Download as pdf or txt
Download as pdf or txt
You are on page 1of 185

STORMWATER & SUBSOIL

DRAINAGE SYSTEMS
VOLUME II
Standard Drawings

(WA-726-2)
Third Edition
April 2022
Standards Guideline
For

STORMWATER & SUBSOIL DRAINAGE


SYSTEMS

VOLUME 2

Standard Drawings

Document No: WA-726-2


Third Edition
April- 2022
Department of Municipalities and Transport
PO Box 20
Abu Dhabi, United Arab Emirates

© Copyright 2022, by the Department of Municipalities and Transport. All Rights Reserved. This manual, or parts thereof, may not
be reproduced in any form without written permission of the publisher
S.# Table of Contents Pages
1 Amendment Page 3

2 About the Abu Dhabi Quality and Conformity Council 4

3 Acknowledgement 5

4 Foreword 6

5 Working group 6

6 Purpose 6

7 Scope 6

2|P a g e
1. Amendment Page
To ensure that each copy of this technical document (Abu Dhabi Guideline) contains a complete
record of amendments, the Amendment Page is updated and issued with each set of revised/new
pages of the document. This ADG/ISGL is a live document which can be amended when necessary.
QCC operates VOLUME I, DESIGN MANUAL Group which prepared this document and can review
stakeholder comments in order to review and amend this document and issue an updated version
when necessary.
EDITION REVISION
DATE PAGE NO. AMENDMENTS NOTES
NO. NO.

01 00 DEC 2016 - According to Volume 1

02 01 JULY 2020 - According to Volume 1

03 02 April 2022 - According to Volume 1

3|P a g e
2. About the Abu Dhabi Quality and Conformity
Council
Abu Dhabi Quality and Conformity Council (QCC) is an Abu Dhabi government
entity established in accordance with Local Law No. (3) of 2009 to raise the
quality of Abu Dhabi’s exports and products traded locally. QCC consists of a
council of regulators and industry with a mandate to ensure provision of quality
infrastructure in line with global standards.
o QCC’s functions are divided into six key areas:
• Developing standards and specifications
• Capacity building of metrology systems
• Strengthening testing infrastructure
• Launching conformity schemes
• Protecting consumer interests
• Ensuring fair trade

o QCC’s key stakeholders include regulatory authorities, consumers, retailers


and wholesalers, industry, conformity assessment bodies (CABs) and
importers.
QCC supports regulators and government organizations through offering
quality and conformity facilities, expertise and resources that allow them to
implement products safety and compliance requirements and regulations.
Additionally, QCC works towards promoting a culture of quality and protecting
the interests of consumers. In doing this, QCC seeks to promote the Emirate’s
competitiveness to become one of the world's most attractive regions for
investments and human capital, and to support the competitiveness of national
industries in world markets.

4|P a g e
3. Acknowledgement
QCC would like to thank the members of the Working Group listed below.

S.# Name Entity

1 Eng. Hamad Muhsen Abdullah Abu Dhabi City Municipality

2 Dr. Amr Adel El-Agroudy Abu Dhabi City Municipality

3 Eng. Mohamed Darwish Jaddawi Abu Dhabi City Municipality

4 Eng. Bakhita Mubarak Saeed Al Ketbi Al Ain City Municipality

5 Eng. Aysha Saeed Ali Al Sharyani Al Ain City Municipality

6 Eng. Anwar Mahmoud Sediqee Al Ain City Municipality

7 Eng. Mohammed Ali Al Ghanem Al Dhafrah Region Municipality

8 Eng.Wael Taher Salem Suleiman Environment Agency -Abu Dhabi

9 Eng. Ehab.Nessim Musanada

10 Eng.Suhail.AlNuaimi Abu Dhabi Sewerage Services Company

11 Eng. Ali Al Hashmi Abu Dhabi Sewerage Services Company

12 Eng. Abdulaziz Jaddawi Abu Dhabi Transmission and Despatch Company-Transco

13 Eng. majed.almarzouqi Abu Dhabi Waste Management Center-Tadweer

14 Eng. Mohamed Abbas Department of Energy

15 Dr.Ashraf Hassn United Arab Emirates University

16 Eng. Mahmoud Alrais Masdar City

17 Eng.Nizar Kouzar Parsons

18 Eng.Hashim Majeed Aldar


4. Foreword
This Storm water and Sub-soil Drainage Systems Design Manual covers the key technical requirements
for designing storm water and sub-soil drainage systems within the jurisdiction of Abu Dhabi Emirate.

Principal guidance is contained in the main body of the manual which includes references to
established and recognised documents. These documents include national and international standards.
Supporting detail such as formulae, information and methodologies are given in the Appendices.

The safety of construction and maintenance workers and of the general public is an important factor
for projects in Abu Dhabi and it is essential that safety is considered throughout the design of each
project. The reader’s attention is drawn to various safety considerations identified by red text.

The Manual is intended to be used by experienced, professional drainage engineers, qualified


professionals with specialised knowledge of geology and the application of soil mechanics and other
suitably qualified and experienced professionals.

5. Working Group
The Professional Working Group was organized by Abu Dhabi Quality and Conformity Council and
established in 2022, which was requested by Department of Municipalities and Transport, to prepare
Design Manuals for Storm Water Network in cooperation with the related stakeholders including
representatives from government and private sectors in order to establish operating procedures and
technical guidelines for the relevant Authorities, Project Developers, Planners, Engineers etc., a step-
by-step guidance on how to prepare the waste management aspect of a planning application for new
development in the Emirate of Abu Dhabi at the Inception, Planning & Design stages of the Project.

6. Purpose
The purpose of the Project is to review the current design manuals (VOLUME I, DESIGN MANUAL) for
storm water network and update the same to count for the Department of Municipalities and Transport
current requirements.

7. Scope
This Manual is one of four volumes relating to the design, construction, operation and maintenance of
storm water and sub-soil drainage systems for Municipal controlled roads and developments in Emirate
of Abu Dhabi:

• Volume 1 – Design Manual

• Volume 2 –Standard Drawings

• Volume 3 – Operation and Maintenance Manual

• Volume 4 – Standard Specifications

6|P a g e
NOTES:
2000 THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
A 300 REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS
WHITE BACKGROUND OTHERWISE STATED.

400

400
BLACK LETTERING
LEGEND

67
REINFORCED CEMENT CONCRETE

SOIL

67
400 CONTRACT No.

400
WHITE BACKGROUND PROJECT TITLE FGL - FINISHED GROUND LEVEL
PROJECT DESCRIPTION : 3 LINES MAXIMUM
COMPLETION DATE : DAY - MONTH - YEAR TYP. - TYPICAL
1800

1800
67

67
400

400
WHITE BACKGROUND
67
3120

3120

67
H gl-r-h , G
400

400
WHITE BACKGROUND

STEEL POST
1320

1320
STEEL POST
1170

1170
200

200
FGL FGL FGL FGL
900

900
MASS CONCRETE BASE (TYP.) MASS CONCRETE BASE (TYP.) MASS CONCRETE BASE (TYP.)

REFERENCE DRAWINGS AND DOCUMENTS

A
100

100
960
650 1275 650
1610

FRONT ELEVATION SECTION A-A

2575

2000

No. REVISION-1 APP'D 2020


CLIENT

TITLE
STANDARD DRAWINGS
1610
960

DRAWING TITLE

STANDARD DRAWING
PROJECT SIGN BOARD

DRAWN - SCALE 1:1000


650 1275 650
CHECKED - DATE -
APPROVED - SIZE A1
PLAN
PROJECT DWG.
No. - No.
100

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
FRONT LAYOUT REAR LAYOUT 1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS
OTHERWISE STATED.
SIGN FACE 3 THK ENGINEERING 2. THE CONTRACTOR SHALL PREPARE DETAILED WORKING
GRADE REFLECTIVE SHEET
THE CONTRACTOR SHALL SELECT SAFETY SIGNS APPROPRIATE TO THE FIXED TO SIGN BOARD DRAWINGS, PROPOSED SIGN BOARD LAYOUTS FOR THE
HAZARDS ASSOCIATED WITH THE CURRENT WORKS AND POSITION ENGINEER'S APPROVAL PRIOR TO MANUFACTURE.
250 250 3. DETAILS OF THE EMERGENCY CONTACT TELEPHONE
SAFETY NOTICEBOARDS ACCORDINGLY NUMBERS IN A THIRD LANGUAGE MAY BE GIVEN IF THE
MAJORITY OF THE CONTRACTOR'S LABOUR FORCE

100
ORIGINATE FROM A NON-ENGLISH OR ARABIC SPEAKING
SITE SAFETY CO.UNTRY. eg. CHINESE, INDIAN etc.
(Contractor's Name) 4. WHERE THE WORKS CROSS OR ARE CLOSE TO EXISTING
(Contract Title) AND GAS PIPELINES OR FACILITIES, ADDITIONAL BOXES
SIGNBOARD 12 THK
MARINE PLY SHALL BE PROVIDED WITH OIL AND GAS COMPANY
EMERGENCY CONTACT NUMBERS.
75 DIA STEEL
5. SIGNS TO BE ON STICKERS OR ON METAL PLATES AND
POST (TYP) ATTACHED TO THE BOARD FACE.
Eye Protection Wear Protective footwear
must be worn Ear Protectors
Wear Helmet Wear Gloves must be worm LEGEND

REINFORCED CEMENT CONCRETE

TYP - TYPICAL

SEE NOTE 4

3 EQUAL SPACING
2440
Wear Respirator

BLUE BACKGROUND
Eye Protection Wear Protective footwear
Wear Helmet Wear Gloves

SUGGESTED LAYOUT
must be worn Ear Protectors must be worm

SEE NOTES
No Smoking No Drinking No Eating Use Adjustable Now Wash your
No Naked Light Guard hands please

BLUE BACKGROUND

100
1220
SEE DETAIL 'A'
DANGER 100 DIA PIPE

500
Men working SLEEVE (TYP)
on equipment

RED BACKGROUND TYPICAL ARRANGEMENT LIFTING


HOOKS (TYP)
REFERENCE DRAWINGS AND DOCUMENTS
SCALE 1:20

SEE NOTE 2
600 (TYP.)
DANGER DANGER DANGER Dangerous DANGER
Electric
Fire risk Shock risk chemicals High voltage
YELLOW BACKGROUND

MASS CONCRETE BASE


600 (TYP)
SLING (TYP)
SAFELY
SINGLE
No. REVISION-1 APP'D 2020
DOUBLE
REEVING
CRADLE TYPICAL INSTALLATION CLIENT
SCALE 1:20

DOUBLE
CRADLE DOUBLE
WRAP
Protect
DANGER DANGER DANGER the trench
Suspended load Compressed air Moving machinery TITLE
YELLOW BACKGROUND
STANDARD DRAWINGS
HIGH TENSILE
EXTRUDED ALUMINUM
CHANNEL (TYP)
DRAWING TITLE
BLUE BACKGROUND
DETAIL 'A'
N.T.S
STANDARD DRAWING PROJECT
SAFETY SIGN BOARD
All visitors must
report to site office
DRAWN - SCALE AS SHOWN
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
101

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
16 DIA STEP BAR CAST INTO COVER SLAB WITH TOE HOLE MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE
DUCTILE IRON COVER INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
COVER SLAB DETAIL
FOR UNPAVED AREA
CHECKED AND APPROVED AS PART OF THE PROJECT
AS SPECIFIED UV RESISTANCE EPOXY DRAWING SET.
COATING TO ALL SURFACES ABOVE GROUND
1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS
CL OTHERWISE STATED.
FGL FGL
250 200

2. ALL CONCRETE TO BE CLASS B UNLESS OTHERWISE


STATED.

100
3. ALL EXTERNAL FACES OF CONCRETE BELOW GROUND TO
BE TANKED.

VARIES
4. ALL INTERNAL FACES OF CONCRETE TO BE COATED WITH
250 250
SHAFT DEPTH VARIES (7000 MAXIMUM)

REINFORCED CONCRETE RINGS SEE NOTE 7 EPOXY COATING AS SPECIFIED.


5. UNLESS OTHERWISE STATED ALL INLET AND OUTLET
GRP LADDER PIPES OF MANHOLES SHALL BE LAID SOFFIT TO SOFFIT.
6. ALL COVERS IN OPEN AREA TO BE PROVIDED WITH 1No.
GRAB BAR.
REINFORCED CONCRETE SHAFT COVER SLAB DETAIL 7. MANHOLES SHALL BE PROVIDED WITH REINFORCED
75 THICK PRECAST CONCRETE FOR PAVED AREA
CONCRETE RINGS (2Nos. AS MINIMUM), THE LOWER RING
SEATING RINGS BEDDED IN 1 PART
SHALL BE 250mm HEIGHT AND THE UPPER RING TO VARY
SEE DETAIL 1 CEMENT / 2 PART SAND MORTAR DUCTILE IRON COVER EPOXY COATING TO ACCORDING TO FINAL GROUND LEVEL.
10 DOWEL DRILLED AND SET INTO 16 DIA STEP BAR CAST INTO ALL INTERNAL SURFACES 8. MANHOLES TO BE PROVIDED WITH SAND TRAP 500mm
COVER SLAB AT 300 CENTERS COVER SLAB WITH TOE HOLE DEEP SUMP.
150 CLASS B 9. THE MANHOLES AND CHAMBERS ARE DESIGNED USING
C C FINISHED LEVEL OF
CARRIAGEWAY (FL) CL CONCRETE SURROUND FULL GROUND WATER LEVEL CONDITION WITH 1.1 FACTOR
250 1100 DIA 250 250 1100 DIA 250 OF SAFETY FOR FLOATATION AND BEARING PRESSURE

(MIN.)
450
NOT EXCEEDING 200kpa AT FORMATION LEVEL.
1000

MAX
600
SEE NOTE 12 SEE NOTE 12 10.DEWATERING OPERATIONS SHALL BE PROVIDED DURING
CONSTRUCTION AND MAY ONLY BE TERMINATED AFTER
TANKING MEMBRANE

250
ROOF SLAB HAS BEEN INSTALLED.
AND PROTECTION BOARD 11. ALL STRUCTURAL DETAILS TO BE VERIFIED BY DESIGNERS
/ CONSULTANTS.
300 300 12.FOR SHALLOW MANHOLES (DEPTH LESS THAN 2.0m)
MANHOLE SHAFT WALL THICKNESS CAN BE REDUCED TO
300 300
200mm.
COVER SLAB DETAIL FOR CARRIAGEWAY & PARKING AREAS LEGEND
(BASE UNIT)

(SEE NOTE 8)

IL
1850

REINFORCED CONCRETE
PVC WATER STOP SOIL COMPACTED TO 95% MDD
500

CONSTRUCTION JOINT
400

500
PLAIN CONCRETE
WEARING COURSE
BASE COURSE
450

450
SUBGRADE
FGL FINAL GROUND LEVEL
250
FL FINAL ASPHALT / INTERLOCKED TILE LEVEL
DIA DIAMETER
50mm THK. CEMENT/SAND SCREED
TANKING MEMBRANE
1700 DIA CL COVER LEVEL
EPDM 'O' RING SEAL IL INVERT LEVEL OF OUTLET PIPE
300 1700 DIA 300 75mm THICK C20 BLINDING OR GASKET STRIP(2 Nos GA GENERAL ARRANGEMENT
1000 GAUGE POLYETHYLENE SHEET OF MIN SIZE 20mm WIDTH)
SECTION B-B
SECTION A-A
SPECIFIED SEALANT
FOR JOINT

80
PROTECTION BOARD
EPOXY
5° COATING AS TANKING MEMBRANE
0°± SPECIFIED
12
AT 5° REFERENCE DRAWINGS AND DOCUMENTS
E N ° ±
OP 90 85 80 85 STANDARD DRAWING - TANKING DETAILS
T
A STANDARD DRAWING - CONSTRUCTION AND MOVEMENT JOINT1001
K 207
C STANDARD DRAWING - MISCELLANEOUS DETAILS
LO FOR MANHOLES
DETAIL 1 STANDARD DRAWING - REINFORCEMENT DETAILS 1000
(SERIES)
SCALE 1:20
STANDARD DRAWING - STORM WATER MANHOLE FRAME 213
AND COVER DETAILS

DETAIL A
HINGE DETAILS B

120

No. REVISION-2 APP'D 2021

300
SEE DETAIL A FOR HINGE CLIENT
DETAILS
MANHOLE DETAILS ARE SHOWN FOR THE A A
VARIES
PRECAST MANHOLE. HOWEVER, CAST
IN-SITU MANHOLES ARE ACCEPTABLE
SUBJECT TO THE ENGINEER'S APPROVAL. TITLE
300

THIS DRAWING APPLIES WHERE SHAFT STANDARD DRAWINGS


- DUCTILE IRON COVER AND DEPTH IS NOT GREATER THAN 7000 . STORM WATER WORKS
FRAME TO SUIT 750 DIA NOMINAL DESIGNERS TO UPDATE AND PROVIDE
SIZE CLEAR OPENING IN ALL DRAWING TITLE
MANHOLES ON STORM WATER
FULL CALCULATIONS FOR DEPTHS
PIPELINES UPTO 500 DIA GREATER THAN 7000. STANDARD DRAWING G.A.
INCLUSIVE.
- GRP COVER WITH ADEQUATE
B OF STORM WATER
FRAME IS ACCEPTABLE SUBJECT
TO THE ENGINEER'S APPROVAL.
MANHOLE ON PIPELINES
300 - 500mm DIA.
PLAN AT COVER LEVEL
DRAWN - SCALE 1:50 & 1:20
SECTION C-C CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
201

THIRD EDITION - APRIL 2022


NOTES:
16 DIA STEP BAR CAST INTO
COVER SLAB WITH TOE HOLE THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
DUCTILE IRON COVER AS SPECIFIED UV RESISTANCE
COVER SLAB DETAIL REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
EPOXY COATING TO ALL
FOR UNPAVED AREA AS SPECIFIED UV RESISTANCE AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
SURFACES ABOVE GROUND
EPOXY COATING TO ALL SURFACES APPROVED AS PART OF THE PROJECT DRAWING SET.

200

100
CL ABOVE GROUND CL 1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS OTHERWISE
250 200

100
FGL FGL FGL FGL
STATED.
2. ALL CONCRETE TO BE CLASS B UNLESS OTHERWISE

250
STATED.

250 VARIES
3. ALL EXTERNAL FACES OF CONCRETE BELOW GROUND TO

250 VARIES
BE TANKED.
REINFORCED CONCRETE RINGS SEE NOTE 7 4. ALL INTERNAL FACES OF CONCRETE TO BE COATED WITH
EPOXY COATING AS SPECIFIED.
DEPTH VARIES (2900 MAXIMUM)

GRP LADDER 5. UNLESS OTHERWISE STATED ALL INLET AND OUTLET PIPES
OF MANHOLES SHALL BE LAID SOFFIT TO SOFFIT.
6. ALL COVERS IN OPEN AREA TO BE PROVIDED WITH 1No.
SEE DETAIL 1 REINFORCED CONCRETE SHAFT EPOXY COATING TO ALL GRAB BAR.

VARIES
INTERNAL SURFACES 7. MANHOLES SHALL BE PROVIDED WITH REINFORCED
TANKING MEMBRANE
400 CONCRETE RINGS (2Nos. AS MINIMUM). THE LOWER RING
AND PROTECTION BOARD
SHALL BE 250mm HEIGHT AND THE UPPER RING TO VARY
REINFORCED CONCRETE SHAFT ACCORDING TO FINAL GROUND LEVEL.
C C 8. MANHOLES TO BE PROVIDED WITH SAND TRAP 500mm DEEP

ABOVE PIPE)
SUMP.

500 (MIN)
(HEIGHT OF NIB
9. THE MANHOLES AND CHAMBERS ARE DESIGNED USING
FULL GROUND WATER LEVEL CONDITION WITH 1.1 FACTOR
OF SAFETY FOR FLOATATION AND BEARING PRESSURE
NOT EXCEEDING 200kpa AT FORMATION LEVEL.

1300
10.DEWATERING OPERATIONS SHALL BE PROVIDED DURING
CONSTRUCTION AND MAY ONLY BE TERMINATED AFTER
ROOF SLAB HAS BEEN INSTALLED.
11. ALL STRUCTURAL DETAILS TO BE VERIFIED BY DESIGNERS /
REINFORCED CONCRETE BASE CONSULTANTS.
IL
(SEE NOTE 8)

(SEE NOTE 8)
PVC WATER STOP LEGEND
500

500
CONSTRUCTION JIONT
400

REINFORCED CONCRETE

SOIL COMPACTED TO 95% MDD


500

500
REINFORCED CONCRETE BASE
PLAIN CONCRETE

FGL FINAL GROUND LEVEL


50mm THK. CEMENT/SAND SCREED FL FINAL ASPHALT / INTERLOCKED TILE LEVEL
TANKING MEMBRANE
SECTION B-B
500 400 400 500 DIA DIAMETER
75mm THICK C20 BLINDING CL COVER LEVEL
1000 GAUGE POLYETHYLENE SHEET
A = OUTLET PIPE INTERNAL DIAMETER + 1200 IL INVERT LEVEL OF OUTLET PIPE
COVER SLAB DETAIL GA GENERAL ARRANGEMENT
SECTION A-A 75 THICK PRECAST CONCRETE FOR PAVED AREA
400 SEATING RINGS BEDDED IN 1 PART
CEMENT / 2 PART SAND MORTAR DUCTILE IRON COVER
10 DOWEL DRILLED AND SET 16 DIA STEP BAR CAST INTO
EPDM 'O' RING SEAL INTO COVER SLAB AT 300 COVER SLAB WITH TOE HOLE
OR GASKET STRIP(2 Nos CENTERS
FINISHED LEVEL OF 150 CLASS B CONCRETE
OF MIN SIZE 20mm WIDTH) CARRIAGEWAY (FL) SURROUND
CL

(MIN.)
130

450

MAX
600
SPECIFIED SEALANT
FOR JOINT

250
PROTECTION BOARD
EPOXY
COATING AS TANKING MEMBRANE REFERENCE DRAWINGS AND DOCUMENTS
SPECIFIED

STANDARD DRAWING - TANKING DETAILS - 801


135 130 135
COVER SLAB DETAIL FOR CARRIAGEWAY & - 1001
STANDARD DRAWING - CONSTRUCTION AND MOVEMENT JOINT
STANDARD DRAWING - MISCELLANEOUS DETAILS - 207
FOR MANHOLES
PARKING AREAS STANDARD DRAWING - REINFORCEMENT DETAILS - 1000
DETAIL 1 (SERIES)
B SCALE 1:20 STANDARD DRAWING - STORM WATER MANHOLE FRAME - 213
AND COVER DETAILS
A = OUTLET PIPE INTERNAL DIAMETER + 1200 A = OUTLET PIPE INTERNAL DIAMETER + 1200
A = OUTLET PIPE INTERNAL DIAMETER + 1200

400 400 400 400


400

SEE DETAIL A FOR HINGE DETAILS

- DUCTILE IRON COVER AND FRAME TO


SUIT 750 DIA. OPENING IN ALL MANHOLES
ON STORM WATER PIPELINES WITH
DIAMETER RANGING FROM 600 TO 800.
500 VARIES 500

No. REVISION-2 APP'D 2021


A/2

- DUCTILE IRON COVER AND FRAME TO


SUIT 900 DIA. OPENING IN ALL MANHOLES CLIENT
ON STORM WATER PIPE LINES WITH
A A DIAMETER RANGING FROM 900 TO 1400.
- GRP COVER WITH ADEQUATE FRAME IS
ACCEPTABLE SUBJECT TO THE
ENGINEER'S APPROVAL.
TITLE
STANDARD DRAWINGS
A/2

STORM WATER WORKS


± 5°
0° DRAWING TITLE
12
AT

EN
°±

OP STANDARD DRAWING G.A. OF


400

90
AT

DUCTILE IRON
SHALLOW STORM WATER
K

COVER AND FRAME


C
LO

MANHOLE DETAILS ARE SHOWN FOR THE PRECAST MANHOLE ON PIPELINES


MANHOLE. HOWEVER, CAST IN-SITU MANHOLES ARE
B ACCEPTABLE SUBJECT TO THE ENGINEER'S APPROVAL. 550 900 550 900 600 - 1400mm DIA.
THIS DRAWING APPLIES WHERE DEPTH FROM UNDERSIDE OF
TOP SLAB TO INVERT OF OUTLET PIPE IS NOT GREATER THAN DRAWN - SCALE 1 : 50
SECTION C-C 2900mm.
FOR DEEP MANHOLES SEE DRAWING No. 203.
DETAIL A PLAN AT COVER LEVEL PLAN AT COVER LEVEL CHECKED - DATE -
HINGE DETAILS APPROVED - SIZE A1
PROJECT DWG.
No. - No.
202

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
75 THICK PRECAST CONCRETE COVER SLAB DETAIL MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
SEATING RINGS BEDDED IN 1 PART FOR PAVED AREA REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
250 CEMENT / 2 PART SAND MORTAR
DUCTILE IRON COVER
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
10 DOWEL DRILLED AND SET INTO 16 DIA STEP BAR CAST INTO
EPDM 'O' RING SEAL COVER SLAB AT 300 CENTERS COVER SLAB WITH TOE HOLE 1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS OTHERWISE
16 DIA STEP BAR CAST INTO OR GASKET STRIP(2 Nos
OF MIN SIZE 20mm WIDTH) FINISHED LEVEL OF 150 CLASS B CONCRETE STATED.
COVER SLAB WITH TOE HOLE CARRIAGEWAY (FL) CL SURROUND 2. ALL CONCRETE TO BE CLASS B UNLESS OTHERWISE
DUCTILE IRON COVER STATED.

(MIN.)
3. ALL EXTERNAL FACES OF CONCRETE BELOW GROUND TO

450
AS SPECIFIED UV RESISTANCE

MAX
COVER SLAB DETAIL

600
FOR UNPAVED AREA SPECIFIED SEALANT BE TANKED.
EPOXY COATING TO ALL
FOR JOINT 4. ALL INTERNAL FACES OF CONCRETE TO BE COATED WITH
SURFACES ABOVE GROUND

80
EPOXY COATING AS SPECIFIED.

250
CL
FGL FGL EPOXY PROTECTION BOARD 5. UNLESS OTHERWISE STATED ALL INLET AND OUTLET PIPES

100
250 200

COATING AS TANKING MEMBRANE OF MANHOLES SHALL BE LAID SOFFIT TO SOFFIT.


SPECIFIED 6. ALL COVERS IN OPEN AREA TO BE PROVIDED WITH 1No.
GRAB BAR.
COVER SLAB DETAIL FOR CARRIAGEWAY & 7. MANHOLES SHALL BE PROVIDED WITH REINFORCED
250 VARIES

REINFORCED CONCRETE RINGS 85 80 85 CONCRETE RINGS (2Nos. AS MINIMUM). THE LOWER RING
SEE NOTE 7 PARKING AREAS SHALL BE 250mm HEIGHT AND THE UPPER RING TO VARY
GRP LADDER ACCORDING TO FINAL GROUND LEVEL.
DETAIL 1 250 1500 DIA SHAFT 250
8. MANHOLES TO BE PROVIDED WITH SAND TRAP 500mm
SCALE 1:20 DEEP SUMP.
REINFORCED CONCRETE SHAFT
SEE DETAIL 1 9. THE MANHOLES AND CHAMBERS ARE DESIGNED USING
TANKING MEMBRANE FULL GROUND WATER LEVEL CONDITION WITH 1.1 FACTOR
250 1500 250 AND PROTECTION BOARD OF SAFETY FOR FLOATATION AND BEARING PRESSURE
NOT EXCEEDING 200kpa AT FORMATION LEVEL.
10.DEWATERING OPERATIONS SHALL BE PROVIDED DURING
CONSTRUCTION AND MAY ONLY BE TERMINATED AFTER
ROOF SLAB HAS BEEN INSTALLED.
300

300

300

300
11. ALL STRUCTURAL DETAILS TO BE VERIFIED BY DESIGNERS
/ CONSULTANTS.

LEGEND
REINFORCED CONCRETE

EPOXY COATING TO ALL SOIL COMPACTED TO 95% MDD


INTERNAL SURFACES PLAIN CONCRETE
C C
2500 (MAXIMUM)

FGL FINAL GROUND LEVEL


FL FINAL ASPHALT / INTERLOCKED TILE LEVEL

2500
(HEIGHT OF NIB

STANDARD BASE
ABOVE PIPE)
DIA DIAMETER

500 (MIN)
CL COVER LEVEL
IL INVERT LEVEL OF OUTLET PIPE
GA GENERAL ARRANGEMENT
REINFORCED
CONCRETE
BASE
IL
(SEE NOTE 8)

(SEE NOTE 8)
PVC WATER STOP
CONSTRUCTION JOINT
500

500
400
500

500
50mm THK. CEMENT/SAND SCREED 50mm THK. CEMENT/SAND SCREED REFERENCE DRAWINGS AND DOCUMENTS
REINFORCED CONCRETE BASE TANKING MEMBRANE TANKING MEMBRANE STANDARD DRAWING - TANKING DETAILS - 801
500 400 400 500 75mm THICK C20 BLINDING 75mm THICK C20 BLINDING STANDARD DRAWING - CONSTRUCTION AND MOVEMENT - 1001
1000 GAUGE POLYETHYLENE SHEET
A = OUTLET PIPE INTERNAL DIAMETER + 1200
1000 GAUGE POLYETHYLENE SHEET SECTION B-B JOINT
STANDARD DRAWING - MISCELLANEOUS DETAILS - 207
SECTION A-A FOR MANHOLES
- 1000
STANDARD DRAWING - REINFORCEMENT DETAILS
(SERIES)
STANDARD DRAWING - STORM WATER MANHOLE FRAME -213
AND COVER DETAILS

B 120
°±
AT


EN

±
SEE DETAIL A FOR HINGE DETAILS OP

°
90
AT
K
C
400

LO
- DUCTILE IRON COVER AND FRAME TO
A = OUTLET PIPE INTERNAL DIAMETER + 1200

SUIT 750 DIA. OPENING IN ALL No. REVISION-2 APP'D 2021


MANHOLES ON STORM WATER
PIPELINES WITH DIAMETER RANGING
CLIENT
FROM 600 TO 800.
500

A/2

- DUCTILE IRON COVER AND FRAME TO


SUIT 900 DIA. OPENING IN ALL DETAIL A
MANHOLES ON STORM WATER PIPE HINGE DETAILS
A A LINES WITH DIAMETER RANGING TITLE
VARIES

FROM 900 TO 1400. STANDARD DRAWINGS


- GRP COVER WITH ADEQUATE FRAME
IS ACCEPTABLE SUBJECT TO THE STORM WATER WORKS
ENGINEER'S APPROVAL.
DRAWING TITLE
A/2
500

MANHOLE DETAILS ARE SHOWN FOR THE PRECAST MANHOLE.


HOWEVER, CAST IN-SITU MANHOLES ARE ACCEPTABLE SUBJECT TO
THE ENGINEER'S APPROVAL
STANDARD DRAWING - G.A.
THIS DRAWING APPLIES FOR MANHOLES WHERE DEPTH FROM OF DEEP STORM WATER
SOFFIT OF ROOF SLAB TO INVERT OF OUTLET PIPE IS BETWEEN 2900
TO 4300. MANHOLE ON PIPELINES 600 -
400

FOR SHALLOW MANHOLES SEE DRAWING No. 202


ENGINEER / DESIGNER TO UPDATE AND PROVIDE FULL
1400mm DIA
CALCULATIONS FOR DEPTHS GREATER THAN 4300.
DRAWN - SCALE 1 : 50
B CHECKED - DATE -
PLAN AT COVER LEVEL APPROVED - SIZE A1
SECTION C-C PROJECT DWG.
No. - No.
203

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT
16 DIA STEP BAR CAST INTO AND MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT
COVER SLAB WITH TOE HOLE PROJECT REQUIREMENTS. THEY ARE EXPECTED TO BE
DUCTILE IRON COVER INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
CHECKED AND APPROVED AS PART OF THE PROJECT
COVER SLAB DETAIL AS SPECIFIED UV RESISTANCE EPOXY AS SPECIFIED UV RESISTANCE EPOXY COATING
TO ALL SURFACES ABOVE GROUND
DRAWING SET.
FOR UNPAVED AREA COATING TO ALL SURFACES ABOVE
200 GROUND
1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS OTHERWISE
CL CL 2. ALL CONCRETE TO BE CLASS B UNLESS OTHERWISE STATED.
FGL FGL FGL FGL 3. ALL EXTERNAL FACES OF CONCRETE BELOW GROUND TO BE

100

100
200
4. ALL INTERNAL FACES OF CONCRETE TO BE COATED WITH
EPOXY COATING AS SPECIFIED.

300
5. UNLESS OTHERWISE STATED ALL INLET AND OUTLET PIPES OF
MANHOLES SHALL BE LAID SOFFIT TO SOFFIT.
6. ALL COVERS IN OPEN AREA TO BE PROVIDED WITH 1No. GRAB
GRP LADDER 7. MANHOLES SHALL BE PROVIDED WITH REINFORCED CONCRETE
REINFORCED RINGS (2Nos. AS MINIMUM). THE LOWER RING SHALL BE 250mm

DEPTH VARIES-MAX 4200mm FOR PIPE DIA. FROM 2500mm - 3000mm


CONCRETE HEIGHT AND THE UPPER RING TO VARY ACCORDING TO FINAL
GROUND LEVEL.

DEPTHVARIES-MAX3200mmFORPIPEDIA.FROM1500mm-2400mm
WALL
8. MANHOLES TO BE PROVIDED WITH SAND TRAP 500mm DEEP
9. THE MANHOLES AND CHAMBERS ARE DESIGNED USING FULL
GROUND WATER LEVEL CONDITION WITH 1.1 FACTOR OF SAFETY
EPOXY FOR FLOATATION AND BEARING PRESSURE NOT EXCEEDING
COATING TO 200kpa AT FORMATION LEVEL.
ALL INTERNAL 10. DEWATERING OPERATIONS SHALL BE PROVIDED DURING
SURFACES CONSTRUCTION AND MAY ONLY BE TERMINATED AFTER ROOF
SLAB HAS BEEN INSTALLED.
11. ALL STRUCTURAL DETAILS TO BE VERIFIED BY DESIGNERS /
CONSULTANTS.
LEGEND
C C REINFORCED CONCRETE
SOIL COMPACTED TO 95% MDD
STAINLESS
STEEL PLAIN CONCRETE
SAFETY CHAIN FGL FINAL GROUND LEVEL
AND FIXINGS FL FINAL ASPHALT / INTERLOCKED TILE LEVEL
IL
DIA DIAMETER
PVC WATER STOP CL COVER LEVEL

(SEE NOTE 8)
IL INVERT LEVEL OF OUTLET PIPE

500
TANKING MEMBRANE CONSTRUCTION
400

GA GENERAL ARRANGEMENT
AND PROTECTION BOARD JOINT

1000
REINFORCED

500
CONCRETE
BASE

50mm THK. CEMENT/SAND SCREED 50mm THK. CEMENT/SAND SCREED


900 1500 900 TANKING MEMBRANE 400 A = OUTLET PIPE INTERNAL DIAMETER + 1200 400 TANKING MEMBRANE
75mm THICK C20 BLINDING 75mm THICK C20 BLINDING
1000 GAUGE POLYETHYLENE SHEET 1000 GAUGE POLYETHYLENE SHEET
SECTION A-A SECTION B-B
- DUCTILE IRON COVER AND FRAME
TO SUIT 900 DIA. OPENING IN ALL
NOTE : THIS DRAWING APPLIES WHERE DEPTH FROM UNDERSIDE OF MANHOLES ON STORM WATER
TOP SLAB TO INVERT OF OUTLET PIPE IS AS FOLLOWING : PIPELINES WITH DIAMETER
B · NOT GREATER THAN 3200mm FOR PIPE DIA FROM 1500mm TILL RANGING FROM 1500 TO 3000.
2400mm. - GRP COVER WITH ADEQUATE
3300 · NOT GREATER THAN 4200mm FOR PIPE DIA FROM 2500mm TILL FRAME IS ACCEPTABLE SUBJECT
3000mm. TO THE ENGINEER'S APPROVAL.
900 1500 900
FOR DEEP MANHOLES SEE DRAWING No. 205
REFERENCE DRAWINGS AND DOCUMENTS
STANDARD DRAWING - TANKING DETAILS - 801
STANDARD DRAWING - CONSTRUCTION AND MOVEMENT 1001
JOINT

400

± STANDARD DRAWING - MISCELLANEOUS DETAILS


2 0° - 207
1 FOR MANHOLES
AT 1000


STANDARD DRAWING - REINFORCEMENT DETAILS

750
EN
±
OP (SERIES)
°
90
STANDARD DRAWING - STORM WATER MANHOLE FRAME - 213
AT

AND COVER DETAILS


K
C
LO
A = OUTLET PIPE INTERNAL DIAMETER + 1200

SEE DETAIL A FOR HINGE


DETAILS

DETAIL A
HINGE DETAILS
A No. REVISION-2 APP'D 2021
NOTE : THIS DRAWING APPLIES WHERE DEPTH CLIENT
FROM UNDERSIDE OF TOP SLAB TO INVERT OF OUTLET
PIPE IS AS FOLLOWING :
· NOT GREATER THAN 3200mm FOR PIPE DIA FROM
1500mm TILL 2400mm.
· NOT GREATER THAN 4200mm FOR PIPE DIA FROM
2500mm TILL 3000mm.
FOR DEEP MANHOLES SEE DRAWING No. 205 75 THICK PRECAST CONCRETE
COVER SLAB DETAIL
SEATING RINGS BEDDED IN 1 PART FOR PAVED AREA PLAN AT COVER LEVEL TITLE
CEMENT / 2 PART SAND MORTAR STANDARD DRAWINGS
DUCTILE IRON COVER
10 DOWEL DRILLED AND SET INTO
16 DIA STEP BAR CAST INTO COVER
STORM WATER WORKS
COVER SLAB AT 300 CENTERS
SLAB WITH TOE HOLE
150 CLASS B
DRAWING TITLE
FINISHED LEVEL OF
CARRIAGEWAY (FL) CL CONCRETE SURROUND
STANDARD DRAWING G.A. OF
400

(MIN.)
450

MAX
600

SHALLOW STORM WATER MANHOLE


ON PIPELINES 1500 - 3000mm DIA.
300

B DRAWN - SCALE 1 : 50
CHECKED - DATE -
COVER SLAB DETAIL FOR CARRIAGEWAY &
SECTION C-C APPROVED - SIZE A1
PARKING AREAS
PROJECT DWG.
No. - No. 204

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE
16 DIA STEP BAR CAST INTO INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
COVER SLAB WITH TOE HOLE CHECKED AND APPROVED AS PART OF THE PROJECT
DUCTILE IRON COVER DRAWING SET.
COVER SLAB DETAIL AS SPECIFIED UV RESISTANCE EPOXY 1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS
FOR UNPAVED AREA COATING TO ALL SURFACES ABOVE GROUND OTHERWISE STATED.
2. ALL CONCRETE TO BE CLASS B UNLESS OTHERWISE

250(VARIES)

100
CL
FGL FGL STATED.
200

3. ALL EXTERNAL FACES OF CONCRETE BELOW GROUND


TO BE TANKED.
4. ALL INTERNAL FACES OF CONCRETE TO BE COATED
250 (VARIES) ( SHAFT ) WITH EPOXY COATING AS SPECIFIED.
CONCRETE SHAFT DIMENSION TO 5. UNLESS OTHERWISE STATED ALL INLET AND OUTLET
BE DETERMINED EPOXY COATING TO PIPES OF MANHOLES SHALL BE LAID SOFFIT TO
ON SITE DURING ALL INTERNAL SOFFIT.
GRP LADDER 6. ALL COVERS IN OPEN AREA TO BE PROVIDED WITH 1No.
SEE DETAIL 1
CONSTRUCTION SURFACES
OF MANHOLE GRAB BAR.
(MAXIMUM 300 7. MANHOLES SHALL BE PROVIDED WITH REINFORCED
TANKING MEMBRANE REINFORCED CONCRETE CONCRETE RINGS (2Nos. AS MINIMUM). THE LOWER

DIA. FROM 1500mm-2400mm)


(MAX. 4200mm FOR PIPE DIA. FROM 2500mm-3000mm)
AND PROTECTION BOARD DEPTH = 6000) REDUCER SLAB
RING SHALL BE 250mm HEIGHT AND THE UPPER RING
TO VARY ACCORDING TO FINAL GROUND LEVEL.

300
EPDM 'O' RING SEAL 8. MANHOLES TO BE PROVIDED WITH SAND TRAP 500mm
OR GASKET STRIP(2 Nos
OF MIN SIZE 20mm WIDTH) DEEP SUMP.
9. THE MANHOLES AND CHAMBERS ARE DESIGNED USING
FULL GROUND WATER LEVEL CONDITION WITH 1.1

100
DEPTH VARIES
FACTOR OF SAFETY FOR FLOATATION AND BEARING
SPECIFIED SEALANT

(MAX. 3200mm FOR PIPE


PRESSURE NOT EXCEEDING 200kpa AT FORMATION

STANDARD BASE
REINFORCED CONCRETE WALL FOR JOINT

.
LEVEL.
PROTECTION BOARD 10.DEWATERING OPERATIONS SHALL BE PROVIDED
EPOXY COATING AS
C C SPECIFIED
TANKING MEMBRANE DURING CONSTRUCTION AND MAY ONLY BE
TERMINATED AFTER ROOF SLAB HAS BEEN INSTALLED.

