Download as pdf or txt
Download as pdf or txt
You are on page 1of 43

Table 18.

7 Continued

Reflectances ceiling/walls/floor Time / years 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0

Environment Room surface maintenance factor


0.70/0.30/0.20 Very clean 0.98 0.97 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96
Clean 0.95 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.93
Normal 0.90 0.88 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87
Dirty 0.82 0.80 0.80 0.80 0.80 0.80 0.80 0.80 0.80 0.80 0.80 0.80
0.50/0.70/0.20 Very clean 0.97 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95 0.95
Clean 0.93 0.91 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90
Normal 0.86 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83
Dirty 0.76 0.74 0.74 0.74 0.74 0.74 0.74 0.74 0.74 0.74 0.74 0.74
0.50/0.50/0.20 Very clean 0.97 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96 0.96
Clean 0.94 0.93 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92
Normal 0.89 0.87 0.86 0.86 0.86 0.86 0.86 0.86 0.86 0.86 0.86 0.86
Dirty 0.81 0.79 0.79 0.79 0.79 0.79 0.79 0.79 0.79 0.79 0.79 0.79
0.50/0.30/0.20 Very clean 0.98 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97 0.97
Clean 0.96 0.95 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.94
Normal 0.92 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90
Dirty 0.85 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84

289
Chapter Eighteen: Predicting maintenance factor
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781
Chapter Eighteen: Predicting maintenance factor

290
Table 18.8 Room surface maintenance factor (RSMF) for indirect flux distribution

Reflectances ceiling/walls/floor Time / years 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0

Environment Room surface maintenance factor


0.80/0.70/0.20 Very clean 0.93 0.91 0.90 0.90 0.90 0.90 0.89 0.89 0.89 0.89 0.89 0.89
Clean 0.86 0.82 0.81 0.81 0.81 0.81 0.81 0.81 0.81 0.81 0.81 0.81
Normal 0.72 0.67 0.66 0.66 0.66 0.66 0.66 0.66 0.66 0.66 0.66 0.66
Dirty 0.54 0.50 0.49 0.49 0.49 0.49 0.49 0.49 0.49 0.49 0.49 0.49
0.80/0.50/0.20 Very clean 0.94 0.93 0.92 0.92 0.92 0.91 0.91 0.91 0.91 0.91 0.91 0.91
Clean 0.88 0.85 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84
Normal 0.76 0.72 0.71 0.71 0.71 0.71 0.71 0.71 0.71 0.71 0.71 0.71
Dirty 0.59 0.55 0.55 0.55 0.55 0.55 0.55 0.55 0.55 0.55 0.55 0.55
0.80/0.30/0.20 Very clean 0.96 0.94 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.93
Clean 0.90 0.88 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87
Normal 0.80 0.76 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75
Dirty 0.64 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60
0.70/0.70/0.20 Very clean 0.93 0.91 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90
Clean 0.86 0.83 0.82 0.81 0.81 0.81 0.81 0.81 0.81 0.81 0.81 0.81
Normal 0.73 0.68 0.67 0.67 0.67 0.67 0.67 0.67 0.67 0.67 0.67 0.67
Dirty 0.55 0.51 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
0.70/0.50/0.20 Very clean 0.95 0.93 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92
Clean 0.89 0.86 0.85 0.85 0.84 0.84 0.84 0.84 0.84 0.84 0.84 0.84
Normal 0.77 0.73 0.72 0.72 0.72 0.72 0.72 0.72 0.72 0.72 0.72 0.72
Dirty 0.60 0.56 0.55 0.55 0.55 0.55 0.55 0.55 0.55 0.55 0.55 0.55
0.70/0.30/0.20 Very clean 0.96 0.94 0.94 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.93 0.93
Clean 0.91 0.88 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87
Normal 0.80 0.77 0.76 0.76 0.76 0.76 0.76 0.75 0.75 0.75 0.75 0.75
Dirty 0.65 0.61 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60 0.60
Table 18.8 Continued

Reflectances ceiling/walls/floor Time / years 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0

Environment Room surface maintenance factor


0.50/0.70/0.20 Very clean 0.94 0.92 0.91 0.91 0.91 0.91 0.91 0.91 0.91 0.91 0.91 0.91
Clean 0.87 0.84 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83 0.83
Normal 0.75 0.70 0.69 0.69 0.69 0.69 0.69 0.69 0.69 0.69 0.69 0.69
Dirty 0.57 0.52 0.52 0.52 0.52 0.52 0.52 0.52 0.52 0.52 0.52 0.52
0.50/0.50/0.20 Very clean 0.95 0.93 0.93 0.93 0.92 0.92 0.92 0.92 0.92 0.92 0.92 0.92
Clean 0.90 0.87 0.86 0.86 0.85 0.85 0.85 0.85 0.85 0.85 0.85 0.85
Normal 0.78 0.74 0.73 0.73 0.73 0.73 0.73 0.73 0.73 0.73 0.73 0.73
Dirty 0.61 0.57 0.57 0.57 0.57 0.57 0.57 0.57 0.57 0.57 0.57 0.57
0.50/0.30/0.20 Very clean 0.96 0.95 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.94 0.94
Clean 0.91 0.89 0.88 0.88 0.88 0.88 0.88 0.88 0.88 0.88 0.88 0.88
Normal 0.81 0.78 0.77 0.77 0.77 0.77 0.77 0.77 0.77 0.77 0.77 0.77
Dirty 0.66 0.62 0.61 0.61 0.61 0.61 0.61 0.61 0.61 0.61 0.61 0.61

291
Chapter Eighteen: Predicting maintenance factor
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781
Chapter Eighteen: Predicting maintenance factor

18.6 Ingress protection (IP) classes


The Ingress Protection (IP) system, see BS EN 60529 (BSI, 1992), classifies luminaires according
to the degree of protection provided against the ingress of foreign bodies, dust and moisture.
The degree of protection is indicated by the letters IP followed by two numbers. The first
number indicates the degree of protection against the ingress of foreign bodies and dust. The
second indicates the protection against the ingress of moisture. Table 18.9 shows the degree of
protection indicated by each number. Using this table, it can be seen that a luminaire classified as
IP55 is dust protected and able to withstand water jets.

Table 18.9 IP Classification of luminaires

First Degree of protection Second Degree of protection


number number

0 Not protected 0 Not protected

1 Protected against solid objects 1 Protected against dripping water


greater than 50 mm

2 Protected against solid objects 2 Protected against dripping water


greater than 12 mm when tilted up to 15 degrees

3 Protected against solid objects 3 Protected against spraying water


greater than 2.5 mm

4 Protected against solid objects 4 Protected against splashing


greater than 1.0 mm

5 Dust-protected 5 Protected against water jets

6 Dust-tight 6 Protected against heavy seas

7 Protected against the effects of


immersion

8 Protected against submersion to a


specified depth

292
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781
Chapter Nineteen: Glossary
Chapter 19: Glossary
The following definitions for lighting terms are taken from BS EN 12665: 2011 (BSI, 2011b).
The list includes some definitions that are not used within the SLL Code, however, some
specialised terms, mainly relating to tunnel lighting, are not given in this glossary. Note that for
some terms, an additional or alternative definition is given.

Absence factor (FA)


Factor indicating the proportion of time that a space is unoccupied

Absorptance
Ratio of the luminous flux absorbed in a body to the luminous flux incident on it

Accommodation
Adjustment of the dioptric power of the crystalline lens by which the image of an object, at a
given distance, is focused on the retina

or

Adjustment of the power of the lens of the eye for focusing an image of an object on the retina

Acuity
See visual acuity

Annual operating time (to)


Number of hours per annum for which the lamps are operating (unit: h)

Atmospheric luminance (Latm)


Light veil as a result of the scatter in the atmosphere expressed as a luminance (unit: cd·m–2)

Average illuminance (Ē)


Illuminance averaged over the specified surface (unit: lx)

Average luminance ( L )
Luminance averaged over the specified surface or solid angle (unit: cd·m–2)

Background area
Area in the workplace adjacent to the immediate surrounding area

Ballast
Device connected between the supply and one or more discharge lamps which serves mainly to
limit the current of the lamp(s) to the required value
Note: A ballast may also include means for transforming the supply voltage, correcting the power factor and,
either alone or in combination with a starting device, provide the necessary conditions for starting the lamp(s)

Ballast lumen factor (FBallast)


Ratio of the luminous flux emitted by a reference lamp when operated with a particular
production ballast to the luminous flux emitted by the same lamp when operated with its
reference ballast
Note: Ballast lumen factor is sometimes signified by the abbreviation BLF
293
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781

Brightness
Chapter Nineteen: Glossary

Attribute of a visual sensation according to which an area appears to emit more or less light
Note: obsolete term – luminosity

Brightness contrast
Subjective assessment of the difference in brightness between two or more surfaces seen
simultaneously or successively

Built-in luminaire
Fixed luminaire installed into structure or equipment to provide illumination

Carriageway
Part of the road normally used by vehicular traffic

Chromaticity
Property of a colour stimulus defined by its chromaticity coordinates, or by its dominant or
complementary wavelength and purity taken together
See also CIE 15: 2004 (CIE, 2004b)

Chromaticity coordinates
Ratio of each of a set of three tristimulus values to their sum
Note 1: As the sum of the three chromaticity coordinates equals 1, two of them are sufficient to define a
chromaticity
Note 2: In the CIE standard colorimetric systems, the chromaticity coordinates are presented by the symbols x,
y, z and x10, y10, z10

CIE 1974 general colour rendering index (Ra)


Mean of the CIE 1974 special colour rendering indices for a specified set of eight test colour
samples

or

Value intended to specify the degree to which objects illuminated by a light source have an
expected colour relative to their colour under a reference light source

Note: Ra is derived from the colour rendering indices for a specified set of 8 test colour samples. Ra has a
maximum of 100, which generally occurs when the spectral distributions of the light source and the reference
light source are substantially identical

Circuit luminous efficacy of a source (c)


Quotient of the luminous flux emitted by the power absorbed by the source and associated
circuits (unit: lm·W–1)

Cold spot
Coldest point on lamp surface

Colorimeter
Instrument for measuring colorimetric quantities, such as the tristimulus values of a colour
stimulus

294
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781
Colour contrast

Chapter Nineteen: Glossary


Subjective assessment of the difference in colour between two or more surfaces seen
simultaneously or successively

Colour rendering
Effect of an illuminant on the colour appearance of objects by conscious or subconscious
comparison with their colour appearance under a reference illuminant

For design purposes, colour rendering requirements shall be specified using the general colour
rendering index and shall take one of the following values of Ra: 20; 40; 60; 80; 90

Colour rendering index


See CIE 1974 general colour rendering index

Colour stimulus
Visible radiation entering the eye and producing a sensation of colour, either chromatic or
achromatic

Colour temperature (Tc)


Temperature of a Planckian radiator whose radiation has the same chromaticity as that of a given
stimulus (unit: K)
Note: The reciprocal colour temperature is also used, unit: K–1

Constant illuminance factor (FC)


Ratio of the average input power over a given time to the initial installed power to the luminaire

Contrast
1. In the perceptual sense: assessment of the difference in appearance of two or more parts of a
field seen simultaneously or successively (hence: brightness contrast, lightness contrast, colour
contrast, simultaneous contrast, successive contrast, etc)

2. In the physical sense: quantity intended to correlate with the perceived brightness contrast,
usually defined by one of a number of formulae which involve the luminances of the stimuli
considered, for example: ∆L/L near the luminance threshold, or L1/L2 for much higher
luminances

Contrast revealing coefficient (qc)


Quotient between the luminance (L) of the road surface, and the vertical illuminance (Ev) at that
point (unit: cd·m–2·lx–1)

