Professional Documents
Culture Documents
Engineering Computations: Article Information
Engineering Computations: Article Information
Interface modelling between CFD and FEM analysis: the dual-layer post-processing
model
Daphne Pantousa, Euripidis Mistakidis,
Article information:
To cite this document:
Daphne Pantousa, Euripidis Mistakidis, (2017) "Interface modelling between CFD and FEM analysis:
the dual-layer post-processing model", Engineering Computations, Vol. 34 Issue: 4, pp.1166-1190,
https://doi.org/10.1108/EC-06-2015-0146
Permanent link to this document:
Downloaded by Doctor Daphne Pantousa At 07:58 02 August 2017 (PT)
https://doi.org/10.1108/EC-06-2015-0146
Downloaded on: 02 August 2017, At: 07:58 (PT)
References: this document contains references to 24 other documents.
To copy this document: permissions@emeraldinsight.com
The fulltext of this document has been downloaded 22 times since 2017*
Users who downloaded this article also downloaded:
(2017),"Fatigue crack growth prediction of 7075 aluminum alloy based on the GMSVR model
optimized by the artificial bee colony algorithm", Engineering Computations, Vol. 34 Iss 4
pp. 1034-1053 <a href="https://doi.org/10.1108/EC-11-2015-0362">https://doi.org/10.1108/
EC-11-2015-0362</a>
(2017),"Pressure fluctuation characteristics in the sidewall gaps of a centrifugal dredging
pump", Engineering Computations, Vol. 34 Iss 4 pp. 1054-1069 <a href="https://doi.org/10.1108/
EC-12-2015-0383">https://doi.org/10.1108/EC-12-2015-0383</a>
EC
34,4 Interface modelling between CFD
and FEM analysis: the dual-layer
post-processing model
1166 Daphne Pantousa
University of Thessaly, Volos, Greece, and
Received 2 June 2015
Revised 15 September 2016 Euripidis Mistakidis
Accepted 19 September 2016
Department of Civil Engineering, University of Thessaly, Volos, Greece
Downloaded by Doctor Daphne Pantousa At 07:58 02 August 2017 (PT)
Abstract
Purpose – The primary purpose of this paper is the development of a fire–structure interface (FSI) model,
which is referred in this study as a simplified “dual-layer” model. It is oriented for design purposes, in the
cases where fire-compartments exceed the “regular” dimensions, as they are defined by the guidelines of the
codes (EN 1991-1-2).
Design/methodology/approach – The model can be used at the post-processing stage of computational
fluid dynamics (CFD) analysis and it is based on the gas-temperature field (spatial and temporal) of the fire-
compartment. To use the “dual-layer” model, first the gas-temperature (discrete) function along the height of
the fire-compartment, at discrete plan–view points should be determined through the output of the CFD
analysis. The model “compresses” the point data to (spatial) virtual zones, which are divided into two layers
(with respect to the height of the fire-compartment) of uniform temperature: the upper (hot) layer and the
lower (cold) layer.
Findings – The model calculates the temporal evolution of the gas-temperature in the fire compartment in
every virtual zone which is divided in two layers (hot and cold layer).
Originality/value – The main advantage of this methodology is that actually only three different
variables (height of interface upper-layer temperature and lower-layer temperature) are exported during the
post-processing stage of the CFD analysis, for every virtual zone. Next, the gas-temperature can be used for
the determination of the temperature profile of structural members using simple models that are proposed in
EN 1993-1-2.
Keywords Computational fluid dynamics analysis, Fire design, Fire–structure interface model,
Natural fire simulation
Paper type Research paper
1. Introduction
The integrated fire design of buildings requires the combination of computational fluid
dynamics (CFD), thermal and structural analysis. This becomes more important in the case
where buildings do not conform to the regulations regarding the geometric characteristics of
the fire-compartments or in the case where the ISO fire design leads to excessive financial
cost. In these special cases, the use of CFD is inevitable. An important issue that arises in the
case of modelling of the evolution of natural fire in a compartment using the principles of
CFD, is the determination of the temperature profile of the structural members. This is
Engineering Computations This research has been co-financed by the European Union (European Social Fund – ESF) and Greek
Vol. 34 No. 4, 2017
pp. 1166-1190 national funds through the Operational Program “Education and Lifelong Learning” of the National
© Emerald Publishing Limited
0264-4401
Strategic Reference Framework (NSRF) – Research Funding Program: Heraclitus II. Investing in
DOI 10.1108/EC-06-2015-0146 knowledge society through the European Social Fund.
critical for the determination of the fire-response of the structure. Actually, the problem that CFD and FEM
is studied involves three different physical phenomena that interact. The first is the fire- analysis
evolution in the compartment, the second is the heat transfer in the solids and the third is the
thermo-mechanical response of the structural system. This indicates that three different
mathematical problems have to be solved to obtain the gas-temperature time-history in the
fire-compartment, the temperature profile of the structural steel members and the stress–
strain field of the structural system. An integrated methodology for the solution of the
problem requires the execution of “fully coupled” thermo-mechanical analysis. Here, the 1167
term “fully coupled” is referred to the interaction between the fire evolution in the fire-
compartment and the structural members. The fire development induces thermal loading in
the structural members that deform due to the concurrent mechanical and thermal actions.
