Sewage Treatment Plant Layout

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

SEWAGE TREATMENT PLANT 1

CAPACITY: 1.0 MLD LOCATION: MEDICAL STORE BACK SIDE

0
1 2 3 4 5 6

Recycle
8B 6A

9 7 7
To Flushing 10 8 A

8A

Item description Size lxbxh (in m) Capacity (in lit)


0 Bar Screen 2 x 2.5 x 1 5000
11 12
1 Raw sludge 10.59 x 3.66 x 3.96 1,53,000
2 Anoxic Tank 2.54 x 3.96 x 2.7 27,000 13 Dry Bed
3 Pre-aeration tank 12.9 x 6.1 x 3.96 2,90,000
4 Aeration tank 14.32 x 6.55 x 4.57 4,28,000
5 Clarifier 9 x 3.96 2,52,000
6 Filter Feed Tank 8.25 x 6.1 x 3.5 1,75,000 Garden
6A Dozing Pump 4 - 6 l/hr 35,000/h
7 PSF, ACF 2 x 2.5 h x 2 set 70,000/h
7A UV system 30,000 l/h 60,000/h
8 Outlet Tank 3.0 x 3.0 x 3.0 27,000
8A Bag filter 20 m3/h 40,000/h
8B Dozing pump 110 l/h x 2 220/h
9 UF filter 2.5 m3/h 25000/h
10 UF Permeate Tank 6.1 x 2.44 x 3.04 45,250 Abbreviations:
11 Aerobic Collection Tank 4.5 x 4.5 x 2.4 48,600 PSF: Pressure Sand Filter UF: Ultra Filter
12 Dry bed 3.0 x 2.4 x 1.0 10 nos ACF: Activated Carbon Filter UV: Ultra Violet
13 Decanter 2 m3/h 2000/h

Page 1 of 6
SOURCE OF INLET WATER SOURCE OF OUTLET
1. Hospital 1. Lagoon  Garden
2. Medical College 2. Harvest pit (Medical Staff Quarters B Block)
3. Staff Quarters A,B,C,D 3. Harvest pit (Medical Staff Quarters D Block)
4. Medical Ladies Hostel
5. Store
6. Mortuary
7. OP Canteen
8. VC Quarters

SEWAGE TREATMENT PLANT PROCESS


1. Raw Water Collection Tank
2. Anoxic Tank Librate Nitrate gas fixed on agitator
3. Aeration Tank Librate Carbon-dioxide and energy
4. Clarifier Tank Sludge accumulated in center of tank. Sludge again recycled Aeration Tank. Clear water wearing out of filter feed tank
5. Filter Feed tank after clarifier water come to the filter feed tank
6. Chemical dozing disinfection chemical chlorine dioxide
7. Sand filter residual bed, Suspended solid removal
8. Treated water collection tank
9. Ultra Filtration up 0.2 micron Turbidity and removes odour

PCB NORMS (STP) RAW SEWAGE WATER PARAMETER TREATED WATER PARAMETER
pH: 6 to 9 pH: 7.81 pH: 6.98
TDS: ≤ 2100 ppm TDS: 1744 ppm TDS: 1682 ppm
TSS: ≤ 30 ppm TSS: 172 ppm TSS: 12 ppm
COD: ≤ 250 ppm COD: 696 ppm COD: 56 ppm
BOD: ≤ 20 ppm BOD: 282 ppm BOD: 8 ppm

Page 2 of 6
SEWAGE TREATMENT PLANT 2
CAPACITY: 2.2 MLD LOCATION: M BLOCK BACK SIDE

0 5 5A
1 2 3 4 6
1A

4A
10 9 6B

To Flushing 7
11 8
6A

Garden
Item description Size lxbxh (in m) Capacity (in lit)
0 Bar Screen 3 x 2.8 x 1.2 10,000
1 Raw Water Collection Tank 14.5 x 12.0 x 3.0 5,00,000
1A Anoxic Tank 6.0 x 4.0 x 4.87 1,17,000
2 Aeration Tank 14.66 x 10.9 x 4.87 7,75,000
3 Clarifier Tank 9 m x 3.65 md 2,80,000
4 Filter Feed Tank 14.5 x 12.0 x 3.0 5,00,000
4A Dozing pumps 4 - 6 l/h 35,000/h
5,5A PSF, ACF 2 x 2.5h x 5 set 1,75,000/h
6 Treated Water Collection Tank 8.25 x 6.10 x 3.5 1,76,000
6A Bag filter 36 m3/h x 2 72000/h
6B Dozing system 200 l/h x 2 400/h
7 UF Filter 50 m3/h 50,000/h
8 UF Permeate Tank 12.9 x 6.10 x 3.96 2,90,000 Abbreviations:
9 Aerobic Collection Tank 4.5 x 4.5 x 2.4 48,600 PSF: Pressure Sand Filter UF: Ultra Filter
10 Decanter 4 m3/h 4000/h ACF: Activated Carbon Filter UV: Ultra Violet
11 Dry beds 3.0 x 2.4 x 1.0 25 nos

