Professional Documents
Culture Documents
June 19, 2012
June 19, 2012
June 19, 2012
TABLE OF CONTENTS
1.0 SCOPE
2.0 GENERAL
5.1 General
6.0 BIBLIOGRAPHY
1.0 SCOPE
This standard covers the selection of a specific type and size of power cable based on
particular applications and conditions in the Transmission system of Saudi Electricity
Company. (SEC) Saudi Arabia..
2.0 GENERAL
2.1 The selection of the specific type and size of power cable will be based on the
following:
To determine the appropriate design of a cable for a particular project, the following
information, with regard to service conditions, is required.
f. System frequency.
g. Type of earthing and, where the neutral is not effectively earthed, the
maximum permitted duration of earth fault conditions on any one
occasion.
i. Where outdoor terminals are specified. the altitude above sea level, if
above 1000m and whether excessive atmospheric pollution is
expected.
2.3 The process used in selecting and sizing a power cable shall be as follows:
d) Increasing, if necessary, the conductor size selected in (b) and (c) based on
short circuit currents.
e) Selection of a metallic shield size for MV, HV & EHV shielded cables
based on ground fault currents and its duration.
b) Depth of laying.
c) Thermal resistivities and kinds of soil along the route (e.g. sand. clay,
made-up ground), and whether this information is based on
measurement and inspection or only assumed parameters.
2.4 It is the responsibility of the Design Engineer to evaluate the economics of a given
power cable installation with the goal of providing the least expensive installation
within the limits of this standard.
3.1.1 Single conductor cables are easy to handle, splice, terminate and are
supplied in longer lengths than three conductor cables.
Their reactance is higher than three conductor cables and the use of a
metallic sheath for mechanical protection would be more expensive and
result in higher losses than with a three conductor cable.
TESP10403R01/FAZ Date of Approval: June 19, 2012 PAGE NO. 5 OF 15
TRANSMISSION ENGINEERING STANDARD TES-P-104.03, Rev.01
3.1.2 In general, the ampacity and voltage drop will be higher for three single
conductor cables when compared with a similar size of three conductor
cable.
Selection of Power Cable Insulation levels shall be as per Table 01-1, Table 01-2 &
Table 01-3 of TES-P-104.01, Rev. 01.
The following is a guide to the determination of the appropriate values of Uo, U, Um,
and Up, where
U- The rated power-frequency voltage between any two conductors for which the
cable and its accessories are designed or manufactured.
Um - The maximum rms power-frequency voltage between any two conductors for
which cables and accessories are designed. It is the highest voltage that can
be sustained under normal operating conditions at any time and at any point in
a system. It excludes temporary voltage variations due to fault conditions and
the sudden disconnection of large loads.
Up - The peak value of the impulse withstand voltage between each conductor and
screen or sheath for which the cable and its accessories are designed.
It is realized that normally the insulation thickness of the cable will be determined
either by Uo, U, Um or by Up. These voltages should be chosen based entirely on
the characteristics and requirements of the system, (U, Uo, Um, Up), and the
insulation thickness should be chosen to meet the most severe requirement. When
selecting the cable for the system, be sure that the cable manufacturer will supply a
cable with a Up value equal to or greater than that required by SEC.
Category A:
Where earth faults are cleared as rapidly as possible but in any case with in
1 min.
Category B:
This category comprises those systems, which, under fault conditions, are
operated for a short time only with one phase earthed. This period should,
in general, not exceed one hour, but a longer period can be tolerated for
radial-feed cables, and in special circumstances. Under no circumstances,
however, shall the period exceed eight hours.
Category C:
This category comprises all systems which do not fall into Category A&B.
3.2.2 Selection of Up
Notes:
The decision as to which of the three levels should be used in particular case
is dictated by the degree of exposure to overvoltages. This matter is dealt
with in Sub-clause 3.2.3.
a) Ampacity
3.3.2 Ampacity will determine the minimum size of conductor that can be used
for a given type of installation.
3.3.3 Voltage drop restrictions will determine a maximum length that a conductor
selected can be used before an increase in size is necessary to maintain the
voltage at the load above a desired minimum value.
3.3.4 Short circuit current will require an increase in the conductor size selected if
it is not already of sufficient size to safely dissipate the heat generated under
fault conditions.
3.3.5 Metallic shield sizing involves consideration of short circuit currents that
may flow in the shield if a fault to ground occurs. In the case of concentric
neutral cable, the shield will also carry neutral current and must be sized on
an ampacity basis.
4.1.a It is the responsibility of Design Engineer to use the basic parameters and factors,
detailed in the following paragraphs so that non-standard applications can be
calculated from the referenced publications.
4.1.b It is mandatory that the Design Engineer have full knowledge of the system route
limitations, circuitry and environment temperatures of the application under
consideration. He should consider the worst conditions of operation plus future
growth requirements of the circuit.
4.2 Since most applications of cable installation on the SEC system involve direct buried
cable, additional replacement cost for undersized cables must be considered. Duct
installed cables can be replaced within the limitations of the duct size.