The deformations of the structural members cause continuous modifications of the initial
configuration of the structural system during the fire evolution and this can affect the gas-
temperature distribution in the enclosure. This approach is extremely complex to be applied
Downloaded by Doctor Daphne Pantousa At 07:58 02 August 2017 (PT)
due to the fact that the structural members should be included in the numerical model which
is used for the CFD analysis. It is clear that it is difficult to couple the different types of
analyses due to the different spatial scales of the interacting phenomena. The incorporation
of the structural members in the CFD model requires a very dense mesh in the
corresponding positions and, consequently, leads to excessive computational cost. Thus, it is
necessary to simplify the calculations and to uncouple the involved problems. In this point
of view, a software “interface” has to be developed to transfer the results of the CFD analysis
to the finite element (FE) analysis.
Several fire–structure interface (FSI) models have been proposed in the literature. The
Research Fund of Coal and Steel (RFCS) project, called FIRESTRUCT (Kumar et al., 2008),
dealt with different approaches for the FSI using different software environments. In
Tondini et al.’s (2012) study, a weak coupling approach between the CFD software fire
dynamics simulator (FDS) (Mcgrattan et al., 2010a, 2010b) and the FE code SAFIR was
presented. The FSI method requires that the fire development is simulated in FDS
(Mcgrattan et al., 2010a, 2010b) and the thermal and mechanical analysis are conducted in
SAFIR (Franssen et al., 2000) using linear elements for the simulation of the structural
members. Specifically, after the end of the CFD analysis, a transfer file, which contains all
the required information (temperature of gas, convective heat transfer coefficient and net
radiative heat fluxes from various directions), is generated. The goal is to compute the fluxes
at the surface of the structural members in the FE software by integrating the radiant
intensities. A spherical interpolation is performed to obtain the radiant intensities in the
directions required by the numerical integration.
Moreover, an algorithm was proposed by Prasad and Baum (2005a, 2005b) which was
adopted in the study of Hamins et al. (2005). The FSI is described in detail by Prasad and
Baum (2005a). The paper describes the collapse of the World Trade Center towers, resulting
from a combination of the aircraft impact damage and the fires that followed. A
methodology was developed to calculate the heat transfer to the structural elements. The
simple radiative transport model assumes that the compartment can be locally divided into
a hot, sooty layer and a cool relatively clear lower layer. The properties of the two layers are
extracted from temporal averages of the results of the fire simulation using CFD.
Specifically, the approach that is proposed in this study takes into account the fact that the
horizontal dimensions of each floor of the WTC towers are much greater than the height of
the individual floor. Hence, in this case, the temperature and the soot concentration change
quite rapidly in the vertical direction but much more slowly in the horizontal directions.
This simplification is very similar to the “zone models” of fire dynamics that ignore the
EC variation of thermal properties in the horizontal directions. Taking this into account, the
34,4 radiative transport equation can be solved explicitly and the heat flux can be obtained as a
function of the temperature, the hot layer depth, the soot concentration and the orientation of
the structural element. This formulation can be used directly as input into FE analysis codes
where the numerical simulation is based on three-dimensional models.
Furthermore, a heat transfer model for coupled processes in fire simulations was
1168 developed in the study of Hohm (2010). The model solves the heat transfer between the gas
phase and the solid phase for both horizontal and vertical plane surfaces and in particular
pipe and duct flows. Multidimensional temperature fields are determined precisely by the
model. The model was optimized both physically, by considering the specific fire effects and
characteristics and numerically, by selecting adequate numerical methods, for integrated
usage within numerical fire simulations.
A new concept of the adiabatic surface temperature was introduced in the study of
Wickström et al. (2007). The concept can be used successfully when the exposure conditions are
Downloaded by Doctor Daphne Pantousa At 07:58 02 August 2017 (PT)
obtained either for a CFD model or directly from measurements during a fire test. The adiabatic
surface is a surface of a perfect insulator exposed to the same heating conditions as the real
surface. Its temperature is the adiabatic surface temperature. The basic characteristic of the
adiabatic surface is that the total net heat flux is by definition zero. The adiabatic surface
temperature can be obtained from the output of a CFD model or it can be measured in real fire
tests using devices as the plate thermometer and it is actually the interface between the fire and
the structural models. This strategy is efficient, as it is required to transfer only one quantity
than three different quantities (a heat flux, a surface temperature and a convective heat transfer
coefficient).
The objective of this paper is the development of an interface model between the CFD and
the FE structural analysis that can be used during fire design. The aim is to find an effective
way to calculate the temperature profile of the structural members of a fire-compartment using
the results of the CFD analysis. The difficulty arises due to the strong spatial non-homogeneity
and the intense time variation of the gas-temperature in the fire compartment. In the case of the
fire design of buildings, it is not possible to take into account this non-homogeneity and,
moreover, it is useful to calculate the temperature history of the structural members using
simplified models, as they are proposed in EN-1993-1-2. In this point of view, the target is to
calculate the gas-temperature evolution needed for the calculation of the temperature profile of
the members to conduct the subsequent thermal/structural analysis. This study is focused on a
library building and the fire is considered to take place in the fire-compartment of the first floor
of the structure. First, the CFD analysis is conducted using FDS. The output of this analysis,
concerning the spatial distribution and temporal evolution of the gas-temperature, is
compressed using the “dual-layer” model. This model is based on the idea of the two-zone
models that have been proposed in EN 1991-1-2. However, the herein developed “dual-layer
model” is totally different and the calculations are conducted in the post-processing stage of the
CFD analysis. The gas-temperature is obtained in a simple way through three different
variables which are the temperature of the upper and the lower layers and the layer-separation
height.