L
qc =
Ev
where:
qc is the contrast revealing coefficient;
L is the luminance of the road surface at the point;
Ev is the vertical illuminance at the point

Control gear
Components required to control the electrical operation of the lamp(s)

295
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781

Note: Control gear may also include means for transforming the supply voltage, correcting the power factor
Chapter Nineteen: Glossary

and, either alone or in combination with a starting device, provide the necessary conditions for starting the
lamp(s)

Correction factor
Factor to modify the luminaire data as presented on a particular photometric data sheet to those
of similar luminaires
Note: Examples are ballast lumen factor, length, lumen corrections

Correlated colour temperature (Tcp)


Temperature of the Planckian radiator whose perceived colour most closely resembles that of a
given stimulus at the same brightness and under specified viewing conditions (unit: K)

Note 1: The recommended method of calculating the correlated colour temperature of a stimulus is to de-
termine on a chromaticity diagram the temperature corresponding to the point on the Planckian locus that is
intersected by the agreed isotemperature line containing the point representing the stimulus (see CIE Publication
No 15; CIE, 2004b)

Note 2: Reciprocal correlated colour temperature is used rather than reciprocal colour temperature whenever
correlated colour temperature is appropriate

Cosine correction
Correction of a detector for the influence of the incident direction of the light

Note: For the ideal detector, the measured illuminance is proportional to the cosine of the angle of incidence of
the light. The angle of incidence is the angle between the direction of the light and the normal to the surface of
the detector

Critical flicker frequency


See fusion frequency

Curfew
Time period during which stricter requirements (for the control of obtrusive light) will apply

Note: It is often a condition of use of lighting applied by a government controlling authority, usually the local
government

Cut-off
Technique used for concealing lamps and surfaces of high luminance from direct view in order to
reduce glare

Note: In public lighting, distinction is made between full-cut-off luminaires, semi-cut-off luminaires and
non-cut-off luminaires

Cut-off angle (of a luminaire)


Angle, measured up from nadir, between the vertical axis and the first line of sight at which the
lamps and the surfaces of high luminance are not visible (unit: degree)

Cylindrical illuminance (at a point, for a direction) (Ez)


Total luminous flux falling on the curved surface of a very small cylinder located at the specified
point divided by the curved surface area of the cylinder (unit: lx)
296
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781
Daylight

Chapter Nineteen: Glossary


Visible part of global solar radiation

Daylight dependency factor (FD)


Level of efficiency that a control system or control strategy achieves in exploiting the saving
potential of daylight in a space

Daylight factor (D or DF)


Ratio of the illuminance at a point on a given plane due to the light received directly or indirectly
from a sky of assumed or known luminance distribution, to the illuminance on a horizontal plane
due to an unobstructed hemisphere of this sky, excluding the contribution of direct sunlight to
both illuminances

Note 1: Glazing, dirt effects, etc are included

Note 2: When calculating the lighting of interiors, the contribution of direct sunlight needs to be considered
separately

Daylight time usage (tD)


Annual operating hours during the daylight time, measured in hours (unit: h)

Daylight screens/daylight louvres


Devices that transmit (part of) the ambient daylight

Design speed
Speed adopted for a particular stated purpose in designing a road (unit: km·h–1)

Diffuse sky radiation


That part of solar radiation which reaches the earth as a result of being scattered by the air
molecules, aerosol particles, cloud particles or other particles

Diffused lighting
Lighting in which the light on the working plane or on an object is not incident predominantly
from a particular direction

Direct lighting
Lighting by means of luminaires having a distribution of luminous intensity such that the
fraction of the emitted luminous flux directly reaching the working plane, assumed to be
unbounded, is 90 to 100 per cent

Direct solar radiation


That part of the extraterrestrial solar radiation which, as a collimated beam, reaches the earth’s
surface after selective attenuation by the atmosphere

Directional lighting
Lighting in which the light on the working plane or on an object is incident predominantly from
a particular direction

Disability glare
Glare that impairs the vision of objects without necessarily causing discomfort. Disability glare
can be produced directly or by reflection
297
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781

Discomfort glare
Chapter Nineteen: Glossary

Glare that causes discomfort without necessarily impairing the vision of objects. Discomfort glare
can be produced directly or by reflection

Display screen equipment


Alphanumeric or graphic display screen, regardless of the display process employed

Note: Display screen equipment is sometimes signified by the abbreviation DSE

Diversity (luminance, illuminance) (Ud) (Extreme uniformity)


Ratio of minimum illuminance (luminance) to maximum illuminance (luminance) on (of) a
surface
See also uniformity

Downward light output ratio (of a luminaire) (RDLO)


Ratio of the downward flux of the luminaire, measured under specified practical conditions with
its own lamps and equipment, to the sum of the individual luminous fluxes of the same lamps
when operated outside the luminaire with the same equipment, under specified conditions

Note 1: The luminaire attitude should be declared so that appropriate corrections to the DLOR can be made
if, in application, the installed attitude is different

Note 2: Downward light output ratio is sometimes signified by the abbreviation DLOR

Efficacy
See luminous efficacy of a source

Emergency ballast lumen factor (FEBallast)


Ratio of the luminous flux of the lamp, operated with ballast under test, at the lowest voltage
which can occur during emergency mode, after failure of the normal supply (for the appropri-
ate start time for the application requirement) and continuously to the end of rated duration of
operation, to the luminous flux of the same lamp operated with the appropriate reference ballast
supplied at its rated voltage and frequency

FEBallast = FBallast × Fmin

where:
FEBallast is the emergency ballast lumen factor;
FBallast is the ballast lumen factor;
Fmin is the worst case of the emergency time-dependent factors

Emergency escape lighting


Part of emergency lighting that provides illumination for visibility for people leaving a location or
attempting to terminate a potentially dangerous process before doing so

Emergency exit
Way out that is intended to be used during an emergency

Emergency lamp flux


See practical emergency lamp flux

298
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781
Emergency lane (hard shoulder)

Chapter Nineteen: Glossary


Lane parallel to the traffic lane(s) provided for emergency and/or broken-down vehicles only

Emergency lighting
Lighting provided for use when the supply to the normal lighting fails

Emergency lighting charge time (tem)


Operating hours during which the emergency lighting batteries are being charged (unit: h)

Emergency lighting charging power (Pei)


Input power to the charging circuit of emergency luminaires when the lamps are not operating
(unit: W)

Emergency lighting, total installed charging power


See total installed charging power of the emergency lighting luminaires in the room or zone

Energy consumption used for illumination (WL,t)


Energy consumed in period t, by the luminaires when the lamps are operating, to fulfil the
illumination function and purpose in the building (unit: kW·h)

Equivalent veiling luminance (for disability glare or veiling reflections) (Lve)


Luminance that, when added by superposition to the luminance of both the adapting background
and the object, makes the luminance threshold or the luminance difference threshold the same
under the two following conditions: (1) glare present, but no additional luminance; (2) additional
luminance present, but no glare (unit: cd·m–2)

Escape route
Route designated for escape in the event of an emergency

Escape route lighting


Part of emergency escape lighting provided to ensure that the means of escape can be effectively
identified and safely used when the location is occupied

Essential data
Lamp and luminaire data required for the verification of conformity to requirements

Externally illuminated safety sign


Safety sign that is illuminated, when it is required, by an external source

Extreme uniformity
See diversity

Flicker
Impression of unsteadiness of visual sensation induced by a light stimulus whose luminance or
spectral distribution fluctuates with time

Flicker frequency
See fusion frequency

299
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781

Floodlighting
Chapter Nineteen: Glossary

Lighting of a scene or object, usually by projectors, in order to increase considerably its


illuminance relative to its surroundings

Flux
See luminous flux, rated lamp luminous flux

Fmin
See minimum value emergency factor

Fusion frequency
Critical flicker frequency (for a given set of conditions)
Frequency of alternation of stimuli above which flicker is not perceptible (unit: Hz)

General colour rendering index


See CIE 1974 general colour rendering index

General lighting
Substantially uniform lighting of an area without provision for special local requirements

Glare
Condition of vision in which there is discomfort or a reduction in the ability to see details or
objects, caused by an unsuitable distribution or range of luminance, or extreme contrasts

See also disability glare and discomfort glare

Glare rating limit (RGL)


Upper limit of glare by the CIE Glare Rating system

Global solar radiation


Combined direct solar radiation and diffuse sky radiation

Grid points for measurement and calculation


Arrangement of calculation and measurement points and their number in each dimension of the
reference surface or plane

Hemispherical illuminance (at a point) (Ehs)


Total luminous flux falling on the curved surface of a very small hemisphere located at the
specified point divided by the curved surface area of the hemisphere (unit: lx)

High risk task area lighting


Part of emergency escape lighting that provides illumination for visibility for people involved in a
potentially dangerous process or situation and facilitates safe termination of activities

Note: In sports lighting, it is referred to as ‘Safety lighting for participants’

Illuminance (at a point of a surface) (E)


Quotient of the luminous flux dW incident on an element of the surface containing the point, by
the area dA of that element (unit: lx = lm·m–2)

300
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781
Note 1: Equivalent definition: Integral, taken over the hemisphere visible from the given point, of the

Chapter Nineteen: Glossary


expression L⋅ cosh ⋅ dV , where L is the luminance at the given point in the various directions of the incident
elementary beams of solid angle dΩ, and θ is the angle between any of these beams and the normal to the surface
at the given point

dV
dA 2p∫sr
E= = L coshdV

where
E is the illuminance at a point on a surface;
L is the luminance at the given point in the various directions of the incident elementary beams of
solid angle dΩ;
θ is the angle between an incident beam and the normal to the surface at the given point;
dΩ is the solid angle

Note 2: The orientation of the surface may be defined, e.g. horizontal, vertical, hence horizontal illuminance,
vertical illuminance

See also average illuminance, cylindrical illuminance, hemispherical illuminance, initial illumi-
nance, maintained illuminance, maximum illuminance, minimum illuminance, semi-cylindrical
illuminance and spherical illuminance

Illuminance meter
Instrument for measuring illuminance

Immediate surrounding area


See surrounding area

Indirect lighting
Lighting by means of luminaires having a distribution of luminous intensity such that the
fraction of the emitted luminous flux directly reaching the working plane, assumed to be
unbounded, is 0 to 10 per cent

Initial average luminance ( Li )


Average luminance when the installation is new (unit: cd·m–2)

Initial illuminance (Ēi)


Average illuminance on the specified surface when the installation is new (unit: lx)

Initial luminous flux


See rated luminous flux

Installed loading
Installed power of the lighting installation per unit area (for interior and exterior areas) or per
unit length (for road lighting) (unit: W·m–2 (for areas) or kW·km–1 (for road lighting))

Integral lighting system (of a machine)


Lighting system consisting of lamp(s), luminaire(s) and associated mechanical and electrical
control devices which forms a permanent part of the machine, designed to provide illumination
in and/or at the machine

301
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781

Intensity
Chapter Nineteen: Glossary

See luminous intensity

Intensity distribution
See luminous intensity distribution

Internally illuminated safety sign


Safety sign that is illuminated, when it is required, by an internal source

Lamp
Source made in order to produce an optical radiation, usually visible

Note: This term is also sometimes used for certain types of luminaires

Lamp code
Any combination of letters and numbers by which the lamp type is identified

Lamp dimensions
All dimensions of the lamp that are relevant for the luminaire

Lamp lumen maintenance factor (FLLM)


Ratio of the luminous flux of a lamp at a given time in its life to the initial luminous flux

Note: Lamp lumen maintenance factor is sometimes signified by the abbreviation LLMF

Lamp luminous flux


See rated luminous flux

Lamp survival factor (FLS)


