Professional Documents
Culture Documents
June 19, 2012
June 19, 2012
June 19, 2012
TABLE OF CONTENTS
1.0 SCOPE
2.1 Definitions
2.2 General Requirements
2.3 Routing Cables
2.4 Connectors
2.5 Conductor Connections
2.6 Heat Shrinkable Sleeve
2.7 Phasing of Cable Splices
2.8 Cable End Caps
2.9 Partial Discharge Test
3.1 Definitions
3.2 General Requirements
3.3 Precautions in Making Cable Terminations
3.4 Locating Cable Terminations
3.5 Grounding of Cable Terminations
3.6 Partial Discharge Measurement
3.7 Elbow Terminations
4.1 Definition
4.2 General Requirements
4.3 Locating Stress Cone
5.0 BIBLIOGRAPHY
1.0 SCOPE
This standard has been prepared as a guide for the splicing & termination of electric
power cables with copper or aluminum conductor that will be used for 0.6/1, 11, 13.8,
33, 34.5, 69, 110, 115, 132, 230 and 380 kV underground cables circuits in the
transmission system of Saudi Electricity Company (SEC) Saudi Arabia.
1.1.1 All splices & terminations shall meet the requirements of applicable
Saudi Electricity Company Material Standard Specification 12-
TMSS-10, 12-SDMS-01 (latest revision), IEEE-48, IEEE-404 and in
strict compliance with manufacturer’s instructions.
1.1.2 The cable joints & terminations shall also meet the standards of
SASO, AEIC, ICEA, IEC and/or any other internationally recognized
organizations.
1.1.6. Quality certificate (check list sheet) for each cable joint & termination
shall be filled and signed by the jointer/terminator and shall be
submitted to SEC as part of “final as built record”.
1.1.8 The contractor must insure in writing to Project Department that the
Cable Accessories stored (for manufacturer’s specifed period) are as
per the manufacturer recommendation.
TESP10404R01/YM Date of Approval: June 19, 2012 PAGE NO. 3 OF 12
TRANSMISSION ENGINEERING STANDARD TES-P-104.04, Rev. 01
This section covers various types of cable splices for all types and sizes of electric
power cables commonly used by SEC for high and low voltage power transmission.
Cable splices, not covered here shall be made according to the cable manufacturer's
recommendations and design.
2.1 Definitions
The term "Cable Splice" as used in the specifications refers to all splices, solid
taps and branches in electric power power cable as may be made in man holes,
hand holes, splice boxes, vaults, tunnels, etc. This term does not apply to
splices for pulling into ducts.
The various types of cable splices referred to in this section are defined as
follows:
Straight Splice:- A splice between two cables having the same number of
conductors.
"Y" Splice:- A splice for connecting one cable to two cables, all of which have
the same number of conductors.
The removal of the semi-conducting layers over the conductor and the
insulation should be executed in a manner prescribed in the manufacturer's
instructions for each splice.
unit. The air conditioning unit shall be capable of maintaining the relative
humidity below 40%.
Route the cables into their final positions, avoiding sharp bends and allowing
the ends to overlap. The overlap for splicing power cable should equal the
length of the completed splice. Also, it is desirable to have at least 15mm of
straight cable beyond ends of finished splice.
2.4 Connectors
2.4.2 Solder type connectors shall not be used with solid dielectric cables.
The normal procedure for cleaning exposed bare conductor ends prior
to installing connectors is brushing the surface of the conductor with
a steel brush until it is clean and bright. When cleaning aluminum
conductor for compression connections, it is necessary to apply an
SEC approved inhibitor compound to the exposed conductors
immediately after the wire brushings. The inhibitor compound will
prevent the formation of a non-conductive film of oxide on the
conductor surface, which would otherwise form as a result of the
chemical reaction between the aluminum surface and air.
After the cable joint connector is installed and prior to applying the
insulation tape, or heat shrink material, the surfaces of the insulation
and insulation shield must be thoroughly cleaned with a SEC
approved cable cleaning fluid. The use of benzine, or gasoline, for
this purpose, is not permitted.
