Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2 Issued: February 2015
Revision: D
ABB 3
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
59N 3Uo>
ROV2 PTOV
64S RSE<
+ REX060
STTI PHIZ
D
Y 60FL 81 f< 81 f>
Y SDD RFUF SA PTUF SA PTOF
VT
78 Ucos
PSP PPAM
IEC11000201-1-en.vsd
IEC11000201 V1 EN
Figure 1. Generator protection application with generator differential, 100% stator earth fault and back-up protection
4 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
59N 3Uo>
ROV2 PTOV
64S RSE<
+ REX060
STTI PHIZ
Meter.
D CV MMXU
Y 60FL 81 f< 81 f>
Y SDD RFUF SA PTUF SA PTOF
VT
78 Ucos
PSP PPAM
64W IN>
EF4 PTOC
REG 670*1.2
IEC11000204-1-en.vsd
IEC11000204 V1 EN
Figure 2. Generator protection application for generator with split winding including generator phase differential, 100% stator earth fault
and back-up protection
ABB 5
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Meter.
D CV MMXU
Y 60FL 81 f< 81 f>
Y SDD RFUF SA PTUF SA PTOF
VT
78 Ucos
PSP PPAM
64W IN>
87W 3Id/I
EF4 PTOC
GEN PDIF
VT
59N UN> 59THD U3d/N
ROV2 PTOV STEF PHIZ
64S RSE<
+ REX060
STTI PHIZ
REG 670*1.2
IEC11000206-1-en.vsd
IEC11000206 V1 EN
Figure 3. Generator protection application for generator with split winding including generator phase differential, generator split-phase
differential, 100% stator earth fault and back-up protection
6 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
87T 3Id/I
T3W PDIF
Y
Unit Trafo
D 50/51 3I>
OC4 PTOC
50/51 3I>
OC4 PTOC
D 59N 3Uo>
Y
Y ROV2 PTOV
Excitation Trafo
Auxiliary Trafo
D
Y 60FL 81 f< 81 f>
Y
SDD RFUF SA PTUF SA PTOF
78 Ucos
PSP PPAM
IEC11000202-1-en.vsd
IEC11000202 V1 EN
Figure 4. Unit protection application with overall differential, generator differential, 100% stator earth fault and back-up protection. Stator
winding grounded via grounding transformer.
ABB 7
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
87T 3Id/I
T2W PDIF
D 50/51 3I>
OC4 PTOC
D
Y 59N 3Uo>
Y
ROV2 PTOV
64S RSE<
+ REX060
STTI PHIZ
REG 670*1.2
IEC11000203-1-en.vsd
IEC11000203 V1 EN
Figure 5. Unit protection application with overall differential, unit transformer differential, generator differential, 100% stator earth fault and
back-up protection. Ungrounded stator winding.
8 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
87T 3Id/I
T2W PDIF
Y 50/51 3I>
OC4 PTOC
D 59N 3Uo>
ROV2 PTOV
64S RSE<
D + REX060
Y STTI PHIZ
Y
59N 3Uo>
ROV2 PTOV
VT 60FL 81 f< 78 Ucos
D
Y SDD RFUF SA PTUF PSP PPAM
Y
51/67 3I-> 50AE U/I> 21 Z< 24 U/f>
OC4 PTOC AEG GAPC ZMH PDIS OEX PVPH
IEC11000207-1-en.vsd
IEC11000207 V1 EN
Figure 6. Unit protection application with overall differential, unit transformer differential, generator differential, 100% stator earth fault and
back-up protection. Stator winding grounded via primary resistor.
ABB 9
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
2. Available functions
REG670
Differential protection
Impedance protection
ROTIPHIZ 64R Sensitive rotor earth fault protection, injection based 0-1
STTIPHIZ 64S 100% stator earth fault protection, injection based 0-1
10 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
REG670
Current protection
NS4PTOC 46I2 Four step directional negative phase sequence overcurrent protection 0-2
SDEPSDE 67N Sensitive directional residual overcurrent and power protection 0-2
NS2PTOC 46I2 Negative sequence time overcurrent protection for machines 0-2
Voltage protection
STEFPHIZ 59THD 100% stator earth fault protection, 3rd harmonic based 0-1
Frequency protection
Multipurpose protection
ABB 11
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
REG670
Control
APC30 3 Apparatus control for up to 6 bays, max 30 apparatuses (6CBs) incl. interlocking 0-1
SLGGIO Logic rotating switch for function selection and LHMI presentation 15
Logic
Monitoring
CVMMXN Measurements 6
12 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
REG670
Metering
Designed to communicate
REG670
Station communication
ABB 13
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
3. Differential protection to other generating blocks, the fast fault clearance is essential
to maintain the transient stability of the non-faulted
Generator differential protection GENPDIF generators.
Short circuit between the phases of the stator windings
causes normally very large fault currents. The short circuit Normally, the short circuit fault current is very large, that is,
gives risk of damages on insulation, windings and stator iron significantly larger than the generator rated current. There is a
core. The large short circuit currents cause large forces, risk that a short circuit can occur between phases close to
which can cause damage even to other components in the the neutral point of the generator, thus causing a relatively
power plant, such as turbine and generator-turbine shaft. small fault current. The fault current can also be limited due to
low excitation of the generator. Therefore, it is desired that
To limit the damage due to stator winding short circuits, the the detection of generator phase-to-phase short circuits shall
fault clearance must be as fast as possible (instantaneous). If be relatively sensitive, detecting small fault currents.
the generator block is connected to the power system close
14 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
IEC05000051 V1 EN
Three-winding applications
three-winding power
transformer with all
three windings
connected
xx05000052.vsd
IEC05000052 V1 EN
three-winding power
transformer with two
circuit breakers and
two CT-sets on one
side
xx05000053.vsd
IEC05000053 V1 EN
Autotransformer with
two circuit breakers
and two CT-sets on
two out of three sides
xx05000057.vsd
IEC05000057 V1 EN
sensitivity thus covering internal faults with low fault level. Autotransformer
CT
IED
Stabilization is included for inrush and overexcitation currents
respectively. Adaptive stabilization is also included for system
recovery inrush and CT saturation during external faults. A The most typical CT CB CB CT
application
high set unrestrained differential current protection element is The most complicated
application - autotransformer
included for a very high speed tripping at a high internal fault
currents.
IEC05000058-2-en.vsd
IEC05000058-2 V1 EN
Included is an innovative sensitive differential protection Figure 8. Examples of applications of the REFPDIF
element based on the theory of symmetrical components.
This element offers the best possible coverage of power
transformer windings turn to turn faults.
16 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
current, thus resulting in increased heating. The the power system through a unit transformer in a block
consequence can be damages on insulation and stator/ connection. An independent signal with a certain frequency
rotor iron. different from the generator rated frequency is injected into
the stator circuit. The responce of this injected signal is used
The Pole slip protection (PSPPPAM) function shall detect pole to detect stator earth faults.
slip conditions and trip the generator as fast as possible if the
locus of the measured impedance is inside the generator- To implement the above concept, a separate injection box is
transformer block. If the centre of pole slip is outside in the required. The injection box generates a square wave voltage
power grid, the first action should be to split the network into signal which for example can be fed into the secondary
two parts, after line protection action. If this fails there should winding of the generator neutral point voltage transformer or
be operation of the generator PSPPPAM in zone 2, to prevent grounding transformer. This signal propagates through this
further damages to the generator, shaft and turbine. transformer into the stator circuit.
