TECHNICAL DATA SHEET

S.No DESCRIPTION SPECIFICATION

Note: Product brochure must be attached along with Technical Bid

Numeric Makes 80kVA UPS with built-in Isolation , 40 X 130AH


1 UPS Discription batteries , along paralleling kit & SNMP Card

2 Warranty 5Yrs on UPS & 5Yrs on Batteries

3 UPS capacity 80 kVA/72kW with built-in Galvanic Isolation, input PF.99 to unity
Configuration For Paralleling with our Existing Numeric make 80kVA UPS
3.1 Technology IGBT on the input and output with
Digital Signal Processor controlled
for the following:
a. Rectifier/Charger
b. Battery management.
c. Inverter
d. Static Switch
3.2 UPS type and configuration True On-Line, Double conversion
meeting VFI-SS-111
3.3 Rated Output 80 kVA / 72kW
The UPS system is compatible for 0.7 lagging
to 0.9 leading PF loads without deration.
3.4 Power factor at full load >/= 0.99
Power factor at 50% load >/= 0.98

3.5 Input current THDi at full load </= 3.0%


Input current THDi at 50% load </= 6.0%
4 Input
4.1 Voltage 380/400/415 V
4.2 Voltage tolerance 320-480V at rated load.
upto 240-480V at 50% load.
4.3 Frequency 50/60 Hz
4.4 Frequency tolerance ± 10%
5 Rectfier/Charger
5.1 Type of rectifier used IGBT based DSP controlled Rectifier.
5.2 Ripple voltage at full load Typically 0.
5.3 Efficiency of rectifier >/= 98%
5.4 Battery charger features
i) Type of charging circuit. Constant Voltage Constant Current.
ii) Battery status monitoring facility. Thro LCD display at the front panel.
iii) Battery protection circuits. Battery MCCB provided in enclosure.
6 Inverter
6.1 Technology of inversion IGBT based PWM design with DSP
controlled.
7 Output
7.1 Voltage 380/400/415 VAC, 3 phase, 4 wire
Settable.
7.2 Output voltage regulation
I) Balanced load ± 1%
ii) Unbalanced load ± 3% for 4 wire system
7.3 Output Frequency 50 Hz
7.4 Output Frequency range ± 0.5 Hz
7.5 OP Frequency synchronising range Selectable between 1Hz to 5Hz
with Bypass
7.6 Transient voltage regulation for ± 2%
0 to 100% and vice versa
7.7 Recovery time < 5 m.sec
7.8 Wave form Sinusoidal
7.9 Crest Factor 3:1
7.10 Harmonics :
i) Total harmonic distortion at 100%

Page 1 of 2
S.No DESCRIPTION SPECIFICATION
non-linear load . < 3%
ii) Total harmonic distortion at 100% < 1%
linear load .
7.11 Phase displacement:
i) Balanced load 120 ± 1 deg. Electrical
ii) 100 % Unbalanced load 120 ± 2 deg. Electrical
7.12 Overload at 0.9 pf loads 150% for 5 sec
125% for 1 min.
110% for 10 mins.
7.13 Neutral current & conductor size 1.5 times of Phase current.
8 Static and Manual Bypass : Standard and built-in
9 Eco mode Available.
10 Intelligent Eco Mode Available (For standalone UPS)

When the UPS is configured to operate in SMART ACTIVE mode, it


automatically selects whether to operate in ON-LINE or ECO mode.
The decision is made based on statistical calculations performed
by the UPS and based on the quality of the mains and bypass
supplies: if the latter remains suitable for a certain period, the unit
selects ECO mode, otherwise it remains in ON-LINE mode. This
feature is very much beneficial for process loads.
11 Efficiency Excluding transformer loss
At Full load >/= 93.0%
At 75 % load >/= 93.5%
At 50% load >/= 93.5%
At 25% load >/= 90.5%
12 Environmental conditions
i)Temperature (design ambient) 0 - 40 deg C
ii)Relative humidity 95 % RH
iii) Acoustic Noise measured at 1 < 52 dBA
Mt distance
13 Event logging Available.
14 Protection
a Overload Available.
b Short circuit Available.
c Input low voltage Available.
d Output over voltage Available.
e Battery over charging Available.
f Battery over discharging Available.
18 Reliability > 99.5%
19 MTBF 2,50,000 hrs
20 MTTR < 4 hours.
21 Conformity to Standards
a Design IEC EN 62040-3
b Safety IEC EN62040-1-1
c EMC IEC EN 62040-2
d CE marking Available.
e ISO certification ISO 9001, 14001,18001
22 Whether capacity addition of UPS Paralleling facility of 6 units of
systems in phases possible and similar capacity is available.
how
23 Service Facility 24 / 7 Support available thro our
own Service Centre in Kanpur.

Page 2 of 2