Fire Pump Controllers for

Business Critical Continuity™

JockeyXG Pump Controllers


FTA550E Series
Firetrol® FTA550E Series JockeyXG Pump · Pressure recording
Controllers are intended for use with fire pump · Event log (3000 events stored in controller
systems. They are used for pressure maintenance memory)
in fire pump installations to prevent unnecessary · Data log (including cycle counter)
operation of the main fire pump. · Door mounted display/user interface featuring
a 128 x 64 pixel backlit LCD Graphical Display,
Approvals — Firetrol Jockey Pump Controllers Membrane Type User Controller Push-buttons
are listed by Underwriters Laboratories, Inc., in and LED indication for:
accordance with UL508A, Standard for Industrial · Power ON
Controls, and CSA, Standard for Industrial Control · Pump Running
Equipment (cUL). They are built to meet or exceed · Alarm
the requirements of the approving authorities as · 2 lines of user selectable display information
well as NEMA and the latest edition of NFPA 70,
National Electrical Code. FTA550 Jockey Pump Controllers
The FTA550E Jockey Pump Controller utilizes
Enclosures — The standard enclosures are NEMA across the line, full voltage starting. Full voltage
Type 2 (IEC IP11), drip-proof, for installation in areas is applied to the motor as soon as the controller is
protected from direct sunlight with an ambient actuated, and the motor supplies its rated torque.
temperature above 41°F (5° C). When using full voltage starting, the power source
must have sufficient KVA capacity to handle motor
Standard Features—The following are included locked rotor current and prevent the line voltage
as standard with each controller: from dropping below acceptable levels.
· NEMA Type 2 (IEC IP11) Painted Steel Enclosure When the controller is actuated, either by a
· Circuit Breaker drop in system pressure (in the “Auto” mode), or by
· Horsepower Rated Motor Starter placing the HAND-OFF-AUTO switch in the “Hand”
· Suitable for use as service equipment position, the pump will start. In the “Auto” mode,
· HAND-OFF-AUTO selector switch the pump will continue to run until the pressure re-
· Minimum run timer turns to a normal level and the minimum run timer
· On-Delay timer has expired, whichever occurs last. In the “Hand”
· Pump restart timer mode, the pump will continue to run until the HAND-
· Control circuit transformer with 24VAC OFF-AUTO selector switch is moved from the “Hand”
secondary position.
· 0-300 psi (0-20.7 bar) stainless steel solid state The stainless steel pressure transducer is mount-
pressure transducer ed inside the enclosure and is piped to a fitting on
· Overpressure indication the bottom of the enclosure.
· Low Pressure indication
· Failed to start indication Options and Modifications —Refer to the Product
· Main switch not in “Auto” alarm Description sheet for a complete listing of Options
and Modifications.
CB550E-01
Emerson Network Power.
The global leader in enabling Business-Critical Continuity. EmersonNetworkPower.com
AC Power Embedded Computing Outside Plant Racks & Integrated Cabinets
Connectivity Embedded Power Power Switching & Controls Services
DC Power Monitoring Precision Cooling Surge Protection
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2010 Emerson Electric Co.
'iretrol Brand Products Cary North Carolina 21 6SA Phone 1 0 200 'aY 1 0 20 www.firetrol.com
FTA550E Fire Pump Controllers for
Business-Critical Continuity
Jockey Pump Controllers
Specifications

