPLIED
THREE-WIRE DISCONNECT
HEATING-ONLY
208/230- OR
BLOWER DOOR SWITCH 460-V
THREE
W PHASE
BLK BLK
C R
WHT WHT
O
N 208/230-V
GND GND T SINGLE
R G PHASE
115-V FIELD- AUXILIARY O
SUPPLIED J-BOX L COM GND
DISCONNECT NOTE 1
Y/Y2
CONDENSING
UNIT
24-V TWO
TERMINAL WIRE
BLOCK
FURNACE NOTES: 1. Connect Y-terminal in furnace as shown for proper blower operation.
2. Some thermostats require a "C" terminal connection as shown.
3. If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
A99440
BLOWER OFF-DELAY
90 150
120 180
Y1
HUMIDIFIER TERMINAL
DHUM
24-V THERMOSTAT
TERMINALS
24V
COM W/W1 Y/Y2
TRANSFORMER 24-VAC
CONNECTIONS
PLT
TEST/TWIN
HUM
R
0.5 AMP@24VAC
STATUS CODE LED
PLT
COOL
HEAT
HEAT
FAN 1-AMP@
L1
SPARE-1
115 VAC (L1) LINE PL2-HOT SURFACE
SPARE-2 FAN VOLTAGE CONNECTION IGNITER & INDUCER
BLOWER SPEED
MOTOR CONNECTOR
SELECTION TERMINALS
EAC-1 TERMINAL
(115-VAC 1.0 AMP MAX.)
A02142
10
Downloaded from www.Manualslib.com manuals search engine
32°F MINIMUM INSTALLED
AMBIENT OR FREEZE
PROTECTION REQUIRED
A93058
A99119
Fig. 15—Funnel in Drain and Antifreeze Running
Through Trap
COMPONENT TEST
11
Downloaded from www.Manualslib.com manuals search engine
(WHEN USED) TO 115VAC FIELD DISCONNECT SCHEMATIC DIAGRAM
BLOWER OFF DELAY LGPS
PRS NOTE #2
Y1
JUMPER SELECT PCB L1
L2
GND EQUIPMENT GROUND
(NATURAL GAS & PROPANE)
PRINTED CIRCIUT BOARD
90 ORN
DHUM 120 ILK FAN LO CAP-1
G NOTE #11 MED LO
150 YEL HEAT MED HI
Com
24V 180 L1 FAN HI
BLU BLU SPARE-1 START
W J1 HI/LO NOTE #10 OL L2
M GV BLWR
COOL EAC-2
Y/Y2 TEST/TWIN RED RED
BLWM
ORN LS FRS COM
R C EAC-1
HUM GRN/YEL
HSIR
FU1 RED NOTE #3
NOTE #6 GRN/YEL
1 1 HSI
IDR
IDM
1 2 3 4 5 6 7 8 9 10 11
WHT 2
SEC-2 SEC-1 PL2 2 PL3 OL
BLU BLK
TRAN
PR1 115VAC M
LED 1 RED AUX
RED WHT
EAC-2 WHT
L2 TRAN
NOTE #8
RED WHT 1
NEUTRAL
PL1 FSE
GRN/YEL AUX F U 1 NOTE #6
2 IDM
PL2 OL
SEC-1 SEC-2 FRS LS
BHT/CLR BFANR BLWR 1 BLK 6
2 1 WHT
COOL L1 PL3 GVR-2
FAN BLK WHT 2 HUM
HSI
HEAT
BLK BLK 1 8
R
SPARE 1 SPARE 2 EAC-1 LGPS (WHEN USED)
PR1 2
W
12
Downloaded from www.Manualslib.com manuals search engine
SERVICE
If status code recall is needed, briefly remove then reconnect one main limit wire to display
stored status code. On RED LED boards do not remove power or blower door before initiat-
ing status code recall. After one status code recall is completed component test will occur.
LED CODE STATUS
CONTINUOUS OFF - Check for 115VAC at L1 & L2, & 24VAC at SEC-1 & SEC-2.
CONTINUOUS ON - Control has 24VAC power.
RAPID FLASHING - Line voltage (115VAC) polarity reversed. If twinned,
refer to twinning kit instructions.
EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST
DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY
THE NUMBER OF LONG FLASHES.
COMPONENT TEST
To initiate the component test sequence, shut OFF the room thermostat or disconnect
the "R" thermostat lead. Briefly short the TEST/TWIN terminal to the "Com 24V" ter-
minal. Status LED will flash code and then turn ON the inducer motor. The inducer
motor will run for the entire component test. The hot surface ignitor, blower motor
FAN speed (AMBER LED boards only) blower motor HEAT speed, and blower motor
COOL speed will be turned ON for 10-15 seconds each. Gas Valve and Humidifier
will not be turned on. 327884-101 REV. B
A02270
13
Downloaded from www.Manualslib.com manuals search engine
TROUBLESHOOTING GUIDE
START
NO NO NO
Is LED status light on? Is there 115V at L1 and L2? Is door switch closed? Close door switch and go back to START.
YES
YES YES
NO NO
Is there 24V at SEC-1 and SEC-2? Is there 115V going to switch? Is circuit breaker closed?