4.2.1 The following basic parameters will assist the Design Engineer to further
evaluate the ampacities and objectively calculate alternative ampacities for a
cable to fulfill any load requirements:
a) Load - MVA.
b) Load Factor (LF).
c) Thermal Resistivity of the Soil (RHO).
d) Ambient Temperature - mean temperature of the soil or riser
temperature at above ground (in air) terminals.
e) Short circuit values with finite information on time duration (affects
sizing of copper in cable shield).
f) Derating factors for circuity (multiplicity of circuits and tie
formations).
g) Route location that might affect placement of splice bays/ manholes
and terminations.
4.3.1 The ampacity shall be calculated from the reference ICEA Specifications P-
46-426 and P-53-426 plus other data from manufacturers quotations and
handbooks.
4.4 For other factors, temperature with thermal resistivity (ρ), number of circuits,, the
following conversions should be utilized:
T = Tc – Ta¹
Tc - Ta
For installation of underground power cables on the SEC system, actual value of
thermal resistivity shall be utilized. This figure also includes the resistivity of the
bedding and backfill on underground cable installations and should be specifically
indicated on any ampacity calculations when using the referenced tables.
All ampacities shall be calculated on the basis of 100% load factor except ampacity
for Power Cables connected between Power Transformers and Switchgear shall be
calculated at 130% Load Factor.
4.7 Circuitry
4.7.1 For the calculation of desired ampacity for the load required, it may be
necessary to consider additional circuits also (installed in the same trench or
in parallel).
4.7.2 The number of circuits required is also predicated upon the availability of
conductor sizes for the insulation level under consideration. However, it is
considered essential that we utilize standard SEC cable sizes as indicated in
Table 04-1.
TABLE 04-1
35 7.7 69 2
70 10.7 138 2/0
120 14.2 237 4/0
185 17.6 369 350
300 22.5 592 600
400 25.6 789 750
500 28.8 986 1000
630 32.7 1233 1250
800 37.0 1579 1750
1000 41.6 1974 2000
1200 45.0 2368 -
1600 48.1 3158 -
2000 54.3 3948 -
2500 62.7 4935 -
4.8 Ampacity
4.8.1 Another source of information about power cable & ampacities is IPCEA
Publication No. P-46-426 and IEEE S-135.
This is for guidance on how to select an adequate cable for a particular application
and should not be considered as a standard method to solve all problems.
The factors that play roles in the selection of power cable are:
a) Voltage to be used.
b) Required reliability of the power supply.
c) Cost of material, installation and maintenance.
The Cost Engineer shall provide Tables with up-to-date costs for each item.
The system requirements and area conditions will determine the type of
installation to be used, which could be:
These factors will depend upon the cable installation conditions, cable
construction and environment where the cable will be laid and also upon the
characteristics of the materials used by the manufacturer to build the cable.
For these reasons, it is imperative to acquire correct data from responsible
sources. Manufacturer's cable data and recommendations should be
available, and this may vary from one manufacturer to another for the same
type of cable.
When the cables are laid in ground the derating factors depend upon
the following
The current carrying capacity of the cables laid in the ground shall be
reduced by a derating factor, if the cables are laid in an unfilled pipe of
PVC or PE in the ground. Normally internal diameter of pipe is 2 to 5
times the outer diameter of cable. It is however possible to reduce this
rating reduction by filling the pipe, after the cable has been pulled in,
with a material which is thermally equal to the ambient ground.
When the cables are laid above the ground the derating factors depend
upon the following
4.9.5 Adiabatic Short Circuit Current Rating for Conductor & Metallic
Screen/Sheath
The maximum short circuit current ratings for copper and aluminum
conductors are:
K .S ⎡θ f + β ⎤
IAD = ln ⎢ ⎥
t ⎣θ i + β ⎦
Where
For Copper=226
For Aluminum=148
For Lead or Lead Alloy=41
The cross-sectional area of the cable selected should be verified for the short
circuit current calculated for the place of application, versus the time
duration until the fault is cleared by the protective system.
Where,
b) Capacitance (C)
Where,
c) Reactance (X)
Where,
π : 3.1416
f : Frequency (Hz)
D : Diamter of conductor.
5.1 General
While the heat generated in a cable conductor determines the maximum current it can
carry without deterioration, it is often necessary to limit the current to an even lower
value because of excessive voltage drop. This problem is usually confined to the high
current, low voltage secondary of distribution circuits. For this reason, it is
advantageous to carry the primary circuit as close to the load as possible before
transforming so the secondary runs, where most of voltage drop occurs, will be small.
The voltage regulation of a cable may be calculated with the following formula:
U = 100 (VS-VL)
VL
Where:
U = voltage regulation in percent
Vs = voltage at source
(VS) 2 = (VL)2 + I2(R2 + X2)
VL = voltage at load
6.0 BIBLIOGRAPHY
i. IEC 60287 Calculation of Continuous Current Rating of Cables 100% Load Factor
ii IEC 60853 Calculation of the Cyclic and Emergency Current Rating of Cables