Jockey Pump Controller The display and interface shall be NEMA rated for Type 2,
The auxiliary jockey pump controller, if required and 3R, 4, 4X, and 12 protection and shall be fully accessible
specified on the plans and specifications, shall be factory without opening the controller door. The display and user
assembled, wired, and tested and specifically designed interface shall utilize multiple levels of password protec-
for this type of service. This controller shall be UL listed, tion for system security. A minimum of 3 password levels
and shall be of the same manufacturer as the main fire shall be provided. The operator shall have the ability to
pump controller. choose up to 2 lines of data to be displayed on the main
(home) information screen.
Approvals
Firetrol Jockey Pump Controllers are listed by Under- Digital Status/Alarm Messages
writers Laboratories, Inc., in accordance with UL508A, The digital display shall indicate text messages for
Standard for Industrial Controls, and CSA, Standard for the status and alarm conditions of:
Industrial Control Equipment (cUL). They are built to meet • Pump Running • Sequential Start Time
or exceed the requirements of the approving authorities as • Minimum Run Time • Low System Pressure
well as NEMA and the latest edition of NFPA 70, National • Pump Restart Timer • Fail to Start
Electrical Code. • Automatic Start • System Overpressure
• User Selectable #11 • Main Switch Position
Construction • User Selectable #21
The jockey pump controller shall be full voltage 1
User may choose from the following to be shown on main display
starting. The controller components shall be housed in (stop pressure setting, start pressure setting, cycles/period, cycles/
month, cycles/day, cycles/hour, total cycle count, pump total run time)
a NEMA Type 2 (IEC IP11) painted steel, wall mounted
enclosure (UL50E Construction). The controller shall
incorporate a circuit breaker and horsepower rated motor The Sequential Start Timer, Minimum Run Timer/Off
starter, control circuit transformer with 24VAC second- Delay Timer and Pump Restart Timer shall be displayed
ary and 200-600V multi-tap primary, main disconnect as numeric values reflecting the value of the remaining
switch, HAND-OFF-AUTOMATIC selector switch and a time.
0-300 psi (0-20.7 bar) stainless steel solid state pressure
transducer. LED Visual Indicators
LED indicators, visible with the door closed, shall
Short Circuit Current Ratings indicate:
The jockey shall have standard short circuit current • Power ON • Alarm
ratings of: • Pump Running
65kA @ 480 Volts Max.
25kA @ 600 Volts Data Logging
The digital display shall monitor the system and log
Operator Interface the following data:
The fire pump controller shall feature an operator in- • Motor Calls/Starts • Pump Total Run Time
terface with user keypad. The interface shall monitor and • Pump Last Run Time • Total Controller Pwr On Time
display motor operating conditions, including all alarms, • Last Pump Start • Min/Max System Pressure
events, and pressure conditions. The display shall be • Last Phase Fail/Reverse • Cycle Counts
a 128x64 Backlit LCD capable of customized graphics.
Event Recording shall be based upon successful tri-axial shake-table
Memory - The controller shall record all operational testing in accordance with ICC-ES AC-156. Certification
and alarm events to system memory. All events shall be without testing shall be unacceptable. Controller shall
time and date stamped and include an index number. be clearly labeled as rated for installation in seismic areas
The system memory shall have the capability of storing and a Certificate of Conformance shall be provided with
3000 events and allow the user access to the event log the controller.
via the user interface. The user shall have the ability to
scroll through the stored messages in groups of 1 or 10. Operation
A digitally set On Delay (Sequential Start) timer shall
Serial Communications be provided as standard. Upon a call to start, the user
The controller shall feature a RS485 serial communica- interface shall display a message indicating the remaining
tions port for use with 2 or 4 wire Modbus communica- time value of the On Delay timer.
tions. The controller shall include a Minimum Run Timer
to allow the motor to run for a set period of timer after
Solid State Pressure Transducer starting. The timer shall be programmable through the
The controller shall be supplied with a stainless steel user interface.
solid state pressure transducer with a range of 0-300 psi A pump restart delay timer shall be provided to al-
(0-20.7 bar) ±1 psi. The solid state pressure transducer low the residual voltage of the motor to decay prior to
shall be used for both display of the system pressure and restarting the motor and to prevent severe short cycling
control of the jockey pump controller. Systems using ana- of the motor. The timer shall be programmable through
log pressure devices or mercury switches for operational the user interface.
control will not be accepted. A Lamp Test feature shall be included. The user
The START and STOP PRESSURE shall be adjustable interface shall also have the ability to display the status
through the user interface. The pressure transducer shall of the system inputs and outputs.
be mounted inside the controller to prevent accidental An Audible Test feature shall be included to test the
damage. The pressure transducer shall be directly pipe operation of the audible alarm device (if supplied).
mounted to a bulkhead pipe coupling without any other The disconnect switch shall be mechanically inter-
supporting members. Field connections shall be made locked so that the enclosure door cannot be opened with
externally at the controller coupling to prevent distortion the handle in the ON position except by a hidden tool
of the pressure switch element and mechanism. operated defeater mechanism. The disconnect switch
shall be capable of being padlocked in the OFF position
Seismic Certification for installation and maintenance safety.
The controller shall be certified to meet or exceed the The controller shall be a Firetrol brand.
requirements of the 2006 International Building Code
and the 2010 California Building Code with Importance
Factor 1.5 and Sds equal to 1.88 or less. Qualifications