1169
Downloaded by Doctor Daphne Pantousa At 07:58 02 August 2017 (PT)
Figure 1.
The library building
Figure 1. Specifically, eight windows of 7.50 2.00 m2 are placed at each level along the 60-m
sides of the building.
The combustible materials consist mostly of paper documents in folders, placed on 2.50-
m-high shelving systems arranged in rows, as indicated in Figure 1. The distance between
the shelving systems is 1.20 m and the dimensions of the plan-view of the shelves are 0.50
10.00 m2. The exterior doors are not defined, as it is assumed that they are closed during the
fire evolution and, subsequently, do not affect the fire evolution in the enclosure.
The structural system of the building consists of 21 double-span steel frames on
every floor, at a distance of 3.00 m, as it is shown in Figure 2. The geometry of a typical
frame of the building is presented in the same figure. A special feature of the library
building is that every floor is a separate “non-regular” fire-compartment and the total
area is equal to 960 m2. The fire-compartment is characterized as “non-regular”, as
several requirements of the Greek Fire Protection regulations are violated. Specifically,
one escape exit is located in the fire-compartment, while the minimum requirement is two
escape exits. The second violation is about the maximum distance of the escape route. The
length of the escape route is larger than 20 m, which is the maximum allowed travel distance in
the fire-compartment. Furthermore, according to the regulations, a sprinkler system is required
for the specific fire-compartment, as the area is larger than 300 m2.
Six scenarios are defined to take into account the effect of the ventilation conditions to the
fire evolution in the enclosure. The ventilation conditions are a critical parameter that affects
the temporal gas-temperature profile in the fire-compartment. Different scenarios are
considered regarding various percentages of the windows that are open/broken. The
percentage and the position of the broken windows modify the ventilation conditions, leading
to different fire scenarios and, consequently, to different gas-temperature time–history
distributions in the fire-compartment. Taking into account the previous results, different
temperature profiles of the structural members are expected. Six different scenarios are defined
that are illustrated in Figure 3.
EC b b1 c c1 d d1 e e1 f f1 g g1 h h1 i i1 j j1 k k1 l
34,4
8m
8m
1170
3m
Level 4
3.5 m
Level 3
3.5 m
Downloaded by Doctor Daphne Pantousa At 07:58 02 August 2017 (PT)
Level 2
3.5 m
Level 1
Figure 2.
3.5 m
The structural
system and a typical
frame
8m 8m
Figure 3.
The fire scenarios
3. Numerical simulation CFD and FEM
The numerical model is developed using FDS (Mcgrattan et al., 2010a, 2010b) and is analysis
presented in Figure 4. In this study, it is assumed that the fire breaks out at the first floor of
the building and that the fire cannot spread to the upper levels. Taking into account the
previous, it is not required to simulate the higher levels.
The boundaries of the computational domain are illustrated in Figure 5. As it can be
observed, the computational domain is Figure 6 not restricted to the outline of the
building but it is extended around it, to simulate the ambient atmospheric conditions in 1171
a realistic way. The domain is extended to 4 m in the x and y directions and 2 m in the z
direction The predefined boundary condition OPEN, which is included in FDS
(Mcgrattan et al., 2010a, 2010b), is used for the description of the exterior boundary of
the computational domain. The OPEN boundary condition assumes that ambient
conditions exist around the building and the flow in and out of the building is treated
naturally as part of the solution of the governing equations. Moreover, this extended
Downloaded by Doctor Daphne Pantousa At 07:58 02 August 2017 (PT)
mesh is useful for the representation of the heat transfer and the smoke movement at
the surroundings of the building.
Figure 4.
The numerical model
for the natural fire-
simulation
Figure 5.
The numerical model
for the first level and
the limits of the
computational
domain
EC A basic parameter for the numerical simulation is the definition of the grid cell size for the
34,4 computational domain. FDS (Mcgrattan et al., 2010a, 2010b) approximates the governing
equations on a rectilinear grid cell. Taking into account results from the literature (Rein
et al., 2007) regarding the mesh sensitivity, the grid cell size is selected to be 0.50 0.48
0.50 m3 for the directions x, y and z, respectively. In this way, a total of 68,000 mesh cells
are included in the numerical model.
1172 It is noted that the structural members are not included in the numerical model. This
assumption is required to simplify the calculations.
Finally, in this study, the large Eddy simulation is used and the radiation transport
solver is enabled. The duration of the fire event is set equal to 3,600 s for all the fire
scenarios. The computational time step is adjusted not to exceed the value of 0.1 s.
Specifically, the time step can be decreased during the analysis if the solution does not
converge.
Downloaded by Doctor Daphne Pantousa At 07:58 02 August 2017 (PT)
2.5 0.25
2 0.2
1.5 0.15
1 0.1
Figure 6.
Variation of thermal 0.5 0.05
properties of the 0 0
1,000
1,200
200
400
600
800
200
400
600
800
0
0
1,000
1,200
insulation material
with temperature.