(SEE NOTE 8)
IL PVC WATER 11. ALL STRUCTURAL DETAILS TO BE VERIFIED BY
STOP 100 100 100 DESIGNERS / CONSULTANTS.
CONSTRUCTION

500 500
400

JOINT LEGEND
REINFORCED
CONCRETE BASE
DETAIL 1 REINFORCED CONCRETE
50mm THK. CEMENT/SAND SCALE 1:20 SOIL COMPACTED TO 95% MDD
SCREED 50mm THK. CEMENT/SAND SCREED
1500 TANKING MEMBRANE TANKING MEMBRANE PLAIN CONCRETE
75mm THICK C20 BLINDING 75mm THICK C20 BLINDING FGL FINAL GROUND LEVEL
1000 GAUGE POLYETHYLENE SHEET 1000 GAUGE POLYETHYLENE SHEET FL FINAL ASPHALT / INTERLOCKED TILE LEVEL
400 400 DIA DIAMETER
A = OUTLET PIPE INTERNAL DIAMETER+1200 CL COVER LEVEL
IL INVERT LEVEL OF OUTLET PIPE
GA GENERAL ARRANGEMENT
SECTION A-A SECTION B-B

REFERENCE DRAWINGS AND DOCUMENTS


STANDARD DRAWING - TANKING DETAILS 801
STANDARD DRAWING - CONSTRUCTION AND MOVEMENT 1001
JOINT
STANDARD DRAWING - MISCELLANEOUS DETAILS 207
B FOR MANHOLES
75 THICK PRECAST CONCRETE COVER SLAB DETAIL
FOR PAVED AREA STANDARD DRAWING - REINFORCEMENT DETAILS 1000
SEATING RINGS BEDDED IN 1 PART
SEE DETAIL A FOR HINGE DETAILS (SERIES)
750 CEMENT / 2 PART SAND MORTAR
DUCTILE IRON COVER STANDARD DRAWING - STORM WATER MANHOLE FRAME 213
- DUCTILE IRON COVER AND FRAME 10 DOWEL DRILLED AND SET INTO AND COVER DETAILS
16 DIA STEP BAR CAST INTO
TO SUIT 900 DIA OPENING IN ALL
A = OUTLET PIPE INTERNAL DIAMETER+1200

COVER SLAB AT 300 CENTERS COVER SLAB WITH TOE HOLE


MANHOLES ON STORM WATER
225

PIPELINES WITH DIAMETER RANGING FINISHED LEVEL OF 150 CLASS B CONCRETE


FROM 1500 TO 3000. CARRIAGEWAY (FL) CL SURROUND
- GRP COVER WITH ADEQUATE FRAME

(MIN.)
IS ACCEPTABLE SUBJECT TO THE

450

MAX
600
ENGINEER'S APPROVAL.
A A
No. REVISION-2 APP'D 2021

250
12

± 5°
CLIENT
AT

EN
°±

OP
90
1600

AT
K
C
LO

COVER SLAB DETAIL FOR CARRIAGEWAY &


DETAIL A TITLE
HINGE DETAILS
PARKING AREAS STANDARD DRAWINGS
STORM WATER WORKS
900 1500 900
400 1500 400 DRAWING TITLE
*

B
STANDARD DRAWING G.A. OF
DEEP STORM WATER MANHOLE
NOTE : THIS DRAWING APPLIES WHERE SHAFT DEPTH IS ON PIPELINES 1500 - 3000mm DIA.
NOT GREATER THAN 6000.
SECTION C-C ROOF PLAN ENGINEER / DESIGNER TO UPDATE AND PROVIDE FULL
CALCULATIONS FOR DEPTHS GREATER THAN 6000.
FOR SHALLOW MANHOLES SEE DRAWING No. 204. DRAWN - SCALE 1 : 100
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
205

THIRD EDITION - APRIL 2022


NOTES:
NOTE : WALL THICKNESS TO BE THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
DETERMINED FROM STRUCTURAL MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
AS SPECIFIED UV RESISTANCE
TOP PRECAST COVER SLAB TO EPOXY COATING PAINT TO ALL CALCULATIONS MINIMUM 250mm REQUIREMENTS. THEY ARE EXPECTED TO BE
BE NO HIGHER THAN UNDERSIDE 16 DIA STEP BAR 75 THICK PRECAST CONCRETE
CAST INTO COVER
SURFACES ABOVE GROUND INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
OF ROAD CONSTRUCTION OF SURFACE OF COVER SEATING RINGS BEDDED IN 1 PART COVER SLAB DETAIL FOR PAVED AREA
MINIMUM 100mm BELOW FGL IN SLAB WITH TOE CEMENT / 2 PART SAND MORTAR CHECKED AND APPROVED AS PART OF THE PROJECT
SLAB TO BE SCABBLED
UNPAVED AREAS HOLE DUCTILE IRON COVER DRAWING SET.
300 TYP PRIOR TO SURROUND
BULL NOSED ARISSES TO CL BEING PLACED 10 DOWEL DRILLED AND SET INTO 1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS OTHERWISE
EXPOSED CORNERS COVER SLAB AT 300 CENTERS 16 DIA STEP BAR CAST INTO COVER SLAB WITH TOE
HOLE MANHOLE WALL STATED.
FINISHED LEVEL OF

100
FGL FGL 150 CLASS B CONCRETE SURROUND 2. ALL COVERS IN OPEN AREA TO BE PROVIDED WITH 1No GRAB
CARRIAGEWAY (FL) CL
BAR.
RIBS OF INVERTED PVC-LINER 3. ENTIRE END OF PLUGGED STUB SHALL BE COVERED WITH 2
SHEET GLUED TO PIPE OUTER
FLEXIBLE NEOPRENE RUBBER SURFACE LAYERS OF 0.25 (10MIL) MINIMUM THICK COMMERCIAL GRADE
OR MASTIC FILLER BETWEEN POLYETHYLENE SHEETING BEFORE BACK FILLING. SECURE

(MIN.)
450
PIPE & WALL

250
WITH TIGHT WRAP OF COPPER WIRE AROUND PIPE.

MAX
600
4. PIPE PLUGS LARGER THAN 1200 DIA SHALL USE TWO LAYERS OF
PIPE COUPLING SOCKET INSIDE FACE OF REINFORCEMENT WITH A MINIMUM CONCRETE THICKNESS OF
TO FACE UPSTREAM MANHOLE 230mm. EQUIP WITH 3 LIFTING HOOKS SPACED EQUALLY
225
AROUND OUTSIDE EDGE OF PLUG.
SEE DETAIL A, B & C WELDED CORNER STRIPS 5. ALL PIPE STUBS SHALL BE IDENTIFIED USING A BRIGHT
PIPE WALL

250
PLAIN SHEET COLOURED VINYL TYPE PERMANENT PAINT NEATLY STENCILED
ON THE INSIDE WALL NEAR THE TOP OF THE CONNECTING
INSIDE FACE OF WALL MANHOLE. MARKING SHALL INCLUDE DIAMETER OF PIPE IN mm,
GRADE IN %, AND LENGTH OF STUB IN METERS, WITH AN
ARROW FROM THE LABLE, CLEARLY IDENTIFYING THE
DESCRIBED STUB INLET.
WELDED STRIP OF PVC 6. BACKFILL AROUND PIPE PLUG TO BE COMPACTED TO SPECIFIED
PRECAST CONCRETE ON FACE OF PIPE
PIPE BACKFILL DENSITIES.
(CLASS A) RING COVER SLAB DETAIL FOR CARRIAGEWAY & PARKING AREAS
MANHOLE COVER DETAILS FOR ROUGHENED CONCRETE SURFACE LEGEND
OF PIPE IN CONTACT WITH
UNPAVED AREA MANHOLE WALL
REINFORCED CONCRETE
SOIL COMPACTED TO 95% MDD
PLAIN CONCRETE

WALL
RIGID PIPES FGL FINAL GROUND LEVEL
(SCALE 1:40) FL FINAL ASPHALT / INTERLOCKED TILE LEVEL
85 80 85
DIA DIAMETER
400

EPOXY LINING TO ALL


139

80
INTERNAL SURFACES 1500 FOR D<1200
139 MIN ABOVE GRP LINER 3000 FOR D>1200
MIN
CEMENT
MIN
139

14Ø LIFTING LOOP MORTAR


NO.2 LIMIT OF PIPEWORK
DETAIL A (250 THICK WALL) FOR FUTURE CONNECTION
1500 FOR D<1200 3000 FOR D>1200
(SCALE 1:15) 300 D<500 SPIGOT/SOCKET ON UPSTREAM SIDE
500 D>500 OF MANHOLE & DOUBLE SPIGOT ON
750 FOR 2000-2400mm DIA DOWNSTREAM SIDE
PLUGGED PORTS ONLY

PRE CAST CONCRETE PLUG WALL


FLEXIBLE
14 * RE BAR FOR USE 100 100 100 NEOPRENE
AS LIFTING HOOK RUBBER STRIP
℄ ℄ EPOXY LINING TO ALL

100
INTERNAL SURFACES
ABOVE GRP LINER
14 * RE BAR FOR USE
PRE CAST CONCRETE PLUG CEMENT CLASS `B` CONCRETE SURROUND
AS LIFTING HOOK
MORTAR WIDTH : D+600 FOR D<500
NO.2 D+1000 FOR D>500

DETAIL B (300 THICK WALL)


NOTE : WALL THICKNESS TO BE (SCALE 1:15)
DETERMINED FROM
°

500
STRUCTURAL CALCULATIONS
MINIMUM 250mm 90 FOR ALL PIPE
GRADIENTS

PIPE GASKET PIPE GASKET WALL MASS CONCRETE CLASS `C`


135 130 135

SECTIONAL VIEW SECTIONAL VIEW EPOXY LINING TO ALL


REFERENCE DRAWINGS AND DOCUMENTS

130
DOWNSTREAM PIPE PLUG UPSTREAM PIPE PLUG INTERNAL SURFACES
ABOVE GRP LINER
STANDARD DRAWING - TANKING DETAILS
STANDARD DRAWING - CONSTRUCTION AND MOVEMENT
-801
-1001
JOINT
STANDARD DRAWING - REINFORCEMENT DETAILS -1000
CEMENT (SERIES)
EDGE OF PIPE TRENCH MORTAR PIPE CONNECTION DETAILS STANDARD DRAWING - STORM WATER MANHOLE FRAME -213
SELECTED
NO.2
DETAIL C (400 THICK WALL) (FOR R.C. PIPES) AND COVER DETAILS
EXCAVATED (SCALE 1:15) (SCALE 1:40)
MATERIAL BED
AND SURROUND
SEE PIPE
CLASS 'C' THRUST BLOCK
FOR THE PLUG PLUG OF SAME BEDDING
DETAIL
MATERIAL AS PIPE LIMIT OF PIPEWORK
FOR FUTURE CONNECTION
VARIES
SHORT LENGTH SHOULD BE
300 D<500 SOCKET/ SPIGOT FOR BOTH
500 D>500 UPSTREAM AND DOWNSTREAM No. REVISION-2 APP'D 2021
CONNECTIONS
FLEXIBLE CLIENT
NEOPRENE
RUBBER STRIP

A A
D+500

CLASS `B` CONCRETE SURROUND 600 D<400


WIDTH : D+600 FOR D<500
1.50 x D, D>400
TITLE
UNDISTURBED
D+1000 FOR D>500
300
STANDARD DRAWINGS
GROUND
STORM WATER WORKS
FOR ALL PIPE GRADIENTS

°
90
500
DRAWING TITLE
300 600 D<400
MASS CONCRETE CLASS 'C'
MASS CONCRETE CLASS `C` STANDARD DRAWING
SECTION A-A MISCELLANEOUS DETAILS
N.T.S. PIPE COMING OUT OF THE NIB
SHOULD HAVE SOCKET IN
FOR MANHOLES
UNDISTURBED UPSTREAM AND SPIGOT IN
GROUND DOWNSTREAM
DRAWN - SCALE AS SHOWN
PLUGED PORT DETAIL PIPE CONNECTION DETAILS CHECKED - DATE -
N.T.S. (FOR GRP PIPES OR OTHER PLASTIC PIPES) APPROVED - SIZE A1
(SCALE 1:40)
PROJECT DWG.
No. - No.
207

THIRD EDITION - APRIL 2022


NOTES:
1000 1000 THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
600 KERB OPENING MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
600 KERB OPENING KERB REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
1000 APPROVED AS PART OF THE PROJECT DRAWING SET.
B 1. ALL DIMENSIONS IN MILLIMETRES UNLESS OTHERWISE
KERB KERB
STATED.
45

2. ALL INTERNAL AND EXTERNAL CONCRETE CORNER TO BE


ROUNDED OR CHAMFERED.
3. ALL CONCRETE TO BE CLASS B UNLESS OTHERWISE
STATED.
4. ALL EXTERNAL FACES OF CONCRETE BELOW GROUND TO
BE TANKED.
5. ALL INTERNAL FACES OF CONCRETE TO BE COATED WITH
EPOXY COATING AS SPECIFIED.
COVER 655x705 6. UNLESS OTHERWISE STATED ALL INLET AND OUTLET
870

FRAME TYPE 1

1000
A A C C PIPES OF INLETS SHALL BE LAID SOFFIT TO SOFFIT.
PLAN ON INLET TYPE-2

1000
7. INLETS TO BE PROVIDED WITH SAND TRAP 500mm DEEP

635

800
KERBS ON TWO SIDES _ONE KERB OPENING SUMP.
(SCALE 1:40) 8. THE MANHOLES AND CHAMBERS ARE DESIGNED USING
FULL GROUND WATER LEVEL CONDITION WITH 1.1
FACTOR OF SAFETY FOR FLOATATION AND BEARING
PRESSURE NOT EXCEEDING 200kpa AT FORMATION
LEVEL.
1000
9. DEWATERING OPERATIONS SHALL BE PROVIDED DURING
600 KERB OPENING CONSTRUCTION AND MAY ONLY BE TERMINATED AFTER
KERB
85

FULL HEIGHT WALL CONSTRUCTION.


10.INLET DIFFERENT SHAPES WITH DIFFERENT EFFICIENCIES
MAY BE USED SUBJECT TO ENGINEER'S APPROVAL.
11. MINIMUM KERB INLET GRATING CLEAR OPENING HEIGHT SHALL
800 COVER 655x705
CLASS OF COVER ACCORDING TO BE (100mm).
FRAME TYPE 1
B SPECIFICATIONS SINGLE PIECE
DUCTILE IRON GRATING AND FRAME
800 x 800mm OVER BASE 635 x 635
LEGEND
1000
COVER GRATE REINFORCED CONCRETE
SOIL COMPACTED TO 95% MDD
PLAN ON INLET TYPE-1 PLAN ON TOP ENTRY INLET GRATE
(SCALE 1:20) PLAIN CONCRETE
ONE KERB OPENING PIPES IN LINE
(SCALE 1:20)
COVER 655x755 FGL FINAL GROUND LEVEL
FRAME TYPE 2 FL FINAL ASPHALT / INTERLOCKED TILE LEVEL
DIA DIAMETER
PLAN ON INLET TYPE-3
100 800 100 TWO KERB OPENING PIPE IN LINE
100 800 100 (SCALE 1:40)
600
600

FRL FINISHED LEVEL OF


AT KERB CARRIAGEWAY (FL) TOP OF PAVEMENT
50

TOP OF PAVEMENT

1000
COVER 655 x 705
FRAME TYPE 4

REFERENCE DRAWINGS AND DOCUMENTS


2000 (MAXIMUM)

2000 (MAXIMUM)
1000

STANDARD DRAWING - TANKING DETAILS - 801


VARIES

VARIES
600 MIN

PLAN ON INLET TYPE-4 STANDARD DRAWING - CONSTRUCTION AND MOVEMENT - 1001


JOINT
CLOSED INLET WITH NO KERB OPENING NOR TOP ENTRY INLET
(SCALE 1:40) STANDARD DRAWING - MISCELLANEOUS DETAILS - 207
EPOXY COATING AS FOR MANHOLES
SPECIFIED ON ALL INTERIOR STANDARD DRAWING - REINFORCEMENT DETAILS - 1000
CONCRETE SURFACES (SERIES)
STANDARD DRAWING - STORM WATER MANHOLE FRAME - 213
AND COVER DETAILS

DETAIL A DETAIL B
INVERT DWG No.213 COVER 655x705 DWG No.213
OF PIPE FRAME TYPE 1 No. REVISION-2 APP'D 2021
KERB INLET
GRATE CLIENT
300
SEE NOTE 7

OP
REINFORCED CONCRETE TOP OF ENI
NG
500

PAVEMENT
LOCALIZED TITLE
800 BASE

TANKING MEMBRANE PAVEMENT STANDARD DRAWINGS


DEPRESSION IN
AND PROTECTION BOARD
FRONT OF KERB STORM WATER WORKS
OPENING (TYP)
DRAWING TITLE
STANDARD DRAWING STORM
300

WATER INLET DETAILS ON


200 600 200 PIPE LINES 300mm DIA.
1000
(MAXIMUM DEPTH 2.0m)
SECTION B-B
50mm THK. CEMENT/SAND SCREED MAXIMUM DEPTH OF INLETS WITH 600x600 ON SIDE ENTRY INLET DRAWN - SCALE AS SHOWN
200 600 200 200 600 200 (SCALE 1:20)
TANKING MEMBRANE INTERNAL DIMENSIONS SHOULD NOT
EXCEED 2000. DEPTH IS MEASURED FROM CHECKED - DATE -
SECTION A-A 75mm THICK C20 BLINDING SECTION C-C TOP OF COVER SLAB TO THE INVERT APPROVED - SIZE A1
SIDE ENTRY INLET 1000 GAUGE POLYETHYLENE SHEET TOP ENTRY INLET LEVEL OF DOWNSTREAM PIPE.
(SCALE 1:20) PROJECT DWG.
(SCALE 1:20)
No. - No.
209

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
1400 1400
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
200 1000 200 1000 REQUIREMENTS. THEY ARE EXPECTED TO BE
1400 600 KERB OPENING INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
600 KERB OPENING KERB
CHECKED AND APPROVED AS PART OF THE PROJECT
1000 DRAWING SET.
B 1. ALL DIMENSIONS IN MILLIMETRES UNLESS OTHERWISE
KERB KERB
STATED.
45

2. ALL INTERNAL AND EXTERNAL CONCRETE CORNER TO BE


ROUNDED OR CHAMFERED.
3. ALL CONCRETE TO BE CLASS B UNLESS OTHERWISE

1400
STATED.
4. ALL EXTERNAL FACES OF CONCRETE BELOW GROUND TO
BE TANKED.
5. ALL INTERNAL FACES OF CONCRETE TO BE COATED WITH
EPOXY COATING AS SPECIFIED.

800
635
920

1100

1100
6. UNLESS OTHERWISE STATED ALL INLET AND OUTLET PIPES
COVER 655x755 OF INLETS SHALL BE LAID SOFFIT TO SOFFIT.
A A C C 7. INLETS TO BE PROVIDED WITH SAND TRAP 500mm DEEP
1400

FRAME TYPE 3
SUMP.
PLAN ON INLET TYPE-2 8. THE MANHOLES AND CHAMBERS ARE DESIGNED USING
KERBS ON TWO SIDES _ ONE KERB OPENING FULL GROUND WATER LEVEL CONDITION WITH 1.1 FACTOR
(SCALE 1:40) OF SAFETY FOR FLOATATION AND BEARING PRESSURE
NOT EXCEEDING 200kpa AT FORMATION LEVEL.
135

9. DEWATERING OPERATIONS SHALL BE PROVIDED DURING


1400 CONSTRUCTION AND MAY ONLY BE TERMINATED AFTER
COVER 655x755 1000 ROOF SLAB HAS BEEN INSTALLED.
10.INLET DIFFERENT SHAPES WITH DIFFERENT EFFICIENCIES
300

FRAME TYPE 3 600 KERB OPENING


KERB MAY BE USED SUBJECT TO ENGINEER'S APPROVAL.
CLASS OF COVER ACCORDING
11. MINIMUM KERB INLET GRATING CLEAR OPENING HEIGHT SHALL
TO SPECIFICATIONS SINGLE
BE (100mm).
PIECE DUCTILE IRON GRATING
AND FRAME 800 x 800mm OVER
B BASE 635 x 635 COVER GRATE LEGEND
800
PLAN ON TOP ENTRY INLET GRATE REINFORCED CONCRETE
1000 SOIL COMPACTED TO 95% MDD

1400
1400 PLAIN CONCRETE
FGL FINAL GROUND LEVEL
PLAN ON INLET TYPE-1 FL FINAL ASPHALT / INTERLOCKED TILE LEVEL
ONE KERB OPENING PIPES IN LINE DIA DIAMETER
COVER 655x755
FRAME TYPE 2

1000 1000
PLAN ON INLET TYPE-3
100 600 100 100 600 100 TWO KERB OPENING PIPE IN LINE
(SCALE 1:40)
100 100 100 100
FL FINISHED LEVEL OF
AT KERB CARRIAGEWAY (FL) TOP OF PAVEMENT
50

TOP OF PAVEMENT

COVER 655 x 705


FRAME TYPE 4

1000
250 100

1400
(TYP.)
2800 (MAXIMUM)

2800 (MAXIMUM)
> 2000

> 2000
REFERENCE DRAWINGS AND DOCUMENTS
STANDARD DRAWING - TANKING DETAILS - 801
VARIES

VARIES
STANDARD DRAWING - CONSTRUCTION AND MOVEMENT - 1001
EPOXY COATING ON
JOINT
ALL INTERIOR - 207
STANDARD DRAWING - MISCELLANEOUS DETAILS
CONCRETE SURFACES
1000 FOR MANHOLES
STEP IRONS AS STANDARD DRAWING - REINFORCEMENT DETAILS - 1000
1400 (SERIES)
SPECIFIED
STANDARD DRAWING - STORM WATER MANHOLE FRAME - 213
AND COVER DETAILS
PLAN ON INLET TYPE-4
CLOSED INLET WITH NO KERB OPENING NOR TOP ENTRY INLET
(SCALE 1:40)
INVERT
OF PIPE
SEE NOTE 7

REINFORCED CONCRETE
No. REVISION-2 APP'D 2021
500

DETAIL B
DETAIL A
800 BASE

DWG No.213 FRL


DWG No.213 COVER 655x755
AT KERB
CLIENT
TANKING MEMBRANE FRAME TYPE 3
150

AND PROTECTION BOARD KERB INLET GRATE

200
300
OPE
NI
300

NG
TITLE

200
TOP OF PAVEMENT
STANDARD DRAWINGS
LOCALIZED PAVEMENT
DEPRESSION IN FRONT OF
650 250
STORM WATER WORKS
KERB OPENING (TYP)
STEP IRONS AS DRAWING TITLE
200 1000 200 50mm THK. CEMENT/SAND SCREED 200 1000 200 SPECIFIED
TANKING MEMBRANE 200 STANDARD DRAWING STORM WATER
75mm THICK C20 BLINDING
SECTION A-A SECTION C-C 1000 200 INLET DETAILS ON PIPE LINES
1000 GAUGE POLYETHYLENE SHEET
SIDE ENTRY INLET TOP ENTRY INLET 300-500mm DIA. (DEPTH VARYING
1400
BETWEEN 2.0m AND 2.8m)
SECTION B-B
MAXIMUM DEPTH OF INLETS WITH 1000x1000 ON SIDE ENTRY INLET
INTERNAL DIMENSIONS SHOULD NOT EXCEED 2800. (SCALE 1:20) DRAWN - SCALE AS SHOWN
DEPTH IS MEASURED FROM TOP OF COVER SLAB TO CHECKED - DATE -
THE INVERT LEVEL OF DOWNSTREAM PIPE.
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
210

THIRD EDITION - APRIL 2022


NOTES:
ROAD ROAD ROAD
B C F ROAD D D
COVER 655x705 G
FRAME TYPE 1 600 KERB OPENING COVER 655x705 600 KERB OPENING 600 KERB OPENING
600 KERB OPENING
KERB FRAME TYPE 4 KERB KERB

1. ALL DIMENSIONS IN MILLIMETRES UNLESS OTHERWISE


STATED.
A A 2. ALL INTERNAL AND EXTERNAL CONCRETE CORNER TO BE
A A

1000
ROUNDED OR CHAMFERED.
3. ALL CONCRETE TO BE CLASS B UNLESS OTHERWISE
STATED.
4. ALL EXTERNAL FACES OF CONCRETE BELOW GROUND TO
COVER 655x755 COVER 655x755 BE TANKED.
FRAME TYPE 3 FRAME TYPE 3 5. ALL INTERNAL FACES OF CONCRETE TO BE COATED WITH
EPOXY COATING AS SPECIFIED.
COVER 655x755 COVER 655x705 6. INLETS TO BE PROVIDED WITH SAND TRAP 500MM DEEP
FRAME TYPE 2 FRAME TYPE 4 E E SUMP.
150 800 800 150 2000 7. THE MANHOLES AND CHAMBERS ARE DESIGNED USING
2000 COVER 655x705 FULL GROUND WATER LEVEL CONDITION WITH 1.1
F G
B C ROAD FRAME TYPE 4 FACTOR OF SAFETY FOR FLOATATION AND BEARING
PRESSURE NOT EXCEEDING 200KPA AT FORMATION
LEVEL.
CATCH BASIN TYPE-2 8. DEWATERING OPERATIONS SHALL BE PROVIDED DURING
CATCH BASIN TYPE-1 CONSTRUCTION AND MAY ONLY BE TERMINATED AFTER
KERB ON TWO SIDES ONE KERB OPENING
KERB ON ONE SIDE ONE KERB OPENING FULL HEIGHT WALL CONSTRUCTION.
CATCH BASIN TYPE-7 CATCH BASIN TYPE-3 9. INLET DIFFERENT SHAPES WITH DIFFERENT EFFICIENCIES
MAY BE USED SUBJECT TO ENGINEER'S APPROVAL.
KERB ON TWO SIDES TWO KERB OPENING
KERB ON ONE SIDE NO KERB OPENING D
10. MINIMUM KERB INLET GRATING CLEAR OPENING HEIGHT SHALL
BE (100mm).
D
1000 1000 LEGEND
CATCH BASIN TYPE-4 CATCH BASIN TYPE-6
150 150 1000 x 2000
750 750 KERB ON ONE SIDE ONE KERB OPENING REINFORCED CONCRETE
LIFTING HOOKS KERB ON TWO SIDE TWO KERB OPENING
50 50 CATCH BASIN TYPE-5 BLOCKWORK
COVER

100 AS SPECIFIED UV RESISTANCE


KERB ON ONE SIDE NO KERB OPENING
80

EPOXY COATING TO ALL SOIL COMPACTED TO 95% MDD


SURFACES ABOVE GROUND POLYTHENE SHEET 1000 PLAIN CONCRETE

150
FRL AT JOINT
TOP OF PAVEMENT
AT KERB 870 85 FRL FINAL ROAD LEVEL
COVER 655x705 EJ EXPANSION JOINT
700 200 700 FRAME TYPE 1
120
50

300
DEPTH VARIES

TOP OF PAVEMENT
DETAIL - A
2000 (MAXIMUM)

TEMPORARY COVER SLAB FOR STAGE 1 CONSTRUCTION LOCALIZED PAVEMENT


VARIES

(SCALE 1:20) DEPRESSION IN FRONT OF


EPOXY COATING KERB OPENING (TYP)
ON ALL INTERIOR CONCRETE 1000
SURFACES STEP IRONS
350 VALID FOR CATCH BASIN TYPE 1 & 7
870 85
VALID FOR CATCH BASIN TYPE 2 & 3
COVER 655x705
200 200 600 200
FRAME TYPE 1
INVERT 1000
OF PIPE KERB INLET GRATE
300 SECTION C-C
STEP IRON AS SPECIFIED OPE (SCALE 1:20)
NING
500

500

TANKING MEMBRANE TOP OF REFERENCE DRAWINGS AND DOCUMENTS


PAVEMENT
BASE

AND PROTECTION BOARD 1030


LOCALIZED PAVEMENT STANDARD DRAWING - TANKING DETAILS - 801
940 STANDARD DRAWING - CONSTRUCTION AND MOVEMENT JOINT- 1001
REINFORCED CONCRETE DEPRESSION IN FRONT OF
KERB OPENING (TYP) COVER 655x755 STANDARD DRAWING - MISCELLANEOUS DETAILS - 207
300

CONSTRUCTION JOINT FRAME TYPE 2 FOR MANHOLES


PVC WATER STOP STEP IRONS STANDARD DRAWING - REINFORCEMENT DETAILS - 1000
(SERIES)
STANDARD DRAWING - STORM WATER MANHOLE FRAME - 213
50mm THK. CEMENT/SAND SCREED AND COVER DETAILS
TOP OF TOP OF
TANKING MEMBRANE 200 600 200
PAVEMENT 300 PAVEMENT
75mm THICK C20 BLINDING 1000

SECTION A-A 1000 GAUGE POLYETHYLENE SHEET SECTION B-B


(SCALE 1:40) (SCALE 1:20)
STEP IRONS

1000 1000 No. REVISION-2 APP'D 2021


200 630 200
1030 CLIENT
1030
920 920
940
COVER 655x755 (FRAME TYPE 3) 70 COVER 655x755 (FRAME TYPE 3) SECTION G-G
COVER 655x755 920 850 115 (SCALE 1:20)
FRAME TYPE 2 COVER 655x755 (FRAME TYPE 3) COVER 655x705 (FRAME TYPE 4)
1000 TITLE
KERB INLET GRATE
KERB INLET STANDARD DRAWINGS
GRATE 100 800 100
STORM WATER WORKS
OPE OPE COVER 655x705
TOP OF NIN NI NG TOP OF NIN
PAVEMENT 300
G OPE TOP OF G
700 200 700 FRAME TYPE 4 DRAWING TITLE
PAVEMENT PAVEMENT

STEP IRONS STANDARD DRAWING STORM WATER


STEP IRONS
CATCH BASIN DETAILS ON PIPE LINES
STEP IRONS
300mm DIA(MAXIMUM DEPTH 2.0m)

200 630 200 200 1600 200 DRAWN - SCALE AS SHOWN


1030 2000
200 600 200 CHECKED - DATE -
SECTION D-D
SECTION F-F APPROVED - SIZE A1
(FOR CATCH BASIN TYPE - 4 & 6) SECTION E-E
(SCALE 1:20) (SCALE 1:20) (SCALE 1:20) PROJECT DWG.
No. - No.
211

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
ROAD ROAD ROAD MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
B C D D
COVER 655x705 F ROAD REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
FRAME TYPE 1 600 KERB OPENING COVER 655x705
G 600 KERB OPENING 600 KERB OPENING AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
KERB FRAME TYPE 4 600 KERB OPENING KERB KERB APPROVED AS PART OF THE PROJECT DRAWING SET.
1. ALL DIMENSIONS IN MILLIMETRES UNLESS OTHERWISE
STATED.
2. ALL INTERNAL AND EXTERNAL CONCRETE CORNER TO BE
A A A A ROUNDED OR CHAMFERED.
3. ALL CONCRETE TO BE CLASS B UNLESS OTHERWISE
STATED.

1400
4. ALL EXTERNAL FACES OF CONCRETE BELOW GROUND TO
COVER 655x755 COVER 655x755 BE TANKED.
FRAME TYPE 3 FRAME TYPE 3 5. ALL INTERNAL FACES OF CONCRETE TO BE COATED WITH
EPOXY COATING AS SPECIFIED.
COVER 655x755 COVER 655x705 6. INLETS TO BE PROVIDED WITH SAND TRAP 500mm DEEP
FRAME TYPE 2 FRAME TYPE 4 SUMP.
E E E E 7. THE MANHOLES AND CHAMBERS ARE DESIGNED USING
150 800 800 150 F G FULL GROUND WATER LEVEL CONDITION WITH 1.1
ROAD COVER 655x705
2000 FACTOR OF SAFETY FOR FLOATATION AND BEARING
2000 FRAME TYPE 4
PRESSURE NOT EXCEEDING 200kpa AT FORMATION
B C LEVEL.
CATCH BASIN TYPE-2
KERB ON TWO SIDES ONE KERB OPENING 8. DEWATERING OPERATIONS SHALL BE PROVIDED DURING
CATCH BASIN TYPE-1 CONSTRUCTION AND MAY ONLY BE TERMINATED AFTER
KERB ON ONE SIDE ONE KERB OPENING
CATCH BASIN TYPE-3 FULL HEIGHT WALL CONSTRUCTION.
KERB ON TWO SIDES TWO KERB OPENING
9. INLET DIFFERENT SHAPES WITH DIFFERENT EFFICIENCIES
CATCH BASIN TYPE-7 MAY BE USED SUBJECT TO ENGINEER'S APPROVAL.
KERB ON ONE SIDE NO KERB OPENING D D 10. MINIMUM KERB INLET GRATING CLEAR OPENING HEIGHT SHALL
BE (100mm).
1000 1000 CATCH BASIN TYPE-4 CATCH BASIN TYPE-6
KERB ON ONE SIDE ONE KERB OPENING KERB ON TWO SIDE TWO KERB OPENING
750 750 LEGEND
150 150 CATCH BASIN TYPE-5
50 50 KERB ON ONE SIDE NO KERB OPENING REINFORCED CONCRETE
COVER

100 AS SPECIFIED UV RESISTANCE 1400 x 2000


80

EPOXY COATING TO ALL LIFTING HOOKS BLOCKWORK


SURFACES ABOVE GROUND
FRL SOIL COMPACTED TO 95% MDD
TOP OF PAVEMENT
AT KERB 1050 PLAIN CONCRETE
POLYTHENE SHEET 870 135

150
700 200 700 AT JOINT FRL FINAL ROAD LEVEL
120

COVER 655x705 FRL


50

FRAME TYPE 1 AT KERB EJ EXPANSION JOINT


DEPTH VARIES
> 2000

300
(2800 MAXIMUM)

TOP OF
SHAFT (VARIES)

PAVEMENT

200
350
EPOXY COATING DETAIL - A LOCALIZED PAVEMENT
ON ALL INTERIOR CONCRETE
SURFACES VALID FOR CATCH BASIN TYPE 1 & 7 TEMPORARY COVER SLAB FOR STAGE 1 CONSTRUCTION DEPRESSION IN FRONT OF
(SCALE 1:20)
VALID FOR CATCH BASIN TYPE 2 & 3 KERB OPENING (TYP)
STEP IRONS
200 1050

INVERT 870 135


OF PIPE

COVER 655x705 FRL 200 1000 200


STEP IRON AS SPECIFIED FRAME TYPE 1 AT KERB 1400
500

500

REINFORCED CONCRETE
SECTION C-C
BASE

KERB INLET
TANKING MEMBRANE GRATE

200
300 (SCALE 1:20)
AND PROTECTION BOARD 1000
OPE
300

CONSTRUCTION JOINT NING 940


PVC WATER STOP TOP OF
PAVEMENT COVER 655x755

200
LOCALIZED PAVEMENT FRAME TYPE 2 REFERENCE DRAWINGS AND DOCUMENTS
DEPRESSION IN FRONT STANDARD DRAWING - TANKING DETAILS - 801
50mm THK. CEMENT/SAND SCREED OF KERB OPENING (TYP) STANDARD DRAWING - CONSTRUCTION AND MOVEMENT JOINT- 1001
TANKING MEMBRANE STANDARD DRAWING - MISCELLANEOUS DETAILS - 207
SECTION A-A STEP IRONS TOP OF TOP OF
75mm THICK C20 BLINDING FOR MANHOLES
(SCALE 1:40)
PAVEMENT 300 PAVEMENT - 1000
1000 GAUGE POLYETHYLENE SHEET STANDARD DRAWING - REINFORCEMENT DETAILS
(SERIES)
STANDARD DRAWING - STORM WATER MANHOLE FRAME - 213
200 1000 200 AND COVER DETAILS
1400
STEP IRONS
SECTION B-B
(SCALE 1:20)

400

1000 1000 200 1000 200


1400 No. REVISION-2 APP'D 2021
1030
920 920 CLIENT
940 SECTION G-G
COVER 655x755 (FRAME TYPE 3) 70 COVER 655x755 (FRAME TYPE 3) (SCALE 1:20)
COVER 655x755 920 850 115 1000
FRAME TYPE 2 COVER 655x755 (FRAME TYPE 3) COVER 655x705 (FRAME TYPE 4) 100 800 100
COVER 655x705
KERB INLET GRATE KERB INLET GRATE
FRAME TYPE 4 OR FRAME TYPE 3
TITLE
STANDARD DRAWINGS
OPE
400

OPE
TOP OF ING
PAVEMENT 300
NIN
G OPE
N TOP OF NIN
G 700 200 700 STEP IRONS
STORM WATER WORKS
PAVEMENT

STEP IRONS DRAWING TITLE


STANDARD DRAWING STORM WATER
STEP IRONS
CATCH BASIN DETAILS ON PIPE LINES
400 300 - 500mm DIA. (DEPTH VARYING
400
BETWEEN 2.0m AND 2.8m)
200 1000 200 200 1600 200 200 1000 200
2000 1400
DRAWN - SCALE AS SHOWN
1400
SECTION D-D CHECKED - DATE -
SECTION F-F (FOR CATCH BASIN TYPE - 4 & 6) SECTION E-E
(SCALE 1:20) (SCALE 1:20) (SCALE 1:20) APPROVED - SIZE A1
PROJECT DWG.
No. - No. 212

THIRD EDITION - APRIL 2022


NOTES:
870 940 920 850 800 THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
710 760 760 710 660 MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
660 710 710 660 20 610 20 REQUIREMENTS. THEY ARE EXPECTED TO BE
DETAIL A ANCHOR INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
DETAIL B ANCHOR
(TYP.) LUGS CHECKED AND APPROVED AS PART OF THE PROJECT
(TYP.) LUGS 25 DRAWING SET.
SECTION C-C SECTION D-D SECTION E-E SECTION F-F SECTION G-G VARIES (20,22.7 & 30) 65 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS
ACCORDING TO KERB 25 70 OTHERWISE INDICATED.
TYPE 2. ALL COVERS AND GRATING SHALL BE SINGLE PIECE.
VARIES (80,100 & 180) 3. INLET DIFFERENT SHAPES WITH DIFFERENT EFFICIENCIES
MAY BE USED SUBJECT TO ENGINEER'S APPROVAL.

80
870 940 920 850 ACCORDING TO KERB
TYPE
45 20
G G G G 45 30
25 45
LEGEND
SEE DETAIL E FOR
HINGE DETAILS TYP TYPICAL
DETAIL A DETAIL B
SEE DETAIL C FOR
C COVER C D COVER D E COVER E F COVER F LETTERING ON COVER
50
655x705 655x755 655x755 655x705
800

800

800

800
NOTCH FLANGE AS
REQUIRED TO MATCH
ANCHOR BOLT
10mm DIAMOND PATTERN AS SHOWN
DESIGN (TYP) ON DWG. US206 (TYP)

50
100 30
B B
G G G (TYP)
G
ANCHOR LUGS
(TYP)
B B
FRAME TYPE 1 FRAME TYPE 2 FRAME TYPE 3 FRAME TYPE 4 A A

FRAMES - CATCH BASINS & INLETS


A A

15 12(TYP)
56.2(TYP) FOR 700 OPENING
46.2(TYP) FOR 600 OPENING
PLAN - HINGED
A A

635
800
6(TYP) 510
12 PLAN - NON HINGED 370
340
PLAN
YEAR OF MANUFACTURING &
MANHOLE COVER STANDARDS K
C/L
700 FOR CATCH BASIN TYPE-1, 2 & 3
112

RAISED LETTERING 5mm


600 F0R INLET TYPE - 1, 2 & 3
13

ABOVE RECESSED AREA


600 FOR CATCH BASIN - 4 & 6 YEAR
(POLISHED FINISH) (TYP)

93
70

10
CLASS D 400 IRON TOP ENTRY BS EN 124 D400
50

20
30
GRATING 800 x 800 COVER BASE

10
PLAN

74
& 635 x 635 COVER GRATE
50

98 85
40 RECESSED AREA
635

48
25x25 ANCHORING LUGS (TYP.) STIPPLE OR TEXTURED C/L C/L
SIDE ELEVATION ELEVATION FINISH (TYP)
27

55
STORM WATER
REFERENCE DRAWINGS AND DOCUMENTS
TOP OF COVER 10mm
25

DIAMOND DESIGN STANDARD DRAWING - MISCELLANEOUS DETAILS - 207


FOR MANHOLES
800 45° BEVEL UNDER STANDARD DRAWING - G.A. OF STORM WATER MANHOLE - 201 TO
15

40 20 20 50 20 20 40
SECTION A-A LIFTING NOTCH (TYP) ON PIPE LINES FOR MANHOLES 205

SECTION J-J FLUSH INLET GRATING AND FRAME DETAILS STANDARD DRAWING - STORM WATER INLET DETAILS - 209 & 210

553 K
420
25

336
DETAIL C
15

40 20 20 50 20 20 40 L 10mm MINIMUM CLEARANCE FROM EDGE OF


25 RECESSED AREA TO RAISED LETTERING
TOP OF COVER 10 94
40 20

SECTION H-H DIAMOND DESIGN TYPICAL FOR ARABIC AND ENGLISH LETTERS
910
YEAR No. REVISION-2 APP'D 2021

30
96

30

40
85
BS EN 124 D400 CLIENT
705 OR 755

215
RECESSED AREA 5
J BELOW TOP OF
VARIES FROM 55
50 20 20

17x10 LIFTING STRAP IN AT CENTER TO


COVER (STIPPLE OR
83

30 RADIUS ENCLOSED POCKET 100 AT OUTSIDE 860


TEXTURED FINISH 20 CLEAR OPENING
SEE SECTION N-N FOR DETAIL EDGE 910
10mm DIAMOND TYP) TITLE
DESIGN (TYP)
SECTION A-A
RISER OPENING
1210
STANDARD DRAWINGS
H H STORM WATER WORKS
30
54

SECTION B-B
655

N STORM WATER
8.5 8.5 DRAWING TITLE
10 25
20

94

N LETTERING 5°
COVER THICKNESS ° ±
CENTRED 20 OVERALL ARABIC
ABOUT CENTRE T1 STANDARD DRAWING STORM
L A

N LETTER HEIGHTS
PE
°±

LINE. (705 & 755


WATER MANHOLE FRAME AND
40

O
90

10 MIN

23
10 20
10 23
C/L COVER
AT

R=30 5 416

10

10

10

10
10
10
WIDTHS)
COVER DETAILS

10

10
K

J
C

SEE DETAIL D 25
LO

85 73 54 65 125 35 140 127


FOR LETTERING
ON COVER LIFTING STRAP DETAIL

30
5
PLAN SECTION L-L DETAIL 'D'
DRAWN - SCALE N.T.S

40

40
CLOSED COVER FOR CATCH BASIN AND INLET SECTION N-N INLET & CATCH BASIN FRAME & COVER CHECKED - DATE -
DETAILS DETAIL E APPROVED - SIZE A1
HINGE DETAILS SECTION K-K
PROJECT DWG.
No. - No.
213

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT
2600 AND MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT
PROJECT REQUIREMENTS. THEY ARE EXPECTED TO BE
300 300 2000 300 INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
CHECKED AND APPROVED AS PART OF THE PROJECT
DRAWING SET.
GRP LADDER 1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS
OTHERWISE STATED.
300

- DUCTILE IRON COVER AND 2. ALL JOINTS BETWEEN PIPEWORK AND CONCRETE ARE
FRAME TO SUIT 900 DIA. TO BE WATERTIGHT.
OPENING. 3. ALL CONCRETE TO BE CLASS C40 UNLESS OTHERWISE
PIPE DIA + 1200

- GRP COVER WITH ADEQUATE STATED.