Loss of excitation LEXPDIS The magnitude of the injected voltage signal is measured on
There are limits for the under-excited operation of a the secondary side of the neutral point voltage transformer or
synchronous machine. A reduction of the excitation current grounding transformer. In addition, the resulting injected
weakens the coupling between the rotor and the stator. The current is measured through a resistive shunt located within
machine may lose the synchronism and start to operate like the injection box. These two measured values are fed to the
an induction machine. Then, the reactive power consumption IED. Based on these two measured quantities, the IED
will increase. Even if the machine does not loose synchronism determines the stator winding resistance to ground. The
it may not be acceptable to operate in this state for a long resistance value is then compared with the preset fault
time. Reduction of excitation increases the generation of heat resistance alarm and trip levels.
in the end region of the synchronous machine. The local
heating may damage the insulation of the stator winding and The protection function can not only detect the earth fault at
the iron core. the generator star point, but also along the stator windings
and at the generator terminals, including the connected
To prevent damages to the generator it should be tripped components such as voltage transformers, circuit breakers,
when excitation is lost. excitation transformer and so on. The measuring principle
used is not influenced by the generator operating mode and
Sensitive rotor earth fault protection, injection based is fully functional even with the generator at standstill. It is still
ROTIPHIZ required to have a standard 95% stator earth-fault protection,
The sensitive rotor earth fault protection (ROTIPHIZ) is used based on the neutral point fundamental frequency
to detect earth faults in the rotor windings of generators. displacement voltage, operating in parallel with the 100%
ROTIPHIZ is applicable for all types of synchronous stator earth-fault protection function.
generators.
Requires injection unit REX060 and optional shunt resistor
To implement the above concept, a separate injection box is unit REX062 for correct operation.
required. The injection box generates a square wave voltage
signal at a certain preset frequency which is fed into the rotor
winding. 5. Current protection
The magnitude of the injected voltage signal and the resulting Instantaneous phase overcurrent protection PHPIOC
injected current is measured through a resistive shunt located The instantaneous three phase overcurrent function has a low
within the injection box. These two measured values are fed transient overreach and short tripping time to allow use as a
to the IED. Based on these two measured quantities, the high set short-circuit protection function.
protection IED determines the rotor winding resistance to
Four step phase overcurrent protection OC4PTOC
ground. The resistance value is then compared with the
The four step phase overcurrent protection function
preset fault resistance alarm and trip levels.
OC4PTOC has an inverse or definite time delay independent
The protection function can detect earth faults in the entire for step 1 and 4 separately. Step 2 and 3 are always definite
rotor winding and associated connections. time delayed.
Requires injection unit REX060 and a coupling capacitor unit All IEC and ANSI inverse time characteristics are available
REX061 for correct operation. together with an optional user defined time characteristic.
100% stator earth fault protection, injection based STTIPHIZ The directional function is voltage polarized with memory. The
The 100% stator earth-fault protection STTIPHIZ is used to function can be set to be directional or non-directional
detect earth faults in the stator windings of generators and independently for each of the steps.
motors. STTIPHIZ is applicable for generators connected to
ABB 17
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Second harmonic blocking level can be set for the function NS4PTOC can be set directional or non-directional
and can be used to block each step individually independently for each of the steps.
Instantaneous residual overcurrent protection EFPIOC NS4PTOC can be used as main protection for unsymmetrical
The Instantaneous residual overcurrent protection EFPIOC fault; phase-phase short circuits, phase-phase-earth short
has a low transient overreach and short tripping times to circuits and single phase earth faults.
allow the use for instantaneous earth-fault protection, with the
reach limited to less than the typical eighty percent of the line NS4PTOC can also be used to provide a system back-up for
at minimum source impedance. EFPIOC can be configured to example, in the case of the primary protection being out of
measure the residual current from the three-phase current service due to communication or voltage transformer circuit
inputs or the current from a separate current input. EFPIOC failure.
can be blocked by activating the input BLOCK.
Directional operation can be combined together with
Four step residual overcurrent protection, zero sequence and corresponding communication logic in permissive or blocking
negative sequence direction EF4PTOC teleprotection scheme. The same logic as for directional zero
The four step residual overcurrent protection EF4PTOC has sequence current can be used. Current reversal and weak-
an inverse or definite time delay independent for each step end infeed functionality are available.
separately.
Sensitive directional residual overcurrent and power
All IEC and ANSI time-delayed characteristics are available protection SDEPSDE
together with an optional user defined characteristic. In isolated networks or in networks with high impedance
earthing, the earth fault current is significantly smaller than
EF4PTOC can be set directional or non-directional the short circuit currents. In addition to this, the magnitude of
independently for each of the steps. the fault current is almost independent on the fault location in
the network. The protection can be selected to use either the
IDir, UPol and IPol can be independently selected to be either residual current or residual power component 3U0·3I0·cos j,
zero sequence or negative sequence. for operating quantity with maintained short circuit capacity.
There is also available one nondirectional 3I0 step and one
Second harmonic blocking can be set individually for each
3U0 overvoltage tripping step.
step.
No specific sensitive current input is needed.SDEPSDE can
EF4PTOC can be used as main protection for phase-to-earth
be set as low 0.25% of IBase.
faults.
Thermal overload protection, two time constant TRPTTR
EF4PTOC can also be used to provide a system back-up for
If a power transformer or generator reaches very high
example, in the case of the primary protection being out of
temperatures the equipment might be damaged. The
service due to communication or voltage transformer circuit
insulation within the transformer/generator will have forced
failure.
ageing. As a consequence of this the risk of internal phase-to-
Directional operation can be combined together with phase or phase-to-earth faults will increase. High temperature
corresponding communication logic in permissive or blocking will degrade the quality of the transformer/generator insulation.
teleprotection scheme. Current reversal and weak-end infeed
The thermal overload protection estimates the internal heat
functionality are available as well.
content of the transformer/generator (temperature)
EF4PTOC can be configured to measure the residual current continuously. This estimation is made by using a thermal
from the three-phase current inputs or the current from a model of the transformer/generator with two time constants,
separate current input. which is based on current measurement.
Four step negative sequence overcurrent protection Two warning levels are available. This enables actions in the
NS4PTOC power system to be done before dangerous temperatures are
Four step negative sequence overcurrent protection reached. If the temperature continues to increase to the trip
(NS4PTOC) has an inverse or definite time delay independent value, the protection initiates a trip of the protected
for each step separately. transformer/generator.
All IEC and ANSI time delayed characteristics are available Breaker failure protection CCRBRF
together with an optional user defined characteristic. Breaker failure protection (CCRBRF) ensures fast back-up
tripping of surrounding breakers in case the own breaker fails
The directional function is voltage polarized or dual polarized. to open. CCRBRF can be current based, contact based, or
an adaptive combination of these two conditions.
18 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
• generator reverse power protection Accidental energizing protection for synchronous generator
• generator low forward power protection AEGGAPC
• detection of over/under excited generator Inadvertent or accidental energizing of off-line generators has
• detection of reversed active power flow occurred often enough due to operating errors, breaker head
• detection of high reactive power flow flashovers, control circuit malfunctions, or a combination of
• excessive line/cable loading with active or reactive power these causes. Inadvertently energized generator operates as
• generator reverse power protection induction motor drawing a large current from the system. The
voltage supervised overcurrent protection is used to protect
Each function has two steps with definite time delay. Reset the inadvertently energized generator.
times for both steps can be set as well.
Accidental energizing protection for synchronous generator
By using optional metering class CT inputs accuracy of 0,5% (AEGGAPC) takes the maximum phase current input from the
can be achieved for steam turbine applications. generator terminal side or from generator neutral side and
maximum phase to phase voltage inputs from the terminal
ABB 19
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
20 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
RN Rf Transformer
uN x 1- x uT
Samples of the Samples of the
neutral voltage 1 or 100 % terminal voltage
from which the from which the
fundamental and 3rd harmonic
3rd harmonic voltage is filtered
Neutral point fundamental frequency
voltages are out
over-voltage protection 5% - 100%
filtered out over- voltage protection 10%– 100%
3rd harmonic
Differential
differential
0% – 30%
0% - 30% IEC10000202-1-en.vsd
IEC10000202 V1 EN
7. Frequency protection plant, generator governor problems can also cause over
frequency.
Underfrequency protection SAPTUF
Underfrequency occurs as a result of a lack of generation in SAPTOF is used mainly for generation shedding and remedial
the network. action schemes. It is also used as a frequency stage initiating
load restoring.
Underfrequency protection SAPTUF is used for load shedding
systems, remedial action schemes, gas turbine startup and SAPTOF is provided with an undervoltage blocking.
so on.
