Jockey Pump Controller The display and interface shall be NEMA rated for Type 2,
The auxiliary jockey pump controller, if required and 3R, 4, 4X, and 12 protection and shall be fully accessible
specified on the plans and specifications, shall be factory without opening the controller door. The display and user
assembled, wired, and tested and specifically designed interface shall utilize multiple levels of password protec-
for this type of service. This controller shall be UL listed, tion for system security. A minimum of 3 password levels
and shall be of the same manufacturer as the main fire shall be provided. The operator shall have the ability to
pump controller. choose up to 2 lines of data to be displayed on the main
(home) information screen.
Approvals
Firetrol Jockey Pump Controllers are listed by Under- Digital Status/Alarm Messages
writers Laboratories, Inc., in accordance with UL508A, The digital display shall indicate text messages for
Standard for Industrial Controls, and CSA, Standard for the status and alarm conditions of:
Industrial Control Equipment (cUL). They are built to meet • Pump Running • Sequential Start Time
or exceed the requirements of the approving authorities as • Minimum Run Time • Low System Pressure
well as NEMA and the latest edition of NFPA 70, National • Pump Restart Timer • Fail to Start
Electrical Code. • Automatic Start • System Overpressure
• User Selectable #11 • Main Switch Position
Construction • User Selectable #21
The jockey pump controller shall be full voltage 1
User may choose from the following to be shown on main display
starting. The controller components shall be housed in (stop pressure setting, start pressure setting, cycles/period, cycles/
month, cycles/day, cycles/hour, total cycle count, pump total run time)
a NEMA Type 2 (IEC IP11) painted steel, wall mounted
enclosure (UL50E Construction). The controller shall
incorporate a circuit breaker and horsepower rated motor The Sequential Start Timer, Minimum Run Timer/Off
starter, control circuit transformer with 24VAC second- Delay Timer and Pump Restart Timer shall be displayed
ary and 200-600V multi-tap primary, main disconnect as numeric values reflecting the value of the remaining
switch, HAND-OFF-AUTOMATIC selector switch and a time.
0-300 psi (0-20.7 bar) stainless steel solid state pressure
transducer. LED Visual Indicators
LED indicators, visible with the door closed, shall
Short Circuit Current Ratings indicate:
The jockey shall have standard short circuit current • Power ON • Alarm
ratings of: • Pump Running
65kA @ 480 Volts Max.
25kA @ 600 Volts Data Logging
The digital display shall monitor the system and log
Operator Interface the following data:
The fire pump controller shall feature an operator in- • Motor Calls/Starts • Pump Total Run Time
terface with user keypad. The interface shall monitor and • Pump Last Run Time • Total Controller Pwr On Time
display motor operating conditions, including all alarms, • Last Pump Start • Min/Max System Pressure
events, and pressure conditions. The display shall be • Last Phase Fail/Reverse • Cycle Counts
a 128x64 Backlit LCD capable of customized graphics.
Event Recording shall be based upon successful tri-axial shake-table
Memory - The controller shall record all operational testing in accordance with ICC-ES AC-156. Certification
and alarm events to system memory. All events shall be without testing shall be unacceptable. Controller shall
time and date stamped and include an index number. be clearly labeled as rated for installation in seismic areas
The system memory shall have the capability of storing and a Certificate of Conformance shall be provided with
3000 events and allow the user access to the event log the controller.
via the user interface. The user shall have the ability to
scroll through the stored messages in groups of 1 or 10. Operation
A digitally set On Delay (Sequential Start) timer shall
Serial Communications be provided as standard. Upon a call to start, the user
The controller shall feature a RS485 serial communica- interface shall display a message indicating the remaining
tions port for use with 2 or 4 wire Modbus communica- time value of the On Delay timer.
tions. The controller shall include a Minimum Run Timer
to allow the motor to run for a set period of timer after
Solid State Pressure Transducer starting. The timer shall be programmable through the
The controller shall be supplied with a stainless steel user interface.
solid state pressure transducer with a range of 0-300 psi A pump restart delay timer shall be provided to al-
(0-20.7 bar) ±1 psi. The solid state pressure transducer low the residual voltage of the motor to decay prior to
shall be used for both display of the system pressure and restarting the motor and to prevent severe short cycling
control of the jockey pump controller. Systems using ana- of the motor. The timer shall be programmable through
log pressure devices or mercury switches for operational the user interface.
control will not be accepted. A Lamp Test feature shall be included. The user
The START and STOP PRESSURE shall be adjustable interface shall also have the ability to display the status
through the user interface. The pressure transducer shall of the system inputs and outputs.
be mounted inside the controller to prevent accidental An Audible Test feature shall be included to test the
damage. The pressure transducer shall be directly pipe operation of the audible alarm device (if supplied).
mounted to a bulkhead pipe coupling without any other The disconnect switch shall be mechanically inter-
supporting members. Field connections shall be made locked so that the enclosure door cannot be opened with
externally at the controller coupling to prevent distortion the handle in the ON position except by a hidden tool
of the pressure switch element and mechanism. operated defeater mechanism. The disconnect switch
shall be capable of being padlocked in the OFF position
Seismic Certification for installation and maintenance safety.