SP550E-01
Emerson Network Power.
The global leader in enabling Business-Critical Continuity. EmersonNetworkPower.com
AC Power Embedded Computing Outside Plant Racks & Integrated Cabinets
Connectivity Embedded Power Power Switching & Controls Services
DC Power Monitoring Precision Cooling Surge Protection
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2012 Emerson Electric Co.
'iretrol Brand Products Cary North Carolina 21 6SA Phone 1 0 200 'aY 1 0 20 www.firetrol.com
FTA550E Fire Pump Controllers for
Business-Critical Continuity
XG Jockey Pump Controllers
Product Description

· Failed to start indication


· Main switch not in “Auto” alarm
· Pressure recording
· Event log (3000 events stored in controller
memory)
· Data log (including cycle counter)
· Door mounted display/user interface featuring
a 128 x 64 pixel backlit LCD Graphical Display,
Membrane Type User Controller Push-buttons
and LED indication for:
· Power ON
· Pump Running
· Alarm
· 2 lines of user selectable display information
Description—Firetrol® FTA550E XG Jockey Pump
Controllers are intended for use with fire pump NOTE: FTA550E XG Jockey Pump Controllers are
systems. They are used for pressure maintenance available as standard in the voltage/horse-
in fire pump installations to prevent unnecessary power combinations shown below and with
operation of the main fire pump. the options shown on the reverse side. For
other combinations and options, please con-
Approvals—Firetrol jockey pump controllers are sult your Firetrol representative or the factory.
listed by Underwriters’ Laboratories, Inc., in ac-
cordance with UL508A, Standard for Industrial VOLTAGE 3-PHASE MAX HP Short Circuit
Controls, and CSA, Standard for Industrial Control (50/60 Hertz) Current Rating
Equipment. They are built to meet or exceed the
requirements of the approving authorities as well -H 200 - 208V 25 65kA
as NEMA and the latest edition NFPA 70, National -A 220 - 240V 30 65kA
Electrical Code. -F 380 - 415V 40 65kA
-B 440 - 480V 50 65kA
Standard Features—The following are included as -C 550 - 600V 50 25kA
standard with each controller:
· NEMA Type 2 (IEC IP11) Painted Steel Enclosure VOLTAGE 1-PHASE* MAX HP Short Circuit
· Circuit Breaker (50/60 Hertz) Current Rating
· Horsepower rated motor starter
· Suitable for use as service equipment -D 110-120V 5 200kA
· HAND-OFF-AUTO selector switch -T 200-208V 15 200kA
· Minimum run timer -E 220-240V 15 200kA
· On-Delay timer
· Pump Restart Timer * Single phase units supplied standard with
· Control circuit transformer with 24VAC fusible disconnect switch and fuses
secondary
· 0-300 psi (0-20.7 bar) stainless steel solid state
pressure transducer NOTE: Firetrol Brand Jockey Pump controllers DO NOT
· Overpressure indication CONTAIN MERCURY filled pressure switches.
· Low Pressure indication
SPECIAL ENCLOSURES -AC Contacts for Remote Indication,
-T NEMA Type 3R (IEC IP14) Pump Run
-E NEMA Type 4 (IEC IP56) -AG Built-in reservoir low alarm (visible)
-F NEMA Type 4X (IEC IP56) -AM Contacts for Remote Indication,
-FXP NEMA Type 4X (IEC IP56), #304 Stainless Steel, Failed to Start
Painted Finish -AST Auto Start Contacts (for connection to
-FD NEMA Type 4X (IEC IP56), #316 Stainless Steel, user supplied N.O. remote starting
Unfinished** device)
-FDB NEMA Type 4X (IEC IP56), 12 Gauge, Seam -AW Contacts for Remote Indication,
Welded, #316 Stainless Steel, Polished and Reservoir Low
Brushed Finish -BW Contacts for Remote Indication,
-FDP NEMA Type 4X (IEC IP56), #316 Stainless Steel Phase Failure/Reversal
Painted Finish -BY Contacts for Remote Indication,
-G NEMA Type 12 (IEC IP52 Pump Overload
** Unfinished (Not painted, polished or brushed) -CPL Contacts for remote indication, system
overpressure
HIGHER SHORT CIRCUIT CURRENT RATING -EF Contacts for Remote Indication,
AF Model (See selection data sheet) Switch Not in Auto
Fusible Disconnect Switch with Fuses (200kA) -HV Audible Alarm
-KH Contacts for Remote Indication, Common
ANTI-CONDENSATION SPACE HEATERS1 Output for Any Alarm
-H 120 Volt Space Heater -NZ Interlock Input Contacts to Prevent Jockey
-J 120 Volt Space Heater With Pump from Starting During Main
Thermostat Controller Operation
-K 120 Volt Space Heater With -PE Contacts for remote indication, low system
Humidistat pressure
-L 240 Volt Space Heater -S Tropicalization
-M 240 Volt Space Heater With -SEI Seismic Certification (in accordance
Thermostat with IBC)
-N 240 Volt Space Heater With -ZPA Customized, annual service display message
Humidistat (when factory programmed or programmed by
Firetrol representative during start-up)
1
Power source supplied by others -ZPJ Communications, Serial Modbus over
RS485, 2 or 4 wire
PRESSURE TRANSDUCERS
-C 0-300 psi (0-21.1 bar) Pressure Transducer *Export Packaging available for additional cost
for corrosive service
-D 0-600 psi (0-42.25 bar) Pressure Transducer
for Corrosive Service NOTE: For requirements not listed here, please contact
MISCELLANEOUS your Firetrol representative or the factory.