NO
Replace furnace control. Replace door switch. Check for continuity in wire from circuit breaker
to furnace.
NO
Is LED status light blinking ON/OFF slowly NO To recall status code briefly remove and reconnect one RED wire from the Limit
with a combination of short and long flashes? Switch or Flame Rollout switch to display stored status code. On RED LED
control do not remove power or blower access panel before initiating status
code recall. You can also recall the previous status code by momentarily shorting
YES
the TEST/TWIN terminal to Com24V terminal until the LED goes out. LED will
flash the previous status code or status code #11 (1 short and 1 long flash) if
there was no previous code. After the control repeats the code 4 times, the
14
Determine status code. The status code is a
2 digit number with the first digit determined control will go through a brief component test sequence. The inducer will start
by the number of short flashes and the second and run for the entire component test. The HSI, blower motor FAN speed
digit by the number of long flashes? (AMBER LED boards only) HEAT speed, and COOL speed will run for 10 – 15 Check room thermostat or
seconds each. Gas valve and humidifier will not be turned on. interconnecting cable.
NO
YES Does the control respond to W, Y1 (if present), NO Is 24V present at W, Y1 (if present), Y/Y2 or
Go to section below for the status code that Was there a previous status code NO
was flashed. other than #11? Y/Y2, and G (24V) thermostat signals? G thermostat terminals on the furnace control?
YES YES
Run system through a heating or cooling cycle Disconnect all the thermostat wires from the
to check operation. Status codes are erased furnace control.
after 72 hours. On RED LED boards stored
status codes can also be erased whenever
(115V or 24V) is interrupted.
NO
A02204a
11 NO PREVIOUS CODE – Stored codes 31 PRESSURE SWITCH DID NOT CLOSE 45 CONTROL CIRCUITRY LOCKOUT
are erased after 72 hours. On RED LED OR REOPENED – If open longer than 5 Auto-reset after 1 hour lockout due to:
boards stored status codes can also be minutes, inducer shuts off for 15 minutes - Flame circuit failure.
erased whenever power (115V or 24V) before retry. If opens during blower on- - Gas valve relay stuck open.
delay period, blower will come on for the
is interrupted. Run system through a selected blower off-delay. Check for: - Software check error.
heating or cooling cycle to check system. - Proper vent sizing. Reset power to clear lockout. Replace
- Low inducer voltage (115V). control if code repeats.
- Low inlet gas pressure (if LGPS used).
12 BLOWER ON AFTER POWER UP – - Inadequate combustion air supply. NO
(115V OR 24V) – Normal operation. - Disconnected or obstructed pressure Unplug igniter harness from control and initiate Replace furnace control.
Blower runs for 90 seconds, if unit is tubing. another component test sequence. Check
powered up during a call for heat (R-W - Defective inducer motor. for 115V between pin 1 and NEUTRAL-L2 on
closed) or when (R-W opens) during the - Defective pressure switch. the control. Was 115V present for the 15 YES Check for continuity in the harness and igniter.
15
- Defective blower motor or capacitor.
- Inadequate combustion air supply - Check for air leakage around igniter bracket.
21 GAS HEATING LOCKOUT – Turn off
power and wait 5 minutes to retry. (flame rollout switch open). YES
Check for: - Restricted vent.
- Stuck closed gas valve relay on control. - Proper vent sizing. Do the main burners stay on? YES Allow blower to come on and repeat test to
- Miswire or short to gas valve wire. - Excessive wind. check for intermittent operation.
- Blower motor on incorrect speed tap.
- Input rate to furnace set too high. NO
22 ABNORMAL FLAME-PROVING SIGNAL
Flame is proved while gas valve is de- Repeat call for heat and check flame sensor Check connections and retry. If current is
current during trial for ignition period. Is the NO near typical value (4.0-6.0 nominal) and
energized. Inducer will run until fault is 34 IGNITION PROVING FAILURE – If flame
cleared. Check for: DC microamps below 0.5? burners will not stay on, replace control.
is not sensed during the trial for ignition
- Stuck open or leaky gas valve. period, the control will repeat the ignition
sequence 3 more times before lockout NO
#14 occurs. If flame signal is lost during YES
23 PRESSURE SWITCH DID NOT OPEN the blower on-delay period, blower will YES
Check for: come on for the selected blower off-delay. Clean flame sensor with fine steel wool and
- Obstructed pressure tube. Check the following items first before recheck current. Nominal current is 4.0 to 6.0
- Pressure switch stuck closed. proceeding to the next step. microamps.
- Gas valve turned off.
- Manual shut-off valve.
24 SECONDARY VOLTAGE FUSE IS OPEN - Green/Yellow wire MUST be connected
Check for: to furnace sheet metal.
- Short circuit in secondary voltage (24V) - Flame sensor must not be grounded. NO
Is current near typical value? Replace electrode.
wiring including thermostat leads. To determine whether the problem is in
Disconnect thermostat leads to isolate the gas valve, igniter, or flame sensor the
short circuit. system can be operated in the component YES
test mode to check the igniter. First
Will main burners ignite and stay on? NO Replace furnace control.
remove the R thermostat connection from
the control and initiate the component
test sequence. Does the igniter glow
YES
orange/white by the end of the 15 second
warm-up period?
Fixed.
A02204b