Fraction of the total number of lamps which continue to operate at a given time under defined
conditions and switching frequency

Note: Lamp survival factor is sometimes signified by the abbreviation LSF

Lamp wattage
See nominal lamp wattage

LENI
See Lighting Energy Numeric Indicator

Life of lighting installation


Period after which the installation cannot be restored to satisfy the required performance because
of non-recoverable deteriorations

Light centre
Point used as origin for photometric measurements and calculations

Light loss factor


See maintenance factor

302
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781
Light output ratio (of a luminaire) (RLO)

Chapter Nineteen: Glossary


Ratio of the total flux of the luminaire, measured under specified practical conditions with its
own lamps and equipment, to the sum of the individual luminous fluxes of the same lamps when
operated outside the luminaire with the same equipment, under specified conditions

Note 1: For luminaires using incandescent lamps only, the optical light output ratio and the light output ratio
are the same in practice

Note 2: Light output ratio is sometimes signified by the abbreviation LOR

See also downward light output ratio and upward light output ratio

Light output ratio working (of a luminaire) (RLOW)


Ratio of the total flux of the luminaire, measured under specified practical conditions with its
own lamps and equipment, to the sum of the individual luminous fluxes of the same lamps when
operating outside the luminaire with a reference ballast, under reference conditions

Light source
See source

Light source colour


The colour of a light source can be expressed by its correlated colour temperature

Loading
See installed loading

Lighting Energy Numeric Indicator (LENI)


A numerical indicator that expresses the total amount of energy used by a lighting system per
square metre per year

Local lighting
Lighting for a specific visual task, additional to and controlled separately from the general lighting

Localised lighting
Lighting designed to illuminate an area with a higher illuminance at certain specified positions,
for instance, those at which work is carried out

Longitudinal uniformity (of road surface luminance of a carriageway) (Ul)


Ratio of the minimum to the maximum road surface luminance found in a line in the centre
along a driving lane

Note: The longitudinal uniformity is considered for each driving lane

Louvres
See daylight screens

Luminaire
Apparatus which distributes, filters or transforms the light transmitted from one or more lamps
and which includes, except the lamps themselves, all of the parts necessary for fixing and protect-
ing the lamps and, where necessary, circuit auxiliaries together with the means for connecting
them to the electric supply
303
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781

Luminaire code
Chapter Nineteen: Glossary

Any combination of letters and numbers by which the luminaire type is identified

Luminaire maintenance factor (FLM)


Ratio of the light output ratio of a luminaire at a given time to the initial light output ratio

Note: Luminaire maintenance factor is sometimes signified by the abbreviation LMF

Luminaire luminous efficacy (l)


Quotient of the luminous flux emitted by the luminaire by the power absorbed by the lamp and
associated circuits of the luminaire (unit: lm·W–1)

Luminaire parasitic energy consumption (WP,t)


Parasitic energy consumed in period t, by the luminaire emergency lighting charging circuit
plus the standby control system controlling the luminaires when the lamps are not operating
(unit: kW·h)

Luminaire parasitic power (Ppi)


Input power consumed by the charging circuit of emergency lighting luminaires and the standby
power for automatic controls in the luminaire when lamps are not operating (unit: W)

Ppi = Pci + Pei

where
Ppi is the luminaire parasitic power consumed by the luminaire with the lamps off,
expressed in watts;
Pci is the parasitic power of the controls only during the time with the lamps off,
expressed in watts;
Pei is the emergency lighting charging power, expressed in watts

Luminaire power (Pi)


Input power consumed by the lamp(s), control gear and control circuit in or associated with the
luminaire, which includes any parasitic power when the luminaire is turned on (unit: W)

Note: The rated luminaire power (Pi) for a specific luminaire may be obtained from the luminaire
manufacturer

Luminance (in a given direction, at a given point of a real or imaginary surface) (L)
Quantity defined by the equation (unit: cd·m–2 = lm·m–2·sr–1)
dW
L=
dA cos hdV
where
L is the luminance in a given direction or at a given point of a surface;
dW is the luminous flux transmitted by an elementary beam passing through the given
point and propagating in the solid angle dV containing the given direction;
dA is the area of a section of that beam containing the given point;
dV is the solid angle;
h is the angle between the normal to that section and the direction of the beam

Luminance shall be specified as maintained luminance and shall take one of the following values:
1 × 10N cd·m–2; 1.5 × 10N cd·m–2; 2.0 × 10N cd·m–2; 3.0 × 10N cd·m–2; 5.0 × 10N cd·m–2;
7.5 × 10N cd·m–2 (where N is an integer)
304
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781
The area over which the luminance is to be calculated or measured shall be specified

Chapter Nineteen: Glossary


See also atmospheric luminance, average luminance, equivalent luminance, initial luminance,
interior luminance, maintained luminance, maximum luminance and minimum luminance

Luminance contrast
Photometric quantity intended to correlate with brightness contrast, usually defined by one of a
number of equations which involve the luminances of the stimuli considered

Note: Luminance contrast can be defined as luminance ratio

L2 (usually for successive stimuli)


C1 =
L1
or by the following equation:

L2 − L1 (usually for surfaces viewed simultaneously)


C2 =
L1
When the areas of different luminance are comparable in size and it is desired to take an average,
the following equation can be used instead:
L2 − L1
C2 =
0.5 × ( L2 + L1 )
where
L1 is the luminance of the background, or largest part of the visual field;
L2 is the luminance of the object

Luminance meter
Instrument for measuring luminance

Luminosity
See brightness

Luminous efficacy of a source (g)


Quotient of the luminous flux emitted by the power absorbed by the source (unit: lm·W–1)

Luminous environment
Lighting considered in relation to its physiological and psychological effects

Luminous flux (W)


Quantity derived from radiant flux We by evaluating the radiation according to its action upon the
CIE standard photometric observer (unit: lm)

Note 1: For photopic vision


 dW ( l ) 

W = Km ∫  e × v (l )
0
dl 
where
W is the luminous flux;
dWe ( l )
is the spectral distribution of the radiant flux;
dl
V(l) is the spectral luminous efficiency function
305
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781

Note 2: For the values of Km (photopic vision) and K′m (scotopic vision), see BS ISO 23539 (ISO, 2005)
Chapter Nineteen: Glossary

or

Quantity derived from radiant flux (radiant power) by evaluating the radiation according to the
spectral sensitivity of the human eye (as defined by the CIE standard photometric observer). It is
the light power emitted by a source or received by a surface (unit: lumen, lm)

See also initial luminous flux and rated luminous flux

Luminous intensity (of a source, in a given direction) (I)


Quotient of the luminous flux dW leaving the source and propagated in the element of solid
angle dV containing the given direction, by the element of solid angle (unit: cd = lm sr –1)
dW
I=
dV
where
I is the luminous intensity of a source in a given direction;
dW is the luminous flux leaving the source;
dV is the solid angle

or

Luminous flux per unit solid angle in the direction in question, i.e. the luminous flux on a small
surface, divided by the solid angle that the surface subtends at the source

(Spatial) Distribution of luminous intensity (of a source)


Display, by means of curves or tables, of the value of the luminous intensity of the source as a
function of direction in space

or

Luminous intensity of a source (lamp or luminaire) as a function of direction in space

Machinery, Machine
Assembly of linked parts or components, at least one of which moves, with the appropriate
machine actuators, control and power circuits, etc joined together for a specific application, in
particular, for the processing, treatment, moving or packaging of a material

Note: The term ‘machinery’ also covers an assembly of machines which, in order to achieve the same end, are
arranged and controlled so that they function as an integral whole

Maintained illuminance (Ēm)


Minimum average illuminance (unit: lx)

Note 1: Value below which the average illuminance on the specified area should not fall

Note 2: It is the average illuminance at the time maintenance should be carried out

306
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781
Chapter Nineteen: Glossary
Maintained luminance ( L m)
Minimum average luminance (unit: cd⋅m–2)

Note 1: Value below which the average luminance on the specified area should not fall

Note 2: It is the average luminance at the time maintenance should be carried out

Maintenance cycle
Repetition of lamp replacement, lamp/luminaire cleaning and room surface cleaning intervals

Maintenance factor
(Light loss factor) (obsolete)
Ratio of the average illuminance on the working plane after a certain period of use of a lighting
installation to the initial average illuminance obtained under the same conditions for the
installation

Note 1: The term depreciation factor has been formerly used to designate the reciprocal of the above ratio
Note 2: The light losses take into account dirt accumulation on luminaire and room surfaces and lamp
depreciation

or

Ratio of maintained illuminance to initial illuminance

Note: Maintenance factor of an installation depends on lamp lumen maintenance factor, lamp survival factor,
luminaire maintenance factor and (for an interior lighting installation) room surface maintenance factor

See also lamp lumen maintenance factor, luminaire maintenance factor and room surface
maintenance factor

Maintenance schedule
Set of instructions specifying maintenance cycle and servicing procedures

Maximum illuminance (Emax)


Highest illuminance at any relevant point on the specified surface (unit: lx)

Maximum luminance (Lmax)


Highest luminance of any relevant point on the specified surface (unit: cd·m–2)

Measurement field (of a photometer)


Area including all points in object space, radiating towards the acceptance area of the detector

Minimum illuminance (Emin)


Lowest illuminance at any relevant point on the specified surface (unit: lx)

Minimum luminance (Lmin)


Lowest luminance at any relevant point on the specified surface (unit: cd·m–2)

Minimum value emergency factor (Fmin)


Worst case of the emergency time-dependent factors
307
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781

Mixed traffic
Chapter Nineteen: Glossary

Traffic that consists of motor vehicles, cyclists, pedestrians, etc

Motor traffic (motorised traffic)


Traffic that consists of motorised vehicles only

Nominal lamp wattage (Wlamp)


Approximate wattage used to designate or identify the lamp (unit: W)

Non-daylight time usage (tN)


Annual operating hours during the non-daylight time (unit: h)

Obtrusive light
Spill light which because of quantitative, directional or spectral attributes in a given context gives
rise to annoyance, discomfort, distraction or reduction in the ability to see essential information

Note 1: In the case of outdoor sports lighting installations, obtrusive light is considered around the
installation and not for spectators, referees or players within the sports area

Note 2: In the case of large tertiary buildings with predominantly glazed facades, interior lighting may be
considered as obtrusive light if it gives rise to annoyance, discomfort, distraction or a reduction in the ability to see
essential information due to light spilling outside of the building structure

Occupancy dependency factor (Fo)


Factor indicating the proportion of time that a space is occupied and lighting is required

Open area lighting (anti-panic lighting)


Part of emergency escape lighting provided to avoid panic and provide illumination allowing
people to see their way to an escape route

Operating time (t)


Time period for the energy consumption (unit: h)

See also annual operating time

Parasitic energy consumption


See luminaire parasitic energy consumption

Parasitic power
See luminaire parasitic power

Parasitic power of the controls (with the lamps off) (Pci)


Parasitic input power to the control system in the luminaires during the period with the lamps
not operating (unit: W)

Principal area (APrincipal)


Actual playing area needed for the performance of a certain sport

Note: Usually this means the actual marked out ‘field’ area for that sport (for instance football), but in some
cases, this area comprises an extra playing area around the marked area (e.g. tennis, volleyball, table
tennis). The dimensions of the particular area should be checked at the time when a lighting installation is being
installed
308
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781
Performance

Chapter Nineteen: Glossary


See visual performance

Photometer
Instrument for measuring photometric quantities

Photometric observer
See luminous flux

Photometry
Measurement of quantities referring to radiation as evaluated according to a given spectral
luminous efficiency function, e.g. V(l) or V′(l)

Photopic vision
See luminous flux

Practical emergency lamp flux (WPEL)