300

INLET PIPE
FRAME IS ACCEPTABLE 4. STRUCTURAL INTEGRITY OF THAT CHAMBER IS THE
SUBJECT TO THE ENGINEER'S RESPONSIBILITY OF THE DESIGNER.
APPROVAL.
LEGEND
SEE DETAIL A FOR
300

A OUTLET PIPE
A HINGE DETAILS
2600
REINFORCED CONCRETE

SOIL COMPACTED TO 95% MDD


300

300
PLAIN CONCRETE
FGL FINAL GROUND LEVEL
CL COVER LEVEL

PIPE DIA + 1200


400 x 400 x 175 SUMP
± 5°

T 12
A 5°
EN °±
SECTION B-B OP 90
AT
K
C
LO
16 DIA STEP BAR CAST INTO
COVER SLAB WITH TOE HOLE

300
COVER SLAB DETAIL
AS SPECIFIED UV RESISTANCE EPOXY
FOR UNPAVED AREA
COATING TO ALL SURFACES ABOVE GROUND
200

100
CL
FGL FGL
DETAIL A
HINGE DETAILS
ROOF PLAN

REINFORCED CONCRETE
VARIES

EPOXY COATING AS SPECIFIED

B B
300

TANKING TO ALL CONCRETE SURFACES


500

BELOW GROUND LEVEL


400

REFERENCE DRAWINGS AND DOCUMENTS


STANDARD DRAWING - TANKING DETAILS - 801
500

VENTILATION BOX DETAILS STANDARD DRAWING - CONSTRUCTION AND MOVEMENT JOINT- 1001
6 STANDARD DRAWING - MISCELLANEOUS DETAILS - 207
FOR MANHOLES
STANDARD DRAWING - REINFORCEMENT DETAILS - 1000
(SERIES)
50mm THK. CEMENT/SAND SCREED STANDARD DRAWING - STORM WATER MANHOLE FRAME - 213
TANKING MEMBRANE AND COVER DETAILS
75mm THICK C20 BLINDING 200mm 200mm
1000 GAUGE POLYETHYLENE SHEET 180mm 180mm
SECTION A-A 160mm 160mm

5 2

200mm
No. REVISION-2 APP'D 2021
1 CLIENT
COVER SLAB DETAIL
75 THICK PRECAST CONCRETE
FOR PAVED AREA
SEATING RINGS BEDDED IN 1 PART
CEMENT / 2 PART SAND MORTAR DUCTILE IRON COVER
10 DOWEL DRILLED AND
16 DIA STEP BAR CAST INTO
SET INTO COVER SLAB AT
COVER SLAB WITH TOE HOLE 80mm
300 CENTERS 4 3 TITLE
FINISHED LEVEL OF
CARRIAGEWAY (FL)
150 CLASS B CONCRETE
SURROUND
215mm STANDARD DRAWINGS
CL
STORM WATER WORKS
(MIN.)

SECTION TOP VIEW


450

MAX
600

DRAWING TITLE
300

DESCRIPTIONS: COATING SYSTEM: STANDARD DRAWING SAND TRAP


1- Ventilation box body, Lid & dust cap Cast Polyester Powder Coating & VENTILATION BOX DETAILS
Aluminum Alloy LM6
2- 10mm stainless Steel 316 Bolt
COVER SLAB DETAIL FOR CARRIAGEWAY & PARKING AREAS 3- Removable Bottom plate with pipe release for
easy cleaning DRAWN - SCALE AS SHOWN
4- 6mm Stainless Steel 316 Bolt CHECKED - DATE -
5- Lifting Key hole
6- 14mm dia Stainless Steel 316 Lifting Key APPROVED - SIZE A1
PROJECT DWG.
No. - No.
214

THIRD EDITION - APRIL 2022


NOTES:
WATERTIGHT SINGLE PIECE COVER & FINISHED LEVEL OF THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
FRAME TO SUIT 750 OR 900 DIA CLEAR CARRIAGEWAY (FL) TOP OF PAVEMENT MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT

DIMENSION
OPENING BEDDED ON CEMENT MORTAR. REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED

TO SUIT
EXISTING COVER & FRAME TO BE REUSED AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
IF SUITABLE IN SIZE & CONDITION. NEW DIMENSION VARIES APPROVED AS PART OF THE PROJECT DRAWING SET.
COVER SIZE & CLASS (D400,C250 OR B125) MAXIMUM 600
EXISTING CONCRETE 1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS
SHALL BE AS DIRECTED BY THE ENGINEER TO BE BROKEN OUT AND
REPLACED AS NECESSARY OTHERWISE STATED.
2. THIS DRAWING TO BE READ IN CONJUNCTION WITH
12 DIA DOWEL BARS

DIMENSION
MANHOLE, CATCHBASIN AND INLET DRAWINGS.
BARS 300 LONG AT

TO SUIT
REINFORCED CONCRETE 3. GRP LADDER TO MAINTAIN CONSTANT RUNG SPACING
300 c/c SPACING
THROUGHOUT THE REVISED DEPTH OF THE MANHOLE
EXISTING COVER LEVEL
REINFORCED CONCRETE OR CHAMBER AND TO BE OF ONE PATTERN
EPOXY COATING AS
SPECIFIED ON ALL INTERIOR THROUGHOUT EXTENDED OR SHORTENED LENGTHS
EPOXY OF LADDER. EXISTING LADDER TO BE REMOVED AND
CONCRETE SURFACES
COATING AS REPLACED AS NECESSARY.
EXISTING COVER SLAB SPECIFIED ON
TO BE BROKEN OUT AND 4. COVER DETAILS TO BE RAISED BY REMOVING THE
REPLACED AS NECESSARY ALL INTERIOR EXISTING COVER SLAB AND EXTENDING THE ACCESS
12 DIA DOWEL BARS CONCRETE
BARS 300 LONG AT SHAFT AS NECESSARY.
25 SURFACES
300 c/c SPACING 5. COVER LEVELS TO BE RAISED USING CONCRETE
UNDER THE COVER FRAME PROVIDING THAT THE
REVISED DEPTH FROM THE COVER LEVEL TO THE TOP
EXISTING PROPOSED LADDER RUNG DOES NOT THEREBY EXCEED 600mm.
6. COVER LEVELS TO BE LOWERED BY BREAKING OUT
AND REFORMING THE ROOF SLAB AND ACCESS
TYPICAL DETAIL FOR RAISING OF CATCHBASIN COVER LEVEL SHAFT AS NECESSARY TO SATISFACTION OF THE
ENGINEER.
GRP LADDER 7. FOR RAISING AND LOWERING OF COVER LEVELS THE
(SEE NOTE 3) EXISTING CONCRETE
TO BE BROKEN OUT AND CONTRACTOR SHALL OBSERVE THE FOLLOWING

DIMENSION
REPLACED AS NECESSARY

TO SUIT
REQUIREMENTS WITH RESPECT TO METHOD AND
TIMING OF THE WORKS,
125 FINISHED LEVEL OF (a) THE METHOD AND TIMING OF THE WORKS
CARRIAGEWAY (FL) TOP OF PAVEMENT SHALL BE APPROVED BY THE ENGINEER AND
EXISTING ACCESS SHAFT EXISTING ACCESS SHAFT
THE ADM.
(b) EXISTING FLOWS WITHIN THE MANHOLE OR
EXISTING PROPOSED CHAMBER SHALL BE MAINTAINED.
12 DIA DOWEL BARS
BARS 300 LONG AT
300 c/c SPACING
TYPICAL DETAIL FOR RAISING OF MANHOLE COVER LEVEL LEGEND
DETAILS FOR OTHER SIZED SHAFT AND ACCESS OPENINGS SIMILAR REINFORCED CONCRETE REINFORCED CONCRETE REINFORCED CONCRETE

EPOXY COATING AS EPOXY COATING AS


SPECIFIED ON ALL INTERIOR SPECIFIED ON ALL INTERIOR
WATERTIGHT SINGLE PIECE COVER & FRAME TO SUIT 750 CONCRETE SURFACES CONCRETE SURFACES
OR 900 DIA CLEAR OPENING BEDDED ON CEMENT MORTAR.
EXISTING COVER & FRAME TO BE REUSED IF SUITABLE IN
SIZE & CONDITION. NEW COVER SIZE & CLASS (D400,C250 EXISTING PROPOSED
EXISTING COVER LEVEL OR B125) SHALL BE AS DIRECTED BY THE ENGINEER
DIMENSION

DIMENSION VARIES
TYPICAL DETAIL FOR LOWERING OF CATCHBASIN COVER LEVEL
TO SUIT

MAXIMUM 600
EXISTING COVER SLAB
TO BE BROKEN OUT AND
REPLACED AS NECESSARY

FINISHED LEVEL OF
CARRIAGEWAY (FL)

DIMENSION
TO SUIT
EXISTING CONCRETE
TO BE BROKEN OUT 12 DIA DOWEL BARS
BARS 300 LONG AT
300 c/c SPACING

EXISTING COVER SLAB


TO BE BROKEN OUT AND
GRP LADDER REPLACED AS NECESSARY
12 DIA DOWEL BARS REFERENCE DRAWINGS AND DOCUMENTS
(SEE NOTE 3) BARS 300 LONG AT
300 c/c SPACING STANDARD DRAWING - TANKING DETAILS - 801
- 1001
STANDARD DRAWING - CONSTRUCTION AND MOVEMENT JOINT
REINFORCED CONCRETE
REINFORCED CONCRETE STANDARD DRAWING - MISCELLANEOUS DETAILS - 207
125 25 FOR MANHOLES
STANDARD DRAWING - REINFORCEMENT DETAILS - 1000
EXISTING ACCESS SHAFT EXISTING ACCESS SHAFT EPOXY COATING AS (SERIES)
SPECIFIED ON ALL INTERIOR EPOXY COATING AS
SPECIFIED ON ALL INTERIOR STANDARD DRAWING - STORM WATER MANHOLE FRAME - 213
CONCRETE SURFACES
EXISTING PROPOSED CONCRETE SURFACES AND COVER DETAILS

TYPICAL DETAIL FOR LOWERING OF MANHOLE COVER LEVEL


DETAILS FOR OTHER SIZED SHAFT AND ACCESS OPENINGS SIMILAR
EXISTING PROPOSED

EXISTING CONCRETE SURROUND TYPICAL DETAIL FOR RAISING OF INLET COVER LEVEL
& ANY BLOCKWORK UNDER
FRAME TO BE BROKEN OUT No. REVISION-2 APP'D 2021
EXISTING COVER & FRAME
TO BE CLEANED & REUSED SURFACE OF COVER SLAB CLIENT

DIMENSION
IF IN SUITABLE CONDITION TO BE SCABBLED PRIOR TO

TO SUIT
SURROUND BEING PLACED EXISTING COVER SLAB
TO BE BROKEN OUT AND
REPLACED AS NECESSARY FINISHED LEVEL OF
CONCRETE TO SUIT FGL CONCRETE C20 SURROUND CARRIAGEWAY (FL)
TO COVER TO UNDERSIDE OF
BASE COURSE EXISTING CONCRETE TITLE
EXISTING COVER SLAB
TO BE RETAINED TO BE BROKEN OUT AND STANDARD DRAWINGS
REPLACED AS NECESSARY
EPOXY COATING MINIMUM
THICKNESS 0.75 TO INTERNAL 12 DIA DOWEL BARS
STORM WATER WORKS
FACES OF CONCRETE BARS 300 LONG AT
REINFORCED CONCRETE 300 c/c SPACING DRAWING TITLE

EPOXY COATING AS REINFORCED CONCRETE


STANDARD DRAWING
SPECIFIED ON ALL INTERIOR
CONCRETE SURFACES
ADJUSTING COVER LEVELS FOR
200 EPOXY COATING AS MANHOLE, CATCHBASIN AND
SHAFT DIA VARIES SPECIFIED ON ALL INTERIOR
CONCRETE SURFACES INLET - TYPICAL DETAILS
TYPICAL DETAIL FOR MINOR EXISTING PROPOSED DRAWN - SCALE N.T.S
ADJUSTMENT TO THE MANHOLE COVER CHECKED - DATE -
(SEE NOTE 7) TYPICAL DETAIL FOR LOWERING OF CATCHBASIN COVER LEVEL APPROVED - SIZE A1
PROJECT DWG.
No. - No.
215

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
5900 600 300 300 2500 300 2500 300 300 600
1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS OTHERWISE
1200 1000 700 100 200 300 STATED.
2. POSITIONS OF THE INLET AND OUTLET PIPEWORK MAY BE
ADJUSTED ON SITE TO SUIT INDIVIDUAL LOCATIONS.
100 DIA PIPEWORK TO OIL
AS TYPICAL VENT PIPE COLLECTION TANK. LEVEL 3. DEPTH OF THE VENTILATION PIPE INLETS MAY BE
DETAIL BUT WITH 100 DIA IS IL.-250 (SEE NOTE 2) ADJUSTED FOR DIRECTION OF RISE.
SURFACED
3 No. PIPE STRAPS VENT PIPE 4. ALL JOINTS BETWEEN PIPES AND CONCRETE ARE TO BE
BOX 250 x 250 B WATERTIGHT.
VENT PIPE INLET PIPEWORK OIL DISCHARGE 5. STRUCTURAL INTEGRITY OF CHAMBER IS THE
SURFACED
BOX 250 x 250
(SEE NOTE 2) PIPE RESPONSIBILITY OF THE DESIGNER.
6. ALL EXTERNAL FACES OF CONCRETE BELOW GROUND TO

300
350
BE TANKED.
7. ALL INTERNAL FACES OF CONCRETE TO BE COATED WITH
EPOXY COATING AS SPECIFIED.

300
8. THE MANHOLES AND CHAMBERS ARE DESIGNED USING
SLUDGE LAYER SENSOR FULL GROUND WATER LEVEL CONDITION WITH 1.1 FACTOR

750

1550
OIL LAYER THICKNESS SENSOR

950
OF SAFETY FOR FLOATATION AND BEARING PRESSURE NOT
EXCEEDING 200kpa AT FORMATION LEVEL.
A A

300
9. DEWATERING OPERATIONS SHALL BE PROVIDED DURING

300
CONSTRUCTION AND MAY ONLY BE TERMINATED AFTER

450
OUTLET PIPEWORK ROOF SLAB HAS BEEN CAST.

300
(SEE NOTE 3)
LEGEND
SUMP 400 x 400 PIPEWORK SUMP 400 x 400 PIPEWORK REINFORCED CONCRETE
1250 600 2 No. SINGLE PIECE HEAVY DUTY 600 1250 x 175 FABRICATED TO SUIT x 175 B FABRICATED TO SUIT
DUCTILE IRON COVERS AND FRAMES 100 200 300 SOIL COMPACTED TO 95% MDD
TO EN124 CLASS D400 TO SUIT 750 x 600 PLAIN CONCRETE
CLEAR OPENINGS
GATE VALVE
ROOF PLAN SECTION C-C
FGL FINAL GROUND LEVEL
FL FINAL ASPHALT / INTERLOCKED TILE LEVEL
IL INVERT LEVEL OF INLET PIPE
WALL AND FOUNDATION CUT BACK
AS NECESSARY TO ALLOW PROPER IL-50 LOWER THAN INVERT LEVEL OF INLET PIPE BY 50mm
75 THICK PRECAST CONCRETE SEATING
FIXING OF VENT PIPE.
RINGS BEDDED IN 1 PART CEMENT / 2
PART SAND MORTAR
WIRE BALLON WITH MOSQUITO SCREEN
10 DOWEL DRILLED AND SET INTO DUCTILE IRON COVER
AIRVENT ABOVE GROUND FIXED TO COVER SLAB AT 300 CENTERS 150 CLASS B CONCRETE SURROUND
WALL AT NOT GREATER THAN 750mm BY FINISHED LEVEL OF
500

HOLDER BATS PAVED AREA (FL) CL CL

(MIN.)
450
750 MAX

300
FGL PROVIDED DIMENSIONS / SIZE OF OIL
SEPARATOR IS INDICATIVE ONLY
ENGINEER IS RESPONSIBLE TO SIZE OF
OIL SEPARATOR TO SUIT INLET PIPES
INVERT LEVELS AND AMOUNT OF FLOW.
COVER SLAB DETAIL FOR CARRIAGEWAY & PARKING AREAS
VENT PIPE
AS SPECIFIED UV
RESISTANCE EPOXY REFERENCE DRAWINGS AND DOCUMENTS
COATING TO ALL AS SPECIFIED UV SEE NOTE 4
RESISTANCE EPOXY STANDARD DRAWING - TANKING DETAILS - 801
SURFACED SURFACES ABOVE SURFACED SURFACED
COATING TO ALL 300
SEE NOTE 3 STANDARD DRAWING - MISCELLANEOUS DETAILS - 207
BOX 250 x 250 GROUND
100

100
BOX 250 x 250 BOX 250 x 250 FOR MANHOLES
SURFACES ABOVE
CL GROUND CL CL STANDARD DRAWING - COLLECTION TANK TO - 217
FGL FGL FGL FGL OIL SEPARATOR
STANDARD DRAWING - REINFORCEMENT DETAILS - 1000
(SERIES)
300

75
175
300 REINFORCED CONCRETE
INTERNAL
EXTENSION SPINDLES
EXTENSION SPINDLES PROTECTION AS
SPECIFIED
C C
300

IL 00
IL -50 IL -50 IL -50 No. REVISION-2 APP'D 2021
3100

OIL LAYER THICKNESS SENSOR


OIL DISCHARGE PIPE
IL -250
BOTTOM OF THE
CLIENT
IL-450 PIPEWORK IL-450 OIL LAYER IL-450
FABRICATED TO SUIT OIL DISCHARGE PIPE

TANKING MEMBRANE
AND PROTECTION BOARD TITLE
TANKING MEMBRANE
AND PROTECTION BOARD SLUDGE OIL STANDARD DRAWINGS
TRAP SLUDGE LAYER SENSOR INTERCEPTOR GRP PIPESTRAP
STORM WATER WORKS
2cm

400

ALARMING LEVEL

400
SCREED 50 - 100 THICK
DRAWING TITLE
SCREED 50-100 THICK
500

STANDARD DRAWING
OIL SEPARATOR
50mm THK. CEMENT/SAND SCREED 50mm THK. CEMENT/SAND SCREED
300 950 300 TANKING MEMBRANE 300 300 2500 300 2500 300 300 TANKING MEMBRANE
75mm THICK C20 BLINDING 75mm THICK C20 BLINDING DRAWN - SCALE 1 : 50
1000 GAUGE POLYETHYLENE SHEET 1000 GAUGE POLYETHYLENE SHEET
SECTION B-B SECTION A-A CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No. 216

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
750 x 600 COVER & FRAME AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
AS SPECIFIED APPROVED AS PART OF THE PROJECT DRAWING SET.
100 DIA SLUICE VALVE WITH
100 x 100 SURFACE BOX 1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS
EXTENSION SPINDLE FOR T.
OTHERWISE STATED.
KEY OPERATION
2. ALL LEVELS ARE IN METRES UNLESS OTHERWISE

50
STATED.
GRP LADDER GRP PIPEWORK 3. POSITION OF THE INLET PIPE WORK MAY BE ADJUSTED ON
D.I. PIPEWORK
SITE TO SUIT INDIVIDUAL LOCATIONS.
4. ALL JOINTS BETWEEN PIPE WORK AND CONCRETE TO BE
WATERPROOF.
5. STRUCTURAL INTEGRITY OF THE CHAMBER IS THE
RESPONSIBILITY OF THE DESIGNER. DETAILS OF

300
100 DIA GRP PIPE WORK FROM REINFORCEMENT TO BE CONFIRMED FOR PARTICULAR
OIL SEPARATOR APPLICATION.
6. ALL EXTERNAL FACES OF CONCRETE BELOW GROUND TO

750
A A BE TANKED.
7. ALL INTERNAL FACES OF CONCRETE TO BE COATED WITH
EPOXY COATING AS SPECIFIED.
8. THE MANHOLES AND CHAMBERS ARE DESIGNED USING
FULL GROUND WATER LEVEL CONDITION WITH 1.1
FACTOR OF SAFETY FOR FLOATATION AND BEARING

300
PRESSURE NOT EXCEEDING 200kpa AT FORMATION LEVEL.
9. DEWATERING OPERATIONS SHALL BE PROVIDED DURING
CONSTRUCTION AND MAY ONLY BE TERMINATED AFTER
ROOF SLAB HAS BEEN CAST.
STEPPED COUPLING
LEGEND
D.I. FLANGED SPIGOT REINFORCED CONCRETE
SOIL COMPACTED TO 95% MDD
PLAIN CONCRETE
35
400 x 400 x 175 SUMP
FGL FINAL GROUND LEVEL
125 600 100 140 FL FINAL ASPHALT / INTERLOCKED TILE LEVEL
IL INVERT LEVEL OF INLET PIPE

SECTION B-B PLAN AT COVER LEVEL

DUCTILE IRON COVER

AS SPECIFIED UV RESISTANCE
EPOXY COATING TO ALL
SURFACES ABOVE GROUND
100

COVER SLAB DETAIL

150
FGL FGL
75 THICK PRECAST CONCRETE FOR PAVED AREA
SEATING RINGS BEDDED IN 1 PART
CEMENT / 2 PART SAND MORTAR DUCTILE IRON COVER

250
10 DOWEL DRILLED AND SET INTO 16 DIA STEP BAR CAST INTO
REINFORCED CONCRETE
COVER SLAB COVER SLAB AT 300 CENTERS COVER SLAB WITH TOE HOLE
FINISHED LEVEL OF 150 CLASS B
CARRIAGEWAY (FL) CL CONCRETE SURROUND
1 No. GRP SUPPORT BRACKET TO
EXTENSION SPINDLE PER METRE LENGTH

MAX
600
300 REFERENCE DRAWINGS AND DOCUMENTS
STANDARD DRAWING - TANKING DETAILS - 801
B B STANDARD DRAWING - MISCELLANEOUS DETAILS - 207

VARIES
FOR MANHOLES
STANDARD DRAWING - OIL SEPARATOR - 216
STANDARD DRAWING - REINFORCEMENT DETAILS - 1000
(SERIES)
300

EPOXY COATING
AS SPECIFIED COVER SLAB DETAIL FOR CARRIAGEWAY & PARKING AREAS

IL

FLOW FROM OIL


TANKING TO ALL SEPARATOR
CONCRETE CONCRETE 70
SURFACES BELOW
GROUND
No. REVISION-2 APP'D 2021
CLIENT

PROVIDED DIMENSIONS / SIZE OF


COLLECTION TANK IS INDICATIVE ONLY
SLOPE CAST IN CONCRETE ENGINEER IS RESPONSIBLE TO SIZE OF
TITLE
25

SELECTION TANK TO SUIT INLET PIPES


INVERT LEVELS AND AMOUNT OF FLOW. STANDARD DRAWINGS
REINFOECED CONCRETE STORM WATER WORKS
DRAWING TITLE

STANDARD DRAWING COLLECTION


TANK TO OIL SEPARATOR

200 1000 200 50mm THK. CEMENT/SAND SCREED


TANKING MEMBRANE DRAWN - SCALE 1 : 20

SECTION A-A 75mm THICK C20 BLINDING CHECKED - DATE -


1000 GAUGE POLYETHYLENE SHEET APPROVED - SIZE A1
PROJECT DWG.
No. - No. 217

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS.
Watertight frame & single piece cover Class D400, THEY ARE EXPECTED TO BE INCORPORATED AS TYPICAL
C250 or B125 as directed by the engineer to suite DETAILS WHICH SHALL BE CHECKED AND APPROVED AS
750x600mm (see detail "A")
E E Pipe Port Pipe Port PART OF THE PROJECT DRAWING SET.
Variable 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
STATED.
Variable GRP Shaft 2. ALL CONCRETE TO BE C40 UNLESS OTHERWISE STATED.
3. MANHOLES ARE TO BE WATERTIGHT.
4. FOR CONNECTION & GRP JOINT LAMINATION DETAILS
REFER TO DRG No. SWGN-STD-221.

Variable
5. FOR COVER AND ACCESS DETAILS REFER TO DRG No.
D D I I

Variable

Variable
SWGN-STD-222.
LATERAL CONNECTION 6. PIPE GRADIENTS TO BE MAINTAINED THROUGH CHANNELS.
(See

500
Note 9)
7. ALL GRP STRUCTURAL MANHOLES SHALL BE
INCORPORATED WITH LIFTING BLOCKS FOR HANDLING.

FLOW
Lateral Connection Lateral Connection
8. ALL COVERS IN OPEN AREA IN OPEN AREA TO BE PROVIDED
C40 Concrete Fill WITH 1NO. GRAB BAR.

*
9. MANHOLES TO BE PROVIDED WITH SAND TRAP 500mm DEEP
GRP Shear key (See Note 15)
SUMP.
10.DEWATERING OPERATIONS SHALL BE PROVIDED DURING
CONSTRUCTION AND MAY ONLY BE TERMINATED AFTER
Variable
COVER HAS BEEN INSTALLED.
11.PORT CONFIGURATION MUST MATCH ALL CONNECTING
SECTION D-D INCOMING AND OUTGOING PIPE LINE.
PLAN AT COVER LEVEL TYPICAL DETAIL OF
SECTION PLAN E-E SECTION PLAN H-H 12. STRUCTURAL INTEGRITY OF MANHOLE IS THE
LATERAL CONNECTIONS
RESPONSIBILITY OF DESIGNER / MANUFACTURER.
13.GRP MANHOLE SHAFT HAVE A MINIMUM SPECIFIC INITIAL
LONGITUDINAL COMPRESSIVE STRENGTH OF 80 MPa

B
(MN/m2) AT BREAK.
Reinforced Concrete C40 H H 14. 4 NOS. GRP SHEAR KEY TO BE PROVIDED FOR ANCHORAGE
GRP COVER Cover Slab (at site as per specs.) BETWEEN SHAFT & CONCRETE FILL.
15.MANUFACTURER TO SUBMIT DETAIL STRUCTURAL
Variable GRP Shaft CALCULATIONS BASED ON ACTUAL SITE CONDITION & TO BE
APPROVED PRIOR TO MANUFACTURING.
MACHINED SEATING 16.GROUND WATER TABLE SHALL BE VERIFIED AT SITE & THE
GRP Shaft
40 WEIGHT OF THE MANHOLE BASE (CONCRETE WORK) SHALL

Variable
GRP Shear Key
A A
Variable

BE PROPORTIONATE TO RESIST UPLIFT.


(100x150x40mm)

100
FLOW
LATERAL
(See

500
CONNECTION
Concrete fill in base Note 9)
Pipe Port
GRP LINING ECR CLEAR OPENING
Clear opening 750x600 D.I. access cover
GLASS,7mm. THICK AS STATED ON DRAWINGS
SHEAR KEY DETAILS C40 Concrete Fill

*
GRP Shaft
(TYPICAL) GRP Shear key
DETAIL "A" B Lifting Block (See Note 15)

(MANHOLE TOP & FRAME DETAILS) Variable

SECTION I-I
SECTION PLAN C-C TYPICAL DETAIL OF
LATERAL CONNECTIONS

Watertight frame & single piece cover Class D400,


C250 or B125 as directed by the engineer to suite G G
750x600mm (see detail "A")
CL CL
Paved Area Paved Area
FGL FGL
70 250 200

70 250 200

Reinforced Concrete C40 Variable

1500 Dia.
Cover Slab (at site as per specs.)

7mm GRP Skin Liner for cover slab REFERENCE DRAWINGS AND DOCUMENTS

Variable

Variable
200 200 EPDM Seal 40x6mm 200 Flow
STAINLESS STEEL
16 DIA STEP BAR CAST INTO SAFETY CHAIN
COVER SLAB WITH TOE HOLE AND FIXINGS
(See

500
Note 9) (See

500
Lifting Block
Pipe port Note 9)
Underground Underground
Manhole Depth ≤ 10000mm

Manhole Depth ≤ 10000mm

Water Table Water Table


C40 Concrete Fill
*

GRP Ladder
C40 Concrete Fill

*
GRP Shaft

Wall Thickness Variable


(See Note 14) Variable
SECTION F-F SECTION FOR
C C 1500DIAMETER

No. REVISION-2 APP'D 2021


GRP Manhole Installation Depth (mm) (Cover Level to Pipe Inert Level)
CLIENT

Dia of GRP
Manhole Manufacturing
≤ 4000 > 4000 ≤ 6000 > 6000 ≤ 8000 > 8000 ≤ 10000
Process
(mm)
Variable

Variable

Flow F F
Variable

IL GRP Manhole Shaft Thickness - mm (Min. Values) TITLE


D
FLOW STANDARD DRAWINGS
(See Not Not
500

500

(See Note 9) Centrifugal Casting 18.0 19.0 STORM WATER WORKS


400

Pipe Port Note 9) Recommended Recommended


Pipe Port 1100
Not Not
Filament Winding 15.5 16.5
Recommended Recommended
Concrete Fill at site DRAWING TITLE
GRP Shear key C40 Concrete Fill Centrifugal Casting 19.5 20.5 24.5 27.5
*

C40 Concrete Fill


10mm GRP Base plate 1200
Filament Winding 16.5 18.0 20.5 23.5
50mm Dry Mortar Screed
Pipe Port Centrifugal Casting
GRP MANHOLE WITH FLAT BASE
75mm thick Concrete C20 Blinding 22.5 24.5 28.5 31.5
Variable Variable
1400
SECTION A-A SECTION B-B Filament Winding 18.5 20.5 24.5 27.5
SECTION PLAN G-G
Centrifugal Casting 23.5 26.5 30.5 33.5
1600 DRAWN - SCALE N.T.S
Filament Winding 19.5 22.5 26.5 29.5
* MAY VARY DEPENDING ON ANTI-FLOATATION
REQUIREMENT BASED ON SITE WATER TABLE.
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
219

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS.
THEY ARE EXPECTED TO BE INCORPORATED AS TYPICAL
DIA. 2000 (SEE NOTE12) E E DETAILS WHICH SHALL BE CHECKED AND APPROVED AS
Cutout for
concrete pouring PART OF THE PROJECT DRAWING SET.
Variable Pipe Port Pipe Port
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
Variable STATED.

200*
2. ALL CONCRETE TO BE C40 UNLESS OTHERWISE STATED.

FLOW
Variable
3. MANHOLES ARE TO BE WATERTIGHT.
4. FOR CONNECTION & GRP JOINT LAMINATION DETAILS

Base (variable)

DIA. 2000 (SEE NOTE13)

DIA. 2000 (SEE NOTE13)


REFER TO DRG No. SWGN-STD-221.
(See 5. FOR COVER AND ACCESS DETAILS REFER TO DRG No.
D D I I

500
LATERAL

Variable

Variable
Note 9) SWGN-STD-222.
CONNECTION
6. PIPE GRADIENTS TO BE MAINTAINED THROUGH CHANNELS.
7. ALL GRP STRUCTURAL MANHOLES SHALL BE
INCORPORATED WITH LIFTING BLOCKS FOR HANDLING.

FLOW
C40 Concrete Fill Lateral Connection Lateral Connection
GRP Shear key 8. PORT CONFIGURATION SHALL BE TO MATCH ALL
(See Note 15) CONNECTING INCOMING AND OUTGOING PIPE LINE.
9. MANHOLES TO BE PROVIDED WITH SAND TRAP 500mm
Variable DEEP SUMP.
Watertight frame & single piece cover Class D400, DIA. 2000 (SEE NOTE13)
10. STRUCTURAL INTEGRITY OF MANHOLES IS THE
C250 or B125 as directed by the engineer to suite
750x600mm (see detail "A") RESPONSIBILITY OF DESIGNER / MANUFACTURER.
SECTION D-D 11.GRP MANHOLE SHAFT HAVE A MINIMUM SPECIFIC INITIAL
7mm GRP External base SECTION PLAN H-H
TYPICAL DETAIL OF LATERAL CONNECTIONS LONGITUDINAL COMPRESSIVE STRENGTH AT BREAK OF 80
MPa (MN/m2).
PLAN AT COVER LEVEL
SECTION PLAN E-E 12. ALL CUT-OUTS / HOLES & AIR VENT HOLES FOR CONCRETE
TO BE CLOSED BY GRP LAMINATION AFTER THE CURING OF

B
CONCRETE.
13.BOX-OUT : EXTERNAL BASE DIMENSIONS TO BE BASED ON
7mm GRP External Base
(for C40 concrete fill at site)
H H ANTI-FLOATATION REQUIREMENT.
Cutout for
Cutout for concrete pouring concrete pouring 14. 4 NOS. GRP SHEAR KEY TO BE PROVIDED FOR ANCHORAGE
GRP COVER Cutout in Shaft wall BETWEEN SHAFT & CONCRETE FILL.
(for concrete passage) Variable 15.MANUFACTURER TO SUBMIT DETAIL STRUCTURAL

200*
Lifting Block CALCULATIONS BASE ON ACTUAL SITE CONDITION & TO BE
DIA. 2000 (SEE NOTE12)

APPROVED PRIOR TO MANUFACTURING.

Variable
MACHINED SEATING
A A GRP Shaft 16.GROUND WATER TABLE SHALL BE VERIFIED AT SITE & THE
Variable

WEIGHT OF THE MANHOLE BASE (CONCRETE WORK) SHALL

Base (variable)
40

100
FLOW GRP Shear Key
(See BE PROPORTIONATE TO RESIST UPLIFT.
(100x150x40mm)

500
Note 9) LATERAL
Pipe Port CONNECTION

Silica Sand non-slip surface Concrete fill in base

*
on benching land C40 Concrete Fill
GRP LINING ECR CLEAR OPENING GRP Shear key
GLASS,7mm. THICK AS STATED ON DRAWINGS GRP Shaft
(See Note 15)
SHEAR KEY DETAILS (TYPICAL)
B Variable
DETAIL "A" DIA. 2000 (SEE NOTE13)
75mm thick Concrete C20 Blinding
(MANHOLE TOP & FRAME DETAILS)

SECTION PLAN C-C SECTION I-I

Watertight frame & single piece cover Class D400,


C250 or B125 as directed by the engineer to suite G G
750x600mm (see detail "A")
CL CL
Paved Area Paved Area
Pipe port
FGL FGL

200*
200

200

Reinforced Concrete C40


Cover Slab (at site as per specs.) REFERENCE DRAWINGS AND DOCUMENTS

Variable
250

250

Variable
Flow
7mm GRP Skin Liner for cover slab STAINLESS STEEL
70

70

SAFETY CHAIN

Base (variable)
200 200 EPDM Seal 40x6mm 125 AND FIXINGS
200 200 (See

500
100
16 DIA STEP BAR CAST INTO

200*
Note 9)
COVER SLAB WITH TOE HOLE
Lifting Block

*
C40 Concrete Fill
Underground Underground
Water Table Water Table

1500 Dia.
GRP Shaft
Manhole Depth ≤ 10000mm

Manhole Depth ≤ 10000mm

GRP Ladder

Base (variable)
Variable
DIA. 2000 (SEE NOTE13)

Wall Thickness
(See Note 14)
SECTION F-F

(See

500
C C Note 9)

No. REVISION-2 APP'D 2021


Pipe Port
CLIENT

*
C40 Concrete Fill
Cutout for concrete pouring
as required
Pipe Port
200*

200*

Variable
Pipe Port DIA. 2000 (SEE NOTE13)
Variable

Variable

Flow TITLE
DIA. 2000 (SEE NOTE13)

IL SECTION FOR STANDARD DRAWINGS


Base (variable)

Base (variable)

F FLOW F 1500 DIAMETER


Variable

(See STORM WATER WORKS

D
500

500

(See Note 9) 400 Note 9)


DRAWING TITLE
7mm GRP External Base
(for C40 concrete fill at site)
*

Shear key C40 Concrete Fill C40 Concrete Fill

GRP Shear key


(See Note 15) GRP MANHOLE WITH BOX-OUT
50mm Dry Mortar Screed
Variable Variable
DIA. 2000 (SEE NOTE13) 75mm thick Concrete C20 Blinding DIA. 2000 (SEE NOTE13)

SECTION A-A SECTION B-B SECTION PLAN G-G


DRAWN - SCALE N.T.S
TYPICAL DETAIL FOR 90° BEND AT MANHOLE
* MAY VARY DEPENDING ON ANTI-FLOATATION CHECKED - DATE -
REQUIREMENT BASED ON SITE WATER TABLE.
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
220

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS.
THEY ARE EXPECTED TO BE INCORPORATED AS TYPICAL
DETAILS WHICH SHALL BE CHECKED AND APPROVED AS
PART OF THE PROJECT DRAWING SET.
SEE DETAIL "C" 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
STATED.
16 DIA STEP BAR CAST INTO 2. ALL CONCRETE TO BE C40 UNLESS OTHERWISE STATED.
COVER SLAB WITH TOE HOLE
3. SHORT PIPE LENGTH EQUALS 1.5 PIPE DIAMETER OR 600mm
SEE DETAIL "B" Lifting Block WHATEVER HIGHER.

TANKING SEAL REFER GRP Shaft


TO DRG No. SWN-STD-801
GRP Ladder

SEE DETAILS GRP SOCKET END TO SUIT


PVC-U DOUBLE SPIGOT
SHORT PIECE PIPE
SHORT PIECE

SEE DETAIL "A"


Cutout for concrete pouring
PVC-U DOUBLE SPIGOT BASE Pipe Port
SHORT PIECE PIPE

400
100 MINIMUM C40 Concrete Fill

WATERPROOF MEMBRANE
MASS CONCRETE C20
MANHOLE SECTION

PIPE CONNECTION DETAILS FOR GRP AND PVC-U PIPES PIPE CONNECTION DETAILS FOR PVC-U PIPES
7mm GRP external base
SCALE 1:10 SCALE 1:2.5 (for C40 concrete fill) 75 GRP Shaft
GRP Shaft

min 100
Cut-out closure
piece GRP Joint Lamination GRP Joint Lamination
75 at factory at factory

100
Lifting Block
C40 Concrete Fill

7 GRP Shear Key


(See Note 15) (In-side) (Out-side)

DETAIL "A" DETAIL "B"


SCALE 1:4 SCALE 1:4
REFERENCE DRAWINGS AND DOCUMENTS

TANKING SEAL REFER


TO DRG No. #### TANKING SEAL REFER OPTION 01 OPTION 02
TO DRG No. #### Reinforced concrete Reinforced concrete
C40 Cover Slab (at C40 Cover Slab (at
GRP SOCKET END site as per specs.) site as per specs.)

7mm GRP Skin Liner 7mm GRP Skin Liner


for cover slab for cover slab

70

70
EPDM Rubber 40x6mm EPDM Rubber 40x6mm
PIPE END
ROUNDED OFF 5
PIPELINE DIRECTION 7 GRP Shaft GRP Shaft
GRP DOUBLE SPIGO BASE GRP DOUBLE SPIGOT BASE
SHORT PIECE PIPE SHORT PIECE PIPE
(600 LONG) Option 02: Applicable with prior approval
filled with vinyl ester paste and subject to site requirement by laminating
DETAIL "C" GRP cover slab skin directly to shaft No. REVISION-2 APP'D 2021
finished with "c" glass surface
SCALE 1:4 after removing or without EPDM rubber
tissue-vinyl ester resin CLIENT
GRP DOUBLE
COUPLING

EDGE OF COUPLING
100 MINIMUM ROUNDED OFF GRP Shaft
WATERPROOF
MEMBRANE TITLE
STANDARD DRAWINGS
WATERPROOF MEMBRANE STORM WATER WORKS

400 min.
200 min.

