Professional Documents
Culture Documents
SOTF
SOTF
ABB LOGIC:
Zone 2 reach (both direction)
Initiated with "CB close command" Binary Input
tSOTF is the time for which SOTF function is activated in the relay (on receive of CB close command) to check the impedance
IPh<, UPh<, tDuration, tDLD settings are only required when we have "Autoinitiation" mode turned on.
MICOM LOGIC:
Initiation with "CB close command" Binary Input
SOTF reaches are Zone 1 and Zone 2
TOR is "Trip on Reclosure", SOTF operation on case of persistent fault during AR operation
"SOTF Delay": It’s the time after which SOTF is enabled when the relay detects open 3pole from CB status
SIEMENS LOGIC:
SOTF is initiated with "CB close command" Binary Input
It is used as a 50HS (Instantaneous Overcurrent) protection. Upon SOTF initiation if the relay detects, 2A current, it immediately
issues a trip on SOTF. The mode is bi-directional (There is no impedance reach setting in case of siemens relay)