The operation is based on positive sequence voltage
SAPTUF is also provided with undervoltage blocking. measurement and requires two phase-phase or three phase-
neutral voltages to be connected. For information about how
The operation is based on positive sequence voltage to connect analog inputs, refer to Application manual/IED
measurement and requires two phase-phase or three phase- application/Analog inputs/Setting guidelines
neutral voltages to be connected. For information about how
to connect analog inputs, refer to Application manual/IED Rate-of-change frequency protection SAPFRC
application/Analog inputs/Setting guidelines Rate-of-change frequency protection function (SAPFRC) gives
an early indication of a main disturbance in the system.
SAPFRC can be used for generation shedding, load shedding
Overfrequency protection SAPTOF
and remedial action schemes. SAPFRC can discriminate
Overfrequency protection function SAPTOF is applicable in all
between positive or negative change of frequency.
situations, where reliable detection of high fundamental power
system frequency is needed. SAPFRC is provided with an undervoltage blocking. The
operation is based on positive sequence voltage
Overfrequency occurs because of sudden load drops or
measurement and requires two phase-phase or three phase-
shunt faults in the power network. Close to the generating
ABB 21
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
neutral voltages to be connected. For information about how field winding has increased considerably. A second earth fault
to connect analog inputs, refer to Application manual/IED will cause a field short-circuit with severe consequences.
application/Analog inputs/Setting guidelines.
The rotor earth fault protection is based on injection of an AC
voltage to the isolated field circuit. In non-faulted conditions
8. Multipurpose protection there will be no current flow associated to this injected
voltage. If a rotor earth fault occurs, this condition will be
General current and voltage protection CVGAPC
detected by the rotor earth fault protection. Depending on the
The protection module is recommended as a general backup
generator owner philosophy this operational state will be
protection with many possible application areas due to its
alarmed and/or the generator will be tripped. An injection unit
flexible measuring and setting facilities.
is required for rotor earth fault protection (RXTTE4) and a
The built-in overcurrent protection feature has two settable protective resistor on plate for correct operation.
current levels. Both of them can be used either with definite
time or inverse time characteristic. The overcurrent protection
steps can be made directional with selectable voltage 9. Secondary system supervision
polarizing quantity. Additionally they can be voltage and/or
current controlled/restrained. 2nd harmonic restraining facility Current circuit supervision CCSRDIF
is available as well. At too low polarizing voltage the Open or short circuited current transformer cores can cause
overcurrent feature can be either blocked, made non unwanted operation of many protection functions such as
directional or ordered to use voltage memory in accordance differential, earth-fault current and negative-sequence current
with a parameter setting. functions.
Additionally two overvoltage and two undervoltage steps, It must be remembered that a blocking of protection
either with definite time or inverse time characteristic, are functions at an occurrence of open CT circuit will mean that
available within each function. the situation will remain and extremely high voltages will
stress the secondary circuit.
The general function suits applications with underimpedance
and voltage controlled overcurrent solutions. The general Current circuit supervision (CCSRDIF) compares the residual
function can also be utilized for generator transformer current from a three phase set of current transformer cores
protection applications where positive, negative or zero with the neutral point current on a separate input taken from
sequence components of current and voltage quantities are another set of cores on the current transformer.
typically required.
A detection of a difference indicates a fault in the circuit and
Additionally, generator applications such as loss of field, is used as alarm or to block protection functions expected to
inadvertent energizing, stator or rotor overload, circuit give unwanted tripping.
breaker head flash-over and open phase detection are just a
Fuse failure supervision SDDRFUF
few of possible protection arrangements with these functions.
The aim of the fuse failure supervision function (SDDRFUF) is
Rotor earth fault protection to block voltage measuring functions at failures in the
The field winding, including the rotor winding and the non- secondary circuits between the voltage transformer and the
rotating excitation equipment, is always insulated from the IED in order to avoid unwanted operations that otherwise
metallic parts of the rotor. The insulation resistance is high if might occur.
the rotor is cooled by air or by hydrogen. The insulation
The fuse failure supervision function basically has three
resistance is much lower if the rotor winding is cooled by
different algorithms, negative sequence and zero sequence
water. This is true even if the insulation is intact. A fault in the
based algorithms and an additional delta voltage and delta
insulation of the field circuit will result in a conducting path
current algorithm.
from the field winding to earth. This means that the fault has
caused a field earth fault. The negative sequence detection algorithm is recommended
for IEDs used in isolated or high-impedance earthed
The field circuit of a synchronous generator is normally
networks. It is based on the negative-sequence measuring
unearthed. Therefore, a single earth fault on the field winding
quantities, a high value of voltage 3U 2 without the presence
will cause only a very small fault current. Thus the earth fault
of the negative-sequence current 3I 2.
does not produce any damage in the generator. Furthermore,
it will not affect the operation of a generating unit in any way.
The zero sequence detection algorithm is recommended for
However, the existence of a single earth fault increases the
IEDs used in directly or low impedance earthed networks. It is
electric stress at other points in the field circuit. This means
based on the zero sequence measuring quantities, a high
that the risk for a second earth fault at another point on the
22 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Synchrocheck, energizing check, and synchronizing SESRSYN Normal security means that only the command is evaluated
The Synchronizing function allows closing of asynchronous and the resulting position is not supervised. Enhanced
networks at the correct moment including the breaker closing security means that the command is evaluated with an
time, which improves the network stability. additional supervision of the status value of the control
object. The command security with enhanced security is
Synchrocheck, energizing check, and synchronizing always terminated by a CommandTermination service
(SESRSYN) function checks that the voltages on both sides of primitive.
the circuit breaker are in synchronism, or with at least one
side dead to ensure that closing can be done safely. Control operation can be performed from the local HMI under
authority control if so defined.
SESRSYN function includes a built-in voltage selection
scheme for double bus and 1½ breaker or ring busbar Tap changer position reading TCMYLTC
arrangements. On-load tap-changer position can be monitored on-line. This
can be done by either using BCD coded binary input signals
Manual closing as well as automatic reclosing can be or alternatively via an mA input signal. The actual tap-position
checked by the function and can have different settings. can be used by the transformer or overall differential
protection function in order to enable more sensitive pickup
For systems which are running asynchronous a synchronizing setting. This will in turn make differential protection more
function is provided. The main purpose of the synchronizing sensitive for low level internal faults such as winding turn-to-
function is to provide controlled closing of circuit breakers turn faults.
when two asynchronous systems are going to be connected.
It is used for slip frequencies that are larger than those for Logic rotating switch for function selection and LHMI
synchrocheck and lower than a set maximum level for the presentation SLGGIO
synchronizing function. The logic rotating switch for function selection and LHMI
presentation (SLGGIO) (or the selector switch function block)
However this function can not be used to automatically is used to get a selector switch functionality similar to the one
synchronize the generator to the network. provided by a hardware selector switch. Hardware selector
switches are used extensively by utilities, in order to have
Apparatus control APC
different functions operating on pre-set values. Hardware
The apparatus control functions are used for control and
switches are however sources for maintenance issues, lower
supervision of circuit breakers, disconnectors and earthing
system reliability and an extended purchase portfolio. The
switches within a bay. Permission to operate is given after
logic selector switches eliminate all these problems.
evaluation of conditions from other functions such as
interlocking, synchrocheck, operator place selection and Selector mini switch VSGGIO
external or internal blockings. The Selector mini switch VSGGIO function block is a
multipurpose function used for a variety of applications, as a
Apparatus control features:
general purpose switch.
• Select-Execute principle to give high reliability
• Selection function to prevent simultaneous operation
• Selection and supervision of operator place
ABB 23
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
24 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
The Disturbance report function is characterized by great Trip value recorder DRPRDRE
flexibility regarding configuration, starting conditions, Information about the pre-fault and fault values for currents
recording times, and large storage capacity. and voltages are vital for the disturbance evaluation.
A disturbance is defined as an activation of an input to the The Trip value recorder calculates the values of all selected
AxRADR or BxRBDR function blocks, which are set to trigger analog input signals connected to the Disturbance report
the disturbance recorder. All signals from start of pre-fault function. The result is magnitude and phase angle before and
time to the end of post-fault time will be included in the during the fault for each analog input signal.
recording.