Temperature (⁰C) Temperature (⁰C)
Absorption
Density Specific heat Conductivity coefficient
Material (kg/m3) (kJ/(kg · K)) (W/(m · K)) Emissivity (1/m)
5=2
Downloaded by Doctor Daphne Pantousa At 07:58 02 August 2017 (PT)
QM LM
¼ (1)
QR LR
1=2
tM LM
¼ (2)
tR LR
500
HRR (KW)
450
400 HRR according to the
experimental results (model)
350
300
250
200
150
100
Figure 7.
50
Experimental HRR
0
curve of the bookshelf
200
400
600
800
0
1,000
1,200
1,400
1,600
1,800
test
time (sec)
this study, the scaled HHR curve is used and the intention is to obtain the parametric CFD and FEM
fire scenarios based on the modification of the ventilation conditions. analysis
3.3 Modelling the spread of fire
The ignition source of fire is supposed to be in the middle (with respect to the y-direction) of
the first row (left side) of the array of book-shelves. It is noted that changing the ignition
point of fire, the results are completely different. In this study, the selection of the ignition 1175
point is completely random, as the goal is to define the parametric fire scenarios taking into
account in all cases the same ignition point. The activation of fire is implemented by the
assumption that the heat release burner that corresponds to the ignition source is active
from the beginning of the analysis.
The simulation of fire spread is an extremely complicated issue, as it depends on several factors
involving the combustible materials, the available oxygen, the orientation of the burning surface
Downloaded by Doctor Daphne Pantousa At 07:58 02 August 2017 (PT)
(Novozhilov, 2001), etc. Although FDS offers the capability to define the rate of fire spread, it is quite
difficult to define this value, as the experimental data on this issue are limited. An alternative
simulation of the fire spread is adopted in this study (Pantousa, 2014, Zografopoulou et al., 2013a,
2013b). It is assumed that the basic requirement for fire spread between combustible materials at a
distance, is that the temperature reaches a specified value near the surface of the material. The
specified temperature indicates that the pyrolysis reaction starts.
Actually, the simulation is based on the activation temperature of the heat release
burning surface placed on the obstructions that represent the book-shelving units.
Specifically, the activation is controlled by a sensor 2.50 m above the centre of the section.
This control device activates the heat release burner when the temperature at the sensor
reaches 250°C. The temperature that is used corresponds approximately to the auto ignition
temperature of wood (Babrauskas, 2002) and paper (Graf, 1949). It is clear that this approach
results in gradual activation of the heat release sections and that it depends on the
temperature distribution in the compartment. Another required condition for the
combustion to occur is the concentration of oxygen to be greater than 0.15. If this is not
satisfied, the fire is suppressed due to lack of oxygen.
2,500
HRR (KW/m2)
1,000
Figure 8.
500
The experimental
and the modified
0 HRR curves used for
200
400
600
800
0
1,000
1,200
1,400
1,600
1,800
2,000
characteristics (upper and lower temperature and layer height). The method used in FDS is
described in detail by Janssens and Tran (1992). First, the continuous function T(z) is obtained
which defines the temperature T as a function of the height above the floor z, where z = 0 is the
floor and z = H is the ceiling. The question that arises is how to calculate the unknown
variables zint, Tu and Tl, from a series of temperature measurements at a discrete number of
heights. Tu represents the upper-layer temperature and Tl the lower-layer temperature and zint
as the interface height (actually the lower layer height). Quintiere et al. (1984) proposed the
method that is used in this study. Initially, Tu is defined as the average of the upper-layer
temperature. Then, zint and Tl are calculated from the following integral equations:
ð
H
ð
H
1 1 1
ð H zint Þ þ zint ¼ dz ¼ I2 (4)
Tu Tl T ð zÞ
0
Here, the Simpson’s rule has been applied for the numerical integration of I1 and I2. Tu is
defined as the average upper layer temperature via:
ð
H
Actually, equation (4) describes mathematically the two-zone model and has no physical
meaning, although it is very close to the requirement for the equivalence of enthalpy.
Equation (5) describes the mass equivalence (Keski-Rahkonen and Hostikka, 2002).
In the current study, the layer-zoning devices are placed every 1 m along the x- and
y- directions on the model plan. The three-dimensional view of the devices is presented
in Figure 9. In total, 1,036 layer-zoning devices are installed in the library interior.
Then, the fire-compartment is separated into 11 different virtual zones (effective length
equal to 6 m), as illustrated in Figure 10(a). Moreover, Figure 10(b) shows a longitudinal
CFD and FEM
analysis
1177
Downloaded by Doctor Daphne Pantousa At 07:58 02 August 2017 (PT)
Figure 9.
3D view of the layer-
zoning devices
Figure 10.
(a) Plan view of the
first floor-virtual
zones; (b) longitudinal
section of the
building
section of the building where the variables zint, Tu and Tl are illustrated. The first and
last zones are assigned different effective widths to take into account the influence of
the boundary conditions and the geometry of the compartment. The effective length for
the internal frames is equal to the typical distance between two frames, i.e. 3 m. Each
virtual zone corresponds to the “effective length” for two frames (e.g. the sub-frames f-b
and f-b1 are included in Zone b, the sub-frames f-c and f-c1 are included in Zone c, etc.).