200 min.
DBC

DRAWING TITLE
GRP Joint
Lamination at site

(In-side) (Out-side) (In-side) (Out-side)


CONNECTION & GRP JOINT LAMINATION
PIPE CONNECTION DETAILS FOR GRP PIPES FROM 200TO 450DIA PIPE CONNECTION DETAILS FOR GRP PIPES 600TO 1000DIA
DETAILS FOR MANHOLES
SCALE 1:2.5 SCALE 1:2.5
ADD ON SHAFT RING
(If Required to Increase the shaft height)

OPTION 01 OPTION 02 DRAWN - SCALE N.T.S


NOT TO SCALE NOT TO SCALE
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
221

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS.
COVER SLAB DETAIL COVER SLAB DETAIL THEY ARE EXPECTED TO BE INCORPORATED AS TYPICAL
FOR PAVED AREA FOR UNPAVED AREA DETAILS WHICH SHALL BE CHECKED AND APPROVED AS
GROUND TYPE DETAIL (CASE No.)
CLASS D400, C250 OR D125 COVER AND FRAME PART OF THE PROJECT DRAWING SET.
UNPAVED AREA CASE 1
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
BULL NOSED ARISSES TO EXISTING UNPAVED ROAD CASE 2 STATED.
(CASE 3) CASE 2 EXPOSED CORNERS EXISTING PAVED ROAD CASE 3 2. THIS DRAWING TO BE READ IN CONJUNCTION WITH
FINISHED LEVEL OF ROAD MANHOLE DRAWINGS.
OR PAVED AREA (FGL) 225 CASE 1 3. ALL CONCRETE TO BE C40 UNLESS OTHERWISE STATED.
FGL

100
250
CONCRETE C20 SURROUND TO COVER

ONE COURSE OF CONCRETE BLOCKWORK OR SURFACE OF COVER SLAB TO BE SCABBLED


NON STRUCTURAL CONCRETE MINIMUM 100 PRIOR TO SURROUND BEING PLACED
HIGH TO SUIT F.G.L.

GRP LINER TO BE EXTENDED &


RETURNED UNDER MANHOLE COVER

125

ACCESS SHAFT

TYPICAL SECTION OF COVER SLAB

250
600 x 750 NOMINAL SIZE CLEAR
OPENING IN ALL MANHOLES

TYPICAL PLAN OF COVER SLAB

MANHOLE COVER DETAILS


GRP COVER

COVER OPENING
MACHINED SEATING

GRP LINING ECR


CLEAR OPENING
GLASS,7mm. THICK
AS STATED ON DRAWINGS

REFERENCE DRAWINGS AND DOCUMENTS


MANHOLE TOPS & COVERS DETAILS

1000 MANHOLE DIAMETER 1025

No. REVISION-2 APP'D 2021


CLIENT
3 3
1 1

TITLE
STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

SELECTED BACKFILL MATERIAL


COMPACTED IN MAXIMUM THICKNESS
LAYERS OF 300 TO GIVE 90% RELATIVE MOD
COVER DETAILS FOR MANHOLES

DRAWN - SCALE N.T.S


PROTECTIVE BUND TO MANHOLES
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
222

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENTS A MINIMUM REQUIREMENT
BUT MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT
PROJECT REQUIREMENTS, THEY ARE EXPECTED TO BE
INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE

C
CHECKED AND APPROVED AS PART OF THE PROJECT

C
DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
STATED.
2. ALL CONCRETE TO BE C40 UNLESS OTHERWISE STATED.
3. IN PLACE WHERE MANHOLE DEPTHS EXCEED 7500,
MANHOLE SHALL BE DESIGNED BY CONTRACTOR ON
INDIVIDUAL BASIS.THE CONTRACTOR SHALL SUBMIT
MANUFACTURER'S CALCULATIONS AND VERIFY THE
SATISFACTION OF STRUCTURAL REQUIREMENTS FOR THE
ENGINEER'S APPROVAL.
4. MANHOLES/CHAMBERS ARE TO BE WATERTIGHT.
5. ALL EXTERNAL FACES OF CONCRETE BELOW GROUND
LEVEL TO BE COATED WITH COAL TAR EPOXY (MIN. 300
D2 MICRONS).
6. FOR STANDARD DETAILS REFER TO DRG NO.SWGN-STD-229.
7. FOR COVER AND ACCESS & MANHOLE BASE DETAILS

SHAFT DEPTH VARIES

SHAFT DEPTH VARIES


REFER TO DRG NO. SWGN-STD-230.
8. STRUCTURAL INTEGRITY OF THE MANHOLES IS THE
D2 RESPONSIBILITY OF THE DESIGNER.

≤ 6.5 M

≤ 6.5 M
9. MANHOLES TO BE PROVIDED WITH SAND TRAP 500MM DEEP
SUMP.
10.GROUND WATER TABLE SHALL BE VERIFIED AT SITE & THE
WEIGHT OF THE MANHOLE BASE (CONCRETE WORK) SHALL
H

BE PROPORTIONATE TO RESIST UPLIFT.

R
R

BH
D1
BH

D1
DN

DN
P
B 500

P
see note 9
Concrete C40 B 500 see note 9 REFERENCE DRAWINGS AND DOCUMENTS

Concrete C40

MANHOLE TYPE (I)


MANHOLE TYPE (II)

No. REVISION-2 APP'D 2021


CLIENT
STRUCTURAL DETAILS OF MANHOLES
NOMINAL PIPE MANHOLE BASE SHAFT BENCHING UNIT BASE SLAB REDUCER / INT- COVER SLAB BASE SLAB BASE
MANHOLE DIAMETER DEPTH DN DN / BASE HEIGHT THICKNESS ERMEDIATE SLAB THICKNESS PROJECTION REINFORCEMENT TITLE
TYPE (mm) STANDARD DRAWINGS
(m) (mm) (mm) (mm) (mm) THICKNESS (mm) (mm) (mm) BARS & SPACING
(H) (D2) (P) (mm) STORM WATER WORKS
(DN) (D1) (BH) (B) (R) (C)
DRAWING TITLE
I-A 150 - 315 ≤4 1000 1000 1500 300 300 250 400 14 @ 150
I-B 150 - 315 ≤ 7.5 1500 1500 2500 500 300 250 400 14 @ 150 STRUCTURAL DETAILS OF
HDPE MANHOLES ≤ 7.5M
II-A 400 - 500 1500 1200 2500 500 300 250 400 14 @ 150
II-B 600 - 900 > 4 & ≤ 7.5 1800 1200 2500 500 300 250 400 14 @ 150
DRAWN - SCALE N.T.S
II-C 1000 - 1200 2200 1200 2500 500 300 250 400 14 @ 150 CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
223

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
100THK. PRE-CAST RECTANGULAR MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REINFORCED CONCRETE SEATING REQUIREMENTS.
GRADE ( C-40)
THEY ARE EXPECTED TO BE INCORPORATED AS TYPICAL
DETAILS WHICH SHALL BE CHECKED AND APPROVED AS
PART OF THE PROJECT DRAWING SET.
R.C COVER
SLAB (C-40) MH SHAFT MH SHAFT 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
STATED.
2. ALL CONCRETE TO BE C40 UNLESS OTHERWISE STATED.
COUPLING BUTT FUSION COUPLING BUTT FUSION 3. IN PLACE WHERE MANHOLE DEPTHS EXCEED 7500,
LINER ( PE ) WELDING WELDING MANHOLE SHALL BE DESIGNED BY CONTRACTOR ON
INDIVIDUAL BASIS.THE CONTRACTOR SHALL SUBMIT
95%COMPACTED MANUFACTURER'S CALCULATIONS AND VERIFY THE
SOIL PIPE PIPE PIPE PIPE SATISFACTION OF STRUCTURAL REQUIREMENTS FOR THE
BUTT ENGINEER'S APPROVAL.
MH FUSION WELDING
SHAFT ANCHOR BLOCK ANCHOR BLOCK
4. ALL EXTERNAL FACES OF CONCRETE BELOW GROUND
(IF REQUIRED)
LEVEL TO BE COATED WITH COAL TAR EPOXY (MIN. 300
Ø32mm HOLES Ø32mm HOLES MICRONS).
5. FOR STANDARD DETAILS REFER TO DRG NO.SWGN-STD-229.
6. FOR COVER AND ACCESS & MANHOLE BASE DETAILS
100mm CONCRETE 100mm CONCRETE
BLINDING (C-20) BLINDING (C-20) REFER TO DRG NO. SWGN-STD-230.
7. ALL PRECAST CONCRETE BASE UNITS SHALL INCORPORATE
SAFE LIFTING POINTS WHICH SHALL BE CLEARLY MARKED
8. STRUCTURAL INTEGRITY OF THE MANHOLES IS THE
RESPONSIBILITY OF THE DESIGNER.
9. MANHOLES TO BE PROVIDED WITH SAND TRAP 500MM DEEP
SUMP.
10.GROUND WATER TABLE SHALL BE VERIFIED AT SITE & THE
WEIGHT OF THE MANHOLE BASE (CONCRETE WORK) SHALL
BE PROPORTIONATE TO RESIST UPLIFT.
300 TI-llCK CUT-OFF WALLS 300 TI-llCK CUT-OFF WALLS
AS DETAILED IN SECTION C-C AS DETAILED IN SECTION C-C
LIMIT OF
EXCAVATION

FLOW
R.C COVER 300 TI-llCK CUT-OFF WALLS 300 TI-llCK CUT-OFF WALLS
AS DETAILED IN SECTION C-C AS DETAILED IN SECTION C-C
SLAB (C-40)
LIMIT OF
EXCAVATION

FLOW
LATERAL
CONNECTION

BUTT FUSION
WELDING LATERAL LATERAL
CONNECTION CONNECTION

Flow PIPE
COUPLING

ANCHOR BLOCK
Ø32mm HOLES

100mm CONCRETE
BLINDING (C-20)

REFERENCE DRAWINGS AND DOCUMENTS

MH SHAFT

BUTT FUSION
WELDING 300 TI-llCK CUT-OFF WALLS 300 TI-llCK CUT-OFF WALLS
AS DETAILED IN SECTION C-C AS DETAILED IN SECTION C-C
300 THICK CONCRETE C20
CUT-OFF WALLS PROTECTED LIMIT OF EXCAVATION LIMIT OF
WITH BITUMINUS PAINT PIPE EXCAVATION

ANCHOR BLOCK

Ø32mm HOLES
COUPLING BUTT FUSION
WELDING
100mm CONCRETE
No. REVISION-2 APP'D 2021
BLINDING (C-20) CLIENT
Flow
PIPE PIPE
LATERAL
CONNECTION

TITLE
STANDARD DRAWINGS
MH MH SHAFT
SHAFT
STORM WATER WORKS
COUPLING
DRAWING TITLE
300 TI-llCK CONCRETE C20 CUT-OFF WALLS TO EXTEND TO
Cllr-OFF WALLS PROTECTED UNDI TURBED
WITH BITUMINUS PAINT GROUND OR TRENCE SUPPORT &
A LEVEL 300 ABOVE TOP OF PIPE G.A. OF HDPE MANHOLES
BED & SURROUND.
TIRENCH SUPPORT IN CONTACT
WITH CUT-OFF WALLS TO BE
(TYPE - I)
LEFT IN-SITIJ
ANCHOR BLOCK

Ø32mm HOLES
DRAWN - SCALE N.T.S
100mm CONCRETE
BLINDING (C-20) CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
224

THIRD EDITION - APRIL 2022


NOTES:

COVER SLAB DETAIL COVER SLAB DETAIL THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
FOR UNPAVED AREA FOR PAVED AREA MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
100 THK.PRE-CAST RECTANGULAR REINFORCED
COVER SLAB DETAIL COVER SLAB DETAIL REQUIREMENTS.
CONCRETE SEATING GRADE (C-40)
FOR UNPAVED AREA FOR PAVED AREA THEY ARE EXPECTED TO BE INCORPORATED AS TYPICAL
100 THK.PRE-CAST RECTANGULAR REINFORCED DETAILS WHICH SHALL BE CHECKED AND APPROVED AS
CONCRETE SEATING GRADE (C-40) PART OF THE PROJECT DRAWING SET.
R.C COVER
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
SLAB (C-40)
STATED.
R.C COVER 2. ALL CONCRETE TO BE C40 UNLESS OTHERWISE STATED.
LINER HDPE
SLAB (C-40) 3. IN PLACE WHERE MANHOLE DEPTHS EXCEED 7500,
MANHOLE SHALL BE DESIGNED BY CONTRACTOR ON
INDIVIDUAL BASIS.THE CONTRACTOR SHALL SUBMIT
95%COMPACTED LINER HDPE MANUFACTURER'S CALCULATIONS AND VERIFY THE
SOIL SATISFACTION OF STRUCTURAL REQUIREMENTS FOR THE
BUTT FUSION WELDING ENGINEER'S APPROVAL.
MH SHAFT 95%COMPACTED
(IF REQUIRED) SOIL 4. ALL EXTERNAL FACES OF CONCRETE BELOW GROUND
LEVEL TO BE COATED WITH COAL TAR EPOXY (MIN. 300
BUTT FUSION WELDING
MH SHAFT MICRONS).
(IF REQUIRED)
5. FOR STANDARD DETAILS REFER TO DRG NO.SWGN-STD-228.
6. FOR COVER AND ACCESS & MANHOLE BASE DETAILS
REFER TO DRG NO. SWGN-STD-229.
7. ALL PRECAST CONCRETE BASE UNITS SHALL INCORPORATE
SAFE LIFTING POINTS WHICH SHALL BE CLEARLY MARKED
8. STRUCTURAL INTEGRITY OF THE MANHOLES IS THE

RESPONSIBILITY OF THE DESIGNER.


9. MANHOLES TO BE PROVIDED WITH SAND TRAP 500MM DEEP


SUMP.
10. GROUND WATER TABLE SHALL BE VERIFIED AT SITE & THE
WEIGHT OF THE MANHOLE BASE (CONCRETE WORK) SHALL
BE PROPORTIONATE TO RESIST UPLIFT.

EXTRUSION MANHOLE SHAFT DN BASE DN


MANHOLE NOMINAL PIPE DEPTH (m)
(mm) (mm)
WELDING TYPE DIAMETER (DN)
(mm)
RC REDUCER (H) (D2) (D1)
EXTRUSION
SLAB (C-40) WELDING II-A 400 - 500 4 to 7.5 1200 1500
II-B 600 - 900 4 to 7.5 1200 1800
LINER HDPE RC REDUCER
SLAB (C-40) II-C 1000 - 1200 4 to 7.5 1200 2200

LINER HDPE
2500

SS 316 DETACHABLE MH SHAFT


SS 316 EYE SS 316 DETACHABLE
SAFETY CHAIN WITH
BLOT SAFETY CHAIN WITH D D
SWIVEL EYE & SNAP HOOK

2500
ANCHORED AT SWIVEL EYE & SNAP HOOK MH SHAFT
TO BE HOOKED AT THE BUTT FUSION
WALL TO BE HOOKED AT THE
WALL1050 HIGH,600 SS 316 EYE
WALL1050 HIGH,600
APART BLOT
APART
ANCHORED AT
WALL
PIPE

PIPE
PIPE

PIPE

ANCHOR BLOCK
CONCRETE (C-40) COUPLING
Ø32mm HOLES
ANCHOR BLOCK
CONCRETE (C-40)
Ø32mm HOLES
100mm REFERENCE DRAWINGS AND DOCUMENTS
CONCRETE
BLINDING (C-20)
100mm
CONCRETE
SECTION C - C BLINDING (C-20)
straight through

SS 316 DETACHABLE
SAFETY CHAIN WITH
SWIVEL EYE & SNAP HOOK
TO BE HOOKED AT THE CUT-OFF WALLS TO EXTEND TO UNDISTURBED
WALL1050 HIGH,600 MH GROUND OR TRENCE SUPPORT & A LEVEL 300
APART SHAFT ABOVE TOP OF PIPE BED & SURROUND.
LIMIT OF TRENCH SUPPORT IN CONTACT WITH CUT-OFF
EXCAVATION WALLS TO BE LEFT IN-SITU
EXTRUSION
WELDING

300 THICK CONCRETE C20


CUT-OFF WALLS PROTECTED No. REVISION-2 APP'D 2021
JOINT TO BE WITH BITUMINUS PAINT
SS 316 EYE
EXTRUSION SS 316 EYE BLOT
CLIENT
BLOT WELDING ANCHORED AT THE WALL
ANCHORED AT
WALL BUTT
FUSION
WELDING
NOTE:-
C C TITLE
WHERE INCOMING AND OUTGOING
PIPE DIAMETER DIFFER A TAPERED
STANDARD DRAWINGS
PIPE
CHANNEL TO BE USED
STORM WATER WORKS
SS 316 DETACHABLE DRAWING TITLE
COUPLING SAFETY CHAIN WITH
COUPLING
SWIVEL EYE & SNAP HOOK
TO BE HOOKED AT THE G.A. OF HDPE DEEP MANHOLES (TYPE II ) (1-2)
WALL1050 HIGH,600
APART

DRAWN - SCALE N.T.S


CHECKED - DATE -
SECTION D - D APPROVED - SIZE A1
PROJECT DWG.
No. - No.
225

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
COVER SLAB DETAIL COVER SLAB DETAIL MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
FOR UNPAVED AREA FOR PAVED AREA COVER SLAB DETAIL COVER SLAB DETAIL
FOR UNPAVED AREA FOR PAVED AREA REQUIREMENTS.
100 THK.PRE-CAST RECTANGULAR REINFORCED
100 THK.PRE-CAST RECTANGULAR REINFORCED THEY ARE EXPECTED TO BE INCORPORATED AS TYPICAL
CONCRETE SEATING GRADE (C-40)
CONCRETE SEATING GRADE (C-40) DETAILS WHICH SHALL BE CHECKED AND APPROVED AS
PART OF THE PROJECT DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
R.C COVER
R.C COVER STATED.
SLAB (C-40)
SLAB (C-40) 2. ALL CONCRETE TO BE C40 UNLESS OTHERWISE STATED.
3. IN PLACE WHERE MANHOLE DEPTHS EXCEED 7500,
LINER HDPE MANHOLE SHALL BE DESIGNED BY CONTRACTOR ON
LINER HDPE INDIVIDUAL BASIS.THE CONTRACTOR SHALL SUBMIT
MANUFACTURER'S CALCULATIONS AND VERIFY THE
95%COMPACTED SATISFACTION OF STRUCTURAL REQUIREMENTS FOR THE
SOIL 95%COMPACTED
SOIL ENGINEER'S APPROVAL.
BUTT FUSION WELDING 4. ALL EXTERNAL FACES OF CONCRETE BELOW GROUND
MH SHAFT BUTT FUSION WELDING
(IF REQUIRED) MH SHAFT LEVEL TO BE COATED WITH COAL TAR EPOXY (MIN. 300
(IF REQUIRED)
MICRONS).
5. FOR STANDARD DETAILS REFER TO DRG NO.SWGN-STD-228.
6. FOR COVER AND ACCESS & MANHOLE BASE DETAILS
REFER TO DRG NO. SWGN-STD-229.
7. ALL PRECAST CONCRETE BASE UNITS SHALL INCORPORATE
SAFE LIFTING POINTS WHICH SHALL BE CLEARLY MARKED
8. STRUCTURAL INTEGRITY OF THE MANHOLES IS THE
RESPONSIBILITY OF THE DESIGNER.


9. MANHOLES TO BE PROVIDED WITH SAND TRAP 500MM DEEP
SUMP.
10. GROUND WATER TABLE SHALL BE VERIFIED AT SITE & THE
WEIGHT OF THE MANHOLE BASE (CONCRETE WORK) SHALL
BE PROPORTIONATE TO RESIST UPLIFT.

MANHOLE SHAFT DN BASE DN


MANHOLE NOMINAL PIPE DEPTH (m)
EXTRUSION (mm) (mm)
TYPE DIAMETER (DN)
WELDING EXTRUSION (mm)
WELDING (H) (D2) (D1)
RC REDUCER II-A 400 - 500 4 to 7.5 1200 1500
SLAB (C-40) RC REDUCER
SLAB (C-40) II-B 600 - 900 4 to 7.5 1200 1800
LINER HDPE II-C 1000 - 1200 4 to 7.5 1200 2200
LINER HDPE

SS 316 DETACHABLE F F SS 316 DETACHABLE


SAFETY CHAIN WITH WHERE DISTANCE BETWEEN TOP OF
SAFETY CHAIN WITH H H
MH SHAFT BENCHING & SOFFIT OF COVER SLAB
SWIVEL EYE & SNAP HOOK EXCEEDS 1500 GRP HANDRAILING & SAFETY SWIVEL EYE & SNAP HOOK MH SHAFT
TO BE HOOKED AT THE SS 316 EYE CHAINS TO BE LOCATED IN MANHOLES AS IN TO BE HOOKED AT THE
BLOT STANDARD BASE IN LIEU OF 550 HIGH SS 316 EYE
WALL1050 HIGH,600 STANCHIONS WALL1050 HIGH,600
ANCHORED AT BLOT
APART APART
WALL ANCHORED AT
IF LESS THAN 1.2m THE COVER DIAMETER TO BE WALL
INCREASE SO THAT ONE MAN WORK
IN THE VOID

PIPE
PIPE PIPE
PIPE
PIPE
PIPE

COUPLING
COUPLING
ANCHOR BLOCK
CONCRETE (C-40) ANCHOR BLOCK
Ø32mm HOLES CONCRETE (C-40)
Ø32mm HOLES

REFERENCE DRAWINGS AND DOCUMENTS


100mm
CONCRETE 100mm
BLINDING (C-20) CONCRETE
SECTION E - E BLINDING (C-20)
SECTION G - G
straight through

CUT-OFF WALLS TO EXTEND TO UNDISTURBED CUT-OFF WALLS TO EXTEND TO UNDISTURBED


LIMIT OF GROUND OR TRENCE SUPPORT & A LEVEL 300 GROUND OR TRENCE SUPPORT & A LEVEL 300
EXCAVATION ABOVE TOP OF PIPE BED & SURROUND. ABOVE TOP OF PIPE BED & SURROUND.
TRENCH SUPPORT IN CONTACT WITH CUT-OFF LIMIT OF TRENCH SUPPORT IN CONTACT WITH CUT-OFF
WALLS TO BE LEFT IN-SITU EXCAVATION WALLS TO BE LEFT IN-SITU

300 THICK CONCRETE C20


CUT-OFF WALLS PROTECTED
JOINT TO BE WITH BITUMINUS PAINT 300 THICK CONCRETE C20
CUT-OFF WALLS PROTECTED No. REVISION-2 APP'D 2021
EXTRUSION SS 316 EYE BLOT
WITH BITUMINUS PAINT
WELDING ANCHORED AT THE WALL JOINT TO BE CLIENT
BUTT FUSION EXTRUSION SS 316 EYE BLOT
WELDING WELDING ANCHORED AT THE WALL

G G TITLE
STANDARD DRAWINGS
PIPE

PIPE STORM WATER WORKS


COUPLING SS 316 DETACHABLE
SAFETY CHAIN WITH
DRAWING TITLE
SWIVEL EYE & SNAP HOOK SS 316 DETACHABLE
COUPLING SAFETY CHAIN WITH G.A. OF HDPE DEEP MANHOLES (TYPE II ) (2-2)
TO BE HOOKED AT THE
WALL1050 HIGH,600 SWIVEL EYE & SNAP HOOK
APART TO BE HOOKED AT THE
WALL1050 HIGH,600
APART

SECTION F - F DRAWN - SCALE N.T.S


(STRAIGHT THROUGH)
SECTION H - H CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
226

THIRD EDITION - APRIL 2022


COVER SLAB DETAILCOVER SLAB
NOTES:
FOR UNPAVED DETAIL COVER SLAB DETAILCOVER SLAB COVER SLAB DETAILCOVER SLAB
AREA FOR PAVED AREA FOR UNPAVED DETAIL FOR UNPAVED DETAIL THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
AREA FOR PAVED AREA AREA FOR PAVED AREA MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
R.C COVER REQUIREMENTS.
SLAB R.C COVER R.C COVER THEY ARE EXPECTED TO BE INCORPORATED AS TYPICAL
(C-40) SLAB SLAB
(C-40) DETAILS WHICH SHALL BE CHECKED AND APPROVED AS
C

(C-40)
PART OF THE PROJECT DRAWING SET.

C
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
STATED.
2. ALL CONCRETE TO BE C40 UNLESS OTHERWISE STATED.
95%COMPACTED
SOIL 95%COMPACTED 95%COMPACTED
3. IN PLACE WHERE MANHOLE DEPTHS EXCEED 7500,
SOIL SOIL MANHOLE SHALL BE DESIGNED BY CONTRACTOR ON
INDIVIDUAL BASIS.THE CONTRACTOR SHALL SUBMIT
SS 316 DETACHABLE B MANUFACTURER'S CALCULATIONS AND VERIFY THE
B SS 316 DETACHABLE D
SAFETY CHAIN WITH
MH SHAFT
D SS 316 DETACHABLE F F SATISFACTION OF STRUCTURAL REQUIREMENTS FOR THE
SWIVEL EYE & SNAP HOOK SAFETY CHAIN WITH SAFETY CHAIN WITH
SS 316 EYE SWIVEL EYE & SNAP HOOK
MH SHAFT MH SHAFT ENGINEER'S APPROVAL.
TO BE HOOKED AT THE SWIVEL EYE & SNAP HOOK
BLOT TO BE HOOKED AT THE SS 316 EYE BLOT SS 316 EYE 4. ALL EXTERNAL FACES OF CONCRETE BELOW GROUND
WALL1050 HIGH,600 TO BE HOOKED AT THE
ANCHORED AT WALL1050 HIGH,600 ANCHORED AT WALL
APART WALL1050 HIGH,600 BLOT LEVEL TO BE COATED WITH COAL TAR EPOXY (MIN. 300
WALL APART APART ANCHORED AT
WALL
BUTT FUSION MICRONS).
WELDING 5. FOR STANDARD DETAILS REFER TO DRG NO.SWGN-STD-228.
6. FOR COVER AND ACCESS & MANHOLE BASE DETAILS
PIPE
PIPE PIPE REFER TO DRG NO. SWGN-STD-229.
PIPE PIPE PIPE
7. ALL PRECAST CONCRETE BASE UNITS SHALL INCORPORATE
PIPE
PIPE SAFE LIFTING POINTS WHICH SHALL BE CLEARLY MARKED
8. STRUCTURAL INTEGRITY OF THE MANHOLES IS THE
RESPONSIBILITY OF THE DESIGNER.
COUPLING
COUPLING COUPLING
9. MANHOLES TO BE PROVIDED WITH SAND TRAP 500MM DEEP
ANCHOR BLOCK SUMP.
CONCRETE (C-40) ANCHOR BLOCK ANCHOR BLOCK 10. GROUND WATER TABLE SHALL BE VERIFIED AT SITE & THE
B

Ø32mm HOLES CONCRETE (C-40)


CONCRETE (C-40)

B
Ø32mm HOLES

B
Ø32mm HOLES WEIGHT OF THE MANHOLE BASE (CONCRETE WORK) SHALL
BE PROPORTIONATE TO RESIST UPLIFT.
100mm
CONCRETE 100mm 100mm
BLINDING (C-20) CONCRETE CONCRETE
BLINDING (C-20) BLINDING (C-20)
SECTION A - A (SHALLOW MANHOLE)
SECTION C - C (SHALLOW MANHOLE) MANHOLE SHAFT DN
MANHOLE NOMINAL PIPE DEPTH (m)
BASE DN
FOR MANHOLES WHERE DEPTH (mm) (mm)
TYPE DIAMETER (DN)
FROM SOFFIT OF ROOF SLAB TO SOFFIT FOR MANHOLES WHERE DEPTH
FROM SOFFIT OF ROOF SLAB TO SOFFIT
straight through (mm)
OF PIPE IS LESS THAN 2.5m (H) (D2) (D1)
OF PIPE IS LESS THAN 2.5m
FOR MANHOLES WHERE DEPTH II-A 400 - 500 4 to 7.5 1200 1500
FROM SOFFIT OF ROOF SLAB TO SOFFIT
OF PIPE IS LESS THAN 2.5m II-B 600 - 900 4 to 7.5 1200 1800
CUT-OFF WALLS TO EXTEND TO II-C 1000 - 1200 4 to 7.5 1200 2200
CUT-OFF WALLS TO EXTEND TO UNDISTURBED
UNDISTURBED GROUND OR TRENCE SUPPORT & A LEVEL
GROUND OR TRENCE SUPPORT & A LEVEL 300
ABOVE TOP OF PIPE BED & SURROUND. LIMIT OF
LIMIT OF 300 LIMIT OF EXCAVATION
ABOVE TOP OF PIPE BED & SURROUND. TRENCH SUPPORT IN CONTACT WITH
EXCAVATION EXCAVATION
TRENCH SUPPORT IN CONTACT WITH CUT-OFF
CUT-OFF WALLS TO BE LEFT IN-SITU
WALLS TO BE LEFT IN-SITU

300 THICK CONCRETE C20


CUT-OFF WALLS PROTECTED 300 THICK CONCRETE C20 300 THICK CONCRETE C20
JOINT TO BE WITH BITUMINUS PAINT CUT-OFF WALLS PROTECTED CUT-OFF WALLS PROTECTED
EXTRUSION SS 316 EYE BLOT WITH BITUMINUS PAINT JOINT TO BE WITH BITUMINUS PAINT
JOINT TO BE
WELDING ANCHORED AT THE WALL EXTRUSION SS 316 EYE BLOT EXTRUSION SS 316 EYE BLOT
WELDING ANCHORED AT THE WALL WELDING ANCHORED AT THE WALL
BUTT FUSION
WELDING

PIPE Flow

PIPE PIPE
SS 316 DETACHABLE
COUPLING SAFETY CHAIN WITH
SWIVEL EYE & SNAP HOOK COUPLING SS 316 DETACHABLE
SS 316 DETACHABLE
TO BE HOOKED AT THE COUPLING SAFETY CHAIN WITH
SAFETY CHAIN WITH
WALL1050 HIGH,600
SWIVEL EYE & SNAP HOOK SWIVEL EYE & SNAP HOOK REFERENCE DRAWINGS AND DOCUMENTS
APART TO BE HOOKED AT THE
TO BE HOOKED AT THE
WALL1050 HIGH,600 WALL1050 HIGH,600
APART APART

COVER SLAB DETAIL COVER SLAB DETAIL SECTION D - D SECTION F - F


FOR UNPAVED AREA FOR PAVED AREA (STRAIGHT THROUGH)

SS 316 DETACHABLE
SAFETY CHAIN WITH
R.C COVER
SWIVEL EYE & SNAP HOOK
SLAB (C-40)
TO BE HOOKED AT THE
WALL1050 HIGH,600 MH
C

APART SHAFT

EXTRUSION
WELDING
95%COMPACTED No. REVISION-2 APP'D 2021
SOIL
CLIENT

SS 316 DETACHABLE H H SS 316 EYE


SAFETY CHAIN WITH G G
MH SHAFT BLOT
SWIVEL EYE & SNAP HOOK
TO BE HOOKED AT THE SS 316 EYE ANCHORED AT
WALL1050 HIGH,600 BLOT WALL BUTT
ANCHORED AT TITLE
APART
WALL
BUTT FUSION
WELDING
FUSION
WELDING
STANDARD DRAWINGS
NOTE:-
WHERE INCOMING AND OUTGOING
STORM WATER WORKS
PIPE DIAMETER DIFFER A TAPERED
PIPE CHANNEL TO BE USED DRAWING TITLE
PIPE
G.A. OF HDPE SHALLOW MANHOLES (TYPE II )
COUPLING

ANCHOR BLOCK
CONCRETE (C-40)
B

Ø32mm HOLES

100mm DRAWN - SCALE N.T.S


CONCRETE
BLINDING (C-20) SECTION H - H CHECKED - DATE -
FOR MANHOLES WHERE DEPTH SECTION G - G (SHALLOW MANHOLE) (90° BEND)
APPROVED - SIZE A1
FROM SOFFIT OF ROOF SLAB TO SOFFIT
OF PIPE IS LESS THAN 2.5m
90° Bend PROJECT DWG.
No. - No.
227

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENTS A MINIMUM REQUIREMENT
BUT MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT
PROJECT REQUIREMENTS, THEY ARE EXPECTED TO BE
INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
CHECKED AND APPROVED AS PART OF THE PROJECT
DRAWING SET.
R.C COVER EPOXY COATING (2 x 150mm) LINER HDPE 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
SLAB (C-40) MIN.1.5mm THICK. STATED.
WITH 50mm UV COAT
2. ALL CONCRETE TO BE C40 UNLESS OTHERWISE STATED.
BENTONITE RAPID 3. IN PLACE WHERE MANHOLE DEPTHS EXCEED 7500,
SWELLING BAR MANHOLE SHALL BE DESIGNED BY CONTRACTOR ON
(MIN. W : 25 x H : 20) INDIVIDUAL BASIS.THE CONTRACTOR SHALL SUBMIT

200
100 MANUFACTURER'S CALCULATIONS AND VERIFY THE
SATISFACTION OF STRUCTURAL REQUIREMENTS FOR THE
ENGINEER'S APPROVAL.

250
75
4. MANHOLES/CHAMBERS ARE TO BE WATERTIGHT.
LINER HDPE 5. ALL EXTERNAL FACES OF CONCRETE BELOW GROUND
CONCRETE LEVEL TO BE COATED WITH COAL TAR EPOXY (MIN. 300
EXTRUSION WELDING
BLINDING (C-20) MICRONS).
MIN.95% MDD 6. STRUCTURAL INTEGRITY OF THE MANHOLES IS THE

50
RESPONSIBILITY OF THE DESIGNER.
COMPACTED SOIL Ø50 POLYSTYRENE EXTRUSION WELDING
7. GROUND WATER TABLE SHALL BE VERIFIED AT SITE & THE
HDPE SEALING BACKING ROD WEIGHT OF THE MANHOLE BASE (CONCRETE WORK) SHALL
LINER HDPE
RING min.10mm BITUMINOUS 100mm x 100mm WIDE BE PROPORTIONATE TO RESIST UPLIFT.

WATER SWEU.ING BAR MH SHAFT MASTIC SEALANT THICK.2mm


( e.g.Bentonite strip) TROWELLABLE GRADE

SHAFT WALL
COAL TAR EPOXY
COATING (300mm) 400 WIDE
REDUCER SLAB LINER (HDPE 2mm thk.)
EXTRUSION WELDING
( C-40 )
EXTRUSION WELDING
HDPE LINER
BENTONITE RAPID 10 WIDTH 400mm,
100

SWELLING BAR THICK. 2mm


300

(MIN. W : 25 x H : 20)
200

100

100
25
75

CONCRETE

200
BITUMINOUS 2t+10
BLINDING (C-20)
BASE WALL MASTIC SEALANT
MIN.95% MDD TROWELLABLE
COMPACTED SOIL

50
GRADE

100
REFERENCE DRAWINGS AND DOCUMENTS
HDPE SEALING
RING min.10mm

MH SHAFT COUPLING EXTRUSION


WELDING No. REVISION-2 APP'D 2021
RUBBER RING
CLIENT
HDPE
PIPE MANHOLE

BUTT FUSION
WELDING TITLE
STANDARD DRAWINGS
STORM WATER WORKS
DN

DRAWING TITLE

STANDARD DETAILS - A, AB, B & C


MH SHAFT

DRAWN - SCALE N.T.S


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
228

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENTS A MINIMUM REQUIREMENT
BUT MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT
CASE 1 PROJECT REQUIREMENTS, THEY ARE EXPECTED TO BE
INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
COVER SLAB DETAIL COVER SLAB DETAIL CHECKED AND APPROVED AS PART OF THE PROJECT
FOR PAVED AREA FOR UNPAVED AREA DRAWING SET.
100THK .PRE-CAST RECTANGULAR REINFORCED 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
(CASE-3) STATED.
CONCRETE SEATING GRADE (C-40)
FINISHED LEVEL OF 2. THIS DRAWING TO BE READ IN CONJUNCTION WITH
MANHOLE AND CHAMBER DRAWINGS..
ROAD OR PAVED AREA (FGL) 3. IN PLACE WHERE MANHOLE DEPTHS EXCEED 7500,
MANHOLE SHALL BE DESIGNED BY CONTRACTOR ON
R.C COVER INDIVIDUAL BASIS.THE CONTRACTOR SHALL SUBMIT
SLAB (C-40) MANUFACTURER'S CALCULATIONS AND VERIFY THE
SATISFACTION OF STRUCTURAL REQUIREMENTS FOR THE
ENGINEER'S APPROVAL.
LINER HDPE 4. ALL CONCRETE TO BE C40 UNLESS OTHERWISE STATED.
R.C COVER 5. MANHOLES TO BE PROVIDED WITH SAND TRAP 500MM DEEP
95%COMPACTED SLAB (C-40) 100THK .PRE-CAST RECTANGULAR SUMP.
SOIL REINFORCED CONCRETE SEATING 6. GROUND WATER TABLE SHALL BE VERIFIED AT SITE & THE
GRADE (C-40) WEIGHT OF THE MANHOLE BASE (CONCRETE WORK) SHALL
BE PROPORTIONATE TO RESIST UPLIFT.
MH SHAFT
GROUND TYPE DETAIL (CASE No.)
750 Ø WATERTIGHT SINGLE PIECE
UNPAVED AREA CASE 1 COVER & FRAME CLASS D400, C250 OR
B125 AS DIRECTED BY THE ENGINEER
EXISTING UNPAVED ROAD CASE 2 WITH HDPE SEALING PLATE TO SUIT
DIA CLEAR OPENING
EXISTING PAVED ROAD CASE 3

R.C COVER
SLAB (C-40)

95%COMPACTED LINER
SOIL HDPE

95%COMPACTED SELECTED BACKFILL MATERIAL


SOIL COMPACTED IN MAXIMUM
MH SHAFT
THICKNESS LAYERS OF 300 TO
GIVE 90% RELATIVE MOD

REFERENCE DRAWINGS AND DOCUMENTS

CHAMBER WALL
(HDPE PROFILED,TWIN
WALLED)
DETAILS OF (B, P, W)
ANCHOR BLOCK
ANTI-FLOATION ANCHOR BLOCK DETAILS
Manhole
Manhole Base Plate No of Anchor Block Anchor Block Min. Internal No. REVISION-2 APP'D 2021
Wall HDPE CASION
DN - ID Thickness Stiffenrs Projection Depth "B" Benching
Thickness CLIENT
(mm) (mm) Type-B "P"(mm) (mm) Depth(mm)
"W" (mm) Ø32mm HOLES
1000 ≥36.0 - S 20 4 400 Will be provided 300
based on DN, HDPE STIFFENER
1100 ≥36.0 - S 20 4 400 W.T.,Manhole 300
EXTRUSION WELDING TITLE
1200 ≥36.0 - S 20 8 400 Depth 300
STANDARD DRAWINGS
CONCRETE (C-40) (OD+20) x 20thk.
STORM WATER WORKS
HDPE PLATE
DRAWING TITLE
100mm CONCRETE
BLINDING (C-20) 16mmØ HDPE
COMPACTION COVER DETAILS FOR HDPE
95Ø OF MDD
4mm WATER STEEL BARS STIFFENER MANHOLES + MANHOLE BASE
PROOFING TYPICAL DETAILS
MEMBRANE

DRAWN - SCALE N.T.S


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
229

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS.
THEY ARE EXPECTED TO BE INCORPORATED AS TYPICAL
DETAILS WHICH SHALL BE CHECKED AND APPROVED AS
PART OF THE PROJECT DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
STATED.
2. ALL CONCRETE TO BE C40 UNLESS OTHERWISE STATED.
RUNG
3. MANHOLES ARE TO BE WATERTIGHT.
4. MANHOLES TO BE PROVIDED WITH SAND TRAP 500mm DEEP
SUMP.
5. DEWATERING OPERATIONS SHALL BE PROVIDED DURING
PRECAST CONCRETE MANHOLE CONSTRUCTION AND MAY ONLY BE TERMINATED AFTER
SAFETY MANHOLE STEPS COVER HAS BEEN INSTALLED.
6. PORT CONFIGURATION MUST MATCH ALL CONNECTING
INCOMING AND OUTGOING PIPE LINE.
7. GROUND WATER TABLE SHALL BE VERIFIED AT SITE & THE
LOCATE MANHOLE FRAME WEIGHT OF THE MANHOLE SHALL BE PROPORTIONATE TO
AND COVER ON UPSTREAM RESIST UPLIFT.
SIDE OF MANHOLE
8. MANUFACTURER TO SUBMIT CLASS AND DIMENSIONS OF
RAIL COVER ACCORDING TO SPECIFICATIONS BASED ON

30 cm O.C.
Variable
ROUND BAR ACTUAL SITE CONDITIONS & TO BE APPROVED PRIOR TO
MANUFACTURING.

A A

5 cm
MANHOLE FRAME PROVIDE 5cm MINIMUM PENETRATION
AND COVER INTO MANHOLE BASE. PROVIDE MEANS
TO SECURELY ANCHOR INTO MANHOLE
BASE AND BOLT LADDER TO SIDE OF
MANHOLE

SECTION B-B

PLAN AT COVER LEVEL


MANHOLE FRAME & COVER
SET FLUSH WITH ASPHALT
OR CONCRETE 33 cm
FINISHED GRADE

FIRST STEP 35 - 60 cm

SAFETY MANHOLE STEPS Variable

REFERENCE DRAWINGS AND DOCUMENTS


COMPACTED TRENCH
BACKFILL

FULL CONTINUOUS MORTAR PLAN AT MANHOLE STEPS


JOINT, RUBBER GASKET OR
APPROVED EQUAL

PRECAST CONCRETE
MANHOLE
Variable

36 cm

WATERTIGHT MANHOLE
ADAPTOR (TYP.)
B B
No. REVISION-2 APP'D 2021
CLIENT
ELEVATION AT MANHOLE STEPS

TITLE
GRP LADDER AND MANHOLE STEPS STANDARD DRAWINGS
FOUNDATION GRAVEL
C40 Concrete Fill
STORM WATER WORKS
*

DRAWING TITLE
DISTURBED EARTH

PRECAST CONCRETE MANHOLE


SECTION A-A & GRP LADDER
* MAY VARY DEPENDING ON ANTI-FLOATATION
REQUIREMENT BASED ON SITE WATER TABLE.

DRAWN - SCALE N.T.S


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
230

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS.
THEY ARE EXPECTED TO BE INCORPORATED AS TYPICAL
1000
DETAILS WHICH SHALL BE CHECKED AND APPROVED AS
150 150 LIFTING EYE PART OF THE PROJECT DRAWING SET.
A

80
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
700 STATED.
TOP OF ASPHALT LEVEL
2. ALL CONCRETE TO BE C40 UNLESS OTHERWISE STATED.
3. DEWATERING OPERATIONS SHALL BE PROVIDED DURING
CONSTRUCTION AND MAY ONLY BE TERMINATED AFTER

KERB
COVER HAS BEEN INSTALLED.
4. GROUND WATER TABLE SHALL BE VERIFIED AT SITE & THE

ROAD
700 WEIGHT OF THE CATCH BASIN CONCRETE PAD SHALL BE
PROPORTIONATE TO RESIST UPLIFT.
5. ALL EXTERNAL FACES OF CONCRETE BELOW GROUND TO
BE TANKED.

100
PRECAST CONCRETE 6. ALL INTERNAL FACES OF CONCRETE TO BE COATED WITH
CATCH BASIN

DEPTH VARIES
EPOXY COATING AS SPECIFIED.
7. MANUFACTURER TO SUBMIT CLASS AND DIMENSIONS OF
COVER ACCORDING TO SPECIFICATIONS BASED ON
ACTUAL SITE CONDITIONS & TO BE APPROVED PRIOR TO
STEP IRON AS SPECIFIED MANUFACTURING.
8. APPROPRIATE SIZING AND LOCATION OF LIFTING DEVICES

800
SHALL BE THE RESPONSIBILITY OF THE FABRICATOR.
9. CONTRACTOR TO SUPPLY AND INSTALL ALL PIPING AND
B B GROUT ALL PIPES IN FIELD

INVERT
OF PIPE

ROAD
KERB

500
BASE
150mm CONCRETE PAD

200
1000

PLAN SECTION A-A

800 TOP SECTION


REFERENCE DRAWINGS AND DOCUMENTS
600 700
TOP OF KERB FINISHED LEVEL COVER FRAME 300
1000 1000

TOP OF ROAD PAVEMENT

LOCALIZED PAVEMENT
DEPRESSION IN FRONT OF TOP
OPENING OF CATCH BASIN (TYP)

LOWER SECTION No. REVISION-2 APP'D 2021


STEP IRON AS SPECIFIED
CLIENT

700

1000 1000 TITLE


PRECAST CONCRETE STANDARD DRAWINGS
CATCH BASIN
STORM WATER WORKS
200 600 200
1000 DRAWING TITLE

BASE SECTION 200 PRECAST CONCRETE CATCH BASIN

SECTION B-B
1000 1000 DRAWN - SCALE N.T.S
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
231

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS.
THEY ARE EXPECTED TO BE INCORPORATED AS TYPICAL
1000 DETAILS WHICH SHALL BE CHECKED AND APPROVED AS
PART OF THE PROJECT DRAWING SET.
150 150 LIFTING EYE
A 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE

80
STATED.
700 2. ALL CONCRETE TO BE C40 UNLESS OTHERWISE STATED.
TOP OF KERB LEVEL
3. DEWATERING OPERATIONS SHALL BE PROVIDED DURING
TOP OF PAVEMENT CONSTRUCTION AND MAY ONLY BE TERMINATED AFTER
FRL AT KERB COVER HAS BEEN INSTALLED.

KERB
4. GROUND WATER TABLE SHALL BE VERIFIED AT SITE & THE
WEIGHT OF THE CATCH BASIN CONCRETE PAD SHALL BE

ROAD
700 PROPORTIONATE TO RESIST UPLIFT.

120
5. ALL EXTERNAL FACES OF CONCRETE BELOW GROUND TO

50
BE TANKED.
6. ALL INTERNAL FACES OF CONCRETE TO BE COATED WITH
150 PRECAST CONCRETE EPOXY COATING AS SPECIFIED.
CATCH BASIN 7. MANUFACTURER TO SUBMIT CLASS AND DIMENSIONS OF
COVER ACCORDING TO SPECIFICATIONS BASED ON

DEPTH VARIES
ACTUAL SITE CONDITIONS & TO BE APPROVED PRIOR TO

600 KERB OPENING


MANUFACTURING.
STEP IRON AS SPECIFIED 8. APPROPRIATE SIZING AND LOCATION OF LIFTING DEVICES
SHALL BE THE RESPONSIBILITY OF THE FABRICATOR.
800

9. CONTRACTOR TO SUPPLY AND INSTALL ALL PIPING AND


B B GROUT ALL PIPES IN FIELD

INVERT
OF PIPE

ROAD
KERB

500
BASE

200
1000

PLAN SECTION A-A 150mm CONCRETE PAD

TOP SECTION
85 1000
REFERENCE DRAWINGS AND DOCUMENTS
870 700
COVER FRAME KERB INLET GRATE
1000 1000
300
N ING
OPE

TOP OF ROAD PAVEMENT

LOCALIZED PAVEMENT
DEPRESSION IN FRONT OF KERB
OPENING (TYP)

LOWER SECTION No. REVISION-2 APP'D 2021


STEP IRON AS SPECIFIED
CLIENT

700

1000 1000 TITLE


PRECAST CONCRETE CATCH STANDARD DRAWINGS
BASIN
STORM WATER WORKS
200 600 200
1000 DRAWING TITLE

PRECAST CONCRETE KERB OPENING


BASE SECTION 200
CATCH BASIN
SECTION B-B
1000 1000 DRAWN - SCALE N.T.S
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
232

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
Shaft Cover*
REQUIREMENTS. THEY ARE EXPECTED TO BE
COVER CLASS INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
CHECKED AND APPROVED AS PART OF THE PROJECT
INSPECTION SHAFT COVER B OR D SHAFT COVER DRAWING SET.

EMERGENCY OVERFLOW SHAFT COVER B, C OR D GUTTER COVER 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS
OTHERWISE INDICATED.
3. SHOWN DETAILS ARE TYPICAL. CONTRACTOR TO REFER
Gully Gutter Gully Gutter TO MANUFACTURER'S DETAILS & REQUIREMENTS FOR
Class B, C or D, CW 610 Class B, C or D, CW 610 PROJECT SPECIFIC INFORMATION & DETAILS.
Shaft Cover* Shaft Cover* 4. A 3 - 5% CBR HAS BEEN ASSUMED AT SUB-BASE LEVEL
ground level Support ring acc. to ground level Support ring acc. to
surface level DIN 4034 surface level DIN 4034 SHOULD THE CBR BE TESTED AND FOUND TO BE LESS
Max. filling level Max. filling level THAN 3% THEN THE ENGINEER SHALL BE NOTIFIED.
ALSO, ANY SOFT SPOTS FOUND AT SUB-BASE LEVEL
SHALL BE REPORTED TO THE ENGINEER.

hD*

hD*
5. INLET/OUTLET PIPES MUST BE SUPPORTED WITH
CONCRETE TO PROTECT IT DURING BACKFILLING.
1 1 6. THE CONTRACTOR SHALL PROHIBIT THE MOVEMENT OF

LExt.

LExt.
CONSTRUCTION PLANT ACROSS THE STORAGE TANK
3 3 AND WHERE NECESSARY PROVIDE ADDITIONAL
2 SUPPORT AND PROTECTION TO THE STRUCTURE.
2 top edge top edge PARTICULARLY POST CONSTRUCTION. TEMPORARY
FENCING CAN BE USED TO PROHIBIT TRADE STOCKS,
PILLING MATERIALS, HEAVY PLANTS ETC.,
Block Height

Block Height
7. NO CONSTRUCTION MACHINERY IS TO TRANSVERSE THE
TANK ONCE IT IT IS INSTALLED WITHOUT CONTACTING
max. ground-water Max. ground-water THE TANK SUPPLIER AND MANUFACTURER IN ADVANCE
level level TO GET THEIR APPROVAL.

bottom edge QuadroControl KEY: bottom edge QuadroControl


Protection fleece Protection fleece
sealing ring sealing ring
Block Length 1 Block Length 1

2 Filter Set 2 sediment trap

Extension Extension
EMERGENCY OVERFLOW INLET DETAIL 3
pipe INSPECTION SHAFT DETAIL 3
pipe

0.03m
Throttle shaft
Outlet side wall lattice
Inlet

A B B

Outlet
2x45° bend QuadroControl
REFERENCE DRAWINGS AND DOCUMENTS

PLAN
PLAN

surface level

Gully Gutter
Concrete support ring Class B, C or D, CW 610
Shaft Cover*
to distribute the loads ground level Support ring acc. to
into the ground surface level DIN 4034
Max. filling
level
No. REVISION-2 APP'D 2021

hD*
2x45° bend CLIENT
Inlet 1

LExt.
3
2 top edge
TITLE
IL STANDARD DRAWINGS
STORM WATER WORKS
Throttle shaft max. ground-water DRAWING TITLE
IL level

Outlet Pipe
KEY: GEOCELLULAR TANK DETAILS
QuadroControl bottom edge
Outlet side wall lattice sealing ring
D Protection fleece 1
Block Length
2 Filter Set
SECTION A-A SECTION B-B DRAWN - SCALE N.T.S
Extension
3 CHECKED - DATE -
pipe
THROTTLE SHAFT + PIPE DETAIL INLET + OUTLET PIPE DETAIL
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
233

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
DIA + 300 AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
SELECTED BACKFILL MATERIAL APPROVED AS PART OF THE PROJECT DRAWING SET.
FREE FROM LARGE STONES ETC.
LIGHTLY COMPACTED BY HAND 1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS
IN 150 THICK LAYERS OTHERWISE STATED.
150 FOR D < 900 ANNULUS OF JOINT TO BE SEALED 2. JOINTING PIPES HOLLOWS LEFT IN THE BEDDING TO
3 3 275 FOR D > 900 BY APPROVED METHOD TO AVOID
INGRESS OF CONCRETE ENABLE PIPES TO BE JOINTED SHALL BE AS SHORT AS

OUTSIDE DIA
1 1
PRACTICABLE AND SHALL BE LEFT UNFILLED UNTIL THE

OF PIPE
JOINTS HAVE BEEN INSPECTED AND THE PIPE TESTED
CONCRETE CLASS C TO THE SATISFACTION OF THE ENGINEER.
MAXIMUM LENGTH OF PIPE SHALL 3. COVER TO PIPES COVER SHALL BE MEASURED FROM THE
H 1650

BE 3000
CROWN OF THE PIPE BARREL TO GROUND LEVEL.
150 FOR < D < 900 4. PROTECTION AGAINST ACCIDENTAL DAMAGE WHERE A
SELECTED BACKFILL MATERIAL
>

275 FOR D > 900


COMPACTED IN MAXIMUM THICKNESS PIPELINE IS LIKELY TO BE DISTURBED IN THE FUTURE BY
THE FIRST 500mm LAYERS OF 300 TO GIVE 90% RELATIVE MOD IF CONCRETE CAST AGAINST CONSTRUCTION WORK, INSTALLATION OF OTHER
OVER PERMENANT EXCAVATED TRENCH SIDES
POLYTHENE OF APPROVED SERVICES ETC. IT MAY ON THE ENGINEERS INSTRUCTION
WORK SELECTED BACKFILL MATERIAL BLINDING CONCRETE 13 FOR 100 < D < 300
.

GAUGE TO BE PLACED OUTSIDE DIA BE GIVEN A CONCRETE BED AND SURROUND.


FREE FROM LARGE STONES ETC. AS SEPARATING MEDIUM. FLEXIBLE JOINT 25 FOR 350 < D < 600
LIGHTLY COMPACTED BY HAND IN OF PIPE 38 FOR 700 < D < 1200 5. SUBKHA BUNDS WHERE PIPES ARE LAID WITHOUT
150 THICK LAYERS 150 FOR D < 900 50 FOR 1400 < D < 2000 ADEQUATE COVER IN AREAS WHICH ARE SCHEDULED FOR
275 FOR D > 900 FILLING, SUBHKA BUNDS SHALL BE CONSTRUCTED OVER
THE PIPE COMPACTED IN ACCORDANCE WITH THE
BED AND SURROUND AS SPECIFIED SPECIFICATION.
CONCRETE BED AND SURROUND PROTECTION DETAILS FOR GRP & PVC-U PIPES 6. TRENCH SHEET TO BE LIFTED BEFORE COMPLETION OF
PIPE ZONE MATERIAL BACKFILLING AND COMPACTION.
(TO BE USED UNDER BUNDS AND WHERE COVER TO CROWN OF PIPES IS LESS THAN 1.20 METRES 7. LAYING PIPES PIPES SHALL BE LAID TO THE DETAILS
AND WHERE SPECIFIED OR INSTRUCTED BY THE ENGINEER) SPECIFIED BY THE MANUFACTURER AS APPROVED BY THE
SCALE 1:40 ENGINEER. PIPE SHALL BE LAID IN DRY TRENCH.
8. PIPE BUILT INTO CONCRETE WHERE REQUIRED BY THE
SUPPLIER. A BAND OF NEOPRENE RUBBER OF 40 TO 70

PROTECTIVE BUND TO PIPELINE UNDER NON-PAVED AREAS SELECTED BACKFILL MATERIAL


COMPACTED IN MAXIMUM THICKNESS LAYERS OF 300
* WHEN THE PIPE IS PROTECTED WITH CONCRETE BED SURROUND
FLEXIBLE JOINT SHALL ALSO COVER THE TOP HALF OF THE PIPE
DUROMETER, 6mm THICK AND 150mm WIDE SHALL BE
WRAPPED AROUND THE PIPE PRIOR TO PLACEMENT OF
TO GIVE 90% RELATIVE MDD. TRENCHES UNDER ANY CONCRETE. THIS BAND SHALL BE POSITIONED
ROADS AND PAVED AREAS TO BE BACKFILLED 600mm WIDTH TANKING AROUND THE BUILT-IN SECTION OF THE PIPE WITH THE
APPLIED AROUND JOINT EDGE OF THE RUBBER AT THE INTERFACE BETWEEN
FGL
CONCRETE AND THE BACKFILL.
9. THE TERMS STABLE AND UNSTABLE ARE USED TO DEFINE
THE NATIVE SOIL TO THE BEDDING MATERIAL. NATIVE
150 WIDE SERVICE WARNING TAPE SELECTED BACKFILL MATERIAL SOILS SUCH AS ROCK AND SOME GRANULAR MATERIALS
300 TYP

PLACED 300 BELOW F.G.L. FREE FROM LARGE STONES ETC.


FOR PRESSURE PIPES ONLY LIGHTLY COMPACTED BY HAND * DUNE SAND PROVIDE A HIGH DEGREE OF SIDE SUPPORT AND THE
IN 150 THICK LAYERS MINIMUM TRENCH WIDTHS GIVEN UNDER THE HEADING
FULLY STABLE SHOULD BE ADOPTED.
UNDER NON-PAVED AREAS SELECTED BACKFILL MATERIAL IF CONCRETE CAST AGAINST 150 FOR D < 900
* MINIMUM TRENCH WIDTHS FOR GRP PIPE COMPACTED IN MAXIMUM THICKNESS LAYERS OF 300 275 FOR D > 900 10.NATIVE SOILS OF A COHESIVE NATURE WOULD
EXCAVATED TRENCH SIDES
TO GIVE 90% RELATIVE MDD. TRENCHES UNDER POLYTHENE OF APPROVED NORMALLY BE CONSIDERED UNSTABLE. FOR THE SOILS

OUTSIDE DIA
NOMINAL EXTERNAL NATIVE SOIL TYPE ROADS AND PAVED AREAS TO BE BACKFILLED IN GAUGE TO BE PLACED CONSIDERED AS UNSTABLE THE SAFE WIDTH OF
ACCORDANCE WITH THE MUNICIPALITY'S ROAD AS SEPARATING MEDIUM
DIAMETER "D" FULLY STABLE SECTION REQUIREMENTS TRENCH SHOULD BE CONSIDERED BASED ON THE

OF PIPE
REPOSE ANGLE OF THE SOIL MATERIAL AND THE
D < 400 D + 600 THE FIRST 500
OVER SELECTED BACKFILL MATERIAL FREE FROM MINIMUM WORKING SPACE INSIDE THE TRENCH,
400 < D < 1400 2.5 X D PERMANENT
LARGE STONES ETC. LIGHTLY COMPACTED CONCRETE C20 ALTERNATIVELY THE TRENCH WALL SUPPORT SYSTEMS
.

BY HAND IN 150 THICK LAYERS


D > 1400 D + 2000 WORK SHOULD BE PROVIDED.
GRANULAR MATERIAL SHALL BE SINGLE SIZE CRUSHED 150 FOR D < 900 11. WHERE THE SIDE SUPPORT PROVIDED BY THE NATIVE
300
300

AGGREGATE, NOMINAL SIZE 10mm. THE BEDDING 275 FOR D > 900 SOIL OFFERS SOME DEGREE OF SUPPORT
LAP
MATERIAL SHALL BE COMPACTED TO BETTER THAN 90% INTERMEDIATE TRENCH WIDTHS MAY BE ADOPTED AS
* MINIMUM TRENCH WIDTHS FOR uPVC PIPE BITUMINOUS FELT PRECAST CONCRETE C40
OF PROCTOR DENSITY. APPROVED GEOTEXTILE FILTER AGREED WITH THE ENGINEER.THE ENGINEER MAY
PIPE SUPPORTS
FABRIC SUFFICIENT SLACK SHALL BE PROVIDED DURING FLEXIBLE JOINT
NOMINAL EXTERNAL NATIVE SOIL TYPE OUTSIDE DIA REQUIRE TESTS TO BE CARRIED OUT TO DETERMINE
OUTSIDE DIA. OF PIPE INSTALLATION OF THE FABRIC TO AVOID TEARING WHEN BLINDING CONCRETE
DIA "D" (mm) FULLY STABLE OF PIPE 38 FOR 600 < D < 1200 WHETHER THE NATIVE SOIL IS STABLE OR NOT. WHERE
PIPE BEDDING MATERIAL IS PLACED 50 FOR 1400 < D < 2400 DIRECTED BY THE ENGINEER THE CONTRACTOR SHALL
150 FOR D < 900
300 + D 150 MIN. DEPTH OF BEDDING SPECIFIED GRANULAR BED AND SURROUND PLACED IN 275 FOR D > 900 OVER EXCAVATE THE TRENCH AND BACKFILL WITH
D < 315 TO BE INCREASED TO 300 IN 150 THICK LAYERS AND COMPACTED AS SPECIFIED FOR CONCRETE C20 OR SUITABLE GRANULAR MATERIAL.
(450 min) UNSTABLE GROUND AS CLASS OF BEDDING MATERIAL. PARTICULAR CARE TO BE
TAKEN TO ENSURE FULL COMPACTION OF MATERIAL
DIRECTED BY THE ENGINEER
UNDER PIPE HAUNCHES BED AND SURROUND PROTECTION DETAILS FOR R.C. PIPES
NOMINAL REFERENCE DRAWINGS AND DOCUMENTS
INTERNAL DIA 4 BARS-16 DIA ANCHORING SCALE 1:40
W* LIFTING HOOK STANDARD DRAWING - STORM WATER PIPE PROTECTION -302
16 DIA LIFTING HOOK
(EPOXY COATED)
* THE ENGINEER MAY DECIDE TO PLACE CLASS C CONCRETE IN LIEU OF DUNE SAND
FOR CERTAIN PIPELINES SO THAT THE PIPES RECEIVE A FULL CLASS C CONCRETE BED AND SUROUNED. DETAILS

C40 CONCRETE SLAB REINFORCED


WITH ONE LAYER OF B.S. LONG MESH
FABRIC REINFORCEMENT REF. C636 SUBGRADE AND SUBBASE MATERIAL
FAIR FACE FINISHING AND COMPACTED TO 100% MDD BITUMINOUS LAYER OR INTERLOCKING
WARNING TAPE
PROTECTION WITH DETAIL '1' 10mm DIA @ 100 C/C (T&B)
TILES AS PER EXISTING PAVEMENTATION
TOP OF ROAD OR
BITUMINOUS PAINT R.C. PRECAST SLAB
*

SELECTED EXCAVATED MATERIAL PARKING PAVEMENT


150

LIFTING HOOKS (SEE DETAIL "1") WARNING TAPE


NATURAL GROUND NATURAL GROUND NATURAL GROUND NATURAL GROUND

THAN 1000mm
1000mm min. COVER

COVER LESS
300

POLYTHENE OF APPROVED VAR. AS PER


WARNING TAPE

1000 (MIN)
GAUGE TO BE PLACED AS 250 EXISTING LIFTING HOOK
300

SEPARATING MEDIUM SELECTED 10mm DIA @ 150 C/C (T&B) PAVEMENTATION No. REVISION-1 APP'D 2020

MIN.
(SEE DETAIL "1")

250
EXCAVATED (STRAIGHT BARS) THICKNESS
CLIENT
300

BED AND SURROUND MATERIAL


SURROUND (SAND 10mm DIA @ 100 C/C (T&B)

300
AS SPECIFIED SURROUND (SAND FROM APPROVED
300

10mm DIA @ 150 C/C (T&B)


FROM APPROVED BORROW PITS)
O.D.

(STRAIGHT BARS)
BORROW PITS)
PROPOSED HDPE

O.D.
BEDDING (SAND
O.D.

PIPE PROPOSED HDPE PIPE


PROPOSED HDPE PIPE FROM APPROVED TITLE
200 TRENCH WIDTH 200
BEDDING (SAND BORROW PITS) BEDDING (SAND FROM STANDARD DRAWINGS
MIN. MIN. 200mm MINIMUM APPROVED BORROW
GRP AND PVC-U FROM APPROVED
300 O.D 300 MIN. MIN. PITS) 200mm MINIMUM STORM WATER WORKS
BORROW PITS)
MIN. MIN.
PIPE PROTECTION DETAILS 300 O.D 300
200mm MINIMUM 300 O.D 300
DRAWING TITLE
REINFORCED CONCRETE SLAB TYPE "B" TYPE "C"
SCALE 1:40 TYPE "A" 1. TYPE "C" SHALL BE USED WHERE PIPES ARE LAID UNDER PARKING AREAS OR STANDARD DRAWING
1. TYPE "B" SHALL BE USED WHERE THE DEPTH OF COVER IS LESS THAN 1000mm
(TO BE USED WHERE THE APPLIED LOADS ON A TYPE "A" SHALL BE USED FOR ALL ALONG CARRIAGEWAYS
PIPE DO NOT GIVE THE REQUIRED STRUCTURAL NETWORKS EXCEPT FOR THE CASES
2. THE WIDTH OF THE PRECAST SLAB IN THE LONGITUDINAL DIRECTION IS 500mm
2. THE WIDTH OF THE PRECAST SLAB IN LONGITUDINAL DIRECTION IS 500mm PIPE BEDDING AND
AND THE LENGTH IS (O.D. +MIN. 600) FOR PIPE DIAMETER UP TO 400mm AND (O.D.
FACTOR OF SAFETY AS REQUIRED BY WHERE TYPE "B", TYPE "C" AND TYPE
"D" SHOULD BE USED.
+MIN. 800) FOR PIPES DIAMETER ABOVE 400mm
AND THE LENGTH IS (O.D. +MIN. 600) FOR PIPE DIAMETER UP TO 400mm AND
(O.D. +MIN. 800) FOR PIPES DIAMETER ABOVE 400mm
BACKFILL DETAILS
APPROPRIATE STANDARD)
* MINIMUM THICKNESS IS 150mm
HDPE TRENCH CROSS SECTION TYPE A, B, & C
3. THE THICKNESS AND THE LENGTH OF THE PRECAST SLAB REPRESENT THE
MINIMUM REQUIREMENT WHICH COULD BE INCREASED AS PER THE DESIGN TO BE
POLYSTYRENE LAYER (APPROXIMATELY PERFORMED BY THE CONTRACTOR SUBJECT TO ADSSC/ENGINEER APPROVAL DRAWN - SCALE AS SHOWN
50mm THICK) NEED UNDERNEATH THE SCALE 1:40
CONCRETE SLAB TO BE VERIFIED BY CHECKED - DATE -
DESIGNERS
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
301

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
B 1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS OTHERWISE
STATED.
2. SLUICE VALVE INSTALLATION WILL BE SUBJECT TO ADM
APPROVAL

LEGEND
GRAVITY DRAIN LINE REINFORCED CONCRETE
SOIL COMPACTED TO 95% MDD
PLAIN CONCRETE

FGL FINAL GROUND LEVEL


CL COVER LEVEL
COVER & FRAME TO D.I. COVER & FRAME
SUIT 750 x 600 CLEAR TO SUIT 1500 x 600 FA FLANGE ADAPTOR
OPENING CLEAR OPENING
FC FLEXIBLE COUPLING
D.I. PIPEWORK SLUICE VALVE
SC STEPPED COUPLING
IPF INTEGRAL PUDDLE FLANGE
PF SV SLUICE VALVE
ST SCREED THICKNESS
PUMPING MAIN

IPF FA FA IPF SC FC FC
B

SV

SURFACE BOX

GRP LADDER GRP LADDER D.I. GRP


500 x 500 x
300 DEEP
SUMP GRAB HANDLES

SECTION A-A
PLAN AT COVER LEVEL

EXTENSION SPINDLE AND


200 THICK CLASS 'B'
SPINDLE BOX SUITABLE FOR
CONCRETE SCREED
TEE KEY OPERATION
FGL FGL REFERENCE DRAWINGS AND DOCUMENTS
75 THICK PRECAST
STANDARD DRAWING - TANKING DETAILS - 801
CONCRETE SEATING
STANDARD DRAWING - CONSTRUCTION AND MOVEMENT JOINT
- 1001
RINGS BEDDED IN 1 PART - 207
STANDARD DRAWING - MISCELLANEOUS DETAILS
CEMENT / 2 PART SAND FOR MANHOLES
EPOXY COATING AS MORTAR - 1000
DUCTILE IRON COVER STANDARD DRAWING - REINFORCEMENT DETAILS
SPECIFIED (SERIES)
10 DOWEL DRILLED AND 150 CLASS B CONCRETE
EXTENSION SPINDLE AND STANDARD DRAWING - STORM WATER MANHOLE FRAME - 213
SET INTO COVER SLAB AT SURROUND
A A 300 CENTERS FINISHED LEVEL OF SPINDLE BOX SUITABLE AND COVER DETAILS
GRP BELLMOUTH WITH PAVED AREA (FL) CL CL FOR TEE KEY OPERATION
TANKING MEMBRANE
MOULDED FLANGE TO AND PROTECTION BOARD
SUIT D.I. FITTINGS
(MIN.)
450

PUMPING MAIN

No. REVISION-1 APP'D 2020


CLIENT
D.I. 90° FLANGED
LONG RADIUS BEND

SLOPE IN CONCRETE COVER SLAB DETAIL FOR CARRIAGEWAY & PARKING AREAS
CONCRETE BENCHING
TITLE
STANDARD DRAWINGS
50mm THK. CEMENT/SAND SCREED STORM WATER WORKS
TANKING MEMBRANE
75mm THICK C20 BLINDING DRAWING TITLE
1000 GAUGE POLYETHYLENE SHEET
STANDARD DRAWING BELL MOUTH
SECTION B-B DISCHARGE CHAMBER FOR STORM
WATER PUMPING MAIN

DRAWN - SCALE 1 : 50
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
401

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS OTHERWISE
STATED.
2. THE MANHOLES AND CHAMBERS ARE DESIGNED USING FULL
GROUND WATER LEVEL CONDITION WITH 1.1 FACTOR OF
SAFETY FOR FLOATATION AND BEARING PRESSURE NOT
B EXCEEDING 200kpa AT FORMATION LEVEL.
3400 3. DEWATERING OPERATIONS SHALL BE PROVIDED DURING
CONSTRUCTION AND MAY ONLY BE TERMINATED AFTER
300 1000 300 1500 300 ROOF SLAB HAS BEEN CAST.
COVER & FRAME TO COVER & FRAME TO
SUIT 750 x 600 SUIT 750 x 600 LEGEND
CLEAR OPENING CLEAR OPENING REINFORCED CONCRETE
SOIL COMPACTED TO 95% MDD
300

PLAIN CONCRETE
FGL FINAL GROUND LEVEL
PUMPING MAIN FL FINAL ASPHALT / INTERLOCKED TILE LEVEL
GRAVITY DRAIN LINE
DIA DIAMETER
PIPE DIA + 1200

PF
IPF FC FC
B FA FLANGE ADAPTOR
FC FLEXIBLE COUPLING
SC STEPPED COUPLING
IPF INTEGRAL PUDDLE FLANGE
ST SCREED THICKNESS
300

GRP LADDER GRP LADDER


500
100mm DIA. OPENING GRAB HANDLES

SECTION A-A
PLAN AT COVER LEVEL

COVER & FRAME TO


SUIT 750 x 600
CLEAR OPENING
200

200 THICK CLASS 'B'


CONCRETE SCREED
FGL FGL
75 THICK PRECAST CONCRETE
SEATING RINGS BEDDED IN 1 PART
250

CEMENT / 2 PART SAND MORTAR

10 DOWEL DRILLED REFERENCE DRAWINGS AND DOCUMENTS


AND SET INTO COVER DUCTILE IRON COVER
STANDARD DRAWING - TANKING DETAILS - 801
TANKING MEMBRANE SLAB AT 300 CENTERS STANDARD DRAWING - CONSTRUCTION AND MOVEMENT JOINT
- 1001
AND PROTECTION BOARD
FINISHED LEVEL OF STANDARD DRAWING - MISCELLANEOUS DETAILS - 207
PAVED AREA (FL) CL CL
FOR MANHOLES
(3000 MAXIMUM)

- 1000
A A STANDARD DRAWING - REINFORCEMENT DETAILS
(SERIES)

(MIN.)
450
VARIES

EPOXY COATING AS SPECIFIED STANDARD DRAWING - STORM WATER MANHOLE FRAME - 213
AND COVER DETAILS

100mm DIA. OPENING PUMPING MAIN


(APPROX.)

IPF FC FC
500

GRAVITY LINE
IPF

COVER SLAB DETAIL FOR CARRIAGEWAY & PARKING AREAS


300

No. REVISION-1 APP'D 2020


400

CLIENT

50mm THK. CEMENT/SAND SCREED


TANKING MEMBRANE
75mm THICK C20 BLINDING TITLE
300 300 1000 300 1500 300 300
1000 GAUGE POLYETHYLENE SHEET
STANDARD DRAWINGS
STORM WATER WORKS
SECTION B-B DRAWING TITLE

STANDARD DRAWING WEIR


DISCHARGE CHAMBER FOR
STORM WATER PUMPING MAIN

DRAWN - SCALE 1 : 50
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
402

THIRD EDITION - APRIL 2022


NOTES:
800 THESE DETAILS REPRESENT A MINIMUM REQUIREMENT
AND MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT
PROJECT REQUIREMENTS. THEY ARE EXPECTED TO BE
INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
CHECKED AND APPROVED AS PART OF THE PROJECT
DRAWING SET.
C C 1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS

800
RECESSED AREA 3mm BELOW OTHERWISE STATED.
MATERIAL OF MARKER BRONZE TOP SURFACE OF MARKER 2. MARKER PLATES ARE TO BE INSTALLED IN PAVED
STIPPLE OR TEXTURED FINISH AREAS.
A 5(MIN) A 5(MIN) 3. MARKER POSTS TO BE INSTALLED IN UNPAVED AREAS.
RAISED LETTERS 3mm ABOVE 4. MARKER POSTS OR PLATES TO BE LOCATED EVERY 50m

5.0
VARIES VARIES
RECESSED AREA (POLISHED FINISH) LONG THE LENGTH OF THE STORM WATER MAIN AS
PLAN DIRECTED BY THE ENGINEER. IN ADDITION TWO
MARKER POSTS TO BE PROVIDED AT EVERY CHANGE

7.5
OF DIRECTION AND AT EACH CHAMBER.
END LAMINATED COVER

2(MIN)

30.0
LEGEND

7.5
MASS CONCRETE

9.0 10.0 10.0


TOP SURFACE OF MARKER 16.5 82 16.5 100 DIA ALUMINIUM FGL FINAL GROUND LEVEL
(POLISHED FINISH) INCISED 2mm ALLOY PIPE
POWDER COATED
WITH POLYESTER

115.0
45.0

TWO COATS OF BRILLIANT


RED FLOURSCENT PAINT
12.5 90 12.5

1250
B *** mm DIA. PIPELINE B B *** mm DIA. PIPELINE B

6.0
10.0
POST TO BE MARKED "***mm DIA
DRAINAGE PUMPING MAIN" IN

7.5
ENGLISH AND ARABIC IN WHITE

STORM WATER NETWORK STORM WATER NETWORK PAINT WITH TWO COATS OF FGL

30.0
RESIN OVER

7.5

750
5.0
RECESSED AREA 3mm BELOW TOP SURFACE RAISED LETTERS 3mm ABOVE
OF MARKER (STIPPLE OR TEXTURED FINISH) RECESSED AREA (POLISHED FINISH)
5.0 MIN 5.0 MIN

105.0
A CONCRETE CLASS `C'

500
5.0 5.0
115.0

A
BACKFILL WELL COMPACTED

PLAN VIEW PLAN VIEW


SECTION C-C

RAISED LETTERING (TYP)

INCISED LETTERING
115.0 2 MARKER POSTS OR PLATES
5.0 7.5 15.0 7.5 45.0 7.5 15.0 7.5 5.0
5.0 13.0

SIDEWALK TILE

13.0
REFERENCE DRAWINGS AND DOCUMENTS
LATEX/CEMENT MORTAR STANDARD DRAWING - TANKING DETAILS - 801
TYPICAL
45.0

INCISED LETTERING
RECESSED AREA (TYP) VALVE CHAMBER
62.0

PLAN

50.0
PRECAST CONCRETE BASE RAISED LETTERING (TYP)

20.0
500 500

30.0 5.0

10.0

47.5 20.0 47.5 20.0 47.5 2 MARKER POSTS OR PLATES


No. REVISION-1 APP'D 2020
CLIENT

SECTION A-A
TITLE
STANDARD DRAWINGS
STORM WATER WORKS
TYPICAL

0
50

50
0
THRUST BLOCK DRAWING TITLE
PLAN
STANDARD DRAWING PUMPING
MAIN MARKER DETAILS
SECTION B-B
TYPICAL LOCATIONS AT VALVE CHAMBER
MARKER PLATE FOR PAVED AREAS AND THRUST BLOCKS DRAWN - SCALE N.T.S
MARKER POSTS FOR OPEN AREAS CHECKED - DATE -
SCALE 1:40 APPROVED - SIZE A1
PROJECT DWG.
No. - No.
403

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
1. UNLESS OTHERWISE SPECIFIED ALL DIMENSIONS
ARE IN MILLIMETRES.
2. CHAMBER IDENTIFICATION PLATES ANCHORS SHALL
BE CAST INTO THE CONCRETE AND THE TOP METAL
SURFACE SHALL BE FLUSH WITH TOP OF CONCRETE.
3. IDENTIFICATION PLATES SHALL BE PROVIDED FOR
THE FOLLOWING LOCATIONS AS SHOWN:
GV GATE VALVE
AV AIR RELEASE VALVE
WO WASH OUT
FM FLOWMETER
150
4. VALVE INDICATION PLATE SHALL BE POLISHED TO A
10 35 60 35 10 SMOOTH FINISH.
5. TEXT FOR SIZE OF VALVE SHALL BE THE ACTUAL

10 15 25 15 25 10 25 15 10
35 60 35 VALVE SIZE.

8
15 THICK ANCHORING LEGEND
STRIP(TYP.)
2 No. 15 THICK DI - DUCTILE IRON
ANCHORING STRIP

50
DIA - DIAMETER

150
25 DIA. HOLE TO FIX STEEL
REINFORCEMENT BAR TYP - TYPICAL
20 (TYP)

150
10 10
20 10

TYPE OF VALVE
10 25 5 20 20 10 30

(SEE NOTE 3)

REFERENCE DRAWINGS AND DOCUMENTS


150

SIZE OF VALVE
(SEE NOTE 5)
DIRECTION OF DRAINAGE
PUMPING MAIN
10

75
WASH OUT
PLAN-CHAMBER INDICATION PLATE (TYPICAL)

No. REVISION-1 APP'D 2020


CLIENT

TITLE
STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE
8

STANDARD DRAWING TYPICAL


DETAILS OF LETTERING ON COVERS,
5

50

CHAMBER INDICATION PLATE &


OWNER INFORMATION PLATE
10
DRAWN - SCALE N.T.S
B AIR RELEASE VALVE FLOWMETER CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
404

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETERS
UNLESS OTHERWISE STATED.
FOR PIPE SUPPORT 2. DIAMETER OF TEE TO BE D/2 OF THE MAIN
REFER TO DETAIL 'A' PIPELINE.
DUCTILE IRON COVER AND FRAME TO SUIT
750 DIA NOMINAL SIZE CLEAR OPENING IN
LEGEND
ALL CHAMBERS ON STORM WATER ARV - AIR RELEASE VALVE
PRESSURE MAINS SLFA - SLIM FLANGE ASSEMBLY
STFA - STUB FLANGE ASSEMBLY

E
TYPICAL LIFTING HOOK DI - DUCTILE IRON
ST75 HDPE - HIGH DENSITY POLYETHYLENE PIPE
300x300x150 SUMP AL - ALUMINIUM
WITH GRP GRATING COVER ALUMINUM AIR VENT IPF - INTEGRAL PUDDLE FLANGE
ST50 (SHORT)

D
200 GROUTING
(MIN) 150 SQUARE SURFACE BOX GRATING
POSITIONED TO SUIT REINFORCED
B B CEMENT CONCRETE
CEMENT/SAND
ALUMINUM AIR VENT SCREED
(LONG) BLINDING CONCRETE

C
150 SQUARE SOIL COMPACTED TO
ST75 ST75 CHAMBER INDICATION PLATE 95% MDD

E
150 SQUARE OWNER
B A B
INFORMATION PLATE

SECTION A-A
PLAN AT COVER LEVEL

150 DN 150

RUBBER INSULATION
10mm THK. (TYPICAL)
ALUMINUM AIR VENT PIPE CONCRETE SUPPORT
DUCTILE IRON COVER
(SHORT)
CHAMFER 25x25 AS SPECIFIED UV RESISTANCE
EPOXY COATING TO ALL
FINISHED LEVEL OF SURFACES ABOVE GROUND
PAVED AREA (FL)
DETAIL A REFERENCE DRAWINGS AND DOCUMENTS
250

FGL
REINFORCED CONCRETE CLASS 'B'
F

ARV
A AIR RELEASE VALVE GRP LADDER A
(MIN)
1150

GATE VALVE WITH


MITRE GEAR (SHORT BODY)
DI

EPOXY COATING TO ALL HDPE PIPE SIZE A B C D E F


INTERNAL SURFACES
HDPE

TANKING MEMBRANE STFA/SLFA OD (mm) (mm) (mm) (mm) (mm) (mm)


AND PROTECTION BOARD
IPF (NOTE 2) IPF 180 1500 250 390 1300 250
OD

200 1500 250 400 1300 250


225 1500 250 400 1300 250
(MIN)
300

PVC WATER STOP 250 1500 300 450 1350 300 No. REVISION-1 APP'D 2020
280 1500 300 450 1350 300 CLIENT
CONSTRUCTION JOINT
315 1500 300 500 1400 300
AS PER
355 1500 300 600 1400 300 MANUFACTURER
RECOMMENDATION
400 1500 300 800 1400 300
50mm THK. CEMENT/SAND SCREED 450 1800 300 850 1450 300 TITLE
TANKING MEMBRANE 500 1800 300 900 1500 300
STANDARD DRAWINGS
SECTION B-B 75mm THICK C20 BLINDING 560 1800 300 900 1500 300 STORM WATER WORKS
1000 GAUGE POLYETHYLENE SHEET 630 1800 350 1000 1600 350
DRAWING TITLE
710 1800 350 1100 1600 350
TYPICAL DRAWING AIR VALVE CHAMBER
GENERAL ARRANGEMENT (HDPE
FITTINGS)

DRAWN - SCALE 1 : 40
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
405

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT
AND MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT
PROJECT REQUIREMENTS. THEY ARE EXPECTED TO BE
INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
CHECKED AND APPROVED AS PART OF THE PROJECT
DRAWING SET.

1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS


OTHERWISE STATED.
DUCTILE IRON COVER AND FRAME
TO SUIT 750 DIA NOMINAL SIZE
FOR PIPE SUPPORT CLEAR OPENING IN ALL CHAMBERS LEGEND
REFER TO DETAIL 'A' ON STORM WATER PRESSURE
GV - GATE VALVE
MAINS
DI - DUCTILE IRON
GRP - GLASS REINFORCED PLASTIC

E
TYPICAL LIFTING HOOK AL - ALUMINIUM
ST75 IPF - INTEGRAL PUDDLE FLANGE
300x300x150 SUMP DJ - DISMANTLING JOINT
WITH GRP GRATING - FLEXIBLE COUPLING
FC
COVER ST50
GROUTING

D
GRATING
REINFORCED
CEMENT CONCRETE
B B SURFACE BOX
CEMENT/SAND
SCREED
POSITIONED TO SUIT BLINDING CONCRETE
SOIL COMPACTED TO

C
150 SQUARE 95% MDD
ST75 ST75 CHAMBER INDICATION PLATE

E
150 SQUARE OWNER
B A B
INFORMATION PLATE

SECTION A-A PLAN AT COVER LEVEL

UPPER AND LOWER


CHAMFER 25x25 DUCTILE IRON COVER
PADS PTFE 5mm GROUTING
THK.
STEEL PLATE
AS SPECIFIED UV RESISTANCE BOX OUT CASING
EPOXY COATING TO ALL CONCRETE VALVE SUPPORT
SURFACES ABOVE GROUND
FINISHED LEVEL OF
PAVED AREA (FL) 250
STEEL PLATE WITH
FGL FISHTAIL UNDER
REINFORCED CONCRETE CLASS 'B' THE FLANGES

DETAIL A REFERENCE DRAWINGS AND DOCUMENTS


A TANKING MEMBRANE GRP LADDER A
(MIN)

AND PROTECTION BOARD


1000

STANDARD DRAWING - TANKING DETAILS - 801

EXTENSION SPINDLE EPOXY COATING TO ALL


INTERNAL SURFACES

GV DJ
IPF IPF
300 OD

HDPE PIPE SIZE A B C D E


(MIN)

OD (mm) (mm) (mm) (mm) (mm) (mm)


PVC WATER STOP
180 1500 250 390 1300 250
CONSTRUCTION JOINT
200 1500 250 400 1300 250
225 1500 250 400 1300 250
250 1500 300 450 1350 300
No. REVISION-1 APP'D 2020
50mm THK. CEMENT/SAND SCREED 280 1500 300 450 1350 300
CLIENT
STFA/SLFA
TANKING MEMBRANE 315 1500 300 500 1400 300
75mm THICK C20 BLINDING 355 1500 300 600 1400 300
SECTION B-B 1000 GAUGE POLYETHYLENE SHEET 400 1500 300 800 1400 300
TITLE
450 1800 300 850 1450 300 STANDARD DRAWINGS
500 1800 300 900 1500 300
STORM WATER WORKS
560 1800 300 900 1500 300
630 1800 350 1000 1600 350 DRAWING TITLE
710 1800 350 1100 1600 350
TYPICAL DRAWING ISOLATION
VALVE CHAMBER GENERAL
ARRANGEMENTS (HDPE FITTINGS)

DRAWN - SCALE 1 : 50
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
406

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS OTHERWISE
STATED.
2. GATE VALVE CHAMBER TO BE INSTALLED UPSTREAM OF
FLOW METER CHAMBER AS PER SITE CONDITIONS.

FOR PIPE SUPPORT DUCTILE IRON COVER AND FRAME TO SUIT LEGEND
REFER TO DETAIL 'A' 750 DIA NOMINAL SIZE CLEAR OPENING IN
ALL CHAMBERS ON STORM WATER GV - GATE VALVE
PRESSURE MAINS DI - DUCTILE IRON
GRP - GLASS REINFORCED PLASTIC
IPF - INTEGRAL PUDDLE FLANGE

E
DJ - DISMANTLING JOINT
TYPICAL LIFTING HOOK FC - FLEXIBLE COUPLING
300x300x150 SUMP WITH ST75
GROUTING
GRP GRATING COVER
GRATING
ST50
REINFORCED

D
CEMENT CONCRETE
CEMENT/SAND
SCREED
B B BLINDING CONCRETE
SOIL COMPACTED TO
95% MDD

C
150 SQUARE
ST75 ST75 CHAMBER INDICATION PLATE

E
150 SQUARE OWNER
B A B
INFORMATION PLATE

SECTION A-A
PLAN AT COVER LEVEL

A36 STEEL PLATE, 19MM THICK


EPOXY COATED

(MIN)
300
CHAMFER 25x25 NON SHRINKABLE GROUTING
DUCTILE IRON COVER
(30mm THICKNESS) TYP.

AS SPECIFIED UV RESISTANCE CONCRETE SUPPORTS UNDER


UPPER AND LOWER PADS

150
EPOXY COATING TO ALL
SURFACES ABOVE GROUND PTFE, 5mm THK THE STEEL SUPPORTS
FINISHED LEVEL OF
PAVED AREA (FL) STEEL PLATE WITH FISHTAIL REFERENCE DRAWINGS AND DOCUMENTS
UNDER THE FLANGES
DETAIL A
250

STANDARD DRAWING - TANKING DETAILS - 801


FGL
REINFORCED CONCRETE CLASS 'B'

A TANKING MEMBRANE GRP LADDER A


(MIN)

AND PROTECTION BOARD


1000

EPOXY COATING TO ALL


STFA/SLFA INTERNAL SURFACES
FM HDPE PIPE SIZE A B C D E
DJ OD (mm) (mm) (mm) (mm) (mm) (mm)
IPF IPF
300 OD

180 1500 250 390 1300 250


200 1500 250 400 1300 250
(MIN)

No. REVISION-1 APP'D 2020


PVC WATER STOP 225 1500 250 400 1300 250
CLIENT
250 1500 300 450 1350 300
CONSTRUCTION JOINT
280 1500 300 450 1350 300
315 1500 300 500 1400 300
355 1500 300 600 1400 300 TITLE
50mm THK. CEMENT/SAND SCREED 400 1500 300 800 1400 300 STANDARD DRAWINGS
TANKING MEMBRANE 450 1800 300 850 1450 300 STORM WATER WORKS
SECTION B-B 75mm THICK C20 BLINDING 500 1800 300 900 1500 300
1000 GAUGE POLYETHYLENE SHEET DRAWING TITLE
560 1800 300 900 1500 300
630 1800 350 1000 1600 350 TYPICAL DRAWING FLOW METER
710 1800 350 1100 1600 350 CHAMBER GENERAL ARRANGEMENTS
(HDPE FITTINGS)

DRAWN - SCALE 1 : 50

CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
407

THIRD EDITION - APRIL 2022


NOTES:
SURFACE BOX THESE DETAILS REPRESENT A MINIMUM REQUIREMENT
150 SQUARE OWNER
POSITIONED TO SUIT THE AND MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT
INFORMATION PLATE
C EXTENSION SPINDLE PROJECT REQUIREMENTS. THEY ARE EXPECTED TO BE
INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
CHECKED AND APPROVED AS PART OF THE PROJECT
DRAWING SET.

E
1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS
PUMPING MAIN (OD1) HDPE PIPE SIZE A B C D E LIFTING HOOK (TYPICAL)
IPF IPF OTHERWISE STATED.
OD1 (mm) (mm) (mm) (mm) (mm) (mm) ALUMINUM AIR VENT 2. SIZE OF THE WASHOUT PIPE (OD2) TO BE AS PER STORM

D
(SHORT) WATER DESIGN MANUAL.
180 1500 250 390 1300 250
200 1500 250 400 1300 250 LEGEND
225 1500 250 400 1300 250
GV - GATE VALVE
250 1500 300 450 1350 300
B HDPE - HIGH DENSITY POLYETHYLENE
GV B 280 1500 300 450 1350 300
IPF - INTEGRAL PUDDLE FLANGE

C
ALUMINUM AIR VENT
GRP LADDER 315 1500 300 500 1400 300 (LONG) FA - FLANGE ADAPTER
FA 355 1500 300 600 1400 300
GV 150 SQUARE CHAMBER GROUTING
300x300x120 DEEP SUMP 400 1500 300 800 1400 300
WITH GRP GRATING COVER INDICATION PLATE GRATING
450 1800 300 850 1450 300
IPF REINFORCED

E
500 1800 300 900 1500 300
CEMENT CONCRETE
560 1800 300 900 1500 300
F 630 1800 350 1000 1600 350 DUCTILE IRON COVER AND CEMENT/SAND
FRAME TO SUIT 750 DIA SCREED
710 1800 350 1100 1600 350
OD2 NOMINAL SIZE CLEAR BLINDING CONCRETE
B A B OPENING IN ALL CHAMBERS SOIL COMPACTED TO
ON STORM WATER 95% MDD
300 MIN. PRESSURE MAINS
TYP

IPF 300 UPPER AND LOWER PADS


PTFE 5mm THK.

STEEL PLATE GV
(100x12mm)
NON-SHRINKABLE CONCRETE

200(Min.)
GROUTING (30mm THK.)
150
1200 DIA

BOX OUT CASING FILLED WITH


NON-SHRINKABLE CONCRETE GROUTING
GRP LADDER STEEL PLATE WITH FISHTAIL
UNDER THE FLANGES
CONCRETE VALVE SUPPORT
DUCTILE IRON COVER AND
FRAME TO SUIT 750 DIA
DETAIL-A VALVE SUPPORT NOMINAL SIZE CLEAR
MIN
225

150
(1:40) OPENING IN ALL CHAMBERS
150 ON STORM WATER
C PRESSURE MAINS

TOP VIEW OF COVER SLAB


SECTION A-A
COVER AND FRAME TO SUIT SURFACE BOX POSITIONED
750 DIA CLEAR OPENING TO SUIT THE EXTENSION SPINDLE
ALUMINUM AIR VENT (SHORT) COVER AND FRAME TO SUIT SURFACE BOX POSITIONED
ALUMINUM AIR VENT (LONG)
200 600 DIA CLEAR OPENING TO SUIT THE EXTENSION SPINDLE ALUMINUM AIR VENT (SHORT)
FINISHED LEVEL OF
PAVED AREA (FL)
FINISHED LEVEL OF CHAMFER 25x25
PAVED AREA (FL) FGL
UNPAVED
250

REFERENCE DRAWINGS AND DOCUMENTS


250

AREAS

STANDARD DRAWING - TANKING DETAILS - 801


EPOXY COATING TO
ALL INTERNAL
SURFACES EPOXY COATING TO
ALL INTERNAL
SURFACES
VARIES

GRP LADDER
TANKING MEMBRANE
EXTENSION SPINDLE AND PROTECTION BOARD
TANKING MEMBRANE
A AND PROTECTION BOARD A A GRP LADDER
A
PUMPING MAIN (OD1)
IPF IPF
VARIES
OD

No. REVISION-1 APP'D 2020


IPF IPF CLIENT
GRP LADDER INVERT OD2
VARIES

LEVEL
PVC WATER STOP 1% SLOPE

CONSTRUCTION JOINT
TITLE
1000

STANDARD DRAWINGS
STORM WATER WORKS
50

50mm THK. CEMENT/SAND 50mm THK. CEMENT/SAND


SCREED 300x300x120 DEEP SUMP SCREED
FOR DETAIL OF VALVE SUPPORT TANKING MEMBRANE WITH GRP GRATING COVER TANKING MEMBRANE DRAWING TITLE
REFER TO DETAIL 'A' 75mm THICK C20 BLINDING 75mm THICK C20 BLINDING
420

300x300x120 DEEP SUMP


WITH GRP GRATING COVER
1000 GAUGE POLYETHYLENE SHEET 1000 GAUGE POLYETHYLENE SHEET TYPICAL DRAWING WASHOUT
CHAMBER (TYPE-1 DETAILS (HDPE
SECTION B-B 50mm THK. CEMENT/SAND
300 x 300 x 150
SCREED FITTINGS)
DEEP SUMP
TANKING MEMBRANE
WASHOUT SUMP 75mm THICK C20 BLINDING
1000 GAUGE POLYETHYLENE SHEET DRAWN - SCALE 1 : 50
CHECKED - DATE -
SECTION C-C APPROVED - SIZE A1
PROJECT DWG.
No. - No.
408

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
C REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
B A B A B AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
ALUMINUM AIR VENT 1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS
(SHORT)
OTHERWISE STATED.
2. SIZE OF THE WASHOUT PIPE (OD2) TO BE AS PER

E
STORM WATER DESIGN MANUAL.
% HDPE PIPE
PUMPING MAIN (OD1) IPF IPF P E1 IPF SIZE A B C D E
SL
O
OD1 (mm)
(mm) (mm) (mm) (mm) (mm) LEGEND

D
180 1500 250 390 1300 250 150 SQUARE OWNER GV - GATE VALVE
200 1500 250 400 1300 250 INFORMATION PLATE HDPE - HIGH DENSITY POLYETHYLENE
225 1500 250 400 1300 250 150 SQUARE CHAMBER IPF - INTEGRAL PUDDLE FLANGE
HDPEDI INDICATION PLATE
250 1500 300 450 1350 300 FA - FLANGE ADAPTER

SL
IPF

OP
OD2 280 1500 300 450 1350 300 DUCTILE IRON COVER AND GROUTING

C
E
B B 315 1500 300 500 1400 300 FRAME TO SUIT 750 DIA

1%
F NOMINAL SIZE CLEAR OPENING GRATING
355 1500 300 600 1400 300 IN ALL CHAMBERS ON STORM
STFA DJ GV REINFORCED
400 1500 300 800 1400 300 WATER PRESSURE MAINS
CEMENT CONCRETE
GRP LADDER GRP LADDER
450 1800 300 850 1450 300 LIFTING HOOK (TYPICAL) CEMENT/SAND

E
500 1800 300 900 1500 300 SCREED
560 1800 300 900 1500 300 BLINDING CONCRETE
630 1800 350 1000 1600 350 ALUMINUM AIR VENT SURFACE BOX SOIL COMPACTED TO
300x300x120 DEEP SUMP POSITIONED TO SUIT THE
WITH GRP GRATING COVER 710 1800 350 1100 1600 350 (LONG) 95% MDD
EXTENSION SPINDLE

SECTION A-A UPPER AND LOWER PADS TOP VIEW OF COVER SLAB
PTFE 5mm THK.

STEEL PLATE GV
(100x12mm)
NON-SHRINKABLE CONCRETE

200(Min.)
GROUTING (30mm THK.)
BOX OUT CASING FILLED WITH
NON-SHRINKABLE CONCRETE GROUTING
STEEL PLATE WITH FISHTAIL
UNDER THE FLANGES
(50x6mm)
CONCRETE VALVE SUPPORT

DETAIL-A VALVE SUPPORT


(1:40)

SURFACE BOX POSITIONED TO SUIT


THE EXTENSION SPINDLE
ALUMINUM AIR VENT (SHORT)
ALUMINUM AIR VENT (LONG) SURFACE BOX POSITIONED TO
ALUMINUM AIR VENT (SHORT)
SUIT THE EXTENSION SPINDLE

FINISHED LEVEL OF FINISHED LEVEL OF CHAMFER 25x25


PAVED AREA (FL) PAVED AREA (FL)
UNPAVED
250

AREAS
REFERENCE DRAWINGS AND DOCUMENTS

EPOXY COATING TO STANDARD DRAWING - TANKING DETAILS - 801


ALL INTERNAL
SURFACES EPOXY COATING TO
ALL INTERNAL
SURFACES
VARIES

EXTENSION SPINDLE TANKING MEMBRANE


AND PROTECTION BOARD
TANKING MEMBRANE
A AND PROTECTION BOARD A EXTENSION SPINDLE
PUMPING MAIN (OD1)
IPF IPF IPF
OD

HDPE DI
IPF
No. REVISION-1 APP'D 2020
OD2
VARIES

CLIENT
PVC WATER STOP 1% SLOPE 1% SLOPE 1% SLOPE
STFA DJ GV

CONSTRUCTION JOINT

TITLE
FOR DETAIL OF VALVE SUPPORT 50mm THK. CEMENT/SAND
STANDARD DRAWINGS
50mm THK. CEMENT/SAND SCREED
REFER TO DETAIL 'A' SCREED
TANKING MEMBRANE
300x300x120 DEEP SUMP
WITH GRP GRATING COVER TANKING MEMBRANE STORM WATER WORKS
300x300x120 DEEP SUMP 75mm THICK C20 BLINDING 75mm THICK C20 BLINDING
WITH GRP GRATING COVER DRAWING TITLE
1000 GAUGE POLYETHYLENE SHEET 1000 GAUGE POLYETHYLENE SHEET

SECTION C-C TYPICAL DRAWING WASHOUT


SECTION B-B
CHAMBER (TYPE-2)DETAILS (HDPE
FITTINGS)

DRAWN - SCALE 1 : 50
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No. 409

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS
OTHERWISE STATED.
2. DIAMETER OF TEE TO BE D/2 OF THE MAIN PIPELINE.

LEGEND
GV - GATE VALVE
ARV - AIR RELEASE VALVE
DI REDUCING TEE
DI - DUCTILE IRON
GRP - GLASS REINFORCED PLASTIC
ROCKER PIPE 300 300 300 A 300 300
IPF - INTEGRAL PUDDLE FLANGE
150 SQUARE OWNER FA - FLANGE ADAPTER
INFORMATION PLATE - FLEXIBLE COUPLING
FC
C GROUTING
STORM WATER
GRP COUPLING GRATING
RISING MAIN
300

REINFORCED
DI GRP 200 D 200 CEMENT CONCRETE
LIFTING HOOK (TYPICAL)
CEMENT/SAND
FC IPF IPF ALUMINUM AIR VENT SCREED
C

(SHORT) BLINDING CONCRETE


SOIL COMPACTED TO
95% MDD
RUBBER INSULATION
GRP COUPLING FC
B

10mm THK. (TYPICAL)


PIPE CONCRETE SUPPORT
GRP DI ALUMINUM AIR VENT
B B (LONG)
GV 150 SQUARE CHAMBER
INDICATION PLATE
300

300x300x120 DEEP SUMP DUCTILE IRON COVER AND FRAME TO DETAIL-A VALVE SUPPORT
WITH GRP GRATING COVER SUIT 600 DIA NOMINAL SIZE CLEAR (1:20)
C OPENING

TOP VIEW OF COVER SLAB


SECTION A-A PIPE DIA A B C
150 1500 1500 450
200 1500 1500 450
250 1500 1500 450
300 1500 1500 450
400 1500 1500 450
500 1700 1700 500
600 1700 1700 500
800 2000 1700 1000
900 2000 1700 1000
1000 2000 1700 1000
DUCTILE IRON COVER ALUMINUM AIR VENT (LONG)
ALUMINUM AIR VENT (SHORT)
ALUMINUM AIR VENT (SHORT)

PAVED PAVED COVER CHAMFER 25x25


AREAS AREAS LEVEL REFERENCE DRAWINGS AND DOCUMENTS
250

FGL FGL STANDARD DRAWING - TANKING DETAILS -801

REINFORCED CONCRETE CLASS 'B' REINFORCED CONCRETE CLASS 'B'

TANKING MEMBRANE TANKING MEMBRANE


AND PROTECTION BOARD AND PROTECTION BOARD

A A
(MIN)
1000

GRP LADDER
EPOXY COATING TO ALL
GRP LADDER INTERNAL SURFACES
ARV GRP COUPLING ARV

STORM WATER
GRP DI GV DI GRP RISING MAIN
GV
300

GRP COUPLING IPF (NOTE 2) IPF


DI REDUCING TEE No. REVISION-1 APP'D 2020
DN

CLIENT
(MIN)
300

FC
301

FC 1% SLOPE

PVC WATER STOP


400

CONSTRUCTION JOINT TITLE


STANDARD DRAWINGS
150
50mm THK. CEMENT/SAND SCREED 50mm THK. CEMENT/SAND SCREED STORM WATER WORKS
FOR DETAIL OF PIPE SUPPORT TANKING MEMBRANE TANKING MEMBRANE
REFER TO DETAIL 'A' 75mm THICK C20 BLINDING 75mm THICK C20 BLINDING DRAWING TITLE
300x300x120 DEEP SUMP 1000 GAUGE POLYETHYLENE SHEET 1000 GAUGE POLYETHYLENE SHEET
WITH GRP GRATING COVER
SECTION B-B SECTION C-C TYPICAL DRAWING AIR VALVE
CHAMBER DETAILS (DI FITTINGS)

DRAWN - SCALE 1 : 50
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
410

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS
OTHERWISE STATED.
2. GATE VALVE CHAMBER TO BE INSTALLED UPSTREAM OF
FOR PIPE SUPPORT FLOW METER CHAMBER AS PER SITE CONDITIONS.
REFER TO DETAIL 'A' 150 SQUARE OWNER
INFORMATION PLATE
SADDLE STRAPS FOR VENT, DRAIN AND 50mm PVC CONDUIT LEGEND
SAMPLE CONNECTIONS
DI - DUCTILE IRON

C-H
FM - FLOW METER
STORM WATER
LIFTING HOOK (TYPICAL) GRP - GLASS REINFORCED PLASTIC
RISING MAIN
ALUMINUM AIR VENT IPF - INTEGRAL PUDDLE FLANGE
GRP COUPLING DI GRP (SHORT) FA - FLANGE ADAPTER
FA FM FC - FLEXIBLE COUPLING

F
FC IPF IPF
FC
GROUTING
GRATING
300/350mm DIA. D.I.
REINFORCED
WATER METER COVER
CEMENT CONCRETE
GRP DI 600 (MIN.) CEMENT/SAND
SCREED
D E
A A BLINDING CONCRETE

B
ALUMINUM AIR VENT
GRP LADDER, FOR DETAILS
(LONG) SOIL COMPACTED TO
REFER TO DWG. No. 109
FM 150 SQUARE CHAMBER 95% MDD
INDICATION PLATE

C-H
300x300x120 DEEP SUMP
WITH AL GRATING COVER COVER AND FRAME TO SUIT
C A C 600 DIA CLEAR OPENING

TOP VIEW OF COVER SLAB


SECTION A-A

A36 STEEL PLATE, 19MM THICK


EPOXY COATED
NON SHRINKABLE GROUTING
(30mm THICKNESS) TYP.
UPPER AND CONCRETE SUPPORTS UNDER

(MIN)
300

150
LOWER PADS THE STEEL SUPPORTS
PTFE, 5mm THK

STEEL PLATE WITH


300/350mm DIA. D.I. WATER METER COVER FISHTAIL UNDER THE
FLANGES
DUCTILE IRON COVER
DETAIL A
ALUMINUM AIR VENT (LONG)
ALUMINUM AIR VENT (SHORT)

CHAMFER 25x25

PAVED
AREAS CL
250 REFERENCE DRAWINGS AND DOCUMENTS
FGL STANDARD DRAWING - TANKING DETAILS - 801
REINFORCED CONCRETE CLASS 'B'
HEIGHT VARIES

EPOXY COATING TO ALL 300

B INTERNAL SURFACES B 100 1900 1200 300 350 350 400 300 100 400
GRP LADDER SAMPLE POINT
VENT FM 150 1900 1300 300 350 350 450 300 100 400
STORM WATER
GRP COUPLING RISING MAIN 200 1900 1300 300 350 350 450 300 100 400
FC IPF IPF FC
250 2000 1400 300 350 650 500 300 100 400
300 2000 1400 300 350 650 500 300 100 400
DN

400 2300 1850 350 500 500 750 350 100 400
500 2400 2050 350 500 500 850 350 100 400
K

GRP DI DI GRP
1% SLOPE
K

DRAIN 600 2400 2050 350 500 500 850 350 100 400
No. REVISION-1 APP'D 2020
CLIENT
TABLE OF DIMENSIONS
50mm THK. CEMENT/SAND SCREED
300x300x120 DEEP SUMP
WITH GRP GRATING COVER TANKING MEMBRANE
75mm THICK C20 BLINDING TITLE
1000 GAUGE POLYETHYLENE SHEET STANDARD DRAWINGS
SECTION B-B STORM WATER WORKS
DRAWING TITLE

TYPICAL DRAWING FLOW METER


CHAMBER DETAILS (DI FITTINGS)

DRAWN - SCALE 1 : 50
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
411

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS
OTHERWISE STATED.

LEGEND
GV - GATE VALVE
300x300x120 DEEP SUMP
DI - DUCTILE IRON
WITH GRP GRATING COVER
GRP - GLASS REINFORCED PLASTIC
GRP LADDER
AL - ALUMINIUM
IPF - INTEGRAL PUDDLE FLANGE
150 SQUARE CHAMBER
INDICATION PLATE DJ - DISMANTLING JOINT
FC - FLEXIBLE COUPLING

250
LIFTING HOOK (TYPICAL) GROUTING
STORM WATER
RISING MAIN ALUMINUM AIR VENT GRATING
COVER AND FRAME TO SUIT
(SHORT) GV
REINFORCED
600 DIA CLEAR OPENING
300 CEMENT CONCRETE
FC IPF IPF FC
CEMENT/SAND

B
FLOW SCREED
BLINDING CONCRETE
300

DI GRP
B ALUMINUM AIR VENT

C
GV DJ
B GRP DI
(LONG)
SOIL COMPACTED TO
95% MDD

250
SURFACE BOX
300 250 A 250 300 150 SQUARE OWNER
POSITIONED TO SUIT THE
INFORMATION PLATE
EXTENSION SPINDLE

SECTION A-A TOP VIEW OF COVER SLAB

SURFACE BOX PIPE DIA A B C


POSITIONED TO SUIT THE
EXTENSION SPINDLE 150 1500 1200 450
ALUMINUM AIR VENT (SHORT) 200 1500 1200 450
CHAMFER 25x25
250 1500 1200 450

FGL 300 1700 1400 500

400 1700 1400 500

REINFORCED CONCRETE CLASS 'B'


REFERENCE DRAWINGS AND DOCUMENTS
EPOXY COATING TO ALL
TANKING MEMBRANE INTERNAL SURFACES STANDARD DRAWING - TANKING DETAILS - 801
AND PROTECTION BOARD
VARIES

GRP COUPLING GRP DI DI GRP

FC IPF GV DJ IPF FC
A A
DN
300

PVC WATER STOP UPPER AND LOWER


PADS PTFE 5mm THK. GROUTING
CONSTRUCTION JOINT STEEL PLATE
400

CONCRETE VALVE SUPPORT BOX OUT CASING

STEEL PLATE WITH FISHTAIL


50mm THK. CEMENT/SAND SCREED
UNDER THE FLANGES
FOR DETAIL OF VALVE SUPPORT 4mm THICK TORCH APPLIED MEMBRANE
REFER TO DETAIL 'A' 75mm THICK C20 BLINDING DETAIL A No. REVISION-1 APP'D 2020
300x300x120 DEEP SUMP 1000 GAUGE POLYETHYLENE SHEET CLIENT
WITH GRP GRATING COVER

SECTION B-B
TITLE
STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

TYPICAL DRAWING ISOLATION VALVE


CHAMBER DETAILS (DI FITTINGS)

DRAWN - SCALE 1 : 50
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
412

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT
AND MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT
C PROJECT REQUIREMENTS. THEY ARE EXPECTED TO BE
INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
CHECKED AND APPROVED AS PART OF THE PROJECT
SURFACE BOX DRAWING SET.
300 300 A 300 300 150 SQUARE OWNER
POSITIONED TO SUIT THE
PIPE INFORMATION PLATE 1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS
A B C EXTENSION SPINDLE
LEVEL INVERT TEE DN OTHERWISE STATED.
STORM WATER
150 1500 1500 450 2. SIZE OF THE WASHOUT PIPE (DN2) TO BE AS PER
RISING MAIN
STORM WATER DESIGN MANUAL.
300

200 1500 1500 450


GRP DI DI GRP GRP COUPLING 250 1500 1500 450 LIFTING HOOK (TYPICAL) LEGEND
IPF IPF
DN1 ALUMINUM AIR VENT GV - GATE VALVE
C

300 1500 1500 450 (SHORT)


DI - DUCTILE IRON
400 1500 1500 450 HDPE - HIGH DENSITY POLYETHYLENE
500 1700 1700 500 GRP - GLASS REINFORCED PLASTIC
IPF - INTEGRAL PUDDLE FLANGE
B

FC FC
GRP COUPLING 600 1700 1700 500 FA - FLANGE ADAPTER
B GV B 800 2000 2000 1000
ALUMINUM AIR VENT
DJ - DISMANTLING JOINT
(LONG)
GRP LADDER FA FC - FLEXIBLE COUPLING
900 2000 2000 1000 GV 150 SQUARE CHAMBER
INDICATION PLATE GROUTING
1000 2000 2000 1000
GRATING
300

IPF
REINFORCED
CEMENT CONCRETE
300

COVER AND FRAME TO SUIT


CEMENT/SAND
DN2 600 DIA CLEAR OPENING
DI SCREED
300x300x120 DEEP SUMP BLINDING CONCRETE
WITH GRP GRATING COVER GRP
SOIL COMPACTED TO
GRP 95% MDD

DI
300

IPF

UPPER AND LOWER


150

PADS PTFE 5mm THK. GROUTING


1200 DIA

STEEL PLATE
CONCRETE VALVE SUPPORT BOX OUT CASING
GRP LADDER COVER AND FRAME TO SUIT
600 DIA CLEAR OPENING
STEEL PLATE WITH FISHTAIL
UNDER THE FLANGES
MIN
225

DETAIL A
150

150
TOP VIEW OF COVER SLAB
C

SECTION A-A
REFERENCE DRAWINGS AND DOCUMENTS
SURFACE BOX POSITIONED
COVER AND FRAME TO SUIT TO SUIT THE EXTENSION SPINDLE STANDARD DRAWING - TANKING DETAILS - 801
600 DIA CLEAR OPENING SURFACE BOX POSITIONED
ALUMINUM AIR VENT (LONG) COVER AND FRAME TO SUIT
325 MAX.
ALUMINUM AIR VENT (SHORT) 200 MIN.
TO SUIT THE EXTENSION ALUMINUM AIR VENT (SHORT)
600 DIA CLEAR OPENING
SPINDLE

PAVED CHAMFER 25x25


AREAS FGL
UNPAVED
250

AREAS
250

REINFORCED CONCRETE CLASS 'B'


TANKING MEMBRANE
AND PROTECTION BOARD EPOXY COATING
GRP LADDER
A A
VARIES

GRP LADDER
EXTENSION SPINDLE
EPOXY COATING TO ALL
INTERNAL SURFACES
No. REVISION-1 APP'D 2020
GRP DI
DI GRP CLIENT
300

IPF IPF DI GRP GRP DI

IPF IPF
VARIES

GRP LADDER
FC FC TITLE
STANDARD DRAWINGS
(MIN.)
400

GRP COUPLING 1% SLOPE GRP COUPLING


STORM WATER WORKS
1000
DRAWING TITLE
50

PVC WATER STOP


TYPICAL DRAWING WASHOUT
CONSTRUCTION JOINT 300x300x120 DEEP SUMP CHAMBER (TYPE-1)DETAILS (DI
420

FOR DETAIL OF VALVE SUPPORT WITH GRP GRATING COVER


REFER TO DETAIL 'A' FITTINGS)
300x300x120 DEEP SUMP
WITH GRP GRATING COVER 300 x 300 x 150
SECTION B-B DEEP SUMP DRAWN - SCALE 1 : 50
SECTION C-C CHECKED - DATE -
WASHOUT SUMP
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
413

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT
AND MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT
PROJECT REQUIREMENTS. THEY ARE EXPECTED TO BE
C INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
300 B A B A B 300 CHECKED AND APPROVED AS PART OF THE PROJECT
DRAWING SET.
ALUMINUM AIR VENT
(SHORT) LEGEND
GV - GATE VALVE

E
DI - DUCTILE IRON
IPF GRP - GLASS REINFORCED PLASTIC
DN1

D
IPF - INTEGRAL PUDDLE FLANGE
150 SQUARE OWNER FA - FLANGE ADAPTOR
INFORMATION PLATE
FC - FLEXIBLE COUPLING
DN1 150 SQUARE CHAMBER
GRP DI IPF DI GRP INDICATION PLATE GROUTING
DN2

C
B F
B DUCTILE IRON COVER AND FRAME TO GRATING
SUIT 750 DIA NOMINAL SIZE CLEAR REINFORCED
SL OPENING IN ALL CHAMBERS ON STORM
OP STFA DJ GV CEMENT CONCRETE
E1
GRP LADDER % GRP LADDER WATER PRESSURE MAINS
CEMENT/SAND
LIFTING HOOK (TYPICAL) SCREED

E
BLINDING CONCRETE
SOIL COMPACTED TO
300x300x120 DEEP SUMP ALUMINUM AIR VENT SURFACE BOX 95% MDD
WITH GRP GRATING COVER (LONG) POSITIONED TO SUIT THE
EXTENSION SPINDLE
C PIPE A B C D E
DN1 (mm) (mm) (mm) (mm) (mm)

100 1500 250 390 1300 250


200 1500 250 400 1300 250
SECTION A-A 250 1500 300 450 1350 300 TOP VIEW OF COVER SLAB
300 1500 300 500 1400 300
350 1500 300 600 1400 300
400 1500 300 800 1400 300
450 1800 300 850 1450 300
500 1800 300 900 1500 300
600 1800 350 1000 1600 350
700 1800 350 1100 1600 350
800 2000 400 1100 1800 400
900 2000 400 1100 1800 400
1000 2000 400 1100 1800 400

UPPER AND LOWER


PADS PTFE 5mm THK. GROUTING
STEEL PLATE
CONCRETE VALVE SUPPORT BOX OUT CASING

STEEL PLATE WITH FISHTAIL


SURFACE BOX POSITIONED TO SUIT UNDER THE FLANGES
THE EXTENSION SPINDLE
ALUMINUM AIR VENT (SHORT) ALUMINUM AIR VENT (LONG)
DETAIL A SURFACE BOX POSITIONED
TO SUIT THE EXTENSION ALUMINUM AIR VENT (SHORT)
SPINDLE

CHAMFER 25x25
REFERENCE DRAWINGS AND DOCUMENTS
FINISHED LEVEL OF
FINISHED LEVEL OF PAVED AREA (FL)
PAVED AREA (FL) STANDARD DRAWING - TANKING DETAILS - 801
UNPAVED
250

AREAS

EPOXY COATING TO
ALL INTERNAL
SURFACES EPOXY COATING TO ALL
INTERNAL SURFACES
TANKING MEMBRANE
VARIES

AND PROTECTION BOARD


TANKING MEMBRANE
EXTENSION SPINDLE AND PROTECTION BOARD

A A EXTENSION SPINDLE

GRP DI DI GRP
GRP COUPLING GRP COUPLING
IPF IPF IPF
No. REVISION-1 APP'D 2020
CLIENT
OD

HDPE DI DN1
FC FC
IPF DN2
300x300x120 DEEP SUMP
WITH GRP GRATING COVER
VARIES

1% SLOPE TITLE
PVC WATER STOP 1% SLOPE
STFA DJ GV
1% SLOPE STANDARD DRAWINGS
CONSTRUCTION JOINT
STORM WATER WORKS
DRAWING TITLE

50mm THK. CEMENT/SAND


50mm THK. CEMENT/SAND TYPICAL DRAWING
FOR DETAIL OF VALVE SUPPORT 300x300x120 DEEP SUMP SCREED
REFER TO DETAIL 'A'
SCREED
TANKING MEMBRANE
WITH GRP GRATING COVER TANKING MEMBRANE WASHOUT CHAMBER
75mm THICK C20 BLINDING
75mm THICK C20 BLINDING
1000 GAUGE POLYETHYLENE SHEET
(TYPE-2)DETAILS (DI
1000 GAUGE POLYETHYLENE SHEET
FITTINGS)
SECTION C-C
SECTION B-B DRAWN - SCALE 1 : 50
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG. 414
No. - No.

THIRD EDITION - APRIL 2022


NOTES:
ROAD WIDTH THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
6100 STRUCTURAL OPENING REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
STAINLESS STEEL ROTATING HANDLES CLEARANCE TO SUIT AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
ON BOTH SIDES OF GATE APPROVED AS PART OF THE PROJECT DRAWING SET.

1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS


STAINLESS STEEL FIXING BOLTS OTHERWISE STATED.
2. ALL CONCRETE TO BE C40 UNLESS OTHERWISE
STATED.
FIXED PIVOT 3. ABOVE THE GROUND BOUNDARY WALL TO BE
OUTSIDE FACE COATED WITH SILANE SILOXANE PRIMER AND
ALIPHATIC ACRYLIC TOP COAT OR SIMILAR
INSIDE FACE APPROVED WITH MINIMUM TOTAL THICKNESS
150 MICRONS APPLIED STRICTLY IN
OPENING LEAF SWING ACCORDANCE WITH MANUFACTURERS
REQUIREMENT. COLOR TO BE LIGHT GRAY AS
2 No. 350 x 350 MORTICE LOCK OPERABLE FROM APPROVED BY THE ENGINEER BELOW THE
STAINLESS STEEL STAPLES
CONCRETE CLASS 'A' GATE POSTS BOTH SIDES OF GATE
FOR PADLOCK CHAIN GROUND THE CONCRETE TO BE PAINTED WITH
6300
ALL GATE LOCKS TO BE SUBMASTER SYSTEM
2 COATS OF BITUMINOUS PAINT (MINIMUM 500
ALL INDIVIDUAL LOCKS TO BE SUPPLIED WITH MICRONS)
PLAN 2 No. KEYS
LEGEND
REINFORCED CONCRETE
250 x 350 x 20 STAINLESS
STEEL GATE STOP
BLOCKWORK
350 6100 350
25 DIA STAINLESS STEEL GATE RETAINING LUG SOIL COMPACTED TO 95% MDD
TO BE ARRANGED SUCH THAT LATCHED LEAF
50 3075 3075 50 OF GATE IS RESTRAINED BY THE GATE STOP 25 DIA STAINLESS STEEL DROP BOLT FGL FINAL GROUND LEVEL
AGAINST LIFTING WHEN THE GATE IS IN
50 50 50 CLOSED POSITION EJ EXPANSION JOINT
TOP & BOTTOM RAILS & STILES TO BE MINIMUM 50 x 100 SECTION STAINLESS STEEL STAPLE FOR
MIDDLE RAILS TO BE 2 No. 50 x 50 SECTIONS WITH VERTICAL TIES RESTRAINING POINT
OF 38 x 38 SECTION FACED WITH 2.5 THK ALUMINIUM SHEET
ALL SECTIONS TO BE HOLLOW ALUMINIUM

25 MIN
50 DIA HOLE FOR GATE RETAING LUG

1200
FRL
750

400 x 400 x 500 DEEP CONCRETE C40


LOCK & LATCH (SEE DETAILS) RETAINING BAR (ALUMINIUM) FOUNDATION FOR GATE STOP NOMINALLY
REINFORCED WITH 8 DIA LINKS VERTICALLY 50 DIA STAINLESS STEEL SOCKET TO
& HORIZONTALLY (LINKS OMITTED FOR CLARITY) BE GROUTED INTO 100 x 100 x 150
750

100
DEEP SLOT
38 x 38 HOLLOW ALUMINIUM
SECTIONS SPACED EQUALLY

900
AT APPROX. 150 CENTRES
300

DISTANCE BETWEEN GROUND LEVEL &


FRL UNDERSIDE OF BOTTOM RAIL VARIES
WITH SITE CONDITIONS
TYPICAL GATE DETAIL
200

SCALE 1:10
STAINLESS STEEL DROP
500

BOLTS & SOCKET

SEE TYPICAL GATE DETAILS REFERENCE DRAWINGS AND DOCUMENTS


350 STANDARD DRAWING - PRECAST BOUNDARY WALL DETAILS - 515
1½ PAIRS OF ADJUSTABLE HINGES PER OPENING LEAF CONSISTING OF
1 No. STAINLESS STEEL HINGE PIN WITH FISHTAIL FIXING FOR BUILDING SHEET 1 OF 2
1350 SIZE & FORMATION LEVEL OF FOOTINGS IN (MINIMUM LENGTH 250) & A STAINLESS STEEL LIFT OFF CIRCULAR STAINLESS STEEL BRACKET TO RESTRAIN STANDARD DRAWING - PRECAST BOUNDARY WALL DETAILS - 516
TO BE DETERMINED ON SITE HINGE BRACKET SECURELY FIXED TO GATE STILE HINGE PINS TO BE DROP_BOLT HANDLE AGAINST LIFTING SHEET 2 OF 2
THREADED TO RECEIVE STAINLESS STEEL NUTS. THREADS TO BE WHEN GATE IS CLOSED STANDARD DRAWING - BLOCK WORK BOUNDARY WALL
DAMAGED TO PREVENT REMOVAL AFTER FIXING 2 No. STAINLESS STEEL WASHERS - 517
DETAILS SHEET 1 OF 2
INTERNAL ELEVATION STANDARD DRAWING - BLOCK WORK BOUNDARY WALL - 518
OUTSIDE FACE DETAILS SHEET 2 OF 2

FIXED STAINLESS STEEL PIVOT


INSIDE HANDLE

TYPICAL LOCKING LATCH DETAIL


SCALE 1:5 No. REVISION-1 APP'D 2020
TYPICAL DROP - BOLT DETAIL
SCALE 1:5 CLIENT

STAINLESS STEEL GATE LATCH


SUITABLE FOR STAPLE ON GATE
TITLE
STANDARD DRAWINGS
DIMENSIONS TO BE DETERMINED
FROM FIXTURES USED & RELATIVE
STORM WATER WORKS
LEVELS OF GROUND & GATE
DRAWING TITLE

STANDARD DRAWING
FRL
PUMPING STATION ALUMINUM
300 x 300 PLAIN CONCRETE C20 SITE ENTRANCE GATE
FOUNDATION FOR GATE LATCH
DECORATIVE RAILING TO BE
25 x 25 HOLLOW ALUMINIUM
SECTION BACKING ON 18
GAUGE ALUMINIUM SHEET DRAWN - SCALE AS SHOWN
CHECKED - DATE -
TYPICAL GATE LATCH DETAIL
SCALE 1:5 APPROVED - SIZE A1
EXTERNAL ELEVATION PROJECT DWG.
No. - No.
514

THIRD EDITION - APRIL 2022


NOTES:
C
L WALL PANELS THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT FINAL
220 160 120 DESIGN SHALL BE BASED ON SITE SPECIFIC PROJECT
REQUIREMENTS. GROUND CONDITIONS TOPOGRAPHY, WIND
C
L COLUMN C
L COLUMN LOADING AND SECURITY REQUIREMENTS. FINAL DESIGN
175 175 25 EJ 175 175 SHALL BE SUBJECT TO THE APPROVAL OF THE ENGINEER.
1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS
100 350 350 100 150 100 OTHERWISE STATED.
C 2. ALL CONCRETE TO BE C40 UNLESS OTHERWISE
L COLUMN
STATED.

100
3. ABOVE THE GROUND BOUNDARY WALL PLINTH TO BE

220
COATED WITH SILANE SILOXANE PRIMER AND

300
120

120

3000 CRS
APPROX.
ALIPHATIC ACRYLIC TOP COAT OR SIMILAR

200

200
APPROVED WITH MINIMUM TOTAL THICKNESS 150

500

625
MICRONS APPLIED STRICTLY IN ACCORDANCE WITH
400

400
160

160

160
C
L WALL PANELS MANUFACTURERS REQUIREMENT. COLOR TO BE
LIGHT GRAY AS APPROVED BY THE ENGINEER.

200

200

200
C
L COLUMN
120

120

120
LEGEND

625
CLEAR 350 350 100 REINFORCED CONCRETE
OPENING AT GATE COLUMNS
GATES 300 200 SOIL COMPACTED TO 95% MDD

500 C
L CENTER LINE
750 750
FGL FINAL GROUND LEVEL
EJ EXPANSION JOINT
GATE COLUMN EXPANSION JOINT INTERMEDIATE COLUMN CORNER COLUMN

3125 CRS APPROX.


TYP TYPICAL
SCALE 1:20 SCALE 1:20 SCALE 1:20 SCALE 1:20

PLOT LINE
COLUMN DETAILS

C
L GATE COLUMN GATE COLUMN CL C
L GATE COLUMN C
L INTERMEDIATE COLUMN C
L INTERMEDIATE COLUMN
625 625 625 375 625 625 625 625 625

350

PC WALL PANEL
(TYP)

(TYP)
750

750

750
750

300
(TYP)
400

C
L COLUMN

200
750

750

750
300 200

750
PLOT LINE

750 750
SECTION A-A

3000 CRS 3000 CRS 375 3000 CRS 3000 CRS 3000 CRS APPROX. 3125 CRS APPROX.
APPROX. APPROX. APPROX. APPROX.
25 EJ 500
REFERENCE DRAWINGS AND DOCUMENTS
350 350 350 350 225 TO SUIT 225 350 300 200 STANDARD DRAWING - PRECAST BOUNDARY WALL - 516
(TYP) (TYP) DETAILS
SHEET 2 OF 2

SLOTS FOR LIFTING EYES


INFILLED WITH RENDER (TYP)

450
2300 HIGH PC WALL PANELS

A A

625
125 125
EXTENT OF EXPANSION JOINT

(TYP) (TYP)

3000 ALL PC COLUMNS


1250
No. REVISION-1 APP'D 2020

2400
CLIENT

625
TITLE
STANDARD DRAWINGS
STORM WATER WORKS
FGL FGL DRAWING TITLE
200

TYPICAL DRAWING
PRECAST BOUNDARY WALL
RC PAD FOOTING

DECORATION FORMED IN DECORATION TO CORNER


THE FACE OF CONCRETE COLUMNS TO BE CENTRAL TO THE
DETAILS SHEET 1 OF 2
800 DEEP

FACE OF THE COLUMN

1000
EXTERNAL ELEVATION ONLY

DRAWN - SCALE AS SHOWN


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
515

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
100 MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS.FINAL DESIGN SHALL BE BASED ON SITE
SPECIFIC GROUND CONDITIONS TOPOGRAPHY, WIND
GROOVE C C GROOVE
LOADING AND SECURITY REQUIREMENTS. FINAL DESIGN
SHALL BE SUBJECT TO THE APPROVAL OF THE ENGINEER.

500
C
GROOVE 1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS

500
OTHERWISE STATED.
1
400 155 (THIS DIMENSION MAY BE 2. ALL CONCRETE TO BE C40 UNLESS OTHERWISE STATED.
- 3. ABOVE THE GROUND BOUNDARY WALL TO BE COATED
= = ADJUSTED TO SUIT SITE SPECIFIC CONDITION
SUBJECT TO THE APPROVAL OF THE ENGINEER WITH SILANE SILOXANE PRIMER AND ALIPHATIC ACRYLIC
TOP COAT OR SIMILAR APPROVED WITH MINIMUM TOTAL
THICKNESS 150 MICRONS APPLIED STRICTLY IN
SLOTS FOR LIFTING EYES
ACCORDANCE WITH MANUFACTURERS REQUIREMENT.
TO BE IN FILLED WITH GROOVE COLOR TO BE LIGHT GRAY AS APPROVED BY THE

90°
CEMENT MORTAR TO

20
C ENGINEER.
FORM FLUSH FINISH
4. BARBED WIRE TOPPING SUBJECT TO SITE SPECIFIC
SECURITY REQUIREMENTS.

TO SUIT COLUMN CENTRES ( HORIZONTAL DECORATION )


20 WIDE GROOVE
(TYP.)

SLOTS FOR

1250 (VERTICAL DECORATION)


PRECAST WALL
PANEL

EXTERNAL FACE
3000 INTERMEDIATE, GATE AND CORNER COLUMNS

OF BLOCKWORK

DECORATION IN THE EXTERNAL

2300
FACE OF CONCRETE WALLS ONLY

TYPICAL GROOVE DETAILS


SCALE 1:2

SEE NOTE 3

STEEL POST

COLUMN POCKET DIMENSIONS


500 x 400 x 300 DEEP FOR INTERMEDIATE COLUMNS COLUMNS COATED WITH 2 SEE NOTE 3
500 x 400 x 300 DEEP FOR GATE COLUMNS COATS OF EPOXY PAINT FROM C 8mm THICK PLATE
600 x 600 x 300 DEEP FOR CORNER COLUMNS BASE TO 150 ABOVE FGL GROOVE
500 x 825 x 300 DEEP FOR EXPANSION JOINTS 4Nos.Ø8mm EXPANSION BOLTS

INTERNAL EXTERNAL EXTERNAL DECORATION IN THE EXTERNAL CONCRETE MIX GROUT

100
FGL FGL INTERNAL FGL FGL FACE OF CONCRETE WALLS ONLY

2 COATS OF EPOXY 300 BARBED WIRE STEEL POST


200

PAINT TO ALL REFERENCE DRAWINGS AND DOCUMENTS


SURFACES DETAIL OF DECORATION DETAIL 1 STANDARD DRAWING - PRECAST BOUNDARY WALL - 515
GROUT FILL TO FOOT OF -
1 : 20 DETAILS
COLUMN 400 SCALE 1:10
SHEET 1 OF 2
POCKET
400

1000

PRECAST CONCRETE WALL


PANEL
800

TANKING MEMBRANE AND PLINTH


AND PROTECTION BOARD 2820
400

INSITU R.C. PAD FOOTING


300

No. REVISION-1 APP'D 2020


CLIENT
250 250 50mm THK. CEMENT/SAND SCREED
POCKET TANKING MEMBRANE 2 COATS OF EPOXY
75mm THICK C20 BLINDING ELEVATION PAINT TO ALL
750 750 1000 GAUGE POLYETHYLENE SHEET SURFACES
TITLE
1500 STANDARD DRAWINGS
PLOT LINE
2820 STORM WATER WORKS
85 85
PRECAST CONCRETE COLUMNS DRAWING TITLE
INTERMEDIATE COLUMN SHOWN
TYPICAL DRAWING PRECAST
BOUNDARY WALL DETAILS
400
150

SHEET 2 OF 2

DRAWN - SCALE AS SHOWN


2 COATS OF EPOXY
PLAN PAINT TO ALL CHECKED - DATE -
SURFACES
PLINTH BEAM DETAILS APPROVED - SIZE A1
PROJECT DWG.
No. - No. 516

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. FINAL DESIGN SHALL BE BASED ON SITE
SPECIFIC GROUND CONDITIONS TOPOGRAPHY, WIND LOADING
AND SECURITY REQUIREMENTS. FINAL DESIGN SHALL BE
SUBJECT TO THE APPROVAL OF THE ENGINEER.
1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS
OTHERWISE STATED.

LEGEND
REINFORCED CONCRETE

BLOCKWORK

SOIL COMPACTED TO 95% MDD

3000
PLAIN CONCRETE

FGL FINAL GROUND LEVEL


1350 EJ EXPANSION JOINT
B A C
INTERMEDIATE COLUMN R.C. REINFORCED CONCRETE
EXPANSION JOINT GATE COLUMN
CORNER COLUMN DETAIL 2 DETAIL 3 DETAIL 4
DETAIL 1
C
L CENTER LINE

1350
1000

25

3000 225 3000 3000 3000 3000 3000


APPROX. APPROX. APPROX. APPROX.
B A C PLAN
2400

INTERNAL
FINISHED LEVEL
FGL

REFERENCE DRAWINGS AND DOCUMENTS


STANDARD DRAWING - PUMPING STATION ALUMINUM - 514
SITE
ENTRANCE GATE - 518
STANDARD DRAWING - BLOCK WORK BOUNDARY WALL
DETAILS SHEET 2 OF 2

EXTERNAL ELEVATION

INTERNAL SIDE
18 THK 18 THK
C
L COLUMN
RENDER RENDER

INTERNAL SIDE 350 R.C. COLUMN


No. REVISION-1 APP'D 2020
CL COLUMN
GMS FISH TAIL TIES CLIENT
200 X 230 R.C. COLUMN EVERY 4th COURSE
200 X 230 R.C. COLUMN 200 X 230 R.C. COLUMN

RENDER

RENDER
18 THK

18 THK
25 EJ

350 R.C. COLUMN


TITLE
STANDARD DRAWINGS
CL COLUMN
STORM WATER WORKS
190 BLOCK WORK
230 R.C. COLUMN

190 BLOCKWORK

190 BLOCKWORK
DRAWING TITLE
C
L COLUMN CL BLOCKWORK

TYPICAL DRAWING BLOCKWORK


BOUNDARY WALL DETAILS
150
SHEET 1 OF 2
C
L COLUMN C
L COLUMN
230 R.C. COLUMN (MIN.)
RENDER

RENDER
18 THK

18 THK
RENDER TO TERMINATE
EACH SIDE OF EJ ( TYP. ) 3000 CRS. APPROX. 3000 CRS. APPROX. 3000 CRS. APPROX.
DRAWN - SCALE AS SHOWN
EXTERNAL SIDE
EXTERNAL SIDE CHECKED - DATE -
CORNER COLUMN - DETAIL 1 EXPANSION JOINT - DETAIL 2 INTERMEDIATE COLUMN - DETAIL 3 GATE COLUMN - DETAIL 4 APPROVED - SIZE A1
SCALE 1:10 SCALE 1:10 SCALE 1:10 SCALE 1:10 PROJECT DWG.
No. - No.
517

THIRD EDITION - APRIL 2022


NOTES:
SITE BOUNDARY THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
SITE BOUNDARY MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. FINAL DESIGN SHALL BE BASED ON SITE
SPECIFIC GROUND CONDITIONS TOPOGRAPHY, WIND LOADING
AND SECURITY REQUIREMENTS. FINAL DESIGN SHALL BE
PRECAST CONCRETE SUBJECT TO THE APPROVAL OF THE ENGINEER.
COPING SEE DETAIL 5
1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS
OTHERWISE STATED.
2. ABOVE THE GROUND BOUNDARY WALL TO BE COATED
WITH SILANE SILOXANE PRIMER AND ALIPHATIC
ACRYLIC TOP COAT OR SIMILAR APPROVED WITH
MINIMUM TOTAL THICKNESS 150 MICRONS APPLIED
STRICTLY IN ACCORDANCE WITH MANUFACTURERS
REQUIREMENT. COLOR TO BE LIGHT GRAY AS
APPROVED BY THE ENGINEER.

LEGEND
190 WIDE SOLID BLOCKWORK
FROM 390 x 190 x 190 BLOCK SIZE REINFORCED CONCRETE

BLOCKWORK

SOIL COMPACTED TO 95% MDD

1950
PLAIN CONCRETE

FGL FINAL GROUND LEVEL


200 x 230 R.C. COLUMN EJ EXPANSION JOINT
R.C. REINFORCED CONCRETE
C
L CENTER LINE
18 THK BASE COAT RENDER

SEE NOTE 2

150
2 COATS OF BITUMINOUS PAINT

SEE NOTE 2 SEE NOTE 2

450
DETAIL 7
150

150
2 COATS OF BITUMINOUS PAINT 2 COATS OF BITUMINOUS PAINT

500
230

500
R.C CONTINUOUS FOOTING
REFERENCE DRAWINGS AND DOCUMENTS

300
TANKING MEMBRANE TANKING MEMBRANE STANDARD DRAWING - BLOCK WORK BOUNDARY WALL - 517
AND PROTECTION BOARD AND PROTECTION BOARD DETAILS SHEET 1 OF 2

1000 1350

50mm THK. CEMENT/SAND SCREED 50mm THK. CEMENT/SAND SCREED 50mm THK. CEMENT/SAND SCREED
TANKING MEMBRANE TANKING MEMBRANE TANKING MEMBRANE
75mm THICK C20 BLINDING 75mm THICK C20 BLINDING 75mm THICK C20 BLINDING
SECTION A-A 1000 GAUGE POLYETHYLENE SHEET SECTION B-B 1000 GAUGE POLYETHYLENE SHEET SECTION C-C 1000 GAUGE POLYETHYLENE SHEET
SCALE 1:20 SCALE 1:20 SCALE 1:20

No. REVISION-1 APP'D 2020


140 140 CLIENT
PRECAST CONCRETE
COPING UNIT 100

190 WIDE BLOCKWORK


50

TITLE
STANDARD DRAWINGS
150

50

18 THK RENDER
STORM WATER WORKS
10

DRAWING TITLE
10

TYPICAL DRAWING BLOCKWORK


RENDER
R.C WALL BOUNDARY WALL DETAILS
SHEET 2 OF 2
18
18 190 50 DRAWN - SCALE AS SHOWN
CHECKED - DATE -
DETAIL 5 DETAIL 7 APPROVED - SIZE A1
SCALE 1:10 SCALE 1:10
PROJECT DWG.
No. - No.
518

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
25 BAYS AT 2000MAX = 50000 MAX TO STRAINER POST 25 BAYS AT 2000MAX = 50000 MAX TO STRAINER POST REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
C GATE POST
114 DIA CHS C GATE POST
114 DIA CHS APPROVED AS PART OF THE PROJECT DRAWING SET.
2000 MAX. TO INTERMEDIATE POST ROAD WIDTH + 900 = VEHICLE GATE POST CENTRES 2000 MAX. TO INTERMEDIATE POST 1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS
OTHERWISE STATED.
VEHICLE GATE POST CENTRES - 254 = GATE LEAVES
2. STRAINER POSTS TO BE PROVIDED AT CHANGES OF
GATE LEAF GATE LEAF DIRECTION AND AT ACUTE VARIATIONS OF LEVEL.
3. ALL GALVANISED POSTS, EXTENSION ARMS, FRAMING
20 GAP AND BRACING MEMBERS SHALL BE POWDER COATED
(PHOSPHATE COAT).
4. GATE FRAMES AND DIAGONAL BRACING TO BE DRILLED
THROUGH AT N.M.T. 450 CENTRES FOR ATTACHING MESH
WITH 2.3/3.2 DIA STIRRUP WIRE

3 DIA PVC COATED CHAINLINK LEGEND


FENCING 50 x 50 MESH FIXED OUTSIDE INSIDE
TO FRAME AND DIAGONALS

150
REINFORCED CEMENT
WITH STIRRUP WIRE THROUGH 3 DIA. PVC COATED
CHAIN LINK MESH CONCRETE
HOLES (TYP.) CHAINLINK FENCING
20 DIA HINGE PIN (TYP.) 50x50 MESH (TYP.) CHS POSTS SOIL
BRACING 63 DIA CHS (TYP.)

2000 (TYP.)

2000 (TYP.)
25 DIA HEAT PROTECTED
3 No HINGES / LEAF DIAGONAL BRACINGS
STAINLESS STEEL 60 DIA CHS (TYP.) 5 DIA HOLES FOR
STIRRUP WIRE (TYP.) EGL - EXISTING GROUND LEVEL
U HANDLES TO BOTH SIDE WITH 5 DIA HOLES
HINGE PLATE FOR STIRRUP WIRE
16 THK (TYP.) OF EACH GATE LEAF (TYP.) SECURITY BOLT (TYP.) FGL - FINISHED GROUND LEVEL
TURNBUCKLE (TYP.)
DROP BOLT STOP (TYP.) DROP BOLT (TYP.)
FRL - FINISHED ROAD LEVEL
GATE FRAMES 80 DIA CHS (TYP.)
WITH 5 DIA HOLES FOR STIRRUP WIRE SLOPED TOP TO ALL CHS - CIRCULAR HOLLOW SECTION
POST FOUNDATIONS
RHS - RECTANGULAR HOLLOW SECTION

25
EGL EGL
FRL ( FGL ) (FGL)
PVC - POLYVINYL CHLORIDE

250
DIA - DIAMETER
SLAM PLATE (SHOWN UP)
100

(THIS DIMENSION MAY VARY FLUSH KERBS TO BE


TO SUIT ROAD LONGITUDINAL USED AT GATES (TYP.) TYP - TYPICAL
GRADIENT OR OTHER SITE CONCRETE BASE FOR
CONDITIONS) SLAM PLATE

CLASS B
CONCRETE (TYP.)

6.0m MAINTENANCE ACCESS GATE TYPICAL SECTION

25 BAYS AT 2000MAX = 50000 MAX TO STRAINER POST 25 BAYS AT 2000MAX = 50000 MAX TO STRAINER POST

C GATE POST
114 DIA CHS
C GATE POST
114 DIA CHS
2000 MAX. TO INTERMEDIATE POST ROAD WIDTH + 900 = VEHICLE GATE POST CENTRES 2000 MAX. TO INTERMEDIATE POST

VEHICLE GATE POST CENTRES - 254 = GATE LEAVES


REFERENCE DRAWINGS AND DOCUMENTS
GATE LEAF

25 DIA HEAT PROTECTED


STAINLESS STEEL
U HANDLES TO BOTH SIDE OF
LINE WIRE (TYP.)
EACH GATE LEAF (TYP.) 3 DIA PVC COATED CHAINLINK
FENCING 50x50 MESH FIXED TO
FRAME AND DIAGONALS WITH
3 DIA PVC COATED CHAINLINK STIRRUP WIRE THROUGH HOLES
FENCING 50 x 50 MESH FIXED (TYP.)
TO FRAME AND DIAGONALS
150

WITH STIRRUP WIRE THROUGH 25 DIA HEAT PROTECTED STAINLESS


HOLES (TYP.) STEEL U HANDLES TO BOTH SIDE OF
20 DIA HINGE PIN (TYP.) LINE WIRE (TYP.) EACH GATE LEAF (TYP.)
BRACING 63 DIA CHS (TYP.)
2000 (TYP.)
3 No HINGES / LEAF SECURITY BOLT (TYP.)
HINGE PLATE
DROP BOLT STOP (TYP.) SECURITY BOLT (TYP.)
No. REVISION-1 APP'D 2020
TURNBUCKLE (TYP.) 16 THK (TYP.)
DROP BOLT (TYP.) CLIENT
25x6 STRETCHER
BAR SECURED TO GATE FRAMES 80 DIA CHS (TYP.) (THIS DIMENSION MAY VARY TO SUIT
GATE POST AND WITH 5 DIA HOLES FOR STIRRUP WIRE LINE WIRE (TYP.) ROAD LONGITUDINAL GRADIENT OR
STRAINER POSTS OTHER SITE CONDITIONS)
EGL
( FGL )
FRL FRL TITLE
STANDARD DRAWINGS
250

STORM WATER WORKS


100

100
(THIS DIMENSION MAY SLAM PLATE
VARY TO SUIT ROAD (SHOWN UP)
LONGITUDINAL GRADIENT
DRAWING TITLE

900
OR OTHER SITE CONDITIONS) CONCRETE BASE
FOR SLAM PLATE
FLUSH KERBS TO BE
USED AT GATES (TYP.) STANDARD DRAWING FENCING AND
SECURITY WORKS GATE FOR SITE
FENCING DETAIL (SHEET 1 OF 2)
500 SQ. 500 SQ.
( TYP. ) ( TYP. )
DRAWN - SCALE 1 : 40
CHECKED - DATE -
3.0m MAINTENANCE ACCESS GATE PEDESTRIAN GATE APPROVED - SIZE A1
PROJECT DWG.
No. - No.
519

THIRD EDITION - APRIL 2022


NOTES:
40 x 50 x 10 THK. THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
450 O/A BOLT
BOLT STOPS ( ONE TO EACH MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
GATE LEAF ) REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
150
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS
OTHERWISE STATED.
GRIND OFF SHARP EDGES 2. STRAINER POSTS TO BE PROVIDED AT CHANGES OF
DIRECTION AND AT ACUTE VARIATIONS OF LEVEL.
50 x 50 x 10 THK. PLATE 3. ALL GALVANISED POSTS, EXTENSION ARMS, FRAMING
25 DIA HEAT PROTECTED WITH 28 DIA HOLE FOR
STAINLESS STEEL DROP BOLT AND BRACING MEMBERS SHALL BE POWDER COATED
U HANDLES (PHOSPHATE COAT).
HOLE FOR STIRRUP WIRE FOR
4. GATE FRAMES AND DIAGONAL BRACING TO BE DRILLED
ATTACHING MESH FENCING (TYP.)
200x150x10 THK. THROUGH AT N.M.T. 450 CENTRES FOR ATTACHING
PLATE F.W. TO CHS 80 DIA GATE FRAME 25 DIA DROP BOLTS MESH WITH 2.3/3.2 DIA STIRRUP WIRE
MEMBERS ( ONE TO EACH GATE LEAF )
ROUNDED LEADING AT 100 CENTRES. ROUND
END TO BOLT OFF LEADING END OF BOLT LEGEND
REINFORCED CEMENT
16 DIA BOLT
CONCRETE
A C
L BOLT
A GALVANISED MILD STEEL 50 x 50 x 10 THK. PLATE
WITH 28 DIA HOLE FOR
THK SLAM PLATE ASSEMBLY
( SEE DETAIL ) DROP BOLT, WELDED TO SOIL
40 x 40 x 10 THK. BOTTOM GATE FRAME MEMBER
LUG WITH 12 DIA 40 x 10 LUGS WITH 18 DIA
HOLE FOR PADLOCK HOLE FOR BOLT LUGS F.W. TO CHS - CIRCULAR HOLLOW SECTION
PLATE OR CHS (TYP.)
EGL - EXISTING GROUND LEVEL
40 x 80 x 6 FLAP PLATE
250 WITH 42 x 12 SLOT FOR LUG DETAIL A FGL - FINISH GROUND LEVEL
F.W. TO BOLT AT LOCATION SHOWN
FRL - FINISH ROAD LEVEL

20 GAP FRL RHS - RECTANGULAR HOLLOW SECTION


CHS GATE FRAME CL CL CHS GATE FRAME PVC - POLYVINYL CHLORIDE

LOCK DETAILS

250
90 DIA ( ONLY ) HINGE HOLDING DOWN BOLT ( TYP. )
TO SLAM PLATE
SECTIONS OF MILD STEEL PIPE
CONCRETE BASE ( 40 DIA APPROX. ) WITH
CAPPING PIECES, WELDED TO
UNDERSIDE OF SLAM PLATE
SITE FENCING DETAIL ( ONE FOR EACH DROP BOLT
AT 100 CENTRES )

25 BAYS AT 2000 MAX. = 50000 MAX. CORNER POST TO FIRST STRAINER POST 25 BAYS AT 2000 MAX. = 5000 MAX. TO NEXT STRAINER POST

2000 MAX. 2000 MAX.* 2000 MAX.* 2000 MAX.*


TO ADJACENT TO ADJACENT INTERMEDIATE POST ADJACENT INTERMEDIATE POST
INTERMEDIATE
POST

CORNER POST INTERMEDIATE POST STRAINER POST


C C C
100

75 DIA CHS 63 DIA CHS 63 DIA CHS


GATE FRAME
GATE FRAME OUTER FACE OF PLATE
TO BE FLUSH WITH CHS
OUTER EDGE

LINE WIRE (TYP.) REFERENCE DRAWINGS AND DOCUMENTS


C
L
LINE WIRE (TYP.) BOLT
M10 BOLT (TYP.)
LINE WIRE NOT FIXED
TO BRACING (TYP.)
3 DIA PVC COATED
TURNBUCKLE TO EACH CHAINLINK FENCING 30°
SECTION A-A
30° LINE WIRE IN FIRST BAY 50 x 50 MESH (TYP.) APPROX.
APPROX. OF CORNERS AND ENDS
(TYP.) (TYP.)
2000

LINE WIRE (TYP.) MESH FIXED TO LINE


WIRES AT 450 CRS
WITH STIRRUP WIRE (TYP.) 12 THK SLAM PLATE

BRACING 63 DIA CHS (TYP.)


(EACH WAY AT CORNER POST)
No. REVISION-1 APP'D 2020
25 x 6 STRETCHER
BARS SECURED TO CLIENT
STRAINER POSTS HINGE 90° ONLY
LINE WIRE (TYP.)
50

LINE WIRE (TYP.)


25

FGL MILD STEEL PLATE SUPPORT

TITLE
300

4 No. BOLTS STANDARD DRAWINGS


500

STORM WATER WORKS


700
900

DRAWING TITLE

STANDARD DRAWING FENCING AND


500 SQ. 2 No. HOLES FOR
DROP BOLTS 25 DIA
SECURITY WORKS GATE FOR SITE
(TYP.) * 2000 MAXIMUM CENTRES BTWEEN POSTS AT
EQUAL CENTRES BETWEEN CORNER POST OR
FENCING DETAIL (SHEET 2 OF 2)
400 SQ.
AT EQUAL CENTRES BETWEEN GATE POST AND SLAM PLATE DETAIL A
CORNER POST NTS
(TYP.) DRAWN - SCALE 1 : 10
CHECKED - DATE -
TYPICAL EXTERNAL ELEVATION AT CORNER POST TYPICAL EXTERNAL ELEVATION AT STRAINER POST
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
520

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
FGL FGL
UV-RESISTANT PVC-u PLUG MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
PLAIN CONCRETE AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
500x500x300 APPROVED AS PART OF THE PROJECT DRAWING SET.
EXCAVATED OR IMPORTED EXCAVATED OR IMPORTED FINAL GL
FILL MATERIAL FILL MATERIAL 1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS
TABLE A : TABLE OF PERFORATION DIMENSIONS OTHERWISE STATED
2. PERFORATED PIPES ARE CLASS 10 PVC-U PIPES UNLESS
OD WIDTH (mm) AREA2 Min.PITCH REINSTATED TO PVC-u PIPE OTHERWISE STATED.
mm Min. Max. mm/m mm ORIGINAL SOIL
3. PERFORATED PIPES ARE CLASS 16 PVC-U PIPES WHERE
180 MINIMUM

160 4 5 4500 150 USED UNDER TRAFFIC AREAS.

180 MINIMUM
225 4 5 6000 150 4. 300mm DIA PERFORATED PIPE IS 315mm DIA PVC-U,
APPROVED GEOTEXTILE FILTER APPROVED GEOTEXTILE FILTER 200mm DIA PERFORATED PIPE IS 225mm DIA PVC-U,
FABRIC SUFFICIENT SLACK SHALL 280 4 5 8000 150
FABRIC SUFFICIENT SLACK 150mm DIA PERFORATED PIPE IS 160mm DIA PVC-U
BE PROVIDED DURING SHALL BE PROVIDED DURING 315 4 5 9000 150
300
INSTALLATION OF THE FABRIC TO GRAVEL 20mm, 5. INVERT LEVEL FOR PERFORATED PIPES SHALL BE
LAP 300 INSTALLATION OF THE FABRIC
AVOID TEARING WHEN PIPE LAP SIZE DETERMINED & CONFIRMED AT SITE AFTER GROUND
BEDDING
TO AVOID TEARING WHEN PIPE
BEDDING MATERIAL IS PLACED.
PERFORATED PIPE DETAILS PVC-u PIPE WATER TABLE INVESTIGATION.
OD

6. MANUFACTURER TO SUBMIT CLASS AND DIMENSIONS

OD
AGGREGATE SURROUND AS SPECIFIED
AGGREGATE SURROUND AS SPECIFIED
OF COVER ACCORDING TO SPECIFICATIONS BASED ON
PERFORATED PIPE SLOTTED / PVC-u 900 ACTUAL SITE CONDITIONS & TO BE APPROVED PRIOR
(MIN. DIA 160) PERFORATED PIPE
FGL PERFORATED BEND TO MANUFACTURING.
(MIN. DIA 160)
100 MINIMUM

B PVC-u PIPE

100 MINIMUM
100 OD 100
(MIN.) (MIN.) 100 OD 100
(MIN.) (MIN.) LEGEND
SELECTED BACKFILL PITCH PITCH 45° 45°
( SEE TABLE A ) PVC-U POLYVINYL CHLORIDE - UNPLASTICISED

1.00 m
MATERIAL FREE FROM
LARGE STONES ETC.
TYPICAL CROSS SECTION FOR PIPE END
FGL FINISHED GROUND LEVEL
LIGHTLY COMPACTED
TYPICAL SECTION THROUGH A LAND DRAIN PE
R

OD
BY HAND IN 150 THK FO OD OUTSIDE DIAMETER
LAYERS. R
AT

(S
IO TABLE B : TABLE OF INSPECTION CHAMBERS GWT GROUND WATER TABLE

EE
N

TA
LE ON SUBSOIL DRAINAGE SYSTEMS

BL
N
G
MIN MINIMUM

E
B TH

A
STORM WATER PIPELINE

)
DEPTH (D) LENGTH (A) WIDTH (B) CL COVER LEVEL
mm mm mm
ELEVATION
D < 2000 600 600
SECTION B - B
PERFORATION WIDTH 2000 < D < 2800 1000 1000
REFERENCE DRAWINGS AND DOCUMENTS
( SEE TABLE A )
VARIES STANDARD DRAWING - SUBSOIL DRAINAGE GROUND WATER - 602
LOWERING PAVEMENT SUBBASE - 603
TYPICAL SECTION SHOWING COMBINED PIPES (STORM DRAINAGE DETAILS
STANDARD DRAWING - PIPE PLUG DETAILS - 801
WATER & PERPORATED) IN SAME TRENCH STANDARD DRAWING - CONSTRUCTION AND MOVEMENT JOINT - 1001
FINISHING AROUND COVER AND FRAME FINISHING AROUND COVER FRAME STANDARD DRAWING - MISCELLANEOUS DETAILS - 207
PERFORATED PIPES A
(TABLE B) FOR UNPAVED AREA FOR TILED AREA FOR MANHOLES
1000 UNPERFORATED PIPE STANDARD DRAWING - REINFORCEMENT DETAILS - 1000
INDICATIVE DETAIL FOR STORM WATER STRUCTURE PLAN AS SPECIFIED UV RESISTANCE STANDARD DRAWING - STORM WATER MANHOLE FRAME
(SERIES)
- 213
(MANHOLE / INLET / CATCH BASIN / INSPECTION EPOXY COATING TO ALL AND COVER DETAILS
CHAMBER) SURFACES ABOVE GROUND DUCTILE IRON COVER
300 300
CL TILE LEVEL STANDARD DRAWING - STORM WATER INLET DETAILS - 209
UNPERFORATED PIPE FGL (MAXIMUM DEPTH 2.0m)
STANDARD DRAWING - STORM WATER INLET DETAILS (DEPTH - 210
VARYING BETWEEN 2.0m AND 2.8m)

50
100
STANDARD DRAWING - STORM WATER CATCH BASIN DETAILS - 211
(MAXIMUM DEPTH 2.0m)
STANDARD DRAWING - STORM WATER CATCH BASIN DETAILS - 212
A A
(TABLE B)

(DEPTH VARYING BETWEEN 2.0m AND 2.8m)


FLOW FLOW STEP IRON AS
B

SPECIFIED
(FOR CHAMBER DEPTH
EXCEEDING 2.0m AND
LESS THAN 2.8m)

(TABLE B)
D
A
(TABLE B)
GEOTEXTILE
GEOTEXTILE FILTER FABRIC FILTER FABRIC
EPOXY COATING AS
PLAN SPECIFIED ON ALL
INTERIOR CONCRETE
TYPICAL PERFORATED PIPE CONNECTION TO STORM WATER
SURFACES
STRUCTURE (MANHOLE / INLET / CATCH BASIN / INSPECTION CHAMBER) SL
O
T
LE
N
G
TH
PERFORATED PIPES
C C
(TABLE B)
B

1000 UNPERFORATED PIPE


PLUG & SOCKET 100
ARE PROJECTION see Note 6
RESTRAINED SINGLE SIZE 10mm No. REVISION-2 APP'D 2021
WITH WATER AGGREGATE
PROOF SURROUND CIRCULAR SHAPE RECTANGULAR SHAPE
CLIENT
WRAPPING TAPE
GRP COVER DETAILS REINFORCED CONCRETE

GRP RECESSED COVER 200


500

FGL FGL TITLE


PVC-U PIPE ( CLASS 10 )
DUCTILE IRON COVER STANDARD DRAWINGS
AND FRAME TO SUIT
600x600. OPENING STORM WATER WORKS
200

PLAN (COVER DETAILS) DRAWING TITLE


500

300mm DIA. 2500 STIFF GRP


EXCAVATED AREA WITH INDICATIVE DETAIL FOR SUBSOIL DRAINAGE STANDARD DRAWING SUBSOIL
SELECTED EXCAVATED SUITABLE BACKFILL INSPECTION CHAMBER A
BACKFILL FREE FROM INSIDE FACE OF CHAMBER 300 mm GRP EQUAL TEE (TABLE B) DRAINAGE GROUND WATER
LARGER STONE
COMPACTED IN LAYERS GRP/uPVC LOWERING PERFORATED PIPES
GEOTEXTILE FILTER FABRIC
ADAPTOR SECTION C-C
300 VARIES ( 200 - 400 )
( ALSO WRAPPED AROUND AGGREGATE INDICATIVE DETAIL FOR SUBSOIL DRAINAGE
SURROUND AGAINST CONCRETE FACE AND uPVC PIPE
RETURNED ALONG PIPE FOR 300 MIN. ) INSPECTION CHAMBER DRAWN - SCALE N.T.S
SECTION A - A CHECKED - DATE -
APPROVED - SIZE A1
GRP INSPECTION SHAFT PROJECT DWG.
No. - No.
601

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
TOP OF KERB (200mm HIGH KERB SHOWN) ℄ OF FLUSH INLET STRUCTURE AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
TOP OF PAVEMENT ℄ OF PERFORATED PIPE APPROVED AS PART OF THE PROJECT DRAWING SET.
CONCRETE BARRIER 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS
TRYPICAL GULLY INLET OR OTHERWISE INDICATED.
SECTIONS CATCH BASIN INTERLOCKING VEHICULAR 2. THE KERB DETAILS SHOWN ARE FOR ILLUSTRATION
400 OFFSET AT 300mm PAVERS AND BASE COURSE PAVEMENT SLOPE (TYP) PURPOSE ONLY, REFER TO LATEST ADM STANDARD
HIGH MEDIAN KERB
LOCATIONS DRAWINGS FOR KERB DETAILS.

PAVEMENT
CROSS-SLOPE
LEGEND

(180MIN)
VARIES
(TYP) PERFORATED PIPE

*
INVERT ELEV
(MIN. DIA 160)
CAP SLOTTED GRATE AT
400 100
FLUSH INLET LOCATION
FLOW
FLOW
GETEXTILE FABRIC
SLOPE

1/2 *
SLOPE ℄ 300Ø
COLLECTOR PIPE
GRAVEL FILTER 1/2 O.D.
NON PERFORATED PIPE *
00 ENVELOPE PAY LIMITS

MIN
100
5 FROM INLET (TYP)
TRYPICAL
PERFORATED PIPE
SECTIONS (MIN. DIA 160)
60m MAXIMUM LENGTH 100 O.D. 100

500
MIN MIN
INSTALL PERFORATED PIPE BETWEEN
(180MIN)
VARIES

INLETS OR CATCH BASINS. OUTLET TYPICAL SECTION FOR SECTOR ROADS AND PARKING
GEOTEXTILE FABRIC ONE END ONLY
AREAS WHERE PAVING IS SLOPED TO FLUSH INLETS
1/2 O.D.
PERFORATED PIPE * SEE TYPICAL SECTION FOR MINIMUM DEPTH
WITHIN THE PAVEMENT AREA
MIN
100

(MIN. DIA 160) (SHOWN WITH INTERLOCKING VEHICULAR PAVERS, ALSO APPLICABLE
TYPICAL ELEVATION FOR ASPHALT PAVING)
GRAVEL FILTER ENVELOPE PAY LIMITS
PAVEMENT SUBBASE DRAINAGE INSTALLATION
100 O.D. 100
MIN MIN
TYPICAL SECTION FOR MAIN ROADS ℄ OF SUBSURFACE
DRAIN PIPE
500
OVERLAP 300 GRAVEL
AT SUPER ELEVATED SECTIONS USING FLUSH
INLETS AGAINST MEDIAN BARRIERS OR KERBS

GETEXTILE FABRIC PAYMENT LIMITS FOR


PERVIOUS BACKFILL
PERVIOUS BACKFILL MATERIAL
MATERIAL

PAYMENT LIMIT FOR 2 2


EXCAVATION FOR
1 1 1
PERFORATED PIPE

100
PERFORATED PIPE

100 O.D. 100

TYPICAL SECTION
(PERFORATED PIPE INSTALLATION REFERENCE DRAWINGS AND DOCUMENTS
SIDEWALK LOCATED IN CENTRAL INTERCHANGE STANDARD DRAWING - SUBSOIL DRAINAGE GROUND - 601
/ MEDIAN AREA AS DIRECTED BY THE WATER
℄ OF PIPE LOWERING PERFORATED PIPES - 603
330 SIDEWALK ENGINEER) STANDARD DRAWING - PIPE PLUG DETAILS - 209
330 ℄ OF PIPE STANDARD DRAWING - STORM WATER INLET DETAILS
ASPHALT AND SUBBASE (MAXIMUM DEPTH 2.0m) - 210
COURSES (TYP) STANDARD DRAWING - STORM WATER INLET DETAILS
400 (DEPTH VARYING BETWEEN 2.0m AND
2.8m) - 211
℄ OF PIPE
STANDARD DRAWING - STORM WATER CATCH BASIN
DETAILS (MAXIMUM DEPTH 2.0m) - 212
STANDARD DRAWING - STORM WATER CATCH BASIN
DETAILS (DEPTH VARYING BETWEEN
2.0m AND 2.8m)

(490 MIN)
(680 MIN)

VARIES
VARIES

300 (TYP)
MIN
1/3 O.D.

300 (TYP) No. REVISION-2 APP'D 2021


MIN GRAVEL FILTER ENVELOPE
PAY LIMITS
CLIENT
MIN O.D.

MIXED AGGREGATE ℄ OF PIPE (TYP)


100 1/2

SUBBASE COURSE (TYP)


MIN O.D.

MIN O.D.(180 MIN)


100 1/2

100 1/2 VARIES


OVERLAP GEOTEXTILE
FABRIC (TYP) PERFORATED PIPE
TITLE
(MIN. DIA 160)
330 1/2 100 STANDARD DRAWINGS
GRAVEL FILTER ENVELOPE O.D. MIN
SUBGRADE (TYP) 100 O.D. 100 CONSISTING OF PERVIOUS GRAVEL FILTER ENVELOPE INSTALL PERVIOUS BACKFILL GRAVEL FILTER ENVELOPE STORM WATER WORKS
MIN MIN BACKFILL MATERIAL TYPE III (TYP) PAY LIMITS MATERIAL TO 1/3 O.D. LEVEL TO PAY LIMITS
GEOTEXTILE FABRIC ACT AS PIPE BEDDING, PRIOR TO DRAWING TITLE
PERFORATED PIPE (MIN. DIA 160),
120° PERFORATED ZONE (TYP) PLACING PIPE AND BACKFILL, SEE
INSTALL
INVERT TO DRAIN ON 0.2% UNIFORM SPECIFICATIONS. (TYP) PERFORATED PIPE
STANDARD DRAWING SUBSOIL
100 O.D. 100
SLOPE (TYP) MIN MIN
(MIN. DIA 160) DRAINAGE GROUND WATER
TYPICAL SECTION FOR MAIN ROADS TYPICAL SECTION FOR SECTOR ROADS OR PARKING AREAS
TYPICAL SECTION FOR MAIN ROADS LOWERING PAVEMENT SUBBASE
AT TYPE "A" KERB LOCATIONS USING INLET TYPE AT YPE "A" KERB LOCATIONS USING INLET TYPE 1 OR CATCH BASIN
AT TYPE "A" KERB LOCATIONS USING FLUSH DRAINAGE DETAILS
1 OR CATCH BASIN TYPE - 1 TYPE - 1
(SHOWN WITH ASPHALT PAVING, ALSO APPLICABLE FOR INTERLOCKING INLETS DRAWN - SCALE N.T.S
VEHICULAR PAVERS) (OFFSET LOCATIONS ALSO APPLICABLE FOR FLUSH INLETS
ALONG SECTOR ROADS AND PARKING AREA KERBS CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
602

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
KERB LINE
INLET STRUCTURE 1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS
OTHERWISE STATED.