Lowest luminous flux of the lamp observed during the rated duration of the emergency mode
(unit: lm)

WPEL = WLD × FEBallast

where
WPEL is the practical emergency lamp flux, expressed in lumens;
WLD is the initial lighting design lumens at 100 h;
FEBallast is the emergency ballast lumen factor

Radiant flux
See luminous flux

Rated luminous flux (of a type of lamp)


Value of the initial luminous flux of a given type of lamp declared by the manufacturer or the
responsible vendor, the lamp being operated under specified conditions (unit: lm)

Note 1: The initial luminous flux is the luminous flux of a lamp after a short ageing period as specified in the
relevant lamp standard

Note 2: The rated luminous flux is sometimes marked on the lamp

Reference ballast
Special type ballast designed for providing comparison standards for use in testing ballasts, for
the selection of reference lamps and for testing regular production lamps under standardised
conditions

Reference surface
Surface on which illuminance is measured or specified

Reflectance (for incident radiation of given spectral composition, polarisation and geometrical
distribution) (r)
Ratio of the reflected radiant or luminous flux to the incident flux in the given conditions
309
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781

Reflections
Chapter Nineteen: Glossary

See veiling reflections

Reflectometer
Instrument for measuring quantities pertaining to reflection

Rooflight
Daylight opening on the roof or on a horizontal surface of a building

Room surface maintenance factor (FRSM)


Ratio of room surface reflectance at a given time to the initial reflectance value

Note: Room surface maintenance factor is sometimes signified by the abbreviation RSMF

Safety sign
Sign which gives a general safety message, obtained by a combination of colour and geometric
shape and which, by the addition of a graphic symbol or text, gives a particular safety message

Scene setting operation time (ts)


Operating hours of the scene setting controls (unit: h)

Scotopic observer
See luminous flux

Screens
See daylight screens

Semi-cylindrical illuminance (at a point) (Esz)


Total luminous flux falling on the curved surface of a very small semi-cylinder located at the
specified point, divided by the curved surface area of the semi-cylinder (unit: lx)

Note: The axis of the semi-cylinder is taken to be vertical unless stated otherwise. The direction of the curved
surface should be specified

Semi-direct lighting
Lighting by means of luminaires having a distribution of luminous intensity such that the
fraction of the emitted luminous flux directly reaching the working plane, assumed to be
unbounded, is 60 to 90 per cent

Semi-indirect lighting
Lighting by means of luminaires having a distribution of luminous intensity such that the
fraction of the emitted luminous flux directly reaching the working plane, assumed to be
unbounded, is 10 to 40 per cent

Shielding angle
The angle between the horizontal plane and the first line of sight at which the luminous parts of
the lamps in the luminaire are directly visible (unit: degrees)

Note: The complementary angle to the shielding angle is named cut-off angle

310
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781
Skylight

Chapter Nineteen: Glossary


Visible part of diffuse sky radiation

Source (light source)


Object that produces light or other radiant flux

Note: The term light source indicates the source is essentially intended for illuminating and signalling
purposes

Solar radiation
Electromagnetic radiation from the sun

See also direct solar radiation and global solar radiation

Spacing (in an installation)


Distance between the light centres of adjacent luminaires of the installation

Spacing to height ratio


Ratio of spacing to the height of the geometric centres of the luminaires above the reference
plane

Note: For indoor lighting, the reference plane is usually the horizontal working plane; for exterior lighting,
the reference plane is usually the ground

Spectral luminous efficiency


See luminous flux

Spherical illuminance (at a point) (Eo)


Total luminous flux falling on the whole surface of a very small sphere located at the specified
point divided by the surface area of the sphere (unit: lx)

Spill light (stray light)


Light emitted by a lighting installation which falls outside the boundaries of the property for
which the lighting installation is designed

Spotlighting
Lighting designed to increase considerably the illuminance of a limited area or of an object
relative to the surroundings, with minimum diffused lighting

Stroboscopic effect
Apparent change of motion and/or appearance of a moving object when the object is illuminated
by a light of varying intensity

Note: To obtain apparent immobilisation or constant change of movement, it is necessary that both the object
movement and the light intensity variation are periodic, and some specific relation between the object movement
and light variation frequencies exists. The effect is only observable if the amplitude of the light variation is above
certain limits. The motion of the object can be rotational or translational

Standard photometric observer


See luminous flux
311
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781

Standard year time (ty)


Chapter Nineteen: Glossary

Time taken for one standard year to pass, taken as 8760 h

Standby lighting
That part of emergency lighting provided to enable normal activities to continue substantially
unchanged

Stray light
See spill light

Sunlight
Visible part of direct solar radiation

Surrounding area (immediate surrounding area)


Band surrounding the task area within the field of vision

Survival factor
See lamp survival factor

Task area
Area within which the visual task is carried out

Total energy used for lighting (Wt)


Energy consumed in period t, by the luminaires, when the lamps are operating plus the parasitic
loads when the lamps are not operating, in a room or zone (unit: kW·h)

Total installed charging power of the emergency lighting luminaires in the room or
zone (Pem)
Input charging power of all emergency lighting luminaires (unit: W)

Pem = ∑ Pe,i
i

where
Pem is the total installed charging power of the emergency lighting luminaires in the
room or zone, expressed in watts;
Pe,i is the emergency lighting charging power of the individual luminaires, expressed
in watts

Total installed lighting power in the room or zone (Pn)


Power of all luminaires (unit: W)

Pn = ∑ Pi
i

where
Pn is the total installed lighting power in the room or zone, expressed in watts;
Pi is the luminaire power expressed in watts

Total installed parasitic power of the controls in the room or zone (Ppc)
Input power of all control systems in luminaires when the lamps are not operating (unit: W)

312
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781
Ppc = ∑ Pc,i

Chapter Nineteen: Glossary


i

where
Ppc is the total installed parasitic power of the controls in the room or zone, expressed
in watts;
Pc,i is the parasitic power of the controls only during the time with the lamps off,
expressed in watts

Traffic lane
Strip of carriageway intended to accommodate a single line of moving vehicles

Transmittance (for incident radiation of given spectral composition, polarisation and


geometrical distribution) (t)
Ratio of the transmitted radiant or luminous flux to the incident flux in the given conditions

Tristimulus values (of a colour stimulus)

Amounts of the three reference colour stimuli, in a given trichromatic system, required to match
the colour of the stimulus considered

Note 1: In the CIE standard colorimetric systems, the tristimulus values are represented by the symbols X, Y,
Z and X10, Y10, Z10
Note 2: See also CIE 15 (CIE, 2004b)

Unified glare rating limit (RUGL)


Upper limit of glare by the CIE Unified Glare Rating system

Uniformity (luminance, illuminance) (Uo)


Ratio of minimum illuminance (luminance) to average illuminance (luminance) on (of) a surface

Upward flux maximum


Maximum possible value of flux in an installation that is potentially emitted above the
horizontal both directly from the luminaire(s) mounted in their installed attitude, and indirectly
due to reflection from lit surfaces within the space (unit: lm)

Upward flux minimum


Minimum possible value of flux in an installation that is emitted above the horizontal (unit: lm)

Upward flux ratio


Ratio between the flux from all considered luminaires above the horizontal plane passing through
the luminaires in their installed position on site plus their flux reflected by the ground and the
minimal irreducible flux reflected towards the sky by the sole reference surface

Note: Upward flux ratio is sometimes signified by the abbreviation UFR

Upward light output ratio (of a luminaire) (RULO)


Ratio of the upward flux of the luminaire, measured under specified practical conditions with its
own lamps and equipment, to the sum of the individual luminous fluxes of the same lamps when
operated outside the luminaire with the same equipment, under specified conditions

313
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781

Note 1: Upward light output ratio is sometimes signified by the abbreviation ULOR
Chapter Nineteen: Glossary

Note 2: The luminaire attitude should be declared so that appropriate corrections to the ULOR can be made
if, in application, the installed attitude is different

Upward light ratio (RUL)


Proportion of the total luminaire flux that is emitted above the horizontal by all luminaires to the
total luminaire flux from all luminaires in an installation, when the luminaires are mounted in
their installed attitudes

Useful area (A)


Floor area inside the outer walls excluding non-habitable cellars and un-illuminated spaces
(unit: m2)

Useful data
Lamp and luminaire data beneficial to the designers and users in the planning and operation of
lighting installations

Utilance (of an installation, for a reference surface) (U)


Ratio of the luminous flux received by the reference surface to the sum of the individual total
fluxes of the luminaires of the installation

Utilisation factor (of an installation, for a reference surface) (FU)


Ratio of the luminous flux received by the reference surface to the sum of the individual fluxes of
the lamps of the installation

V(l) correction
Correction of the spectral responsivity of a detector to match the photopic spectral sensitivity of
the human eye

Veiling luminance
See equivalent veiling luminance

Veiling reflections
Specular reflections that appear on the object viewed and that partially or wholly obscure the
details by reducing contrast

Visual acuity
1. Qualitatively: capacity for seeing distinctly fine details that have very small angular separation

2. Quantitatively: any of a number of measures of spatial discrimination such as the reciprocal of


the value of the angular separation in minutes of arc of two neighbouring objects (points or lines
or other specified stimuli) which the observer can just perceive to be separate

Visual comfort
Subjective condition of visual well-being induced by the visual environment

Visual field
Area or extent of physical space visible to an eye at a given position and direction of view

Note: It should be stated whether the visual field is monocular or binocular


314
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781
Visual performance

Chapter Nineteen: Glossary


Performance of the visual system as measured for instance by the speed and accuracy with which
a visual task is performed

Visual task
Visual elements of the activity being undertaken

Note: The main visual elements are the size of the structure, its luminance, its contrast against the
background and its duration

Window
Daylight opening on a vertical or nearly vertical area of a room envelope

Work place
Place intended to house work stations on the premises of the undertaking and/or establishment
and any other place within the area of undertaking and/or establishment to which the worker has
access in the course of his employment

Work plane (working plane)


Reference surface defined as the plane at which work is normally done

Work station
Combination and spatial arrangement of work equipment, surrounded by the work environment
under the conditions imposed by the work tasks

315
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781
Chapter Twenty: Bibliography

Chapter 20: Bibliography


20.1 Standards
British Standards Institution (1976) BS 5252: 1976: Framework for colour co-ordination for building
purposes, London: BSI.

British Standards Institution (1992) BS EN 60529: 1992: Specification for degrees of protection provided
by enclosures (IP code), London: BSI.

British Standards Institution (1998) BS EN 60598-2-5: 1998: Luminaires. Particular requirements.


Floodlights, London: BSI.

British Standards Institution (2003a) BS EN 13201-2: 2003: Road lighting. Performance requirements,
London: BSI.

British Standards Institution (2003b) BS EN 60598-2-3: 2003: Luminaires. Particular requirements.


Luminaires for road and street lighting, London: BSI.

British Standards Institution (2003c) BS EN 13201-3: 2003: Road lighting. Calculation of


performance, London: BSI.

British Standards Institution (2003d) BS EN 13201-4: 2003: Road lighting. Methods of measuring
lighting performance, London: BSI.

British Standards Institution (2003e) BS 5489-1:2003+A2: 2008: Code of practice for the design of
road lighting. Lighting of roads and public amenity areas, London: BSI.

British Standards Institution (2004a) BS EN 13032-1: 2004: Light and lighting. Measurement and
presentation of photometric data of lamps and luminaires. Measurement and file format, London: BSI.

British Standards Institution (2004b) BS EN 13032-2: 2004: Light and lighting. Measurement and
presentation of photometric data of lamps and luminaires. Presentation of data for indoor and outdoor work
places, London: BSI.

British Standards Institution (2005a) BS EN 14225: Measurement and assessment of personal exposure
to incoherent optical radiation, Parts 1 to 4, London: BSI.

British Standards Institution (2005b) BS 667: Illuminance meters. Requirements and test methods,
London: BSI.

British Standards Institution (2005c) BS 7920: Luminance meters. Requirements and test methods,
London: BSI.

British Standards Institution (2007a) BS EN 15193: 2007: Energy performance of buildings. Energy
requirements for lighting, London: BSI.

British Standards Institution (2007b) BS EN 12193: 2007: Light and lighting. Sports lighting,
London: BSI.

316
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781
British Standards Institution (2007c) BS EN 12464-2: 2007: Light and lighting – Lighting of work

Chapter Twenty: Bibliography


places – Part 2: Outdoor work places, London: BSI.

British Standards Institution (2007d) BS EN 13032-3: 2007: Measurement and presentation of


photometric data of lamps and luminaires. Presentation of data for emergency lighting of work places,
London: BSI.

British Standards Institution (2008) BS 8206-2: 2008: Lighting for buildings – Part 2: Code of practice
for daylighting, London: BSI.

British Standards Institution (2011a) BS EN 12464-1: 2011: Light and lighting – Lighting of work
places – Part 1: Indoor work places, London: BSI.

British Standards Institution (2011b) BS EN 12665: 2011: Light and lighting. Basic terms and criteria
for specifying lighting requirements, London: BSI.

International Standards Organisation / Commission Internationale de l’Eclairage (2003)


ISO 15469: 2004 (E) / CIE S 011/E: 2003, Spatial distribution of daylight – CIE standard general sky,
Geneva: ISO, Vienna: CIE.

International Standards Organisation (2005) BS EN ISO 23539: 2005: Photometry – The CIE
system of physical photometry, Geneva: ISO.

International Standards Organisation (2007) BS EN ISO 9680: 2007: Dentistry. Operating lights,
Geneva: ISO.

International Standards Organisation (2008a) BS EN ISO 9241-307: 2008: Ergonomics of


human–system interaction. Analysis and compliance test methods for electronic visual displays, Geneva: ISO.

International Standards Organisation (2008b) BS EN ISO 9241-302: 2008: Ergonomics of


human–system interaction. Terminology for electronic visual displays, Geneva: ISO.

International Standards Organisation (2009) BS ISO 3864-1: 2009: Graphical symbols. Safety colours
and safety signs. Part 1. Design principles for safety signs and safety markings, Geneva: ISO.

20.2 Guidance
Commission Internationale de l’Eclairage CIE (1978) CIE Publication 40: 1978: Calculations for
interior lighting: Basic method, Vienna: CIE.

Commission Internationale de l’Eclairage CIE (1994) CIE Publication 112: 1994: Glare evaluation
system for use within outdoor sports and area lighting, Vienna: CIE.

Commission Internationale de l’Eclairage CIE (1995a) CIE Publication 117: 1995: Discomfort glare
in interior lighting, Vienna: CIE.

Commission Internationale de l’Eclairage CIE (1995b) CIE Publication 13-3: 1995: Method of
measuring and specifying colour rendering properties of light sources, Vienna: CIE.

317
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781

Commission Internationale de l’Eclairage (CIE) (1997) CIE Publication 126: 1997: Guidelines for
Chapter Twenty: Bibliography

minimizing sky glow, Vienna: CIE.

Commission Internationale de l’Eclairage (CIE) (2000) CIE Publication 140: 2000: Road lighting
calculations, Vienna: CIE.

Commission Internationale de l’Eclairage CIE (2003) CIE Publication 154: 2003: The maintenance
of outdoor lighting systems, Vienna: CIE.

Commission Internationale de l’Eclairage (CIE) (2004a) CIE Publication 158: 2004: Ocular
lighting effects on human physiology and behaviour, Vienna: CIE.

Commission Internationale de l’Eclairage (CIE) (2004b) CIE Publication 15: 2004: Colorimetry,
3rd edition, Vienna: CIE.

Commission Internationale de l’Eclairage CIE (2005) CIE Publication 97: 2005: Guide on the
maintenance of indoor electric lighting systems, Vienna: CIE.

Commission Internationale de l’Eclairage (CIE) (2006) CIE Publication S009: 2006: Photobiologic
safety of lamps and lamp systems, Vienna: CIE.

Commission Internationale de l’Eclairage (CIE) (2010) CIE Publication 190: 2010: Calculation
and presentation of unified glare rating tables for indoor lighting luminaires, Vienna: CIE.

The Society of Light and Lighting (SLL) (1999) SLL Lighting Guide 10: Daylighting and window
design. ISBN 0 900953 98 5, London: CIBSE.

The Society of Light and Lighting (SLL) (2001) SLL Lighting Guide 11: Surface reflectance and
colour. ISBN 1 903287 14 6, London: CIBSE.

The Society of Light and Lighting (SLL) (2004) SLL Lighting Guide 12: Emergency lighting design
guide. ISBN 1 903287 51 0, London: CIBSE.

The Society of Light and Lighting (SLL) (2006) SLL Lighting Guide 4: Sports.
ISBN 1 903287 78 2, London: CIBSE.

The Society of Light and Lighting (SLL) (2008) SLL Lighting Guide 2: Hospital and health care
buildings. ISBN 978 1 903287 99 6, London: CIBSE.

The Society of Light and Lighting (SLL) (2009) The SLL Lighting Handbook.
ISBN: 9781906846022, London: The Society of Light and Lighting.

The Society of Light and Lighting (SLL) (2011) SLL Lighting Guide 5: Lighting for education.
ISBN 978 1 906846 17 6, London: CIBSE.

20.3 References
Akashi, Y., Myer, M. and Boyce, P.R. (2006) Identifying sparkle. Lighting Research and Technology,
38, 325–340.

318
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781
Akashi, Y., Rea, M.S. and Bullough, J.D. (2007) Driver decision making in response to peripheral

Chapter Twenty: Bibliography


moving targets under mesopic lighting levels. Lighting Research and Technology, 39, 53–67.

American Conference of Governmental Industrial Hygienists (ACGIH) (2010) TLVs and BEIs
threshold limit values for chemical substances and physical agents, biological exposure indices, Cincinnati,
OH: ACGIH.

Badia, P., Myers, B., Boecker, M. and Culpeper, J. (1991) Bright light effects on body
temperature, alertness, EEG and behavior. Physiology and Behavior, 50, 583–588.

Baron, R. A. (1990) Environmentally induced positive affect: Its impact on self-efficacy, task
performance, negotiation, and conflict. Journal of Applied Social Psychology, 20(5), 368–384.

Baron, R.A. and Thomley, J. (1994) A whiff of reality: Positive affect as a potential mediator of
the effects of pleasant fragrances on task performance and helping. Environment and Behavior,
26(6), 766–784.

Baron, R.A., Rea, M.S. and Daniels, S.G. (1992) Effects of indoor lighting (illuminance and
spectral distribution) on the performance of cognitive tasks and interpersonal behaviors:
The potential mediating role of positive affect. Motivation and Emotion, 16, 1–33.

Begley, K. and Linderson, T. (1991) Management of mercury in lighting products, Proceedings


of the 1st European Conference on Energy-Efficient Lighting. Stockholm, Sweden: Swedish National
Board for Industrial and Technical Development.

Berman, S.M. (1992) Energy efficiency consequences of scotopic sensitivity. Journal of the
Illuminating Engineering Society, 21, 3–14.

Berman, S.M., Navvab, M., Martin, M.J., Sheedy, J. and Tithof, W. (2006) A comparison of
traditional and high colour temperature lighting on the near acuity of elementary school children.
Lighting Research and Technology, 38, 41–52.

Berson, D.M., Dunn, F.A. and Takao, M. (2002) Phototransduction by retinal ganglion cells that
set the circadian clock. Science, 295, (5557), 1070–1073.

Boyce, P.R. (1996) Illuminance selection based on visual performance – and other fairy stories.
Journal of the Illuminating Engineering Society, 25, 41–49.

Boyce, P.R. (2003) Human factors in lighting. London: Taylor and Francis.

Boyce, P.R. (2006) Lemmings, light and health. Leukos, 2(3), 175–184.

Boyce, P.R. and Rea, M.S. (1987) Plateau and escarpment: The shape of visual performance,
Proceedings of the CIE 21st Session, Venice. Vienna: CIE.

Boyce, P.R., Beckstead, J.W., Eklund, N.H., Strobel, R.W. and Rea, M.S. (1997) Lighting the
graveyard shift: the influence of a daylight-simulating skylight on the task performance and mood
of night-shift workers. Lighting Research and Technology, 29, 105–142.

Boyce, P.R., Eklund, N.H., Hamilton, B.J. and Bruno, L.D. (2000) Perceptions of safety at night
in different lighting conditions. Lighting Research and Technology, 32, 79–91.
319
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781

Boyce, P.R., Akashi, Y., Hunter, C.M. and Bullough, J.D. (2003) The impact of spectral power
Chapter Twenty: Bibliography

distribution on visual performance. Lighting Research and Technology, 35, 141–161.

Boyce, P.R., Veitch, J.A., Newsham, G.R., Jones, C.C., Heerwagen, J., Myer, M. and Hunter,
C.M. (2006a) Lighting quality and office work: Two field simulation experiments. Lighting
Research and Technology, 38(3), 191–223.

Boyce, P. R., Veitch, J.A., Newsham, G.R., Jones, C.C., Heerwagen, J., Myer, M. and Hunter,
C.M. (2006b) Occupants use of switching and dimming in offices. Lighting Research and
Technology, 38, 358–378.

Campbell, S.S., Dawson, D. and Anderson, M.W. (1993) Alleviation of sleep maintenance
insomnia with timed exposure to bright light. Journal of the American Geriatric Society, 41, 829–836.

Campbell, S.S., Dijk, D.J., Boulos, Z., Eastman, C.I., Lewy, A.J. and Terman, M. (1995) Light
treatment for sleep disorders: Consensus report III Alerting and activating effects. Journal of
Biological Rhythms, 10, 129–132.

Chartered Institution of Building Services Engineers (CIBSE) (1999) Environmental factors


affecting office worker performance: A review of evidence, CIBSE Technical Memorandum TM24.
London: CIBSE.

Clear, R. and Berman, S. (1994) Environmental and health aspects of lighting: Mercury. Journal of
the Illuminating Engineering Society, 23, 138–156.

Cuttle, C. (1997) Cubic illumination. Lighting Research and Technology, 29, 1–14.

Cuttle, C. and Brandston, H. (1995) Evaluation of retail lighting. Journal of the Illuminating
Engineering Society, 24(2), 33–49.

Czeisler, C.A., Rios, C.D., Sanchez, R., Brown, E.N., Richardson, G.S., Ronda, J.M. and Rogacz,
S. (1988) Phase advance and reduction in amplitude of the endogenous circadian oscillator
correspond with systematic changes in sleep/wake habits and daytime functioning in the elderly.
Sleep Research, 15, 268.

Davis, W. and Ohno, Y. (2010) Color quality scale. Optical Engineering, 49(3), 033602.

Dijk, D-J., Boulos, Z., Eastman, C.I., Lewy, A.J., Campbell, S.S. and Terman, M. (1995) Light
treatment for sleep disorders: Consensus report II Basic properties of circadian physiology and
sleep regulation. Journal of Biological Rhythms, 10, 113–125.

Eastman, C.I., Stewart, K.T., Mahoney, M.P., Liu, L. and Fogg, L.F. (1994) Dark goggles and
bright light improve circadian rhythm adaptation to night shift work. Sleep, 17, 535–543.