The controller shall be certified to meet or exceed the The controller shall be a Firetrol brand.
requirements of the 2006 International Building Code
and the 2010 California Building Code with Importance
Factor 1.5 and Sds equal to 1.88 or less. Qualifications
SP550E-01
Emerson Network Power.
The global leader in enabling Business-Critical Continuity. EmersonNetworkPower.com
AC Power Embedded Computing Outside Plant Racks & Integrated Cabinets
Connectivity Embedded Power Power Switching & Controls Services
DC Power Monitoring Precision Cooling Surge Protection
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2012 Emerson Electric Co.
'iretrol Brand Products Cary North Carolina 21 6SA Phone 1 0 200 'aY 1 0 20 www.firetrol.com
FTA550E Fire Pump Controllers for
Business-Critical Continuity
XG Jockey Pump Controllers
Product Description
PD550E-01
Emerson Network Power.
The global leader in enabling Business-Critical Continuity. EmersonNetworkPower.com
AC Power Embedded Computing Outside Plant Racks & Integrated Cabinets
Connectivity Embedded Power Power Switching & Controls Services
DC Power Monitoring Precision Cooling Surge Protection
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2012 Emerson Electric Co.
'iretrol Brand Products Cary North Carolina 21 6SA Phone 1 0 200 'aY 1 0 20 www.firetrol.com
FTA550E Fire Pump Controllers for
Business-Critical Continuity
XG Jockey Pump Controllers
Model Number Selection Guide
TIMER OPTION
-A With Programmable VOLTAGE 3-PHASE MAX HP
Running Period Timer (50/60 Hertz)
(See Voltage Selection for Maximum NOTE: For requirements not listed here please
HP/Voltage Combinations) contact a Firetrol representative or the
factory.
SPECIAL ENCLOSURES MISCELLANEOUS
-T NEMA Type 3R (IEC IP14) -AC Contacts for Remote Indication,
-E NEMA Type 4 (IEC IP56) Pump Run
-F NEMA Type 4X (IEC IP56) -AG Built-in reservoir low alarm (visible)
-FXP NEMA Type 4X (IEC IP56), #304 Stainless Steel, -AM Contacts for Remote Indication,
Painted Finish Failed to Start
-FD NEMA Type 4X (IEC IP56), #316 Stainless Steel, -AST Auto Start Contacts (for connection to
Unfinished** user supplied N.O. remote starting
-FDB NEMA Type 4X (IEC IP56), 12 Gauge, Seam device)
Welded, #316 Stainless Steel, Polished and -AW Contacts for Remote Indication,
Brushed Finish Reservoir Low
-FDP NEMA Type 4X (IEC IP56), #316 Stainless Steel -BW Contacts for Remote Indication,
Painted Finish Phase Failure/Reversal
-G NEMA Type 12 (IEC IP52 -BY Contacts for Remote Indication,
** Unfinished (Not painted, polished or brushed) Pump Overload
-CPL Contacts for remote indication, system
HIGHER SHORT CIRCUIT CURRENT RATING overpressure
AF Model (See selection data sheet) -EF Contacts for Remote Indication,
Fusible Disconnect Switch with Fuses (200kA) Switch Not in Auto
-HV Audible Alarm
ANTI-CONDENSATION SPACE HEATERS1 -KH Contacts for Remote Indication, Common
-H 120 Volt Space Heater Output for Any Alarm
-J 120 Volt Space Heater With -NZ Interlock Input Contacts to Prevent Jockey
Thermostat Pump from Starting During Main
-K 120 Volt Space Heater With Controller Operation
Humidistat -PE Contacts for remote indication, low system
-L 240 Volt Space Heater pressure
-M 240 Volt Space Heater With -S Tropicalization
Thermostat -SEI Seismic Certification (in accordance
-N 240 Volt Space Heater With with IBC)
Humidistat -ZPA Customized, annual service display message
(when factory programmed or programmed by
1
Power source supplied by others Firetrol representative during start-up)
-ZPJ Communications, Serial Modbus over
PRESSURE TRANSDUCERS RS485, 2 or 4 wire
-C 0-300 psi (0-21.1 bar) Pressure Transducer
for corrosive service *Export Packaging available for additional cost
-D 0-600 psi (0-42.25 bar) Pressure Transducer
for Corrosive Service
NOTE: For requirements not listed here, please contact
your Firetrol representative or the factory.
SD550E-01
Emerson Network Power.
The global leader in enabling Business-Critical Continuity. EmersonNetworkPower.com
AC Power Embedded Computing Outside Plant Racks & Integrated Cabinets
Connectivity Embedded Power Power Switching & Controls Services
DC Power Monitoring Precision Cooling Surge Protection
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2012 Emerson Electric Co.
'iretrol Brand Products Cary North Carolina 21 6SA Phone 1 0 200 'aY 1 0 20 www.firetrol.com