PD550E-01
Emerson Network Power.
The global leader in enabling Business-Critical Continuity. EmersonNetworkPower.com
AC Power Embedded Computing Outside Plant Racks & Integrated Cabinets
Connectivity Embedded Power Power Switching & Controls Services
DC Power Monitoring Precision Cooling Surge Protection
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2012 Emerson Electric Co.
'iretrol Brand Products Cary North Carolina 21 6SA Phone 1 0 200 'aY 1 0 20 www.firetrol.com
FTA550E Fire Pump Controllers for
Business-Critical Continuity
XG Jockey Pump Controllers
Model Number Selection Guide

FTA550E XG JOCKEY PUMP CONTROLLERS


FTA550E-A A __ __ __ __ - __ (Example: FTA550E-AA015B-T-BY)

FTA NUMBER OPTIONS & MODIFICATIONS


FTA550E (See other side)

TIMER OPTION
-A With Programmable VOLTAGE 3-PHASE MAX HP
Running Period Timer (50/60 Hertz)

MOTOR CURRENT PROTECTION -H 200 - 208V 25


-A Circuit Breaker -A 220 - 240V 30
*Suitable for Use as Service Equipment* -F 380 - 415V WYE 40
Short Circuit Current Rating -B 440 - 480V WYE 50
200-480V - 65kA -C 550 - 600V WYE 50
550-600V - 25kA
-F Fusible Disconnect Switch w/ Fuses VOLTAGE 1-PHASE * MAX HP
*Suitable for Use as Service Equipment* (50/60 Hertz)
Short Circuit Current Rating
200-600V - 200kA -D 110-120 Volts 5
-T 200-208 Volts 15
HORSEPOWER (KW) -E 220-240 Volts 15
014 - 1/4 HP (.18) 004 - 4 HP (3)
013 - 1/3 HP (.23) 005 - 5 HP (3.7) * Single phase units supplied standard
012 - 1/2 HP (.37) 006 - 5 1/2 HP (4) with Fusible Disconnect Switch & Fuses
034 - 3/4 HP (.56) 007 - 7 1/2 HP (5.5) (Select Model FTA550E-AF....)
001 - 1 HP (.75) 010 - 10 HP (7.5)
011 - 1 1/2 HP (1.1) 015 - 15 HP (11)
002 - 2 HP (1.5) 020 - 20 HP (15)
003 - 3 HP (2.2) 025 - 25 HP (19)
030 - 30 HP (22)
040 - 40 HP (29)
050 - 50 HP (37)

(See Voltage Selection for Maximum NOTE: For requirements not listed here please
HP/Voltage Combinations) contact a Firetrol representative or the
factory.
SPECIAL ENCLOSURES MISCELLANEOUS
-T NEMA Type 3R (IEC IP14) -AC Contacts for Remote Indication,
-E NEMA Type 4 (IEC IP56) Pump Run
-F NEMA Type 4X (IEC IP56) -AG Built-in reservoir low alarm (visible)
-FXP NEMA Type 4X (IEC IP56), #304 Stainless Steel, -AM Contacts for Remote Indication,
Painted Finish Failed to Start