EC (2002) Directive 2002/91/EC of the European Parliament and of the Council of 16 December
2002 on the energy performance of buildings. Official Journal of the European Communities, 4.1.2003.

Eklund, N.H. (1999) Exit sign recognition for color normal and color deficient observers. Journal
of the Illuminating Engineering Society, 28, 71–81.

320
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781
Eklund, N.H., Boyce, P.R. and Simpson, S.N. (2001) Lighting and sustained performance:

Chapter Twenty: Bibliography


Modeling data-entry task performance. Journal of the Illuminating Engineering Society, 30, 126–141.

Elvik, R. (1995) Meta-analysis of evaluations of public lighting as accident countermeasure.


Transportation Research Record, 1485, 112–123.

Environmental Protection Agency (EPA) (1997) Mercury study report to Congress. Washington, DC:
EPA.

Farley, K.M.J. and Veitch, J.A. (2001) A room with a view: A review of the effects of windows on work and
well-being (IRC-RR-136). Ottawa, ON: NRC Institute for Research in Construction. Retrieved
from http://irc.nrc-cnrc.gc.ca/fulltext/rr/rr136/

Figueiro, M.G., Rea, M.S. and Bullough, J.D. (2006) Does architectural lighting contribute to
breast cancer? Journal of Carcinogenesis, 5(1), 20.

Fotios, S. and Cheal, C. (2009) Obstacle detection: A pilot study investigating the effects of lamp
type, illuminance and age. Lighting Research and Technology, 41, 321–342.

Galasiu, A.D. and Veitch, J.A. (2006) Occupant preferences and satisfaction with the luminous
environment and control systems in daylit offices: a literature review. Energy and Buildings, 38(7),
728–742.

Heschong Mahone Group (1999) Skylighting and retail sales: An investigation into the relationship
between daylighting and human performance. San Francisco, CA: Pacific Gas & Electric Co. Retrieved
from http://www.pge.com/mybusiness/edusafety/training/pec/daylight/daylight.shtml

HMSO (1992) The Workplace (Health, Safety and Welfare) Regulations 1992, http://www.
legislation.gov.uk/uksi/1992/3004/contents/made (accessed September 2011)

HMSO (1999) The Management of Health and Safety at Work Regulations 1999, Regulation 3,
http://www.legislation.gov.uk/uksi/1999/3242/regulation/3/made (accessed September 2011)

HMSO (2005) Clean Neighbourhoods and Environment Act 2005, Chapter 16, Section 102
Statutory nuisance: lighting, http://www.legislation.gov.uk/ukpga/2005/16/section/102

HMSO (2007) The Construction (Design and Management) Regulations 2007 Statutory
Instruments No. 320 2007, http://www.legislation.gov.uk/uksi/2007/320/contents/made (accessed
September 2011)

Hosoda, M., Stone-Romero, E.F. and Coats, G. (2003) The effects of physical attractiveness
on job-related outcomes: A meta-analysis of experimental studies. Personnel Psychology, 56(2),
431–462.

Houser, K.W., Tiller, D.K., Bernecker, C.A. and Mistrick, R.G. (2002) The subjective response to
linear fluorescent direct/indirect lighting systems. Lighting Research and Technology, 34(3), 243–264.

HSE (2007) Managing health and safety in construction. HSE Approved Code of Practice L144.
Bootle: Health and Safety Executive, http://www.hse.gov.uk/pubns/priced/l144.pdf (accessed
September 2011)
321
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781

Illuminating Engineering Society of North America (IESNA) (2000) The IESNA lighting
Chapter Twenty: Bibliography

handbook, 9th edition. New York: IESNA.

Illuminating Engineering Society of North America (IESNA) (2005, 2007, 2009) Photobiological
safety for lamps and lamp systems – General requirements (2005), Photobiological safety for lamps and lamp
systems – Risk group classification and labeling (2007) and Photobiological safety for lamps and lamp systems
– Measurement techniques (2009). New York: IESNA.

Isen, A.M. and Baron, R.A. (1991) Positive affect as a factor in organizational behavior. In
B.M. Staw and L.L. Cummings (eds), Research in organizational behavior, 13. Greenwich,
CT: JAI Press.

Jasser, S.A., Blask, D.E. and Brainard, G.C. (2006) Light during darkness and cancer: relation-
ships in circadian photoreception and tumor biology. Cancer Causes and Control, 17(4), 513–523.

Jay, P.A. (1973) The theory of practice in lighting engineering. Light and Lighting, 66, 303–306.

Kang, J. (2004) The effect of light on the movement of people. Dissertation Abstracts International
Section A: Humanities and Social Sciences, 65(6-A), 2007.

Kaplan, S. and Kaplan, R. (Eds.) (1982) Cognition and environment: Functioning in an uncertain world.
New York: Praeger.

Lack, L. and Schumacher, K. (1993) Evening light treatment of early morning insomnia. Sleep
Research, 22, 225.

LaGiusa, F.F. and Perney, L.R. (1973) Brightness patterns influence attention spans. Lighting
Design and Application, 3(5), 26–30.

LaGiusa, F.F. and Perney, L.R. (1974) Further studies on the effects of brightness variations on
attention span in a learning environment. Journal of the Illuminating Engineering Society, 3, 249–252.

Lam, R.W. and Levitt, A.J. (1998) Canadian consensus guidelines for the treatment of seasonal
affective disorder: A summary of the report of the Canadian consensus group on SAD. Canadian
Journal of Diagnosis, 15(10 (October supplement)), 1–17.

Langlois, J.H., Kalakanis, L., Rubenstein, A.J., Larson, A., Hallam, M. and Smoot, M. (2000)
Maxims or myths of beauty? A meta-analytic and theoretical review. Psychological Bulletin, 126(3),
390–423.

Liebel, B., Berman, S., Clear, R. and Lee, R. (2010) Reading performance is affected by light
level and lamp spectrum, Proceedings of the Illuminating Engineering Society of North America Annual
Conference, Toronto. New York: IESNA.

Lockley, S.W., Barger, L.K., Ayas, N.T., Rothschild, J.M., Czeisler, C.A. and Landrigan, C.P.
(2007) Effects of health care provider work hours and sleep deprivation on safety and
performance. Joint Commission Journal on Quality and Patient Safety, 33(1), 7–18.

Loe, D.L., Mansfield, K.P. and Rowlands, E. (1994) Appearance of lit environment and its
relevance in lighting design: Experimental study. Lighting Research and Technology, 26, 119–133.
322
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781
MacAdam, D.L. (1942) Visual sensitivity to color differences in daylight. Journal of the Optical

Chapter Twenty: Bibliography


Society of America, 32, 247–274.

Mangum, S.R. (1998) Effective constrained illumination of three-dimensional, light-sensitive


objects. Journal of the Illuminating Engineering Society, 27, 115–131.

McCloughan, C.L.B., Aspinall, P.A. and Webb, R.S. (1999) The impact of lighting on mood.
Lighting Research and Technology, 31, 81–88.

McNally, D. (1994) The vanishing universe, Cambridge, UK: Cambridge University Press.

Megaw, E.D. and Richardson, J. (1979) Eye movements and industrial inspection. Applied
Ergonomics, 10, 145–154.

Mills, E. and Borg, N. (1999) Trends in recommended illuminance levels: An international


comparison. Journal of the Illuminating Engineering Society, 28, 155–163.

Newsham, G.R. and Veitch, J.A. (2001) Lighting quality recommendations for VDT offices:
A new method of derivation. Lighting Research and Technology, 33, 97–116.

Newsham, G.R., Richardson, C., Blanchet, C. and Veitch, J.A. (2005) Lighting quality research
using rendered images of offices. Lighting Research and Technology, 37(2), 93–115.

O’Donell, B.M., Colombo, E.M. and Boyce, P.R. (2011) Colour information improves relative
visual performance. Lighting Research and Technology, 43, 423–438.

O’Hagan, J.B., Khazova, M. and Jones, B.W. (2011) Ultra-violet emissions from HMI daylight
luminaires. Lighting Research and Technology, 43, 249–257.

Ouellette, M.J. and Rea, M.S. (1989) Illuminance requirements for emergency lighting. Journal of
the llluminating Engineering Society, 18, 37–42.

Painter, K. and Farrington, D.P. (1999) Street lighting and crime: Diffusion of benefits in the
Stoke-on-Trent project, in K. Painter and N. Tilley (eds), Crime prevention studies, Monsey, NY:
Criminal Justice Press.

Painter, K.A. and Farrington, D.P. (2001) The financial benefits of improved street lighting based
on crime reduction. Lighting Research and Technology, 33, 3–12.

Partonen, T. and Lönnqvist, J. (2000) Bright light improves vitality and alleviates distress in
healthy people. Journal of Affective Disorders, 57(1–3), 55–61.

Ravindran, A.V., Lam, R.W., Filteau, M.J., Lespérance, F., Kennedy, S.H., Parikh, S.V. et al. (2009)
Canadian Network for Mood and Anxiety Treatments (CANMAT) Clinical guidelines for the
management of major depressive disorder in adults. V. Complementary and alternative medicine
treatments. Journal of Affective Disorders,117 (Suppl. 1).

Rea, M.S. (1986) Toward a model of visual performance: Foundations and data. Journal of the
Illuminating Engineering Society, 15, 41–58.

Rea, M.S. and Ouellette, M.J. (1991) Relative visual performance: A basis for application. Lighting
Research and Technology, 23, 135–144.
323
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781

Rich, C. and Longcore, T. (2006) Ecological consequences of artificial night lighting. Washington, DC:
Chapter Twenty: Bibliography

Island Press.

Rosa, R.R. and Colligan, M.J. (1997) Plain language on shiftwork. Cincinnati, OH: NIIOSH.

Rosekind, M.R., Gregory K.B., Mallis, M.M., Brandt, S.L., Seal, B. and Lerner, D. (2010)
The cost of poor sleep: Workplace productivity loss and associated costs. Journal of Occupational and
Environmental Medicine, 52(1), 91–98.

Slater, A.I. and Boyce, P.R. (1990) Illuminance uniformity on desks: where is the limit? Lighting
Research and Technology, 22, 165–174.

Sullivan, J.M. and Flannagan, M.J. (2007) Determining the potential safety benefit of improved
lighting in three pedestrian crash scenarios. Accident Analysis and Prevention, 39, 638–647.

Summers, T.A. and Hebert, P.R. (2001) Shedding some light on store atmospherics: Influence of
illumination on consumer behavior. Journal of Business Research, 54(2), 145–150.

Taylor, L.H. and Sucov, E.W. (1974) The movement of people towards lights. Journal of the
Illuminating Engineering Society, 3(3), 237–241.

van Someren, E.J.W., Hagebeuk, E.E.O., Lijzenga, C., Schellens, P., de Rooij, S.E., Jonker, C.,
Pot, A.M., Mirmiran, M. and Swaab, D.F. (1996) Circadian rest-activity rhythm disturbances in
Alzheimer’s disease. Biological Psychiatry, 40, 259–270.

van Someren, E.J.W., Kessler, A., Mirmiran, M. and Swaab, D.F. (1997) Indirect bright light
improves circadian rest-activity rhythm disturbances in demented patients. Biological Psychiatry,
41, 955–963.

Veitch, J.A. (2001a) Lighting quality considerations from biophysical processes. Journal of the
Illuminating Engineering Society, 30, 3–16.

Veitch, J.A. (2001b) Psychological processes influencing lighting quality. Journal of the Illuminating
Engineering Society, 30, 124–140.

Veitch, J.A. and Newsham, G.R. (2000) Preferred luminous conditions in open-plan offices:
Research and practice recommendations. Lighting Research and Technology, 32, 199–212.