When the cable splices are installed for the purpose of circuit expansion or
repair, the cables to be spliced shall be identified and labeled to correspond
with phase identification at the source side of the cable termination. Splicing of
the cables in accordance with proper phase identification will eliminate the
possibility of the splice introducing an out-of-phase condition in the circuit.
During the period that cables have been placed in ducts or trenches, and are to
be spliced at a later time, the cable ends are to be sealed to eliminate moisture
entering and corroding the cable conductor.
Heat shrinkable caps shall be utilized and installed on open ends of the cables
in order to maintain the integrity of the cable.
Partial discharge measurements shall be carried out for extra high voltage cable
230kV & 380kV at site after completion of splicing/jointing of the cable to
detect the weak points. The tests shall be carried out preferably during the HV
test or immediately thereafter.
3.1 Definitions
The term "Cable Termination" as used in this Section refers to all terminations
of electric power cable in order to effect an electrical connection to the cable
conductor.
TESP10404R01/YM Date of Approval: June 19, 2012 PAGE NO. 6 OF 12
TRANSMISSION ENGINEERING STANDARD TES-P-104.04, Rev. 01
Extreme care shall be taken in every step from start to finish to keep the cable
termination free from moisture, dirt, particles of metal and air pockets. To
accomplish this, the technician's hands, tools, containers and supplies must be
kept clean, dry and free from foreign matter at all times.
After the cable insulation has been exposed by removal of any section of the
outer covering, operations should be continued without interruption until the
cable termination is complete. Should it be necessary to leave an incomplete
cable termination overnight, the exposed cable insulation shall be protected by
a carefully applied covering of tape of the final type to be applied to the
termination and, in damp locations, this tape shall be covered by a waterproof
rubber or plastic tape. Suitable protection (depending on moisture and dirt
conditions and the voltage of the termination being made up) shall also be
applied to exposed insulation when terminating is interrupted for break time or
for necessary tests.
An exception can be there, when the open end of a single point grounded
section of circuit is terminated. Special provisions will be required to isolate
the cable shield or concentric neutral from the ground potential of metal parts
of the terminating rack or device.
Partial discharge measurements shall be carried out for extra high voltage cable
230 kV & 380 kV at site after completion of termination of the cable to detect
the weak points. The tests shall be carried out preferably during the HV test or
immediately thereafter.
3.6.2 All elbow terminations shall be rated 200 amperes for load break
service and 600 amperes for no-load break services.
3.6.3 The elbow terminations shall be provided with a capacitive test point.
3.6.5 All elbows shall comply with IEEE Standard No. 386.
4.1 Definition
The term "Stress Relief Cone" as used in this section is an essential part of
joints/splices & terminations, refers to a rubber or elastomer body which is
pushed over the insulation of the cable. The electric field/equipotential lines
are evenly spread out by the shape of the stress cone. The electric field
concentrations are prevented in this way. For insulated power cables,
however, it is necessary to remove a section of the outer jacket and shielding
etc and slip the body of stress cone that is stretched over the cable end.
The joints & splices/terminations must manage the electric field, otherwise the
electric field will concentrate at the end as shown in figure-1. The figure-1
shows the equipotential lines, the nearer these lines are to each other, the
greater the electric field, which can cause an electric breakdown in this region.
Fig-1
Fig-2
The bore diameter of the Stress Cone shall be narrower than the diameter over
cable insulation. The interface between cable and stress cone shall be brought
under mechanical pressure so that no cavities or air pockets can be formed
between cable and cone to prevent the electric breakdown.
5.0 BIBLIOGRAPHY
1. F.H. Kreuger, Industrial High Voltage, Delft University Press, 1991, ISBN 90-
6275-561-5. Parts 1, 2 and 3 in one Volume.
2. IBID, Industrial High Voltage, Delft University Press, 1992, ISBN 90-6275-
562-3. Parts 4, 5 and 6 in one Volume.
8. IEEE 1300 (IEEE Guide for Cable Connections for Gas-Insulated Substations)
12. EPRI Underground Transmission Systems Reference Book, 2006 Edition, 1014840