The trip value recorder information is available for the
Every disturbance report recording is saved in the IED in the disturbances locally in the IED.
standard Comtrade format. The same applies to all events,
The trip value recorder information is an integrated part of the
which are continuously saved in a ring-buffer. The local HMI is
disturbance record (Comtrade file).
used to get information about the recordings. The
disturbance report files may be uploaded to PCM600 for Disturbance recorder DRPRDRE
further analysis using the disturbance handling tool. The Disturbance recorder function supplies fast, complete
and reliable information about disturbances in the power
Event list DRPRDRE
system. It facilitates understanding system behavior and
Continuous event-logging is useful for monitoring the system
related primary and secondary equipment during and after a
from an overview perspective and is a complement to specific
disturbance. Recorded information is used for different
disturbance recorder functions.
purposes in the short perspective (for example corrective
The event list logs all binary input signals connected to the actions) and long perspective (for example functional analysis).
Disturbance report function. The list may contain up to 1000
The Disturbance recorder acquires sampled data from
time-tagged events stored in a ring-buffer.
selected analog- and binary signals connected to the
Indications DRPRDRE Disturbance report function (maximum 40 analog and 96
To get fast, condensed and reliable information about binary signals). The binary signals available are the same as
disturbances in the primary and/or in the secondary system it for the event recorder function.
is important to know, for example binary signals that have
The function is characterized by great flexibility and is not
changed status during a disturbance. This information is used
dependent on the operation of protection functions. It can
in the short perspective to get information via the local HMI in
record disturbances not detected by protection functions. Up
a straightforward way.
to ten seconds of data before the trigger instant can be saved
There are three LEDs on the local HMI (green, yellow and in the disturbance file.
red), which will display status information about the IED and
The disturbance recorder information for up to 100
the Disturbance report function (triggered).
disturbances are saved in the IED and the local HMI is used
The Indication list function shows all selected binary input to view the list of recordings.
signals connected to the Disturbance report function that
Event function
have changed status during a disturbance.
When using a Substation Automation system with LON or
Event recorder DRPRDRE SPA communication, time-tagged events can be sent at
Quick, complete and reliable information about disturbances change or cyclically from the IED to the station level. These
in the primary and/or in the secondary system is vital, for events are created from any available signal in the IED that is
example, time-tagged events logged during disturbances. connected to the Event function (EVENT). The event function
This information is used for different purposes in the short block is used for LON and SPA communication.
term (for example corrective actions) and in the long term (for
Analog and double indication values are also transferred
example functional analysis).
through EVENT function.
The event recorder logs all selected binary input signals
connected to the Disturbance report function. Each recording
can contain up to 150 time-tagged events.
ABB 25
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
13. Metering
Time synchronization
The time synchronization source selector is used to select a
common source of absolute time for the IED when it is a part
of a protection system. This makes it possible to compare
event and disturbance data between all IEDs in a station
automation system.
26 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Figure 11. Example of medium graphic HMI Multiple command and transmit
When 670 IED's are used in Substation Automation systems
with LON, SPA or IEC60870-5-103 communication protocols
the Event and Multiple Command function blocks are used as
the communication interface for vertical communication to
16. Station communication
station HMI and gateway and as interface for horizontal peer-
Overview to-peer communication (over LON only).
Each IED is provided with a communication interface,
enabling it to connect to one or many substation level IEC 62439-3 Parallel Redundant Protocol
systems or equipment, either on the Substation Automation Redundant station bus communication according to IEC
(SA) bus or Substation Monitoring (SM) bus. 62439-3 Edition 1 and IEC 62439-3 Edition 2 are available as
options in 670 series IEDs. IEC 62439-3 parallel redundant
Following communication protocols are available: protocol is an optional quantity and the selection is made at
ordering. Redundant station bus communication according to
• IEC 61850-8-1 communication protocol IEC 62439-3 uses both port AB and port CD on the OEM
• LON communication protocol module.
• SPA or IEC 60870-5-103 communication protocol
• DNP3.0 communication protocol
Select IEC 62439-3 Edition 1 protocol at
Theoretically, several protocols can be combined in the same the time of ordering when an existing
IED. redundant station bus DuoDriver installation
is extended.
IEC 61850-8-1 communication protocol Select IEC 62439-3 Edition 2 protocol at
The IED is equipped with single or double optical Ethernet the time of ordering for new installations
rear ports (order dependent) for IEC 61850-8-1 station bus with redundant station bus.
communication. The IEC 61850-8-1 communication is also IEC 62439-3 Edition 1 is NOT compatible
possible from the optical Ethernet front port. IEC 61850-8-1 with IEC 62439-3 Edition 2.
protocol allows intelligent electrical devices (IEDs) from
different vendors to exchange information and simplifies
system engineering. Peer-to-peer communication according
17. Remote communication
to GOOSE is part of the standard. Disturbance files uploading
is provided. Analog and binary signal transfer to remote end
Three analog and eight binary signals can be exchanged
Serial communication, LON
between two IEDs. This functionality is mainly used for the
Existing stations with ABB station bus LON can be extended
line differential protection. However it can be used in other
with use of the optical LON interface. This allows full SA
functionality including peer-to-peer messaging and
ABB 27
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
products as well. An IED can communicate with up to 4 The two high speed signal output channels are used for
remote IEDs. applications where short operating time is essential. Eight
optically isolated binary inputs cater for required binary input
Binary signal transfer to remote end, 192 signals information.
If the communication channel is used for transfer of binary
signals only, up to 192 binary signals can be exchanged mA input module MIM
between two IEDs. For example, this functionality can be The milli-ampere input module is used to interface transducer
used to send information such as status of primary signals in the –20 to +20 mA range from for example OLTC
switchgear apparatus or intertripping signals to the remote position, temperature or pressure transducers. The module
IED. An IED can communicate with up to 4 remote IEDs. has six independent, galvanically separated channels.
Line data communication module, short and medium range Optical ethernet module OEM
LDCM The optical fast-ethernet module is used to connect an IED to
The line data communication module (LDCM) is used for the communication buses (like the station bus) that use the
communication between the IEDs situated at distances <60 IEC 61850-8-1 protocol (port A, B). The module has one or
km or from the IED to optical to electrical converter with G. two optical ports with ST connectors.
703 or G.703E1 interface located on a distances <3 km
away. The LDCM module sends and receives data, to and Serial and LON communication module SLM, supports SPA/
from another LDCM module. The IEEE/ANSI C37.94 standard IEC 60870-5-103, LON and DNP 3.0
format is used. The serial and LON communication module (SLM) is used for
SPA, IEC 60870-5-103, DNP3 and LON communication. The
This feature can be for example used in power stations to module has two optical communication ports for plastic/
exchange up to 192 binary signals (e.g. tripping, signaling, plastic, plastic/glass or glass/glass. One port is used for serial
alarming) between the generator and HV station in power communication (SPA, IEC 60870-5-103 and DNP3 port or
plants dedicated IEC 60870-5-103 port depending on ordered SLM
module) and one port is dedicated for LON communication.
B C
D
xx05000003.vsd
IEC05000003 V1 EN
xx05000004.vsd
IEC05000004 V1 EN
Case size A B C D E F
(mm)
ABB 29
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Mounting alternatives
• 19” rack mounting kit
• Wall mounting kit
injection into the rotor circuit via a capacitor unit REX061 for
Injection equipment hardware isolation. The RIM module measures the voltage and current
Injection unit REX060 from the injected signal and the IED consecutively calculates
The injection unit REX060 is used to inject voltage and the rotor to earth impedance. If the calculated impedance is
current signals to the generator or motor stator and rotor lower than the preset value an ALARM and/or TRIP output is
circuits. REX060 generates two square wave signals with set.
different frequencies for injection into the stator and rotor
circuits respectively. The response from the injected voltage Coupling capacitor unit REX061
and currents are then measured by the REX060 unit and REX061 isolates the injection circuit from the rotor exciter
amplified to a level suitable for the analog voltage inputs of voltage.
IED.
Stator injection module SIM The REX061 coupling capacitor unit grounding point and
The SIM module is installed into the REX060 enclosure. The grounding brush of the rotor shaft should be properly
SIM module generates a square wave voltage signal for interconnected.
injection into the stator circuit via the neutral point resistor or
Shunt resistor unit REX062
VT/DT. The SIM module measures the voltage and current
REX062 is typically used when injection is done via a
from the injected signal and the IED consecutively calculates
grounding transformer.
the stator to earth impedance. If the calculated impedance is
lower than the preset value an ALARM and/or TRIP output is
set.