Thus, the effective length for each zone is set equal to 6 m. A denser discretization
(“effective area” for every frame) of the area of the building, in virtual zones, leads to
EC extended results with no actual profit, as, the gas-temperature of adjacent sub-frames
34,4 (e.g. f-c and f-c1) seem to be very close (according to the results of several trial analyses
that were conducted with respect to the length of the virtual zones). Obviously, the
determination of the virtual zones depends both on the geometric characteristics of the
fire-compartment and on the exact allocation of the structural members. Subsequently,
concerning the spatial zone division, non-special guidelines can be framed.
1178 Regarding each virtual zone, the mean values of the output results for the layer-zoning
devices (layer height, upper and lower zone temperature), are calculated. This indicates that
the gas-temperature is assumed to be uniform along every virtual zone. Moreover, it is
highlighted that the temperature is assumed to be uniform at the upper and the lower layers,
in the z-direction. Taking into account the previous results, the problem is simplified and
three different time-histories are calculated in each virtual zone: the layer height, the gas-
temperature of the upper and the lower layers.
It is noted that in this study, the averaging of the results is conducted through a simple code
Downloaded by Doctor Daphne Pantousa At 07:58 02 August 2017 (PT)
using the programming language Fortran 90. Alternatively, simple Excel sheets can be used.
5. Results
5.1 Gas-temperature at the lower and upper layers
The temporal evolution of the gas-temperature for the upper and the lower layers is
presented in Figures 11-16 for all fire scenarios. The results concern all the virtual zones
Lower layer T (⁰C)
1,000 1,000
Lower layer T (⁰C)
b c d h i j
900 900 k l
e f g
800 800
700 700
600 600
500 500
400 400
300 300
200 200
100 100
0 0
0
300
600
900
1,800
1,200
1,500
2,100
2,400
2,700
3,000
3,300
3,600
0
300
600
900
1,200
1,500
1,800
2,100
2,400
2,700
3,000
3,300
3,600
1,000 1,000
b c d h i j
900 900
e f g k l
800 800
700 700
600 600
500 500
400 400
Figure 11. 300 300
Lower- and upper- 200 200
layer temperature 100 100
evolution with time 0 0
0
900
300
600
1,200
1,500
1,800
2,100
2,400
2,700
3,000
3,300
3,600
0
300
600
900
1,800
1,200
1,500
2,100
2,400
2,700
3,000
3,300
3,600
b c d h i j
900 e f g
900
k l analysis
800 800
700 700
600 600
500 500
400 400 1179
300 300
200 200
100 100
0 0
0
300
600
900
1,800
1,200
1,500
2,100
2,400
2,700
3,000
3,300
3,600
0
300
600
900
1,200
1,500
1,800
2,100
2,400
2,700
3,000
3,300
3,600
Downloaded by Doctor Daphne Pantousa At 07:58 02 August 2017 (PT)
1,000 1,000
b c d h i j
900 900
e f g k l
800 800
700 700
600 600
500 500
400 400
300 300
Figure 12.
200 200
Lower- and upper-
100 100 layer temperature
0 0 evolution with time
0
300
600
900
2,100
2,400
1,200
1,500
1,800
2,700
3,000
3,300
3,600
0
300
600
900
1,800
1,200
1,500
2,100
2,400
2,700
3,000
3,300
3,600
that are included in the “interface model”, to understand the spatial temperature variation in
the fire-compartment.
In the scenario SC-25A (Figure 11), it is observed that at first the temperature increases
and a peak is recorded approximately between the 600 s and the 900 s of the analysis. This
peak is recorded at different time-frames for each of virtual zone and it can be attributed to
the fire spread in the compartment. In the sequel, the temperature remains quite constant.
Regarding the lower layer, the temperature varies between 200°C and 300°C, while the
corresponding values for the upper layers are between 300°C and 500°C. After a rather
constant temperature branch, a second peak is recorded. This is a local phenomenon and can
be connected to the sudden increase in heat from the burners located at Zones j, k and l. This
is also visualized in Figure 17. After this, the temperature decreases rapidly in both layers.
The spatial gas-temperature distribution in the enclosure during the analysis is quite
constant, as the variations between the layers are small. The same remarks, concerning the
peak values and the constant branch, hold also for the SC-25B scenario (Figure 12). In this
case, the difference lies on the fact that the curves that correspond to the different virtual
zones (especially for the upper layer) are more discrete and this indicates that the spatial
temperature distribution in the enclosure is non-uniform. As the percentage of the broken/
open windows increases (SC-50A and SC-50C), the temperature distribution in the enclosure
is completely non-uniform (Figures 13 and 14). The time evolution is different for each
EC
900
300
600
1,200
3,600
1,500
1,800
2,100
2,400
2,700
3,000
3,300
0
300
600
900
1,200
1,500
1,800
2,100
2,400
2,700
3,000
3,300
3,600
Downloaded by Doctor Daphne Pantousa At 07:58 02 August 2017 (PT)
1,000 1,000
b 900 h
900
c i
800 800
d j
700 e 700
k
600 f 600 l
500 g 500
400 400
300 300
Figure 13.