-FD NEMA Type 4X (IEC IP56), #316 Stainless Steel, -AST Auto Start Contacts (for connection to
Unfinished** user supplied N.O. remote starting
-FDB NEMA Type 4X (IEC IP56), 12 Gauge, Seam device)
Welded, #316 Stainless Steel, Polished and -AW Contacts for Remote Indication,
Brushed Finish Reservoir Low
-FDP NEMA Type 4X (IEC IP56), #316 Stainless Steel -BW Contacts for Remote Indication,
Painted Finish Phase Failure/Reversal
-G NEMA Type 12 (IEC IP52 -BY Contacts for Remote Indication,
** Unfinished (Not painted, polished or brushed) Pump Overload
-CPL Contacts for remote indication, system
HIGHER SHORT CIRCUIT CURRENT RATING overpressure
AF Model (See selection data sheet) -EF Contacts for Remote Indication,
Fusible Disconnect Switch with Fuses (200kA) Switch Not in Auto
-HV Audible Alarm
ANTI-CONDENSATION SPACE HEATERS1 -KH Contacts for Remote Indication, Common
-H 120 Volt Space Heater Output for Any Alarm
-J 120 Volt Space Heater With -NZ Interlock Input Contacts to Prevent Jockey
Thermostat Pump from Starting During Main
-K 120 Volt Space Heater With Controller Operation
Humidistat -PE Contacts for remote indication, low system
-L 240 Volt Space Heater pressure
-M 240 Volt Space Heater With -S Tropicalization
Thermostat -SEI Seismic Certification (in accordance
-N 240 Volt Space Heater With with IBC)
Humidistat -ZPA Customized, annual service display message
(when factory programmed or programmed by
1
Power source supplied by others Firetrol representative during start-up)
-ZPJ Communications, Serial Modbus over
PRESSURE TRANSDUCERS RS485, 2 or 4 wire
-C 0-300 psi (0-21.1 bar) Pressure Transducer
for corrosive service *Export Packaging available for additional cost
-D 0-600 psi (0-42.25 bar) Pressure Transducer
for Corrosive Service
NOTE: For requirements not listed here, please contact
your Firetrol representative or the factory.

SD550E-01
Emerson Network Power.
The global leader in enabling Business-Critical Continuity. EmersonNetworkPower.com
AC Power Embedded Computing Outside Plant Racks & Integrated Cabinets
Connectivity Embedded Power Power Switching & Controls Services
DC Power Monitoring Precision Cooling Surge Protection
Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co. ©2012 Emerson Electric Co.