30 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
1MRK002801-AC-2-670-1.2-PG V1 EN
1MRK002801-AC-3-670-1.2-PG V1 EN
ABB 31
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
1MRK002801-AC-4-670-1.2-PG V1 EN
1MRK002801-AC-5-670-1.2-PG V1 EN
32 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
1MRK002801-AC-6-670-1.2-PG V1 EN
ABB 33
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
1MRK002801-AC-10-670-1.2-PG V1 EN
12I, 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A
12I, 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A
9I+3U, 1A 1A 1A 1A 1A 1A 1A 1A 1A 1A 110-220V 110-220V 110-220V
9I+3U, 5A 5A 5A 5A 5A 5A 5A 5A 5A 5A 110-220V 110-220V 110-220V
5I, 1A+4I, 5A+3U 1A 1A 1A 1A 1A 5A 5A 5A 5A 110-220V 110-220V 110-220V
7I+5U, 1A 1A 1A 1A 1A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V
7I+5U, 5A 5A 5A 5A 5A 5A 5A 5A 110-220V 110-220V 110-220V 110-220V 110-220V
6I, 5A+1I, 1A+5U 5A 5A 5A 5A 5A 5A 1A 110-220V 110-220V 110-220V 110-220V 110-220V
3I, 5A+4I, 1A+5U 5A 5A 5A 1A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V
3IM, 1A+4IP, 1A+5U 1AM 1AM 1AM 1A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V
*) *) *)
3IM, 5A+4IP, 5A+5U 5AM 5AM 5AM 5A 5A 5A 5A 110-220V 110-220V 110-220V 110-220V 110-220V
*) *) *)
6I+6U, 1A 1A 1A 1A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V 110-220V
6I+6U, 5A 5A 5A 5A 5A 5A 5A 110-220V 110-220V 110-220V 110-220V 110-220V 110-220V
3I, 5A+3I, 1A+6U 5A 5A 5A 1A 1A 1A 110-220V 110-220V 110-220V 110-220V 110-220V 110-220V
6I, 1A 1A 1A 1A 1A 1A 1A - - - - - -
6I, 5A 5A 5A 5A 5A 5A 5A - - - - - -
*) Metering
Note that internal polarity can be adjusted by setting of analog input CT neutral direction and/or on SMAI pre-processing function blocks.
34 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
1MRK002801-AC-15-670-1.2-PG V1 EN
1MRK002801-AC-11-670-1.2-PG V1 EN
1MRK002801-AC-8-670-1.2-PG V1 EN
ABB 35
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
1MRK002801-AC-7-670-1.2-PG V1 EN
1MRK002801-AC-12-670-1.2-PG V1 EN
Figure 19. Binary output module (BOM). Output contacts named XA corresponds to rear position X31, X41, and so on, and output
contacts named XB to rear position X32, X42, and so on.
36 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
1MRK002801-AC-13-670-1.2-PG V1 EN
1MRK002801-AC-14-670-1.2-PG V1 EN
Figure 21. Binary in/out module (IOM). Input contacts named XA corresponds to rear position X31, X41, and so on, and output contacts
named XB to rear position X32, X42, and so on.
ABB 37
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
1MRK002501-BA-2-PG V1 EN
1MRK002501-BA-3-PG V1 EN
38 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
1MRK002501-BA-4-PG V1 EN
1MRK002501-BA-5-PG V1 EN
ABB 39
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
1MRK002551-BA-1-PG V1 EN
1MRK002551-BA-2-PG V1 EN
40 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
1MRK002556-BA-1-PG V1 EN
1MRK002556-BA-2-PG V1 EN
ABB 41
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
General
Definitions
Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment
Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the
specified requirements
Operative range The range of values of a given energizing quantity for which the equipment, under specified conditions, is able to perform its
intended functions according to the specified requirements
Table 6. TRM - Energizing quantities, rated values and limits for protection transformer modules
Current Ir = 1 or 5 A (0.2-40) × Ir
Frequency fr = 50/60 Hz ± 5%
42 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Table 7. TRM - Energizing quantities, rated values and limits for measuring transformer modules
Frequency fr = 50/60 Hz ± 5%
Power consumption -
each mA-board £2W
each mA input £ 0.1 W
Number of channels 1 or 2
Auxiliary DC voltage
ABB 43
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Binary inputs 16 -
Power consumption
24/30 V, 50mA max. 0.05 W/input -
48/60 V, 50mA max. 0.1 W/input
110/125 V, 50mA max. 0.2 W/input
220/250 V, 50mA max. 0.4 W/input
220/250 V, 110mA max. 0.5 W/input
Table 12. BIM - Binary input module with enhanced pulse counting capabilities
Binary inputs 16 -
Power consumption
24/30 V max. 0.05 W/input -
48/60 V max. 0.1 W/input
110/125 V max. 0.2 W/input
220/250 V max. 0.4 W/input
44 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Binary inputs 8 -
Power consumption -
24/30 V, 50 mA max. 0.05 W/input
48/60 V, 50 mA max. 0.1 W/input
110/125 V, 50 mA max. 0.2 W/input
220/250 V, 50 mA max. 0.4 W/input
220/250 V, 110 mA max. 0.5 W/input
Table 14. IOM - Binary input/output module contact data (reference standard: IEC 61810-2)
Function or quantity Trip and signal relays Fast signal relays (parallel
reed relay)
Binary outputs 10 2
0.2 s
1.0 s 30 A 0.4 A
10 A 0.4 A
Breaking capacity for AC, cos φ > 0.4 250 V/8.0 A 250 V/8.0 A
ABB 45
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Table 15. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-2)
Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay)
Table 16. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs
Number of outputs 6 6
Test voltage across open contact, 1 min No galvanic separation No galvanic separation
Continuous 5A 5A
220V / 0.2A
250V / 0.15A
46 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Table 17. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs
Number of outputs 6
Continuous 8A
1.0s 10A
0.2s 30A
1.0s 10A
110V / 0.4A
125V / 0.35A
220V / 0.2A
250V / 0.15A
Table 18. BOM - Binary output module contact data (reference standard: IEC 61810-2)
Binary outputs 24
Influencing factors
ABB 47
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
90-250 V DC ± 20%
Interruption interval
0–50 ms
No restart
Harmonic frequency dependence (20% content) 2nd, 3rd and 5th harmonic of fr ± 1.0%
Harmonic frequency dependence for high impedance differential 2nd, 3rd and 5th harmonic of fr ±5.0%
protection (10% content)