Page 3 of 6
SOURCE OF INLET WATER SOURCE OF INLET WATER SOURCE OF OUTLET
1. Meenakshi Hostel 7. VEC Staff Quarters 1. Lagoon  Garden
2. Director Quarters 8. Kalpana Chawla 2. Harvest pit (Medical College East side)
3. Mens Hostel G,H,I,J Block 9. Senbagam block 3. Lake Area Garden
4. D, E, F, K, J mess, NRI hostel 10. M Block
5. Sannasi Hostel 11. Vanga Laundry
6. Old Staff Quarters 12. UG Kitchen Block

SEWAGE TREATMENT PLANT PROCESS


1. Raw Water Collection Tank
2. Anoxic Tank Librate Nitrate gas fixed on agitator
3. Aeration Tank Librtae Carbon-dioxide and energy
4. Clarifier Tank Sludge accumulated in center of tank. Sludge again recycled Aeration Tank. Clear water wearing out of filter feed tank
5. Filter Feed tank after clarifier water come to the filter feed tank
6. Chemical dozing disinfection chemical chlorine dioxide
7. Sand filter residual bed, Suspended solid removed
8. Treated water collection tank
9. Ultra Filtration up 0.2 micron Turbidity and removes odour

PCB NORMS (STP) RAW SEWAGE WATER PARAMETER TREATED WATER PARAMETER
pH: 6 to 9 pH: 7.64 pH: 7.04
TDS: ≤ 2100 ppm TDS: 1712 ppm TDS: 1656 ppm
TSS: ≤ 30 ppm TSS: 168 ppm TSS: 14 ppm
COD: ≤ 250 ppm COD: 712 ppm COD: 64 ppm
BOD: ≤ 20 ppm BOD: 256 ppm BOD: 12 ppm

Page 4 of 6
SEWAGE TREATMENT PLANT 3
CAPACITY: 3.7 MLD LOCATION: DENTAL BACK SIDE

0 1A
5 5A
1 2 3 4 6

4A

6B
10 9
To Flushing 7
8
11
6A

Garden
Item description Size lxbxh (in m) Capacity (in lit)
0 Bar Screen 1.75 x 1.50 x 1.20 3000
1 Raw Water Collection Tank 11.0 X 12.9 X 3.65 5,00,000
1A Anoxic Tank 12 x 6 x 4 2,88,000
2 Aeration Tank 25.0 X 12.19 X 4.00 12,00,000
3 Clarifier Tank 12.1 m x 4.50 md 2,80,000
4 Filter Feed Tank 12.10 X 6.10 X 3.35 2,47,000
4A Dozing pumps 4 - 6 l/h 35,000/h
5,5A PSF, ACF 2  x 2.5 h x 7 set 2,45,000/h
6 Treated Water Collection Tank 8.25 x 6.10 x 3.5 1,76,000
6A Bag filter 36 m3/h x 2 72,000/h
6B Dozing system 200 lh x 2 400/h
7 UF Filter 50 m3/h 5,00,000/h
8 UF Permeate Tank 7.33 x 10.9 x 4.87 3, 87,500 Abbreviations:
9 Aerobic Collection Tank 4.5 x 4.5 x 2.4 48,600 PSF: Pressure Sand Filter UF: Ultra Filter
10 Decanter 6 m3/h 6000/h ACF: Activated Carbon Filter UV: Ultra Violet
11 Dry beds 4.0 x 4.0 x 2.0 25 nos

Page 5 of 6
SOURCE OF INLET WATER 10. Guest House 20. Auditorium SOURCE OF OUTLET
11. Basic Engineering 21. FSH
1. Main campus 1. Outlet I: Lake Area Garden
12. Began Hostel 22. PF Hostel
2. University Building 2. Outlet II: VEC Area Garden
13. Food Court 23. Dental College
3. NRI Hostel 3. Outlet III: Medical Ladies Hostel
14. Architecture 24. Public Toilet – I
4. SRM Hotel Garden and Harvest pit
15. Bio Tech 25. Public Toilet - II
5. VEC, VEC Admin block, Canteen 4. Outlet IV: Dental Ground Area
16. Tech Park 26. BC Roy Hostel
6. TRS Hostel 27. PG Gents Hostel Garden and Harvest pit
17. Canteen
7. KRS Hostel 18. VPT 28. PG Ladies Hostel
8. Arts & Science 19. SRMPT 29. Medical Old Ladies
9. MBA Block Hostel

SEWAGE TREATMENT PLANT PROCESS


1. Raw Water Collection Tank
2. Anoxic Tank Librate Nitrate gas fixed on agitator
3. Aeration Tank Librtae Carbon-dioxide and energy
4. Clarifier Tank Sludge accumulated in center of tank. Sludge again recycled Aeration Tank. Clear water wearing out of filter feed tank
5. Filter Feed tank after clarifier water come to the filter feed tank
6. Chemical dozing disinfection chemical chlorine dioxide
7. Sand filter residual bed, Suspended solid removed
8. Treated water collection tank
9. Ultra Filtration up 0.2 micron Turbidity and removes odour

PCB NORMS RAW SEWAGE WATER PARAMETER TREATED WATER PARAMETER


pH: 6 to 9 pH: 7.56 pH: 6.94
TDS: ≤ 2100 ppm TDS: 1672 ppm TDS: 1610 ppm
TSS: ≤ 30 ppm TSS: 168 ppm TSS: 10 ppm
COD: ≤ 250 ppm COD: 664 mg/l COD: 44 mg/l
BOD: ≤ 20 ppm BOD: 248 mg/l BOD: 8 mg/l