200 200
Lower- and upper-
layer temperature 100 100
evolution with time 0 0
1,800
3,300
1,200
1,500
2,100
2,400
2,700
3,000
3,600
0
300
600
900
0
300
600
900
2,100
2,400
2,700
3,000
3,300
3,600
1,200
1,500
1,800
virtual zone and this strongly depends on the position of the broken windows. The spatial
variation is strongly non-uniform, especially in the upper layer, where the zones are well-
separated. This behaviour conforms to the temperature distribution, as it is presented in
Figures 18 and 19. The spatial distribution of the gas-temperature is totally non-uniform
for the scenarios SC-75 and SC-100 (Figures 15 and 16). It is noted that in both cases, the
gas-temperature is high in the lower layer for most of the virtual zones. Finally, it is
observed that for low percentage of the broken/open windows, a constant plateau (with
respect to the time evolution) can be detected in most virtual zones. This plateau is not
present in the cases that the percentage of open/broken windows is higher and it is
replaced by a single peak. This is more obvious in SC-100.
b c d h i j
900 e f g
900
k l analysis
800 800
700 700
600 600
500 500
400 400 1181
300 300
200 200
100 100
0 0
0
300
600
900
1,500
2,100
2,700
1,200
1,800
2,400
3,000
3,300
3,600
0
300
600
900
1,200
1,500
1,800
2,100
2,400
2,700
3,000
3,300
3,600
Downloaded by Doctor Daphne Pantousa At 07:58 02 August 2017 (PT)
1,000 1,000
b h
900 900
c i
800 d 800 j
700 e 700 k
f l
600 g 600
500 500
400 400
300 300
Figure 14.
200 200
Lower- and upper-
100 100 layer temperature
0 0 evolution with time
0
300
600
900
1,800
3,300
1,200
1,500
2,100
2,400
2,700
3,000
3,600
0
300
600
900
2,100
2,400
2,700
3,000
3,300
3,600
1,200
1,500
1,800
0
300
600
900
1,800
1,200
1,500
2,100
2,400
2,700
3,000
3,300
3,600
0
300
600
900
1,200
1,500
1,800
2,100
2,400
2,700
3,000
3,300
3,600
time (sec)
Downloaded by Doctor Daphne Pantousa At 07:58 02 August 2017 (PT)
time (sec)
1,000 1,000
b h
900 900
c i
800 d 800 j
e 700 k
700
f l
600 g 600
500 500
400 400
300 300
Figure 15.
200 200
Lower- and upper-
layer temperature 100 100
evolution with time 0 0
0
300
600
900
1,800
3,300
1,200
1,500
2,100
2,400
2,700
3,000
3,600
0
300
600
900
1,800
1,200
1,500
2,100
2,400
2,700
3,000
3,300
3,600
the layer height is the difference between the temperatures that are recorded in the
distinct layers.
In SC-25B, it is observed that during the fire exposure, the layer height is quite
constant, especially for the steady branch, as it is indicated in the HRR diagram that is
included in Figure 20. It is noticed that the HRR diagram shows an approximation of
the steady-state branch and it is not supported by calculations. The layer height varies
between 1.00 and 1.20 m in most zones, except Zones b and c. The value of the interface
height, which corresponds to the steady burning stage, is marked on the diagrams of
Figure 16 as zint/av. This indicates that in this region (Zones b and c), the temperature
profile is uniform with respect to the z-axis and the temperature varies between 200°C
and 300°C. In the rest of the virtual zones, the difference between the temperature
recorded at the upper and the lower layers is rather large. The maximum values appear
at Zones j and k, where the open/damaged windows are located.
In the case of SC-75 (Figure 21), the layer height is characterized by a continuous
variation during the fire exposure. During the early stages of the fire exposure, in virtual
Zones b, c, j and k, the layer height is almost constant and in the rest of the zones, it
decreases. During the time interval of 3,000-3,600 s of the decay phase of the fire, the
lower-zone temperature is slightly increased. A more “stable” behaviour is observed
CFD and FEM
b c d h i j
900 e f g 900
k l
analysis
800 800
700 700
600 600
500 500
400 400
1183
300 300
200 200
100 100
0 0
1,200
1,500
1,800
2,100
2,400
2,700
3,000
3,300
3,600
1,200
2,700
1,500
1,800
2,100
2,400
3,000
3,300
3,600
0
300
600
900
0
300
600
900
time (sec) time (sec)
Downloaded by Doctor Daphne Pantousa At 07:58 02 August 2017 (PT)
1,000 1,000
b c d h
900 900 i
e f g
800 800 j
k
700 700
l
600 600
500 500
400 400
300 300
Figure 16.
200 200 Lower- and upper-
100 100 layer temperature
0 0 evolution with time
2,100
2,400
1,200
1,500
1,800
2,700
3,000
3,300
3,600
0
300
600
900
1,800
1,200
1,500
2,100
2,400
2,700
3,000
3,300
3,600
0
300
600
900
Figure 17.
Temperature
distribution inside of
the fire-compartment
at different sections
for SC-25A
EC
34,4
1184
Figure 18.
Downloaded by Doctor Daphne Pantousa At 07:58 02 August 2017 (PT)
Temperature
distribution inside the
fire-compartment at
different sections for
SC-50A
Figure 19.
Temperature
distribution inside/
outside of the fire-
compartment at
different sections for
SC-50C
during the steady burning stage in all virtual zones, except Zones b and l. These regions
present strong fluctuations and this can be attributed to the fact that the zones are located
at the boundaries of the enclosure. In the rest zones, the layer height varies between 1 and
1.5 m. The previous results indicate that the differences between the temperatures that
are recorded at the distinct layers are considerable. This can be verified through the time
evolution of the gas-temperature of both layers, as it is illustrated in Figure 21. The
maximum temperatures are recorded in the region that includes the virtual Zones f, g, h, i
and j.
CFD and FEM
T (⁰C)
T (⁰C)
zint (m)
zint (m)
1,000 3.5 1,000 3.5
virtual zone b virtual zone c
900
3.0
900
3.0 analysis
800 800 Steady burning stage
700 2.5 700 2.5
600 zint/av -2.5m 600
2.0 zint/av -1.8m 2.0
500 500
400 1.5 400 1.5
Steady burning stage
300 1.0 300 1.0 1185
200 200
0.5 0.5
100 100
0 0.0 0 0.0
2,400
2,700
300
600
900
1,200
1,500
1,800
2,100
2,400
2,700
3,000
3,300
3,600
300
600
900
1,200
1,500
1,800
2,100
3,000
3,300
3,600
0
0
time (sec) time (sec)
Lower layer Upper layer Layer height Lower layer Upper layer Layer height
Downloaded by Doctor Daphne Pantousa At 07:58 02 August 2017 (PT)
T (⁰C)
T (⁰C)
zint (m)
zint (m)
1,000 3.5 1,000 3.5
virtual zone d virtual zone e
900 900
3.0 3.0
800 Steady burning stage 800 Steady burning stage
700 2.5 700 2.5
600 2.0 600 2.0
500 500
zint/av -1.2m 1.5 1.5
400 400 zint/av -1.0m
300 1.0 300 1.0
200 200
0.5 0.5
100 100
0 0.0 0 0.0
2,700
1,200
1,500
1,800
2,100
2,400
2,700
3,000
3,300
3,600
1,200
1,500
2,400
1,800
2,100
3,000
3,300
3,600
300
600
900
300
600
900
0
T (⁰C)
zint (m)
zint (m)
1,000 3.5 1,000 3.5
virtual zone f virtual zone g
900 900
3.0 3.0
800 Steady burning stage 800 Steady burning stage
700 2.5 700 2.5
600 2.0 600 2.0
500 500
400 1.5 400 zint/av -1.0m 1.5
zint/av -1.0m
300 1.0 300 1.0
200 200
0.5 0.5
100 100
0 0.0 0 0.0 Figure 20.
Upper – lower
1,200
1,500
1,800
2,100
2,400
2,700
3,000
3,300
3,600
1,200
1,500
2,700
1,800
2,100
2,400
3,000
3,300
3,600
300
600
900
300
600
900
0
temperature and
time (sec) time (sec)
Lower layer Upper layer Layer height Lower layer Upper layer Layer height layer height at
different virtual zones
for SC-25B
(continued)
EC
T (⁰C)
T (⁰C)
zint (m)
zint (m)
1,000 3.5 1,000 3.5
virtual zone h virtual zone i
34,4 900
Steady burning stage
3.0
900 Steady burning stage 3.0
800 800
700 2.5 700 2.5
600 2.0 600 2.0
500 500 zint/av -1.0m
zint/av -1.0m 1.5 1.5
400 400
1186 300 1.0 300 1.0
200 200
0.5 0.5
100 100
0 0.0 0 0.0
1,200
3,600
300
600
900
1,500
1,800
2,100
2,400
2,700
3,000
3,300
3,600
300
600
900
1,200
1,500
1,800
2,100
2,400
2,700
3,000
3,300
0
0
T (⁰C)
T (⁰C)
zint (m)
zint (m)
1,000 3.5 1,000 3.5
virtual zone j virtual zone k
900 900
3.0 Steady burning stage 3.0
800 Steady burning stage 800
700 2.5 700 2.5
600 2.0 600 2.0
500 500
400 zint/av -1.1m 1.5 400 1.5
300 1.0 300 1.0
200 200 zint/av -1.0m
0.5 0.5
100 100
0 0.0 0 0.0
1,200
1,500
1,800
2,100
2,400
2,700
3,000
3,300
3,600
1,200
1,500
1,800
2,100
2,400
2,700
3,000
3,300
3,600
300
600
900
300
600
900
0
zint (m)
1,000 3.5
virtual zone l
900
Steady burning stage 3.0
800 HRR
160,000 (KW) Steady burning stage
700 2.5 SC-25B
600 140,000
2.0
500 120,000
400 1.5 100,000
300 1.0 80,000
200 zint/av -0.9m 60,000
0.5
100
40,000
0 0.0
20,000
1,200
1,500
1,800
2,100
2,400
2,700
3,000
3,300
3,600
300
600
900
0
time(sec)
0
time (sec)
0
300
600
900
1,500
3,300
1,200
1,800
2,100
2,400
2,700
3,000
3,600
Figure 20.