48 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Class III
Ring wave immunity test, 100 kHz 2-4 kV IEC 61000-4-12, Class IV
Conducted common mode immunity test 15 Hz-150 kHz IEC 61000-4-16, Class IV
Power frequency magnetic field test 1000 A/m, 3 s IEC 61000-4-8, Class V
100 A/m, cont.
Damped oscillatory magnetic field test 100 A/m IEC 61000-4-10, Class V
1.4-2.7 GHz
ABB 49
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Damp heat test, steady state Test Ca for 4 days at +40 °C and humidity 93% IEC 60068-2-78
Damp heat test, cyclic Test Db for 6 cycles at +25 to +55 °C and humidity 93 to 95% (1 cycle = IEC 60068-2-30
24 hours)
Test According to
Immunity EN 50263
Emissivity EN 50263
50 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Injection equipment
100 kHz slow damped oscillatory wave immunity test 2.5 kV IEC 61000-4-18, Class III
Surge immunity test 1-2 kV, and 2-4 kV, 1.2/50 µs IEC 60255-22-5
High energy
Radiated electromagnetic field disturbance test 20 V/m, 80-1000 MHz IEC 60255-22-3
1.4-2.7 GHz
Radiated electromagnetic field disturbance test 20 V/m, 80-1000 MHz IEEE/ANSI C37.90.2
Impulse voltage test 5.0 kV, 1.2/50 µs, 0.5 J IEC 60255-5
ABB 51
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Impulse voltage test 12.0 kV, 1.2/50 µs, 0.5 J IEC 60664-1
(connections to rotor)
52 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Description Values
REX060
Front side IP40
Panel mounted, front IP54
Rear side, connection terminals IP20
ABB 53
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Differential protection
54 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
ABB 55
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
56 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Impedance protection
ABB 57
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Typically 50 kΩ
Typically 10 kΩ
58 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Current protection
Inverse characteristics, see 16 curve types See table 111, table 112 and table 113
table 111, table 112 and table 113
ABB 59
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Inverse characteristics, see table 18 curve types See table 111, table 112 and
111, table 112 and table 113 table 113
60 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Inverse characteristics, see table 18 curve types See table 111, table 112 and
111, table 112 and table 113 table 113
Minimum operate current for step (1.00 - 10000.00)% of IBase ± 1.0% of Ir at I < Ir
1-4 ± 1.0% of I at I > Ir
ABB 61
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Table 49. Sensitive directional residual overcurrent and power protection SDEPSDE
At low setting:
(0.25-1.00)% of Ir: ±0.05% of Ir
(1.00-5.00)% of Ir: ±0.1% of Ir
At low setting:
(0.25-1.00)% of Ir: ±0.05% of Ir
(1.00-5.00)% of Ir: ±0.1% of Ir
Inverse characteristics, see 19 curve types See table 111, table 112 and table 113
table 111, table 112 and
table 113
62 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Table 49. Sensitive directional residual overcurrent and power protection SDEPSDE, continued
Function Range or value Accuracy
Operate time: Ip = load current before overload IEC 60255–8, ±5% + 200 ms
occurs
æ I 2 - I p2 ö Time constant τ = (1–500)
t = t × ln ç 2 ÷ minutes
ç I - Ib 2 ÷
è ø
EQUATION1356 V1 EN (Equation 1)
I = Imeasured
Alarm level 1 and 2 (50–99)% of heat content trip ± 2.0% of heat content trip
value
Reset level temperature (10–95)% of heat content trip ± 2.0% of heat content trip
Phase current level for blocking of contact function (5-200)% of lBase ± 1.0% of Ir at I £ Ir
± 1.0% of I at I > Ir
ABB 63
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
*) To achieve this accuracy for reverse power protection it is also recommended to apply setting AngleN=-179.3 degrees instead of standard 180
degrees. This setting will help to minimize the overall measurement error ensuring the above stated accuracy for this application.
*) To achieve this accuracy for reverse power protection it is also recommended to apply setting AngleN=-179.3 degrees instead of standard 180
degrees. This setting will help to minimize the overall measurement error ensuring the above stated accuracy for this application.
64 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Table 55. Negative sequence time overcurrent protection for machines NS2PTOC
Operate value, step 1 and 2, negative sequence overcurrent (3-500)% of IBase ± 1.0% of Ir at I < Ir
± 1.0% of I at I > Ir
K=1.0-99.0 ± 5% + 40 ms
Inverse time characteristic step 1, I 22t = K
K=0.01-20.00 ± 10% + 40 ms
Reset time, inverse characteristic step 1, I 22t = K
ABB 65
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Voltage protection
Inverse time characteristics for step 1 and step 2, see table 115 - See table 115
Inverse time characteristics for steps 1 and 2, see table 114 - See table 114
66 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Inverse time characteristics for low and high step, see table 116 - See table 116
(0.18 × k )
IEEE : t =
( M - 1) 2
EQUATION1319 V1 EN (Equation 2)
where M = (E/f)/(Ur/fr)
ABB 67
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Filter characteristic: -
Fundamental Reject third harmonic by 1–40
Third harmonic Reject fundamental harmonic by
1–40
68 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Frequency protection
Operate time, start function 100 ms typically at fset -0.5 Hz to fset +0.5 Hz -
ABB 69
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Multipurpose protection
See table 111 and table 112 Parameter ranges for customer defined See table 111 and table 112
characteristic no 17:
k: 0.05 - 999.00
A: 0.0000 - 999.0000
B: 0.0000 - 99.0000
C: 0.0000 - 1.0000
P: 0.0001 - 10.0000
PR: 0.005 - 3.000
TR: 0.005 - 600.000
CR: 0.1 - 10.0
Voltage level where voltage memory takes over (0.0 - 5.0)% of UBase ± 0.5% of Ur
Start overvoltage, step 1 and 2 (2.0 - 200.0)% of UBase ± 0.5% of Ur for U<Ur
± 0.5% of U for U>Ur
Start undervoltage, step 1 and 2 (2.0 - 150.0)% of UBase ± 0.5% of Ur for U<Ur
± 0.5% of U for U>Ur
High and low voltage limit, voltage dependent operation (1.0 - 200.0)% of UBase ± 1.0% of Ur for U<Ur
± 1.0% of U for U>Ur
70 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Overcurrent:
Undercurrent:
Overvoltage:
Undervoltage:
Table 67. Rotor earth fault protection based on General current and voltage protection (CVGAPC) and RXTTE4
ABB 71
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
72 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Control
Voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of UBaseBus and ± 0.5% of Ur at U ≤ Ur
UBaseLIne ± 0.5% of U at U >Ur
Frequency difference limit between bus and line for synchrocheck (0.003-1.000) Hz ± 2.0 mHz
Phase angle difference limit between bus and line for synchrocheck (5.0-90.0) degrees ± 2.0 degrees
Voltage difference limit between bus and line for synchronizing and (0.02-0.5) p.u ± 0.5% of Ur
synchrocheck
tMaxSynch, which resets synchronizing function if no close has been (0.000-60.000) s ± 0.5% ± 10 ms
made before set time
Voltage high limit for energizing check (50.0-120.0)% of UBaseBus and ± 0.5% of Ur at U ≤ Ur
UBaseLIne ± 0.5% of U at U >Ur
Voltage low limit for energizing check (10.0-80.0)% of UBaseBus and ± 0.5% of Ur
UBaseLine
ABB 73
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Logic
LogicAND 60 60 160 - -
LogicOR 60 60 160 - -
LogicXOR 10 10 20 - -
LogicInverter 30 30 80 - -
LogicSRMemory 10 10 20 - -
LogicRSMemory 10 10 20 - -
LogicGate 10 10 20 - -
Boolean 16 to Integer 4 4 8 - -
Boolean 16 to integer 4 4 8 - -
with Logic Node
Integer to Boolean 16 4 4 8 - -
Integer to Boolean 16 4 4 8 - -
with Logic Node
74 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Monitoring
ABB 75
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
76 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Maximum number of events in the Event list 1000, first in - first out -
Maximum total recording time (3.4 s recording time and maximum number of 340 seconds (100 recordings) at -
channels, typical value) 50 Hz, 280 seconds (80
recordings) at 60 Hz
Function Value
Resolution 1 ms
Function Value
Function Value
Resolution 1 ms
ABB 77
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Function Value
Function Value
Maximum total recording time (3.4 s recording time and maximum number 340 seconds (100 recordings) at 50 Hz
of channels, typical value) 280 seconds (80 recordings) at 60 Hz
78 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Metering
Energy metering kWh Export/Import, kvarh Export/ Input from MMXU. No extra error at steady load
Import
ABB 79
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Station communication
Function Value
Protocol DNP3.0
Function Value
Protocol LON
Function Value
Protocol SPA
Function Value
80 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Table 96. IEC 62439-3 Edition 1 and Edition 2 parallel redundancy protocol
Function Value
ABB 81
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Remote communication
Type of LDCM Short range (SR) Medium range (MR) Long range (LR)
Transmission rate / Data rate 2 Mb/s / 64 kbit/s 2 Mb/s / 64 kbit/s 2 Mb/s / 64 kbit/s
Clock source Internal or derived Internal or derived Internal or derived from received
from received from received signal signal
signal
82 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Hardware
IED
Table 99. Water and dust protection level according to IEC 60529
Connection system
Terminal blocks suitable for ring lug terminals 250 V AC, 20 A 4 mm2 (AWG12)
Terminal blocks suitable for ring lug terminals 300 V AC 3 mm2 (AWG14)
ABB 83
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Specifications Values
Weight 8.0 kg
Specifications Values
Weight 4.8 kg
Specifications Values
Weight 4.5 kg
84 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Data Value
Function Value
Time tagging error with synchronization once/min (minute pulse synchronization), events and sampled ± 1.0 ms typically
measurement values
Time tagging error with SNTP synchronization, sampled measurement values ± 1.0 ms typically
Function Value
Accuracy +/-2μs
ABB 85
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Electrical connector:
Amplitude modulated
– low level 1-3 Vpp
– high level 3 x low level, max 9 Vpp
Accuracy +/-10μs for IRIG-B 00x and +/-100μs for IRIG-B 12x
Optical connector:
86 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Inverse characteristic
æ A ö
t = ç P + B÷ × k
ç ( I - 1) ÷
è ø
EQUATION1249-SMALL V1 EN
Reset characteristic:
tr
t = ×k
(I 2
)
-1
EQUATION1250-SMALL V1 EN
I = Imeasured/Iset
ABB 87
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
æ A ö
t = ç P ÷×k
ç ( I - 1) ÷
è ø
EQUATION1251-SMALL V1 EN
I = Imeasured/Iset
Time delay to reset, IEC inverse time (0.000-60.000) s ± 0.5% of set time ± 10 ms
TR
t = ×k
(I PR
- CR )
EQUATION1253-SMALL V1 EN
I = Imeasured/Iset
I = Imeasured/Iset
æ I ö
t = 5.8 - ç 1.35 × In ÷
è k ø
EQUATION1138-SMALL V1 EN
I = Imeasured/Iset
88 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
k
t =
æU -U >ö
ç ÷
è U> ø
EQUATION1436-SMALL V1 EN
U> = Uset
U = Umeasured
k × 480
t =
2.0
æ 32 × U - U > - 0.5 ö
ç ÷ - 0.035
è U > ø
EQUATION1437-SMALL V1 EN
k × 480
t =
3.0
æ 32 × U - U > - 0.5 ö
ç ÷ - 0.035
è U > ø
EQUATION1438-SMALL V1 EN
ABB 89
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
k
t =
æ U < -U
ö
ç ÷
è U< ø
EQUATION1431-SMALL V1 EN
U< = Uset
U = UVmeasured
k × 480
t = + 0.055
2.0
æ 32 × U < -U - 0.5 ö
ç ÷
è U < ø
EQUATION1432-SMALL V1 EN
U< = Uset
U = Umeasured
U< = Uset
U = Umeasured
90 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
U> = Uset
U = Umeasured
ABB 91
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
21. Ordering
Guidelines
Carefully read and follow the set of rules to ensure problem-free order management. Be aware that certain functions can only be ordered in
combination with other functions and that some functions require specific hardware selections.
Please refer to the available functions table for included application functions.
Product specification
Basic IED 670 platform and common functions housed in selected casing
Default:
The IED connect CD contains configuration alternative. Use the PCM600 to create or modify the configuration. The PCM600 can also be used for
adaptation of an included example configuration.
Option:
Customer specific configuration On request
Rule: Same connection type for Power supply modules and I/O modules must be ordered
Compression terminals 1MRK 002 960-AA
Logic
Optional functions
92 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Differential protection
1 2
Transformer differential protection, two winding (T2WPDIF) Qty: 1MRK 002 901-AC
1 2
Transformer differential protection, three winding (T3WPDIF) Qty: 1MRK 002 901-CC
1 2 3 4 5 6
1Ph High impedance differential protection (HZPDIF) Qty: 1MRK 002 901-HB
1 2
Generator differential protection (GENPDIF) Qty: 1MRK 002 901-PB
1 2 3
Restricted earth fault protection, low impedance (REFPDIF) Qty: 1MRK 002 901-EB
Impedance protection
1 2
Directional impedance element for mho characteristic (ZDMRDIR) Qty: 1MRK 002 924-PA
1 2
Loss of excitation (LEXPDIS) Qty: 1MRK 002 925-MB
Note: If ROTIPHIZ or STTIPHIZ is ordered, Injection equipment is also required, see section
Accessories, "Injection equipment"
Sensitive rotor earth fault protection, injection based (ROTIPHIZ) Qty: 1MRK 002 908-YA
ABB 93
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Current protection
1 2 3 4
Instantaneous phase overcurrent protection (PHPIOC) Qty: 1MRK 002 906-AC
1 2 3 4 5 6
Four step phase overcurrent protection (OC4PTOC) Qty: 1MRK 002 906-BD
1 2
Instantaneous residual overcurrent protection (EFPIOC) Qty: 1MRK 002 906-CC
1 2 3 4 5 6
Four step residual overcurrent protection (EF4PTOC) Qty: 1MRK 002 906-DD
1 2
Four step directional negative phase sequence overcurrent protection (NS4PTOC) Qty: 1MRK 002 906-DM
1 2
Sensitive directional residual overcurrent and power protection (SDEPSDE) Qty: 1MRK 002 907-DC
1 2 3
Thermal overload protection, two time constants (TRPTTR) Qty: 1MRK 002 906-NC
1 2 3 4
Breaker failure protection (CCRBRF) Qty 1MRK 002 906-RC
1 2 3 4
Pole discordance protection (CCRPLD) Qty: 1MRK 002 907-AC
1 2 3 4
Directional underpower protection (GUPPDUP) Qty: 1MRK 002 902-FB
1 2 3 4
Directional overpower protection (GOPPDUP) Qty: 1MRK 002 902-GB
1 2
Negative sequence time overcurrent protection for machines (NS2PTOC) Qty: 1MRK 002 902-LA
1 2
Accidental energizing protection for synchronous generator (AEGGAPC) Qty: 1MRK 002 902-NA
Voltage protection
1 2
Two step undervoltage protection (UV2PTUV) Qty: 1MRK 002 908-AC
1 2
Two step overvoltage protection (OV2PTOV) Qty: 1MRK 002 908-DC
1 2 3
Two step residual overvoltage protection (ROV2PTOV) Qty: 1MRK 002 908-GC
1 2
Overexcitation protection (OEXPVPH) Qty: 1MRK 002 908-MC
1 2
Voltage differential protection (VDCPTOV) Qty: 1MRK 002 924-TB
100% Stator E/F 3rd harmonic (STEFPHIZ) Qty: 1MRK 002 908-TB
94 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Frequency protection
1 2 3 4 5 6
Underfrequency protection (SAPTUF) Qty: 1MRK 002 908-NC
1 2 3 4 5 6
Overfrequency protection (SAPTOF) Qty: 1MRK 002 908-RC
1 2 3
Rate-of-change frequency protection (SAPFRC) Qty: 1MRK 002 908-SB
Multipurpose protection
1 2 3 4 5 6
General current and voltage protection (CVGAPC) Qty: 1MRK 002 902-AB
7 8 9 10 11 12
1 2 3 4 5
Current circuit supervision (CCSRDIF) Qty: 1MRK 002 914-AB
1 2 3
Fuse failure supervision (SDDRFUF) Qty: 1MRK 002 914-GC
Control
1 2
Synchrocheck, energizing check and synchronizing (SESRSYN) Qty: 1MRK 002 916-AD
Apparatus control for up to 6 bays, max 30 apparatuses (6CBs) incl. interlocking 1MRK 002 916-RD
1 2 3 4
Tap changer control and supervision, 6 binary inputs, coded binary (Binary, BCD, Qty: 1MRK 002 925-PC
Gray) (TCMYLTC)
1 2 3 4
Tap changer control and supervision, 32 binary inputs, one per position (TCLYLTC) Qty: 1MRK 002 924-UB
Station communication
ABB 95
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Optional hardware
Human machine hardware interface
96 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Analog system
Transformer input module, compression terminals 3IM, 1A+4IP, 1A+5U, Qty: 1 2 1MRK 002 247-EA
50/60 Hz
Transformer input module, compression terminals 3IM, 5A+4IP, 5A+5U, Qty: 1 2 1MRK 002 247-EB
50/60 Hz
ABB 97
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Transformer input module, ring lug terminals 3IM, 1A+4IP, 1A+5U, Qty: 1 2 1MRK 002 247-EC
50/60 Hz
Transformer input module, ring lug terminals 3IM, 5A+4IP, 5A+5U, Qty: 1 2 1MRK 002 247-ED
50/60 Hz
Note: One Analog digital conversion module, with time synchronization is always delivered with each Transformer input module.
Case size
When ordering I/O modules, observe the maximum quantities according to tables below.
Note: Standard order of location for I/O modules is BIM-BOM-SOM-IOM-MIM from left to right as seen from the rear side of the IED, but can also
be freely placed.
Note: Maximum quantity of I/O modules depends on the type of connection terminals.
98 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Maximum quantity of I/O modules, with ring lug terminals, module limits see above
Case sizes Maximum in case Possible locations for I/O modules
with ringlugs
1/1 x 19”, one (1) TRM 7 P3, P5, P7, P9, P11, P13, P15 1MRK 000 151-NC
1/1 x 19”, two (2) TRM 5 P3, P5, P7, P9, P11 1MRK 000 151-ND
3/4 x 19”, one (1) TRM 4 P3, P5, P7, P9 1MRK 000 151-NB
ABB 99
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Make BIM with 50 mA inrush current the primary choice. BIM with 50 mA inrush current fulfill additional standards. As a consequence the EMC
withstand capability is further increased.
For pulse counting, for example kWh metering, the BIM with enhanced pulse counting capabilities must be used.
Binary input module (BIM) 16 inputs
RL 24-30 VDC, 30 mA Qty: 1 2 3 4 5 6 7 1MRK 000 508-DB
8 9 10 11 12 13 14
8 9 10 11 12 13 14
8 9 10 11 12 13 14
8 9 10 11 12 13 14
8 9 10 11 12 13 14
8 9 10 11 12 13 14
8 9 10 11 12 13 14
8 9 10 11 12 13 14
Binary input module (BIM) with enhanced pulse counting capabilities, 16 inputs
100 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
8 9 10 11 12 13 14
8 9 10 11 12 13 14
8 9 10 11 12 13 14
8 9 10 11 12 13 14
Binary output module 24 output relays (BOM) Qty: 1 2 3 4 5 6 7 1MRK 000 614-AB
8 9 10 11 12 13 14
8 9 10 11 12 13 14
8 9 10 11 12 13 14
ABB 101
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Make IOM with 50 mA inrush current the primary choice. IOM with 50 mA inrush current fulfill additional standards. As a
consequence the EMC withstand capability is further increased.
IOM with 30 mA inrush current is still available.
Binary input/output module (IOM) 8 inputs, 10 outputs, 2 high-speed outputs
RL 24-30 VDC, 30 mA Qty: 1 2 3 4 5 6 1MRK 000 173-GB
Binary input/output module (IOM with MOV), 8 inputs, 10 outputs, 2 high-speed outputs
RL 24-30 VDC Qty: 1 2 3 4 5 6
1MRK 000 173-GC
102 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Note: Optical ethernet module, 2 glass interfaces is not allowed together with SLM.
Optical ethernet module, 1 channel glass 1MRK 002 266-AA
Serial and LON communication module, supports SPA/IEC 60870-5-103, LON and DNP 3.0
Serial/LON plastic interface 1MRK 001 608-AB
Galvanic RS485 communication module for DNP 3.0 1MRK 002 309-AA
Time synchronization
Engineering facilities
19” rack mounting kit for 1/2 x 19” case or 2 x RHGS6 or RHGS12 Quantity: 1MRK 002 420-BB
19” rack mounting kit for 3/4 x 19” case or 3 x RHGS6 Quantity: 1MRK 002 420-BA
19” rack mounting kit for 1/1 x 19” case Quantity: 1MRK 002 420-CA
Note: Wall mounting not recommended with communication modules with fibre connection (SLM, Quantity: 1MRK 002 420-DA
OEM, LDCM)
Wall mounting kit for terminal
Flush mounting kit + IP54 sealing (factory mounted). Cannot be ordered separately thus must be Quantity: 1MRK 002 420-EA
specified when ordering a terminal.
Accessories
ABB 103
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
External interface converter from C37.94 to G703 Quantity: 1 2 1MRK 002 245-AA
External interface converter from C37.94 to G703.E1 Quantity: 1 2 1MRK 002 245-BA
Due to the high flexibility of our product and the wide variety The normally open "In test mode" contact 29-30 on the RTXP
of applications possible the test switches needs to be test switches should be connected to the input of the test
selected for each specific application. function block to allow activation of functions individually
during testing.
Select your suitable test switch based on the available
contacts arrangements shown in the reference Test switches type RTXP 24 is ordered separately. Please
documentation. refer to Section "Related documents" for reference to
corresponding documents.
However our proposals for suitable variants are:
RHGS 6 Case or RHGS 12 Case with mounted RTXP 24 and
Two winding transformer with internal neutral on current the on/off switch for dc-supply are ordered separately. Please
circuits. Two pcs can be used in applications for three refer to Section "Related documents" for reference to
winding transformers in single or multi-breaker arrangement corresponding documents.
(ordering number RK926 315-BD)
Protective cover for rear side of RHGS6, 6U, 1/4 x 19” Quantity: 1MRK 002 420-AE
Protective cover for rear side of terminal, 6U, 1/2 x 19” Quantity: 1MRK 002 420-AC
Protective cover for rear side of terminal, 6U, 3/4 x 19” Quantity: 1MRK 002 420-AB
Protective cover for rear side of terminal, 6U, 1/1 x 19” Quantity: 1MRK 002 420-AA
104 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
High impedance resistor unit 1-ph with resistor and voltage dependent resistor for 1 2 3
20-100V operating voltage Quantity: RK795101-MA
High impedance resistor unit 3-ph with resistor and voltage dependent resistor for Quantity: RK795101-MB
20-100V operating voltage
High impedance resistor unit 1-ph with resistor and voltage dependent resistor for 1 2 3
100-400V operating voltage Quantity: RK795101-CB
High impedance resistor unit 3-ph with resistor and voltage dependent resistor for Quantity: RK795101-DC
100-400V operating voltage
ABB 105
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Injection equipment
Casing
1/2 x 19" rack casing Basic
Backplane module (BPM) Basic
Human machine interface
HMI and logic module (HLM) Basic
Injection modules
Rule: Stator injection module (SIM) is required if 100% stator earth fault protection,
injection based (STTIPHIZ) is selected/active in REG670
Stator injection module (SIM) 1MRK 002 544-AA
Rule: Rotor injection module (RIM) is required if Sensitive rotor earth fault protection,
injection based (ROTIPHIZ) is selected/active in REG670
Rotor injection module (RIM) 1MRK 002 544-BA
Extra IP54 mounting seal + Flush mounting kit for terminal 1MRK 002 420-EA
Rule: REX061 requires REX060 and that Rotor injection module (RIM) is selected in REX060
and that Sensitive rotor earth fault protection, injection based (ROTIPHIZ) is selected/active in
REG670.
Coupling capacitor unit (REX061) Quantity: 1MRK 002 550-AA
Rule: REX062 requires REX060 and that Stator injection module (SIM) is selected in REX060
and that 100% stator earth fault protection, injection based (STTIPHIZ) is selected/active in
REG670
Shunt resistor unit (REX062) Quantity: 1MRK 002 555-AA
Combiflex
Key switch for lock-out of settings via LCD-HMI Quantity: 1MRK 000 611-A
Note: To connect the key switch, leads with 10 A Combiflex socket on one end must be used.
106 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
Injection unit for Rotor earth fault protection (RXTTE 4) Quantity: 1MRK 002 108-BA
Front connection cable between LCD-HMI and PC Quantity: 1MRK 001 665-CA
Manuals
Note: One (1) IED Connect CD containing user documentation (Operator’s manual, Technical reference
manual, Installation and commissioning manual, Application manual and Getting started guide),
Connectivity packages and LED label template is always included for each IED.
Rule: Specify additional quantity of IED Connect CD requested. Quantity: 1MRK 002 290-AB
ABB 107
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
User documentation
Rule: Specify the number of printed manuals requested
Operator’s manual IEC Quantity: 1MRK 502 028-UEN
Reference information
For our reference and statistics we would be pleased to be provided with the following application data:
Type of prime mover: steam , gas , hydro , pumpstorage , nuclear , other ______________________
Related documents
108 ABB
Generator protection REG670 1MRK502031-BEN D
Customized
Product version: 1.2
ABB 109
110