SITUATION:
One day, an unusual loud sound was heard found with bursting of 132KV LA on one
132KV feeder, causing the tripping of connected transformer.
TASK:
1. To identify the reason of fault, Search
Operation/inspection at the concerned bay in
the switch yard started.
2. In Distance-protection relay it indicated that
the fault has occurred at a distance of 1km
3. Some traces of burnt materials and pieces of
broken ZnO blocks found at a place under the
B-phase limb of Surge arrester of 132 KV one
feeder.
4. It was observed that flashover has occurred
at the B-phase surge arrester and it was
completely broken from the middle of the
limb.
Analysis:
1. The LCM of the burst surge arrester was taken few days before & found to be in place,
still it burst. The following reading have been attached here.