Veitch, J.A., Newsham, G.R., Boyce, P.R. and Jones, C.C. (2008) Lighting appraisal, well-
being and performance in open-plan offices: A linked mechanisms approach. Lighting Research and
Technology, 40, 133–151.

Weston, H.C. (1935) The relation between illumination and visual efficiency: The effect of size
of work. Industrial Health Research Board and the Medical Research Council. London: HMSO.

Weston, H.C. (1945) The relation between illumination and visual efficiency: The effect of
brightness contrast. Industrial Health Research Board, Report No. 87. London: HMSO.

Zhou, Y. and Boyce, P.R. (2001) Evaluation of speech intelligibility under different lighting
conditions. Journal of the Illuminating Engineering Society, 30(1), 34–46.
324
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781
Index
Index
Note: page numbers in italics refer to figures; page numbers in bold refer to tables.

absence factor 293 CIE


absorptance 293 chromaticity (1931) diagram 243, 243, 244
absorption 145 Colour Rendering Index (CRI) 249–255, 294
accent lighting 13 colour-matching functions 241–243
accommodation, definition 293 daylight calculations 274
acuity see visual acuity environmental zones 27, 27
adaptation luminances 4, 8, 10–11 glare rating (GR) 89
agricultural premises 52, 97 L*a*b* colour space 272–273
airports 83, 96 maintenance factors (MF) 280
angular co-ordinate systems 187–189 UCS (1976) diagram 244–247
annual operating time 293 Unified Glare Rating (UGR) 36–37
area sources 167 cinemas 70
aspect factors 166 circadian system 5, 21–23, 45, 115
assembly buildings 69–72 circuit luminous efficacy 294
atmospheric luminance 293 circulation areas 49, 74, 96, 129
average daylight factor 119–120, 120, 274–275 classrooms 13, 73
average illuminance 293 client duties 137–138
average luminance 112, 293 cold spot 294
colorimeter 294
background area 35, 293 colour 241–273
bakeries 53 colour appearance 40–41
ballast 293 chromaticity diagrams 241–247
ballast lumen factor (BLF) 293 daylighting 123
behavioural effects 6, 12–14, 18–19, 115 groups 41, 92
BREEAM 134 verification 85
brick industry 53 colour contrast 295
brightness 294 colour perception 4, 16
brightness contrast 294 colour properties of surfaces 263–273
brightness perception 16, 119 Colour Quality Scale (CQS) 255–263
colour rendering 41, 248–263, 295
British Standards 316–317
Colour Rendering Index (CRI) 41, 249–255
colour co-ordination 267–272
calculation 251–263
daylighting 115
limiting values 49–84, 96–105
energy performance of buildings 130–133
verification 85, 105
ingress protection (IP) 292
colour spaces 263–273
lighting of indoor workplaces 29
colour stimulus 295
lighting of outdoor workplaces 86 colour temperature 41, 247–248, 295
luminaire tests 94 communication performance 13–14
photometric measurements 187, 234 compact fluorescent lamps 263, 282
road lighting 106 competent person 136–137
safety colours 41 computer display screens 21, 42–43, 122, 195
sports lighting 232 concert halls 70
visual display units 43 constant illuminance factor 131, 295
building energy rating (BER) 129 constant illuminance systems 126
Building Regulations 127 Construction (Design and Management) Regulations
building sites 97 135–142
built-in luminaire 294 contractor duties 138–139, 140, 141
contrast 295
calibration, photometers 235 see also luminance contrast
canals 97 contrast revealing coefficient 295
candela 156 control gear 295–296
canteens 50 control rooms 51
car parks 72, 100 control systems 125, 126, 130
carriageway 294 co-ordinate systems 187–189, 223–225
CDM co-ordinator 139, 140 correction factors 296
CDM regulations 135–142 spectral correction factor 235
CE classes 110, 111, 114 UGR metrics 198
cement industry 53 correlated colour temperature (CCT) 241, 247, 296
ceramic metal halide lamps 11, 263, 282 cosine correction 296
ceramics industry 54 cosine error 235–236
chemical industry 55 costs of lighting 24–28
chemical pollution 26 crime prevention 15, 109
chromatic adaptation 16, 251 see also security lighting
chromaticity 294 critical flicker frequency see fusion frequency
chromaticity coordinates 243, 251, 294 cubic illuminance 219–220
chromaticity diagrams 243–247 curfew 28, 90, 296
325
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781

cut-off 296 emergency lighting charge time 299


Index

cut-off angle 296 emergency lighting charging power 299


cylindrical illuminance 17, 39, 162, 222, 296 energy consumption 25–26, 299
standardised calculation method 126, 131–133
daylight 44, 115–123 energy efficiency 25, 44–45, 93
benefits 45, 115–116 guidance 124–126
calculations 274–279 regulations and standards 126–134
definitions 297 entertainment premises 70
with electric lighting 122–123 environment classes 283
reference spectrum 249, 250 environmental issues 2, 26
and room brightness 118–121 environmental zones (CIE) 27, 27
task area 121–122 equivalent veiling luminance 299
windows and view 116–118 escalators 49
daylight dependency factor 131, 297 escape route lighting 14, 299
daylight factor 274–275, 297 escape routes 299
daylight screens/louvres 123, 297 essential data 299
daylight time usage 297 European Directive on the Energy Performance of
design criteria Buildings 130
indoor workplaces 29–85 exhibition halls 70
outdoor workplaces 86–94 exterior lighting see outdoor lighting
design speed 297 externally illuminated safety sign 299
designer duties 138, 139 extreme uniformity see diversity (luminance, illuminance)
diffraction 146 eyestrain 20–21
diffuse reflection and transmission 146
diffuse sky radiation 297 factories see industrial premises
diffused lighting 297 farms 52, 97
dimming systems 126 field measurements 238–240
DIN colour system 266–267 filling stations 98
direct lighting 297 financial costs 25
illuminance calculations first aid rooms 50
area sources 167 flashing lights 13
non point sources 164–167 flicker 21, 42, 93
point sources 161–164 flicker frequency see fusion frequency
direct solar radiation 297 floodlighting 300
directional lighting 40, 91–92, 297 fluorescent lamps 11, 263, 282
disability glare 297 flux see luminous flux
outdoor workplaces 89 focus error 238
road lighting 107, 112, 113, 114, 232 food industry 57
discomfort glare 36, 36–37, 121–122, 298 form, perception of 16–17
dispersion 145 form factors 172–175, 176
Display Energy Certificates (DEC) 134 foundries 58
display lighting 13, 130 fuel filling stations 98
display screen equipment (DSE) 42–43, 122, 195, 298 fusion frequency 300
disposal of equipment 25, 26
diversity (luminance, illuminance) 89, 298 G classes 114
docks (shipping) 103 gas plants 101
downward light output ratio (DLOR) 193, 298 general lighting 300
dry cleaning premises 59 glare
dwellings control 37–38, 120, 121–122
energy efficiency requirements 127, 128, 128–129 daylight 120, 121–122
recommended daylight factors 120 definition 300
indoor workplaces 36–39
educational premises 73–75, 133 outdoor workplaces 89–90
efficacy see luminous efficacy Glare Rating (GR) 89, 232
electric lighting, with daylighting 122–123 limiting values 96–105, 300
electrical and electronic industry 56 verification 105
electrical installations 101 see also Unified Glare Rating (UGR)
electrical safety 142 glass industry 54
electricity consumption 25–26 global solar radiation 300
see also energy efficiency grid points 35–36, 89, 238–240, 300
electromagnetic spectrum 143 guidance, published 317–318
electromagnetic waves 143–146 gyms 50
elevators 49
emergency ballast lumen factor 298 hairdressers 59
emergency exit 298 halogen lamps 11, 263, 282
emergency lamp flux see practical emergency lamp flux harbours 97
emergency lane (hard shoulder) 299 hazardous industries 100
emergency lighting 94, 142, 299 health and safety 141–142
escape lighting 14, 298 health care premises 76–82, 133
spacing tables 199–200 health effects 20–24, 115–116
total installed charging power 299 hearing impairments 14
326
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781
heat plants 101 interior space see dwellings; indoor workplaces

Index
hemispherical illuminance 163–164, 221, 300 internally illuminated safety sign 302
high pressure sodium lamps 11, 282 international standards 316–317
high risk task area lighting 300 iron and steel works 64
hospitals see health care premises ISO standards 317
hotels 69, 133
human circadian system see circadian system jewellery manufacturing 59
human face, visual perception 16–17, 17
human perceptual system 5–6 kerbside light output ratio 193
human performance 3–14
see also visual performance Lambertian radiator 158–159
human vision see visual system lamp, definition 302
lamp code 302
illuminance 157, 159–160, 300–301 lamp dimensions 302
brightness perception 16 lamp lumen maintenance factor (LLMF) 280–281, 282,
calculations 302
direct lighting 161–168 lamp luminous flux see rated luminous flux
indirect lighting 169–186 lamp survival factor (LSF) 281, 282, 302
indoor lighting 217–222 lamp wattage see nominal lamp wattage
outdoor lighting 229–230 lamps 73
measurement 238–240 choosing 126
and safety perception 19, 19, 20 colour properties 40–41, 92, 123, 263
scale of 32 LLMF and LSF values 282
verification 85, 105 luminous efficacy 128, 130
and visual performance 7–9 rated luminous flux 309
see also maintained illuminance scotopic/photopic ratio 11
illuminance grid 35–36, 89 Landolt C matrices 7, 8
illuminance meters 234–236, 301 laundries 59
illuminance uniformity 8, 35 leather industry 60
indoor workplaces 35, 49–84 LED lamps 11, 263
outdoor workplaces 89, 96–105 LEED (Leadership in Energy and Environmental Design)
road lighting 107, 110 134
illumination vector 219 LENI see Lighting Energy Numeric Indicator (LENI)
immediate surrounding area see surrounding area libraries 71
incandescent lamps 25–26, 282 life cycle costs 25
indirect lighting 301 life of lighting installation 302
illuminance calculations see also lamp survival factor (LSF)
Sumpner’s method 169–170 lifts 49
transfer factors 170–179 light boxes 23, 24
indoor lighting light centre 302
maintenance factors (MF) 280, 281, 282 light distribution see luminance distribution
photometric calculations 217–222 light exposure patterns 21–22
recommended standards for dwellings 128 light loss factor see maintenance factors (MF)
room surface maintenance factor (RSMF) 285, light measuring equipment 234–240
286–291 light output ratio (LOR) 27–28, 192–193, 303
indoor workplaces 29–85 light pollution 26–28, 90–91, 105
colour aspects 40–41 light radiation 143–147
daylight 44, 45, 121–122 light spectrum
energy efficiency 44–45, 124–125 brightness perception 16
flicker and stroboscopic effects 42 and human performance 5
glare 36–39 UV and IR tissue damage 24
illuminance 31–36 and visual perception 17
lighting in the interior space 39–40 and visual performance 9
lighting requirements 45–48, 49–84 lighting design criteria
luminance distribution 30–32 indoor workplaces 29–85
luminous environment 29–30 outdoor workplaces 86–94
maintenance factor (MF) 44 Lighting Energy Numeric Indicator (LENI) 45, 131,
variability of light 45 133, 303
industrial premises 53–67, 98, 100 lighting quality 1–2
lighting energy requirements 133 lighting requirements
minimum lighting efficacy 130 indoor workplaces 45–48, 49–84
infrared (IR) radiation 24 outdoor workplaces 94–95, 96–105
ingress protection (IP) classes 292 line sources 164–167
initial average luminance 301 linearity error 235
initial illuminance 301 loading see installed loading
initial luminous flux see rated luminous flux loading ramps/bays 49
installed loading 301 local lighting 303
integral lighting system 301 see also task area
intensity see luminous intensity localised lighting 303
intensity diagrams 192 longitudinal uniformity 113, 303
interference 146 louvres see daylight screens/louvres
327
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781

