Professional Documents
Culture Documents
(12.4) Double Line To Ground Faults
(12.4) Double Line To Ground Faults
(12.4) Double Line To Ground Faults
Done by:
1-Omair_ Abdul Qawi _Abdo_ Hamid. 202073066.
2-Akram Nasser Anbar. 202073401.
Supervisor:
Dr. Mohammed Aliadomi
Double Line-to-Ground Faults
• With a double line-to-ground (DLG) fault two
line conductors come in contact both with
each other and ground. We'll assume these
are phases b and c.
f f f f f
Ia 0 V b g V cg Z f ( I b I c )
2
DLG Faults, cont'd
3
DLG Faults, cont'd
4
DLG Faults, cont'd
5
DLG Faults
• The first step in the analysis of unbalanced
faults is to assemble the three sequence
networks. For example, for the earlier single
generator, single motor example let’s develop
the sequence networks
6
Create Thevenin Equivalents
• To do further analysis we first need to calculate
the thevenin equivalents as seen from the fault
location. In this example the fault is at the
terminal of the right machine so the thevenin
equivalents are:
7
DLG Faults
• Positive, negative and zero sequence
networks are connected in parallel, with the
zero sequence network including three times
the fault impedance
V 1 .0 5 0
I
f 0
Z Z (Z 3Z f ) j 0 .1 3 8 9 j 0 .0 9 2
4 .5 4 7 0 8
DLG Faults
e1 – ( * )
9
Example 1:
10
Example 1 Solution
11
Example 1 Solution
12
Example 1 Solution
• To do further analysis we first need to calculate
the thevenin equivalents as seen from the fault
location. In this example the fault is at the
terminal of the right machine so the thevenin
equivalents are:
13
Example 1 Solution
• The three sequence networks are joined as
follows
4 .5 4 7 0
14
Example 1 Solution
V f 1 .0 5 4 .5 4 7 9 0 j 0 .1 3 8 9 0 .4 1 8 4
I f 0 .4 1 8 4 / j 0 .1 4 5 6 j 2 .8 7 4
0
I f I f I f j 4 .5 4 7 j 2 .8 7 4 j 1 .6 7 3
f
C on v erti n g to p h ase: Ib 1 .0 4 j 6 .8 2
f
I c 1 .0 4 j 6 .8 2
15
Example 2:
16
Example 2:
17
Examples: