Three Phase Transformer: Presented by
Three Phase Transformer: Presented by
Three Phase Transformer: Presented by
Transformer
Presented by:
Rizwan Yaseen 2017-EE-432
Zeeshan Saeed 2017-EE-414
Muhammad Hamad 2017-EE-404
Muhammad Zeeshan 2017-EE-402
Outline
We are going to design a 250 VA step down three phase transformer of 440V to
74V. Necessary calculations along with formulae are given in the next slides.
As we are going to design small transformer (of small power rating) so we are
neglecting core and copper losses as they doesn’t matters in small transformers and
seriously considered in designing power transformers (high power rating transforms
Calculations of a Transformer
As, we are going to design a practical transformer so we must consider the core
available in market. The standard Bobbins available in market practically is 1”x1”,
1.25”x1.5”, 1.5”x1.5” and so on. We took nearest core area available to our
calculation. We took bobbin of 1.875 inch sq. (1.25”x1.5”) or 0.0012065 meter
square. We have the core area. We can calculate turns per volts using this area by
following:
Putting f=50 Hz; B = 1.2 wb/(m^2); A= 0.0012065 m^2,
we got:
1
𝑇𝑢𝑟𝑛/𝑉𝑜𝑙𝑡 =
4.44 × 𝑓 × 𝐵 × 𝐴
So, Turns per volts are 3.1 Turns per volts.
A = area of core
F = operating frequency
B = magnetic flux density
Calculations of a Transformer