lumen (unit) 156 maximum illuminance 307


Index

luminaire code 304 maximum luminance 307


luminaire maintenance factor (LMF) 199, 304 ME classes 107–108, 112
indoor lighting 281, 284 measurement field 237, 307
outdoor lighting 283, 285 measurement grids 238–239
luminaire parasitic energy consumption 132–133, 304 mercury, environmental impact 26
luminaire parasitic power 304 mercury vapour lamps 282
luminaire power 304 mesopic vision 10–11, 147
luminaires metal casting 58
choosing 125–126 metal halide lamps 11, 282
classification 283, 292 metal working and processing 61, 64
definitions 303–304 minimum illuminance 307
durability 94 minimum luminance 307
luminance limits for DSE 43, 43 minimum value emergency factor 307
luminance verification 85 mixed traffic 308
luminous efficacy 128, 130, 304 modelling
luminous intensity 159 daylighting 122
photometric datasheets 191–217 indoor workplaces 40
photometric measurements 187–189, 190 outdoor workplaces 91–92
recommended standards 128 mood, and lighting quality 6, 18–19, 115
shielding angles 38, 38, 194–195, 310 motion of object 5
upward light output ratio (ULOR) 193, 313–314 motivation, and lighting quality 6, 18–19
luminance 4, 157–158, 304–305 motor traffic/motorised traffic 308
measurement 240 movement direction 13
normalised 195, 206 multi phosphor fluorescent lamps 263, 282
road surfaces 231, 240 Munsell system 263–264
verification 85 museums 71
luminance coefficients 228–229
luminance contrast 4, 7–8, 305 national calculation method (NCM) 129
between interior and view outside 120–121, 122 Natural Colour System (NCS) 264–265
luminance distribution 30–32 nominal lamp wattage 308
and visual perception 16–17, 17, 30 non point sources 164–167
see also illuminance uniformity non-daylight time usage 308
luminance meters 236–238, 305 non-domestic buildings
luminance uniformity 103, 107 Display Energy Certificates (DEC) 134
luminosity see brightness minimum lighting efficacy 130
luminous efficacy 128, 130, 305 recommended standards 129–130, 130
luminous environment 29–30, 305 non-visual effects 5, 21–23
luminous flux 147, 156, 305–306 normalised intensity tables 191–192
calculations 200–201 normalised luminance 195, 206
luminous intensity 156, 158–159, 306 Northern Ireland, energy efficiency requirements 127
calculations 223–233
G classes 114 obtrusive light 26–28, 90–91, 105, 308
(spacial) distribution 306 occupancy dependency factor 131, 308
lux (unit) 157 occupant behaviour 6, 12–14, 18–19, 115
occupant preferences 18
MacAdam ellipses 244–245 offices
machinery/machine, definition 306 lighting energy requirements 133
mail rooms 51 lighting requirements 84
maintained illuminance minimum lighting efficacy 130
definition 306 occupant preferences 18
indoor workplaces 31–35, 49–84, 96–105 offshore gas and oil structures 99
background area 35 open area lighting 308
illuminance on surfaces 31–32 operating costs 25
illuminance uniformity 35 operating time 308
immediate surrounding area 33–35 outdoor lighting
interior space 39–40 energy efficiency requirements 128
task area 32–33 maintenance factor (MF) 280
outdoor workplaces 87–89 photometric calculations 223–233
surrounding area 88 road lighting 223–232
task area 87–88 other outdoor areas 232–233
maintained luminance 307 see also road lighting
maintenance, luminaires 126 outdoor workplaces 86–114
maintenance costs 25 colour aspects 92–93
maintenance cycle 307 directional lighting 91–92
maintenance factors (MF) 280–285, 282, 307 energy considerations 93
indoor lighting 44, 280, 281, 284 flicker and stroboscopic effects 93
outdoor lighting 93, 280, 283, 285 glare 89–90
see also room surface maintenance factor (RSMF) illuminance 87–89
maintenance schedules 85, 307 lighting requirements 94–95, 96–105
manufacturing premises see industrial premises luminance distribution 87
328
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781
luminous environment parameters 86 reflectometers 310

Index
maintenance factor (MF) 93 refraction 144–145
obtrusive light 90–91 Relative Visual Performance (RVP) model 8–9, 9
photometric calculations 232 residential buildings see dwellings
outside view 116–118 rest rooms 50
overall uniformity 113 restaurants 69, 133
retail premises 13, 68, 133
parasitic energy consumption see luminaire parasitic retinal illumination 4–5
energy consumption retinal image quality 4–5
parasitic power see luminaire parasitic power road lighting 15, 106–114
parking areas 72, 100 calculations 223–233
perceptual system 5–6 classification of roads 106–111
performance see visual performance conflict areas 110, 110–111, 111, 114
peripheral vision 4, 147 lighting classes 112–114
petrochemical industry 100 measurement grids 239
photometers 309 subsidiary roads 109, 109, 113
see also luminance meters threshold increment (TI) 91, 232
photometric angles 187–189, 223–225
town and city centres 111
photometric calculations 200–212
traffic routes 106–107, 107–108, 112
indoor lighting 217–222
veiling luminance 91, 232
outdoor lighting 223–233
photometric centres 187–189, 190 road surfaces
photometric datasheets 191–217 luminance measurement 240
photometric measurements 187–189 reflective properties 228–229
field measurements 238–240 roadside light output ratio 193
light measuring equipment 234–240 rolling mills 64
photometric observer see luminous flux rooflights 120, 121, 122, 310
photometric quantities 156–160 room surface maintenance factor (RSMF) 285, 286–291,
photometry 309 310
photons 146 room surfaces
photopic vision 10, 147, 148–151 illuminance calculations 169–170
planar illuminance 159–160, 161–162, 221 maintained illuminances 31–32
Planck’s law 247 rubber industry 55
plant rooms 51
plastics industry 55 S classes 109, 113
point sources 161–164 safety
polar curve 192 lighting for 14–15, 104–105
polarisation 146 perception of 19, 19, 20
‘positive affect’ 19 safety sign 310
post rooms 51 sanitary facilities 50
power consumption 25–26 saw mills 103
see also energy efficiency SBEM (Simplified Building Energy Model) 129
power plants/stations 62, 101 scalar illuminance 221
practical emergency lamp flux 309 scattering 145
principal area 308 scene setting operation time 310
printers 62 schools 73–75
project management 137–138 Scotland, energy efficiency requirements 127, 129
protection of luminaires 292 scotopic vision 10, 147, 152–155
psychological effects 5–6, 17–18, 21–23 scotopic/photopic (S/P) ratios 9, 11
public assembly buildings 69–72 screens see daylight screens/louvres
public car parks 72, 100 Seasonal Affective Disorder (SAD) 23, 115
security lighting 15, 104–105
quality of lighting 1–2
see also crime prevention
quantum phenomena 146
semi-cylindrical illuminance 162–163, 222, 310
quartz metal halide lamps 11
semi-direct lighting 310
radiant flux see luminous flux semi-indirect lighting 310
railway installations 84, 101–102 sewage plants 104
RAL design system 271–272 shading devices 123
rated luminous flux 309 shielding against glare 37–38
recursive source subdivision 167–168 shielding angles 38, 38, 194–195, 310
reference ballast 309 shipyards 103
reference surface 32, 87, 309 shops see retail premises
reflectance 31, 309 signals, illuminated 13
glare control 37, 120 sky glow 26–28, 90–91
transfer factors 170–179, 179–186, 214–216 skylight 119–120, 311
reflected glare 38–39, 89–90 sleep phase disorder 22
reflections see veiling reflections Snell’s law 145
reflective properties solar altitude and azimuth 275–279
road surfaces 228–229 solar radiation 311
spectral reflectance values 252–254, 257–259 see also direct solar radiation; global solar radiation
329
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781

solar shading 123 tristimulus values 241–243, 313


Index

source (light source) 311 tungsten halogen lamps 11, 263


spacing (in an installation) 311
spacing tables (emergency lighting) 199–200, 200 ultra-violet (UV) radiation 24, 116
spacing to height ratio (SHR) 193, 201–203, 311 Unified Glare Rating (UGR) 36–37
spectral correction factor 235 calculation 206–212
spectral luminous efficiency 147, 148–155 limiting values 49–84, 313
spectral power distribution 247 photometric datasheets 196–198, 197
spectral reflectance 252–254, 257–259 verification 85
spectral sensitivities 11, 147 uniformity 313
specular reflection 122, 144 see also illuminance uniformity; luminance uniformity
see also veiling reflections upward flux maximum 313
spherical illuminance 163, 311 upward flux minimum 313
spill light 311 upward flux ratio (UFR) 313
sports facilities 75, 232 upward light output ratio (ULOR) 193, 313–314
lighting energy requirements 133 upward light ratio 314
measurement grids 239 useful area 131, 314
spotlighting 13, 311 useful data 314
stairs 49, 74, 102, 129 utilance 314
standard year time 312 utilisation factors (UF) 193, 203–206, 314
standards see British Standards
standby lighting 312 variability of light 45
steradian 156 vehicle construction and repair 66
storage areas 52, 98, 130 veiling luminance 91, 232, 233
store rooms 51 see also equivalent veiling luminance
stray light see spill light veiling reflections 38–39, 89–90, 314
stroboscopic effects 42, 93, 311 verification procedures 85, 105
sunlight 119, 312 view of outside 116–118
see also solar shading visual acuity 4, 9, 314
suprachiasmatic nuclei (SCN) 5 visual adaptation 4, 8
suprathreshold visual performance 7 visual comfort 314
surface colour 263–273
visual discomfort 5–6, 20
surface reflectance see reflectance
see also discomfort glare
surround ratio (SR) 107
visual field 4, 314
surrounding area
visual perception 16–19, 119
definition 312
visual performance 3, 3–6, 7–9, 315
indoor workplaces 33–35
see also visual task performance
outdoor workplaces 88
visual search 9–10
survival factor see lamp survival factor (LSF)
sustainability 94 visual sensitivity 11, 147
visual size 4
task area visual spectrum 9
definition 312 visual system 3–4, 147
energy efficient lighting 124–125 eye-brain pathways 23
indoor workplaces 31–32 spectral sensitivities 11, 147
daylighting 121–122 visual task, definition 315
directional lighting 40 visual task performance 6–12
illuminance uniformity 35 and glare 38–39
maintained illuminance 32–33 improving 12
outdoor workplaces Landolt C matrices 7, 8
directional lighting 92 mesopic conditions 10–11
illuminance uniformity and diversity 89 Relative Visual Performance (RVP) model 8–9, 9
maintained illuminance 87–88 visual search 9–10
textile manufacture and processing 65
theatres 70 water and sewage plants 104
threshold increment (TI) 91, 113, 232 well-being 19
threshold visual performance 7 Wien’s displacement law 247
tissue damage 24 window, definition 315
total energy used for lighting 132–133, 312 windows
total installed charging power 132, 312 glare control 120–121
total installed lighting power 132, 312 minimum glazed area for view 118
total installed parasitic power 132, 312–313 size and proportion 118, 128
total reflection 145 and view 116–118
toxic materials 26 work place 315
traffic lane 313 see also indoor workplaces; outdoor workplaces
tramways 101–102 work plane/working plane 315
transfer factors 170–179, 179–186, 214–216 work station 315
transmittance 313 see also display screen equipment (DSE)
travelators 49
tri-phosphor fluorescent lamps 263, 282 zone size calculation 201
330
Ho Ching Tang, thc.kevin@gmail.com, 7:26am 15/10/2012, 3, 40781

You might also like