Lower layer Upper layer Layer height
6. Conclusions
An FSI (fire structure interface) model is presented in this study aiming to overcome the
difficulties which arise due to the strong spatial non-homogeneity and the intense time
variation of the gas-temperature profile in the fire-compartment. The “dual-layer” model is
developed to “condense” the results (concerning the spatial and temporal gas-temperature
CFD and FEM
T (⁰C)
T (⁰C)
zint (m)
zint (m)
1,000 3.5 1,000 3.5
virtual zone b virtual zone c
900 900
800 Steady burning stage 3.0
800 Steady burning stage 3.0 analysis
700 2.5 700 2.5
600 2.0 600 2.0
500 500
400 1.5 400 1.5
300 1.0 300 1.0 1187
200 200
0.5 0.5
100 100
0 0.0 0 0.0
1,200
1,500
1,800
2,100
2,400
2,700
3,000
3,300
3,600
1,200
1,500
1,800
2,100
2,400
2,700
3,000
3,300
3,600
0
300
600
900
0
300
600
900
T (⁰C)
T (⁰C)
zint (m)
zint (m)
0
300
600
900
1,200
1,500
1,800
2,100
2,400
2,700
3,000
3,300
3,600
0
300
600
900
zint (m)
zint (m)
0
300
600
900
1,200
1,500
1,800
2,100
2,400
2,700
3,000
3,300
3,600
0
300
600
900
temperature and
time (sec) time (sec) layer height at
Lower layer Upper layer Layer height Lower layer Upper layer Layer height different virtual zones
for SC-75
(continued)
EC
T (⁰C)
T (⁰C)
zint (m)
zint (m)
1,000 3.5 1,000 3.5
virtual zone h virtual zone i
900 900
34,4 800
Steady burning stage 3.0
800 Steady burning stage 3.0
1,200
1,500
1,800
2,100
2,400
2,700
3,000
3,300
3,600
0
300
600
900
0
300
600
900
time (sec) time (sec)
Lower layer Upper layer Layer height Lower layer Upper layer Layer height
Downloaded by Doctor Daphne Pantousa At 07:58 02 August 2017 (PT)
T (⁰C)
T (⁰C)
zint (m)
zint (m)
1,000 3.5 1,000 3.5
virtual zone j virtual zone k
900 900
Steady burning stage 3.0 Steady burning stage 3.0
800 800
700 2.5 700 2.5
600 2.0 600 2.0
500 500
400 1.5 400 1.5
300 1.0 300 1.0
200 200
0.5 0.5
100 100
0 0.0 0 1,200 0.0
1,500
1,800
2,100
2,400
2,700
3,000
3,300
3,600
1,200
1,500
1,800
2,100
2,400
2,700
3,000
3,300
3,600
0
0
300
600
900
300
600
900
zint (m)
1,000 3.5
virtual zone l
900 HRR
Steady burning stage 3.0 250,000
800 (KW)
2.5 Steady burning stage
700
200,000 SC-75
600 2.0
500
1.5 150,000
400
300 1.0 100,000
200
0.5
100 50,000
0 0.0 time(sec)
1,200
1,500
1,800
2,100
2,400
2,700
3,000
3,300
3,600
0
300
600
900
0
1,200
1,500
1,800
2,100
2,400
2,700
3,000
3,300
3,600
0
300
600
900
time (sec)
Figure 21. Lower layer Upper layer Layer height
evolution) and the fire-compartment is divided into 11 virtual zones. The model is based on
the idea of the “two-zone” models, as they are proposed in EN 1991-1-2 and adopts the
assumption that each virtual zone is further divided into two layers of uniform temperature:
the upper (hotter) layer and the lower (colder) layer. It is concluded that the “dual-layer”
post-processing model can describe effectively the temperature distribution in the fire- CFD and FEM
compartment. The advantage of the developed methodology lies in the fact that the analysis
phenomenon is depicted in a simple way through three different variables which are the
temperature of the upper and the lower layers and the layer height.
References
Babrauskas, V. (2002), “Ignition of wood: a review of the state of the art”, Journal of Fire Protection 1189
Engineering, Vol. 12, pp. 163-189.
Dembele, S., Rosario, R., Wen, J., Paul, W. and Stuart, D. (2008), “Simulation of glazing behavior in
fires using computational fluid dynamics and spectral radiation modeling”, Fire Safety
Science, Vol. 9, pp. 1029-1039.
Fong, Y.Y. and Fong, N.K. (2003), “Scale modelling of smoke movement in linear atrium”, International
Downloaded by Doctor Daphne Pantousa At 07:58 02 August 2017 (PT)
ASFE, Application of Structural Fire Engineering, in Prague, Czech Republic, pp. 131-137
Zografopoulou, K., Pantousa, D. and Mystakidis, E. (2013b), “The fire – after – earthquake event in an
industrial building, part 1: simulation of the natural fire”, Proceedings of 10th HSTAM
International Congress on Mechanics Chania, Greece, pp. 611-666.
Further reading
European Committee for Standardization (EN 1991-1-2) (2001), Eurocode 1, Actions on Structures
Exposed to Fire – Part 1-2: General actions – Structural Fire Design.
European Committee for Standardization (EN 1993-1-2) (2003), Eurocode 3, Design of Steel Structures-
Part 1-2: General Rules – Structural Fire Design.
Corresponding author
Daphne Pantousa can be contacted at: dpantousa@gmail.com
For instructions on how to order reprints of this article, please visit our website:
www.emeraldgrouppublishing.com/licensing/reprints.htm
Or contact us for further details: permissions@emeraldinsight.com