300 DIA OUTLET PIPE, CONCRETE


ENCASED. INSTALL WITH ELBOWS ON KERB LINE LEGEND
1000 CLEAR ALONG C/L OF OUTLET SLIGHT SKEW TO INLET STRUCTURE.

FLOW
PIPE BETWEEN END OF SLOTTED MAINTAIN MINIMUM SLOPE OF 0.3%. END 655 REINFORCED CONCRETE
TRENCH DRAIN AND KERB LINE CHANNEL UNIT TO HAVE HORIZONTAL 315 KERB
* PVC OUTLET END FITTING SOIL COMPACTED TO 95% MDD
* TOP OF KERB
USE 509 DEEP CHANNEL UNIT ON
OUTLET END, UPTO 9 No.,1000 LONG CAST-IN-SITU
LAYING UNITS MAY BE USED. MATCH FINAL GRADE FLUSH
KERB TOP OF PAVEMENT
300

10
CROSS SLOPE CROSS SLOPE

MAIN ROAD PAVEMENT


* 7No., 1000 LONG LAYING LENGTHS
UPTO
SECTOR
OF 449 DEEP CHANNEL UNITS

389 OR 449
ROAD/PARKING AREA PARKING AREA PAVEMENT

OR 509
SECTION (INTERLOCKING

SECTION
KERB LINE (TYP)
VEHICULAR PAVERS SHOWN)
A A

150
GEOTEXTILE FABRIC
150 355 150
655 CAST-IN-SITU FLUSH KERB CLASS B CONCRETE
WITH SLOTTED DRAIN CHANNEL
UPTO
* 7No., 1000 LONG LAYING LENGTHS PRE-CAST POLYESTER CONCRETE
OF 389 DEEP CHANNEL UNITS MIXED AGGREGATE
DRAIN CHANNEL WITH INTEGRAL
SUBBASE COURSE
DUCTILE IRON FRAME AND BOLT
DOWN GRATE FOR HEAVY DUTY USE,
LAY PLASTIC SHEET OVER IN 150 CONCRETE BEDDING, INSTALL
EXPOSED PERVIOUS BACKFILL ON GRADE TO MATCH FINISHED
MATERIAL PRIOR TO CASTING PAVEMENT GRADE.
CONCRETE.
FLOW

BLANK END-CAP FITTING ON ENDS


1000

TYPICAL SECTION
FLOW

A-A SLOTTED
TRENCH DRAIN
*MAXIMUM LENGTH OF FLOW RUN IS 23 m INSTALLATION NOTE: SLOTTED TRENCH DRAIN IN A 455 WIDE FLUSH
SUCH AS AT BUS STOP DIVIDED INTO CHANNEL KERB IS TO BE INSTALLED PARALLEL WITH THE
BUS/TAXI STOP KERB LINE (TYP)
DEPTH LAYING LENGTHS AS SHOWN ABOVE MAIN ROAD OUTER KERB LINE AT ALL SIDE ROAD,
PARKING AREA AND BUS/TAXI STOP KERB
OPENINGS WHERE SHOWN ON THE PLAN
DRAWINGS OR AS DIRECTED BY THE ENGINEER.
INSTALL EXPANSION JOINTS IN FLUSH
KERB AS SHOWN AND AT 4M MAXIMUM REFERENCE DRAWINGS AND DOCUMENTS
SPACING TO COINCIDE WITH POLYESTER
STANDARD DRAWING - PAVING DETAILS - 804
CONCRETE CHANNEL UNIT JOINTS.

BLOCK PAVING
1000 CLEAR
MAINTAIN 150 MINIMUM
CLEARANCE BETWEEN FINAL PAVING GRADE DUCTILE IRON FRAME
TOP OF OUTLET PIPE AND GRATE
B

10
1000 CLEAR ALONG CONCRETE END CAP FITTING
CENTERLINE OF OUTLET PIPE AND BOTTOM OF KERB
STONE (TYP) HUNCHING WITH 315 x PVC
BETWEEN END OF SLOTTED

150 CLEAR
KERB CAST-IN-SITU PIPE OUTLET
TRENCH DRAIN AND KERB LINE 150
FLOW

(MIN.)
CONCRETE
(MIN.) POLYESTER
KERB, 455 15° ELBOW CONCRETE DRAIN

509
WIDE
CHANNEL

(MIN)
MORTAR

150
CONCRETE FLOW
FOUNDATION
B No. REVISION-1 APP'D 2020
IPE

150
IA P
INLET STRUCTURE 300 D CLIENT
15° ELBOW

150 EXPANSION JOINT FILLER

TITLE
TYPICAL PLAN VIEW CUT OFF PIPE
STANDARD DRAWINGS
FLUSH WITH EXPANSION JOINT FILLER
SLOTTED TRENCH INSIDE WALL
NOTE: WHERE INLET STRUCTURE IS FURTHER
STORM WATER WORKS
CONCRETE PIPE AWAY THAN SHOWN ABOVE, MAINTAIN
DRAINS SIDE WALL
BEDDING/SURROUND CLEAR SPACING OF 150mm UNDER KERB
OF INLET AND 0.3% MINIMUM PIPE SLOPE. DRAWING TITLE
STRUCTURE EXPANSION JOINT FILLER
STANDARD DRAWING SURFACE
DRAINAGE DETAIL SLOTTED
* FOR SHORTER RUNS USE 389 DEEP CHANNEL TRENCH DRAINS
UNITS FOR MAJORITY OF LAYING LENGTH
(UPTO 7 NOS. OF 1000 LONG LAYING
TYPICAL SECTION
LENGTHS) WITH 449 AND 509 DEEP CHANNEL B-B OUTLET PIPE
UNITS ON OUTLET END. DRAWN - SCALE AS SHOWN
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
604

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT
AND MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT
PROJECT REQUIREMENTS. THEY ARE EXPECTED TO BE
LIMIT OF RIPRAP
PROTECTION INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
CHECKED AND APPROVED AS PART OF THE PROJECT
DRAWING SET.

VARIES
1. ALL DIMENSIONS IN MILLIMETRES UNLESS
RIPRAP AND WING WALLS OTHERWISE STATED
ARRANGEMENT SHALL BE 2. ALL INTERNAL CONCRETE TO BE COATED AS
DESIGNED TO SUIT EXISTING SPECIFIED.
SEA WALL AND SEALED 3. ALL EXTERNAL CONCRETE TO BE TANKED AS
CONDITIONS SPECIFIED.
VARIES
LEGEND
REINFORCED CONCRETE

PLAIN CONCRETE

RIP RAP
VARIES 1 DIA DIAMETER
4
CBS CONCRETE BED AND SURROUND

A A FGL FINAL GROUND LEVEL

PIPE DIA.
VARIES

VARIES
2000

STAINLESS STEEL BAR AS


SPECIFIED 12mm DIA BARS @
STAINLESS STEEL BAR AS
100mm SPACING
SPECIFIED 12mm DIA BARS @
100mm SPACING
WING WALL
STEPS TO BE PROVIDED IN BANK WING WALL
VARIES
VARIES

TO GIVE MAINTENANCE
ACCESS

VARIES
PLAN

WING WALL

STAINLESS STEEL BAR AS

150(MIN.)
SPECIFIED 12mm DIA BARS
WATER LEVEL
@ 100mm SPACING
VARIES REFERENCE DRAWINGS AND DOCUMENTS

500
FGL STANDARD DRAWING - TANKING DETAILS - 801
BED LEVEL
STANDARD DRAWING - CONSTRUCTION AND MOVEMENT JOINT
- 1001

200
STANDARD DRAWING - MISCELLANEOUS DETAILS - 207
NOTE : WEIR WALL LEVEL
500

FOR MANHOLES (FOR PIPE


TO SUIT NETWORK CONNECTION DETAILS)
HYDRAULIC DESIGN.
ELEVATION
200

ABOVE MEAN HIGH


WATER SPRING IF
VARIES

POSSIBLE.

GEOTEXTILE FILTER
FABRIC
PIPE MATERIAL & DIA VARIES

No. REVISION-1 APP'D 2020


RIPRAP TO SUIT CLIENT
(MIN.)
150

WATER LEVEL

TANKING MEMBRANE
500

AND PROTECTION BOARD


BED LEVEL
TITLE
STANDARD DRAWINGS
200

STORM WATER WORKS


1000

200 COMPACTED VARIES


THIS DEPTH MAY NEED DRAWING TITLE
GRAVEL BEDDING
TO BE INCREASED TO
GIVE SOLID STANDARD DRAWING TYPICAL
FOUNDATION
DETAILS OF STORM WATER
50mm THK. CEMENT/SAND SCREED BLINDING CONCRETE
TANKING MEMBRANE BACKFILL TO EXCAVATED OUTFALL GENERAL ARRANGEMENT
AREA TYPE 1 DETAIL APPLICABLE TO
75mm THICK C20 BLINDING DISCHARGE ABOVE HIGH TAIL WATER
LEVEL
TYPE-1
1000 GAUGE POLYETHYLENE SHEET

VARIES VARIES VARIES DRAWN - SCALE 1 : 50


CHECKED - DATE -
VARIES VARIES
SECTION A-A APPROVED - SIZE A1
PROJECT DWG.
No. - No. 701

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
LIMIT OF RIPRAP AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
PROTECTION
APPROVED AS PART OF THE PROJECT DRAWING SET.
VARIES 1. ALL DIMENSIONS IN MILLIMETRES UNLESS
OTHERWISE STATED
RIPRAP AND WING WALLS 2. ALL INTERNAL CONCRETE TO BE COATED AS
ARRANGEMENT SHALL BE SPECIFIED.
DESIGNED TO SUIT SITE 3. ALL EXTERNAL CONCRETE TO BE TANKED AS
CONDITIONS SPECIFIED.

VARIES LEGEND
REINFORCED CONCRETE

PLAIN CONCRETE

RIP RAP

DIA DIAMETER
VARIES 1 CBS CONCRETE BED AND SURROUND
4
FGL FINAL GROUND LEVEL

A A

PIPE DIA.
VARIES

VARIES
VARIES

FLAP VALVE/ NON RETURN


VALVE
GROOVE FOR STOP LOG USE
FLAP VALVE/ NON RETURN
VALVE WING WALL
GROOVE FOR STOP LOG USE VARIES
STEPS TO BE PROVIDED IN BANK
VARIES

TO GIVE MAINTENANCE WING WALL


ACCESS

VARIES
WATER LEVEL

PLAN
WING WALL
GROOVE FOR STOP LOG USE

150(MIN.)
FLAP VALVE/ NON RETURN
VALVE

500
VARIES
BED LEVEL REFERENCE DRAWINGS AND DOCUMENTS
FGL STANDARD DRAWING - TANKING DETAILS - 801

200
STANDARD DRAWING - CONSTRUCTION AND MOVEMENT- 1001
JOINT - 704
500

STANDARD DRAWING - TRASH RACK / SCREEN CHAMBER


- 207
ELEVATION STANDARD DRAWING - MISCELLANEOUS DETAILS
FOR MANHOLES (FOR PIPE
200

CONNECTION DETAILS)
VARIES

WATER LEVEL
GEOTEXTILE FILTER
FABRIC
PIPE MATERIAL & DIA VARIES

No. REVISION-2 APP'D 2021


RIPRAP TO SUIT
CLIENT
(MIN.)
150

TANKING MEMBRANE
500

AND PROTECTION BOARD


BED LEVEL
TITLE
STANDARD DRAWINGS
200

STORM WATER WORKS


1000

VARIES
200 COMPACTED DRAWING TITLE
GRAVEL BEDDING THIS DEPTH MAY NEED
TO BE INCREASED TO
GIVE SOLID STANDARD DRAWING TYPICAL
FOUNDATION DETAILS OF STORM WATER
50mm THK. CEMENT/SAND SCREED
BLINDING CONCRETE
TANKING MEMBRANE BACKFILL TO TYPE 2 DETAIL APPLICABLE TO
OUTFALL GENERAL ARRANGEMENT
75mm THICK C20 BLINDING
1000 GAUGE POLYETHYLENE SHEET
EXCAVATED AREA DISCHARGE BELOW HIGH TAIL WATER TYPE-2
LEVEL
VARIES VARIES VARIES DRAWN - SCALE 1 : 50
VARIES VARIES CHECKED - DATE -
APPROVED - SIZE A1
SECTION A-A PROJECT DWG.
No. - No. 702

THIRD EDITION - APRIL 2022


NOTES:
· TYPICAL DETAIL FOR MANHOLES AT THE UPSTREAM OF OUTFALLS 75 THICK PRECAST CONCRETE
SEATING RINGS BEDDED IN 1 COVER SLAB DETAIL
AND/OR HEAD WALL STRUCTURES WHERE HIDDEN PIPES ARE FOR PAVED AREA
AS SPECIFIED UV RESISTANCE PART CEMENT / 2 PART SAND
COVER SLAB DETAIL EPOXY COATING TO ALL
REQUIRED AT SEA WALLS FOR AESTHETIC PURPOSES.
FOR UNPAVED AREA · MANHOLES DETAILS WILL VARY ACCORDING TO PIPE DIAMETER AND MORTAR
SURFACES ABOVE GROUND DUCTILE IRON COVER
MANHOLE DEPTHS. 10 DOWEL DRILLED AND
16 DIA STEP BAR CAST INTO COVER 1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS

100
FGL · THIS DRAWING PROVIDES INDICATIVE DETAILS FOR CONSULTANT'S SET INTO COVER SLAB AT
FGL SLAB WITH TOE HOLE OTHERWISE STATED.
GUIDANCE. SPECIFIC MANHOLE DETAILS SHALL BE ACCORDING TO 300 CENTERS
RELEVANT MANHOLE DRAWINGS AND SHOULD ACCOMMODATE FLAP FINISHED LEVEL OF 150 CLASS B CONCRETE 2. ALL CONCRETE TO BE CLASS B UNLESS OTHERWISE
CARRIAGEWAY (FL) CL SURROUND STATED.
VALVE/ NON RETURN VALVE INSTALLATION AND OPERATION
REQUIREMENTS. 3. ALL EXTERNAL FACES OF CONCRETE BELOW GROUND

(MIN.)
TO BE TANKED.

450
· ARRANGEMENT IS WORKABLE FOR INLETS AND CATCH BASINS

MAX
600
WHERE REQUIRED. 4. ALL INTERNAL FACES OF CONCRETE TO BE COATED
WITH EPOXY COATING AS SPECIFIED.

250
5. MANHOLES SHALL BE PROVIDED WITH REINFORCED
CONCRETE RINGS (2Nos. AS MINIMUM), THE LOWER
RING SHALL BE 250mm HEIGHT AND THE UPPER RING
TO VARY ACCORDING TO FINAL GROUND LEVEL.
6. MANHOLES TO BE PROVIDED WITH SAND TRAP 500mm
COVER SLAB DETAIL FOR CARRIAGEWAY & PARKING AREAS DEEP SUMP.
7. ALL COVERS IN OPEN AREA TO BE PROVIDED WITH 1
No. GRAB BAR.
8. THE MANHOLES AND CHAMBERS ARE DESIGNED USING
P IPE
INLET FULL GROUND WATER LEVEL CONDITION WITH 1.1
FLOW
GRP LADDER FACTOR OF SAFETY FOR FLOATATION AND BEARING
PRESSURE NOT EXCEEDING 200kpa AT FORMATION
LEVEL.
9. DEWATERING OPERATIONS SHALL BE PROVIDED
DURING CONSTRUCTION AND MAY ONLY BE
FLAP VALVE 1500 FOR D<1200 TERMINATED AFTER ROOF SLAB HAS BEEN INSTALLED.
3000 FOR D>1200

LEGEND
LIMIT OF PIPEWORK
TANKING MEMBRANE EPOXY COATING ON ALL INTERIOR FOR FUTURE CONNECTION REINFORCED CONCRETE
AND PROTECTION BOARD SURFACES AS SPECIFIED 300 D<500
500 D>500 SOIL COMPACTED TO 95% MDD
750 FOR 2000-2400mm DIA
PLUGGED PORTS ONLY PLAIN CONCRETE

FLEXIBLE NEOPRENE 1500 FOR D<1200 3000 FOR D>1200 FGL FINAL GROUND LEVEL
RUBBER STRIP SPIGOT/SOCKET ON UPSTREAM SIDE
OF MANHOLE & DOUBLE SPIGOT ON FL FINAL ASPHALT / INTERLOCKED TILE LEVEL
FLOW DOWNSTREAM SIDE DIA DIAMETER
OUTLET PIPE TO OUTFALL
HEAD WALL STRUCTURE
CLASS `B` CONCRETE SURROUND
WIDTH : D+600 FOR D<500
D+1000 FOR D>500
500

°
90
CONCRETE BASE

1 1

200
PERVOUS BACKFILL 1 1 PIPE CONNECTION DETAILS TO CONCRETE SEA WALL OPENING
(PROVISIONAL)
(FOR R.C. PIPES)
50mm THK. CEMENT/SAND SCREED
(SCALE 1:40) REFERENCE DRAWINGS AND DOCUMENTS
TANKING MEMBRANE STANDARD DRAWING - TANKING DETAILS - 801
SECTION A-A 75mm THICK C20 BLINDING STANDARD DRAWING - MISCELLANEOUS DETAILS - 207
1000 GAUGE POLYETHYLENE SHEET FOR MANHOLES
STANDARD DRAWING - REINFORCEMENT DETAILS - 1000
(SERIES)
STANDARD DRAWING - STORM WATER MANHOLE FRAME - 213
AND COVER DETAILS
STANDARD DRAWING - G.A. OF STORM WATER MANHOLE - 201
ON PIPE LINES FOR MANHOLES TO
205

LIMIT OF PIPEWORK
FOR FUTURE CONNECTION SHORT LENGTH SHOULD BE
SOCKET SPIGOT FOR BOTH
300 D<500
UPSTREAM AND DOWNSTREAM
500 D>500 CONNECTIONS No. REVISION-2 APP'D 2021
FLEXIBLE NEOPRENE
RUBBER STRIP CLIENT

CLASS `B` CONCRETE SURROUND 600 D<400


WIDTH : D+600 FOR D<500
300 1.50 x D, D>400 TITLE
D+1000 FOR D>500 STANDARD DRAWINGS
FOR ALL PIPE GRADIENTS
STORM WATER WORKS

°
90
300 600 D<400 DRAWING TITLE
DUCTILE IRON COVER AND
FRAME TO SUIT RELEVANT STANDARD DRAWING STORM WATER
NOMINAL SIZE CLEAR PIPE COMING OUT OF THE
OPENING
NIB SHOULD HAVE OUTFALL MANHOLE GENERAL
SOCKET IN UPSTREAM
AND SPIGOT IN ARRANGEMENT
DOWNSTREAM

PIPE CONNECTION DETAILS TO CONCRETE SEA WALL OPENING


DRAWN - SCALE 1 : 20
(FOR GRP PIPES OR OTHER PLASTIC PIPES)
CHECKED - DATE -
(SCALE 1:40)
PLAN AT COVER LEVEL APPROVED - SIZE A1
PROJECT DWG.
No. - No.
703

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
B REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.

1. ALL DIMENSIONS IN MILLIMETRES UNLESS OTHERWISE


STATED.
2. ALL INTERNAL AND EXTERNAL CONCRETE CORNER TO
BE ROUNDED OR CHAMFERED.
3. ALL CONCRETE TO BE CLASS B UNLESS OTHERWISE
STATED.

250 255
HEAVY DUTY HEAVY DUTY MULTIPLE 4. ALL EXTERNAL FACES OF CONCRETE BELOW GROUND
DUCTILE IRON ACCESS MANHOLE TO BE TANKED.

500
COVER AND FRAME COVER & FRAME TO SUIT 5. ALL INTERNAL FACES OF CONCRETE TO BE COATED
500x500x300mm TO EN124 CLASS CLEAR OPENING WITH WITH EPOXY COATING AS SPECIFIED.
INLET 500
DEEP SUMP D400 TO SUIT —X— REMOVABLE 6. CHAMBER DIMENSIONS AND ARRANGEMENT WILL VARY
REMOVABLE CLEAR OPENING INTERMEDIATE BEAM ACCORDING TO OUTFALL PIPE SIZE AND
TRASH RACK / ARRANGEMENT.
FLOW FLOW A A

4000
1990
SCREEN _ _

TOWARDS PUMPING STATION / SEA OUTFALL LEGEND


PENSTOCK
REINFORCED CONCRETE

SOIL COMPACTED TO 95% MDD

255 250
OUTLET
PLAIN CONCRETE

FGL FINAL GROUND LEVEL


FL FINAL ASPHALT / INTERLOCKED TILE LEVEL
DIA DIAMETER

PLAN -
ROOF PLAN
1 : 25 -
1 : 25

PENSTOCK PENSTOCK

REFERENCE DRAWINGS AND DOCUMENTS


INLET REMOVABLE
STANDARD DRAWING - TANKING DETAILS - 801
1000

TRASH
STANDARD DRAWING - CONSTRUCTION AND MOVEMENT - 1001
RACK / JOINT - 207
FLOW SCREEN FLOW STANDARD DRAWING - MISCELLANEOUS DETAILS
FOR MANHOLES - 213
TOWARDS PUMPING STATION / SEA OUTFALL
STANDARD DRAWING - STORM WATER MANHOLE FRAME
1000

AND COVER DETAILS

EPOXY COATING
OUTLET
INTERNAL
1200

PROTECTION AS REINFORCED CONCRETE EPOXY


SPECIFIED SCREED COATING
500x500x300mm SCREED
INTERNAL
DEEP SUMP
200

PROTECTION
50

AS
SPECIFIED No. REVISION-2 APP'D 2021
CLIENT

50mm THK. CEMENT/SAND SCREED 50mm THK. CEMENT/SAND SCREED


SECTIONA TANKING MEMBRANE SECTIONB TANKING MEMBRANE
TITLE
1 : 25 - 75mm THICK C20 BLINDING 1 : 25 - 75mm THICK C20 BLINDING STANDARD DRAWINGS
1000 GAUGE POLYETHYLENE SHEET 1000 GAUGE POLYETHYLENE SHEET
STORM WATER WORKS
DRAWING TITLE

STANDARD DRAWING TRASH


RACK / SCREEN CHAMBER

DRAWN - SCALE 1 : 200


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
704

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS
OTHERWISE STATED.
2. THIS DRAWING TO BE READ IN CONJUNCTION WITH
MANHOLE AND CHAMBER DRAWINGS.
3. THE DETAILS ON THIS DRAWING ARE GENERALLY DRAWN
TO SCALE AND ARE RELEVANT TO SPECIFIC PIPE SIZES,
MANHOLE CONSTRUCTION DETAILS, ETC. SIMILAR
DETAILS SHALL APPLY AS APPROPRIATE TO OTHER PIPE
SIZES, MANHOLE CONSTRUCTION DETAILS, ETC.

LEGEND

PROTECTION TO REINFORCED CONCRETE


MEMBRANE AS
WATERPROOF MEMBRANE SPECIFIED PLAIN CONCRETE
PROTECTION TO
AS SPECIFIED UV RESISTANCE MEMBRANE AS
EPOXY COATING TO ALL SPECIFIED
SURFACES ABOVE GROUND
20 X 20 REBATE TO TUCK
150 MIN
THE MEMBRANE IN AND SEAL

150 MIN

50

50
SURFACE OF COVER SLAB TO
BE SCABBLED PRIOR TO
SURROUND BEING PLACED 20 x 20 CHAMFER
PROTECTION TO MEMBRANE
WATERPROOF MEMBRANE AS SPECIFIED
40 x 40 FILLET
WATERPROOF MEMBRANE

DETAIL A DETAIL B DETAIL C


TANKING AT GROUND LEVEL TANKING AT INTERNAL CORNER TANKING AT EXTERNAL CORNER

PROTECTION TO MEMBRANE AS
WATERPROOF MEMBRANE SPECIFIED
PROTECTION TO
MEMBRANE AS
40 x 40 FILLET
SPECIFIED
PROTECTIVE 150 150 MIN
SYNTHETIC RUBBER
STRIP MIN. 6 THICK
150 MIN

REFERENCE DRAWINGS AND DOCUMENTS


50

STANDARD DRAWING - TANKING DETAILS - 801


STANDARD DRAWING - MISCELLANEOUS DETAILS - 207
75

FOR MANHOLES

WATERPROOF MEMBRANE
COLLAR MIN. 300 WIDE
150 C20 BLINDING 40 x 40 FILLET
CEMENT STARCUT WATERPROOF
MORTAR
MEMBRANE WORKED
PROTECTION TO
MEMBRANE ARROUND PIPE AND
LAPPED WITH COLLAR
DETAIL D DETAIL E
TANKING AT FORMATION LEVEL TANKING SEAL AT PIPE ENTRY

PLAIN CONCRETE

No. REVISION-1 APP'D 2020


CLIENT

TITLE
STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

STANDARD DRAWING TYPICAL


TANKING DETAILS FOR
UNDERGROUND STRUCTURES

DRAWN - SCALE 1 : 20
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
801

THIRD EDITION - APRIL 2022


325 NOTES:
47 18 THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
225 200 18 47 MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE
65 300 65 80 100 INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
HOLE TO ACCOMMODATE NEXT LADDER CHECKED AND APPROVED AS PART OF THE PROJECT
NON SLIP SILICA SAND
DRAWING SET.
100

1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS

60

25
OTHERWISE STATED.

50

50
150 250 250 250 250 250 250 250

MATERIAL SPECIFICATION

500
RESIN TO BE VINYLESTER

GLASS TO BE ALL 'E.C.R.'

150

150
RUNG
5 THICK GRP
FIRST LAYER TISSUE TYPE 'C'

55
100

100
500
GRP WALL LINER 7 THICK HARDWOOD STIFFENER 40 X 37 FIVE LAYERS C.S.M. 450 g/m 'E.C.R.' OR EQUIVALENT DENSITY MAT
STRINGER LAST LAYER TISSUE TYPE 'C'

FINAL FLOWCOAT VINYLESTER RESIN


A A

500
LADDER GRP THICKNESS NOT LESS THAN 5mm ANYWHERE

R6
80 RAIL DETAIL
(SCALE 1:1)

255
DETAIL B DETAIL A
(SCALE 1:2) (SCALE 1:2) NON SLIP SILICA SAND
50
SEE DETAIL 'A' SEE DETAIL 'B'

FRONT VIEW SIDE VIEW


GRP LADDER

18
(SCALE 1:20)

STAINLESS STEEL ANCHOR BOLT 100 5 THICK GRP

50
NEOPRENE GASKETS TO BE LONG MINIMUM 9 DIA. WITH WASHER
INSTALLED TO SEAL JOINT FIXING TO BE AT MAXIMUM OF
BETWEEN CONCRETE PROTECTION B 500 CENTRES

32
& LADDER
200 CONCRETE

HARDWOOD STIFFENER

STEP DETAIL
(SCALE 1:1)
60
145

PROTECTION TO CONCRETE 5
AS SPECIFIED
8025

GRP PLATE 15mm THICK


55

HARDWOOD STIFFENER
LAMINATED TO WALL

B 80 145
18 47 47 18
55
430 REFERENCE DRAWINGS AND DOCUMENTS

SECTION A-A (THROUGH LADDER)

75
GRP LADDER LAMINATION JOINT
FLAT WALLS
45

(SCALE 1:5)

GRP MANHOLE
250

B
80

200 CONCRETE
INSIDE JOINTS OF CONCRETE
GRP LADDER TO GRP MANHOLE
80
70

LINER TO BE SEALED

CONNECTION DETAILS

No. REVISION-2 APP'D 2021


CLIENT
SECTION B-B
300

60 200 TITLE
STANDARD DRAWINGS
145

5 STORM WATER WORKS


25

350
INTERNAL LINER

DRAWING TITLE
80
55

HARDWOOD STIFFENER
STANDARD DRAWING TYPICAL
18 47
B 47 18 LAMINATE JOINT GRP LADDER DETAILS
430
AND IRON STEP DETAILS

95
DRAWN - SCALE N.T.S
SECTION A-A (THROUGH LADDER) CHECKED - DATE -
CURVED WALLS IRON STEP DETAILS APPROVED - SIZE A1
(SCALE 1:5) PROJECT DWG.
No. - No.
802

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
65 x 10 EXTENDER STRINGER
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
HANDRAIL REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
STANDARD (TYP)
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.

A
R=345 MIN. 1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS
3 EQUAL SPACED 380 MAX.
HORIZONTAL RUNGS OTHERWISE STATED.
R (C)L= 100 MIN. AT FFL 2. ALL HANDRAILING SHALL BE FIELD MEASURED BEFORE
C FABRICATION. NO FIELD CUTTING OR WELDING WILL
B
BE PERMITTED RAILING WHICH DOES NOT FIT
EITHER A OR B TO BE NOT MORE THAN 300 MOUNTING PREVIOUSLY SET IN CONCRETE WILL BE
C NOT MORE THAN 1500 REJECTED.
3. ALL FABRICATIONS SHALL BE GALVANISED. EXCEPT AT
250 STAIR RUNS AND WHERE THERE IS A KERB.
POSITIONS OF STANDARDS AT BENDS PLAN OF HANDRAIL RETURN 4. TOE PLATE IS REQUIRED AT ALL HANDRAILING
SECTION A-A LOCATIONS.
5. ALTERNATE METHODS OF TOE PLATE ATTACHMENT TO
STANDARDS MAY BE ACCEPTABLE IF APPROVED BY
THE ENGINEER.
6. THE DESIGN OF STAIRS, LADDERS AND WALKWAYS
100 (SYMMETRICAL ABOUT FACE OF WALL 230 (TYP) SHALL BE TO BS5395:PART 3 1985.
WHERE PLANS INDICATE REMOVABLE
CHAIN RAILING PROVIDE 5 THK STRUCTURAL JOINT) BELOW BACK OF RUNGS 7. PLATFORM AND WALKWAY FLOOR LOADS SHALL BE
ALUMINIUM PASSING LINK CHAIN FOR HEAVY DUTY AS DEFINED IN BS5395; CLAUSE 8.1,
WITH SNAP LOCK HOOK AT ONE END
900 VERTICALLY TABLE 3.
TUBULAR FLANGE ABOVE PITCH LINE
LEGEND
R=345 MIN.
380 MAX.
6 DIA ANCHOR PITCH LINE
BOLTS (TYP)

TOE PLATE
RUNG
FFL

M6 BOLTS CONTRETE KERB/ SECTION B-B


EDGE UPSTAND
6 THK CLIP ANGLE TYPE 1 (TYP)
STRUCTURAL JOINT

350 690
HANDRAILING DETAILS TYP

65 x 10 EXTENDED
50 x 10 VERTICAL STRINGER BEYOND
STRAP (TYP) VERTICAL STRAP (TYP)

1330
150 x 75 x 6 x THK. TOE PLATE
SPLICE PLATE WELDED TO
HANDRAIL STANDARD WITH
M10 BOLTS WITH A A
NUTS & WASHERS
5 x 75 LONG FILLET WELD
TO EACH SIDE

FFL FFL

900 MAX
BASEPLATE
150 x 120 x 10 THK
5
REFERENCE DRAWINGS AND DOCUMENTS

PLAN

HANDRAIL STANDARD HANDRAIL STANDARD

TOE PLATE 100 x 6 THK


18

(WHERE REQUIRED) TOE PLATE 100 x 6 THK


CHAMFER 50 x 10 SAFETY HOOPS
C FIXING 65 x 10 STRINGERS
40

TOE PLATE SPLICE

6000 MAX
FFL OR
TOP OF KERB
CONCRETE PLATFORM M10 COUNTERSUNK HEAD BOLTS
WITH NUTS & WASHERS
50

5 x 180 LONG FILLET


No. REVISION-1 APP'D 2020
WELDS TO STANDARD B B
2000 MAX (TYP)

2400 MAX
CLIENT
4 No. 13 DIA ANCHOR BOLTS 13 DIA ANCHOR BOLTS
2 No. 65 x 50 x 10 THK
ANGLES OR ALTERNATE
SUPPORT PLATE

RUNGS @ 250 CENTRES TITLE


STANDARD DRAWINGS
ELEVATION WALL BRACKET
15 DIA 316L S.S
STORM WATER WORKS
FLOOR BRACKET ANCHOR BOLT (TYP)
DRAWING TITLE

MAX
250
HANDRAIL STANDARD HANDRAIL STANDARD C FIXING FFL
FIXING DETAIL TYPE 1 FIXING DETAIL TYPE 2 STANDARD DRAWING
SCALE 1:10 SCALE 1:10 LADDER, WALKWAY,STAIRS
FIXED TO WALL

FLOOR BRACKET TO BE AND HANDRAILING DETAILS


100MIN IF

400
OMIITTED IF BOTTOM FIXING
CAN BE MADE TO WALL

DRAWN - SCALE AS SHOWN


GALVANISED MILD STEEL LADDER DETAILS
CHECKED - DATE -
WITH SAFETY CAGE
SCALE 1:40 APPROVED - SIZE A1
PROJECT DWG.
No. - No. 803

THIRD EDITION - APRIL 2022


LAGOON OUTLET PIPE TO NEAREST NOTES:
STORM WATER NETWORK THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
OR OTHER LOCATION (PROVISIONAL) MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT

ACCESS ROAD
EMERGENCY OVERFLOW CHANNEL REQUIREMENTS. THEY ARE EXPECTED TO BE
MINIMUM LINED LENGTH IS TO BE DESIGNED BASED ON INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
DOWNSTREAM CONDITIONS CHECKED AND APPROVED AS PART OF THE PROJECT
THEN EARTH CHANNEL DUG TO SUITABLE END POINT DRAWING SET.
SEE DETAIL-1 IN DRAWING No. 905 1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS OTHERWISE
X X X X X X X
LAGOON INLET PIPELINE STATED.
2. IF EXCAVATED SURFACE CONTAINS SOFT SPOTS THESE SHALL

X
FROM STORMWATER
VC NETWORK BE DUG OUT AND REPLACED WITH FIRM MATERIAL. ANY SHARP

X
STONES OR PROJECTIONS SHALL BE REMOVED BEFORE
CONTROL PS

X
PLACING THE GEOTEXTILE / LINER.
BUILDING 3. WITHIN THE RANGE FOR STABILITY THE BUND SIDE SLOPES

X
MH
ARE TO BE SUCH THAT AS FAR AS POSSIBLE. THE BUND ABOVE

X
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X

X
EXISTING GROUND LEVEL IS FORMED ENTIRELY FROM
SUITABLE EXCAVATED MATERIAL ( i.e. THE 'CUT AND FILL' ARE

X
TO BE EQUAL).

X
EXISTING GROUND 4. SURFACE AERATORS(EG.FOUNTAIN)SHALL BE USED IN PONDS

X
PIPE INLET / OUTFALL 1.8M DEEP OR LESS AND BOTTOM AERATORS ARE USED
SLOPE LINE IS INDICATIVE OTHERWISE.

X
EXISTING
ONLY STAIRCASE GROUND 5. THE SHOWN AERATOR IS JUST FOR ILLUSTRATION, FOR

X
SEDIMENTATION AREA AERATOR DETAILS REFER TO VOLUME 4 - SECTION 1.2.26.

X
15 LUX LIGHTING INTENSITY 6. FOR OUTLET DETAILS REFER TO DRAWING NO. 905.
TOP OF BUND TO BE X 7. FOR MORE DETAILS ABOUT LAGOON BED LINING MATERIALS,

X
(SEE NOTE 8)
HORIZONTAL AROUND SLOPE LINE IS REFER TO DRAWING NO. 902.
X

X
PERIMETER INDICATIVE 8. LIGHTING POLE IS FOR INDICATIVE PURPOSES. ANY SOURCE
X

X
ONLY OF OUTDOOR LIGHTING MAYBE USED UPON ENGINEERS
X

X
OUTLET APPROVAL.
X

X
VARIES

A A
X

X
902 902 LEGEND
X

X
AIR COMPRESSOR FOR
WEIR STORM WATER GRAVITY LINE
SUBMERGED AERATOR
X

X
1 SUBMERGED AERATOR 1 STORM WATER PRESSURE LINE
X

X
LA 3.00m WIDE AT TOP OF PERIMETER
TO STILLING BASIN OU GO BUND AROUND PERIMETER
X

X
E TL ON FENCING BTL BUND TOP LEVEL
OP T ET SL
X

X
S PO OP
N OIN
O P IN E T TWL TOP WATER LEVEL
X

X
A GO LET FLOATING AERATOR T O
AIR TUBE L T
POWER
X

X
OU PS PUMPING STATION
X

X
SUPPLY
VC VALVE CHAMBER
X

X
X

X
EGL EXISTING GROUND LEVEL
X

X
CABLE TO
1 IN 100 (APPROXIMATELY)

INTEGRATED AERATION
X

X
LAGOON FLOOR SLOPE

1 IN 100 (APPROXIMATELY)
CONTROL PANEL

LAGOON FLOOR SLOPE


CONTROL PANEL
X

X
LAGOON BED LINING MATERIAL
X

X
ANCHORING CIVIL BASE
X

X
(RUBBER COVERED)
X

X
X

X
X

X
X

X
X

X
ELECTRICAL MCC GRP
X

X
LAGOON FLOOR HORIZONTAL
KIOSK IN THIS DIRECTION
X

X
X

X
X

X
STORAGE LAGOON REFERENCE DRAWINGS AND DOCUMENTS
X

X
T.W.L. (TO BE STATED ON AS-BUILT DRAWINGS) STANDARD DRAWING - G.A. OF STORM WATER MANHOLES -201 TO 205
X

X
STANDARD DRAWING - TYPICAL DETAILS OF STORM WATER OUTFALL -701
INLET CHAMBER STANDARD DRAWING - STORM WATER LAGOON ARRANGEMENT LAYOUT
X

X
SHEET 2 OF 3 -902
X

X
STANDARD DRAWING - STORM WATER LAGOON MISCELLANEOUS DETAILS
SHEET 1 OF 2 -904
X

X
STANDARD DRAWING - STORM WATER LAGOON MISCELLANEOUS DETAILS
X

X
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
15 LUX SHEET 2 OF 2 -905
VARIES LIGHTING
INTENSITY
EXISTING GROUND (SEE NOTE 8)

LAYOUT DRAWING
N.T.S

GUIDING RING
No. REVISION-2 APP'D 2021
NORMAL TWL
CLIENT

CABLE TO TITLE
CONTROL PANEL FLOATING AERATOR
STANDARD DRAWINGS
STORM WATER WORKS
ANCHORING CIVIL BASE DRAWING TITLE
(RUBBER COVERED) BED LINING

AIR TUBE CONNECTED TO


SUBMERGED AERATOR MATERIAL STANDARD DRAWING
AIR COMPRESSOR
LAGOON BED
STORM WATER LAGOON
GEOTEXTILE
2 THICK TEXTURED HDPE MEMBRANE ARRANGEMENT LAYOUT
LINER
150 THICK LAYER OF 5 DOWN WELL GRADED
SHEET 1 OF 3
150 THICK LAYER OF 5 DOWN CRUSHED ROCK COMPACTED TO 95% MAXIMUM
WELL GRADED CRUSHED DRY DENSITY DRAWN - SCALE N.T.S
ROCK COMPACTED TO 95%
MAXIMUM DRY DENSITY CHECKED - DATE -
SECTION (1-1) APPROVED - SIZE A1
N.T.S PROJECT DWG.
No. - No.
901

THIRD EDITION - APRIL 2022


NOTES:
15 LUX LIGHTING INTENSITY (SEE THESE DETAILS REPRESENT A MINIMUM REQUIREMENT
NOTE 7) AND MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT
5000 PROJECT REQUIREMENTS. THEY ARE EXPECTED TO BE
INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
3400 300 THICK LAYER OF 75 DOWN CHECKED AND APPROVED AS PART OF THE PROJECT
WELL GRADED GRANULAR DRAWING SET.
DETAIL-5 MATERIAL COMPACTED TO 95%
(TWL + 1m FREE BOARD)
MAXIMUM DRY DENSITY 1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS
OTHERWISE STATED.
NORMAL TWL 2. IF EXCAVATED SURFACE CONTAINS SOFT SPOTS
THESE SHALL BE DUG OUT AND REPLACED WITH FIRM
DETAIL-6
B MATERIAL. ANY SHARP STONES OR PROJECTIONS
3000 1
SHALL BE REMOVED BEFORE PLACING THE
INTERMEDIATE BERM 1 n (SEE NOTE 5) DETAIL-3
n (SEE NOTE 5)
GEOTEXTILE / LINER.
IF REQURIED FOR
3. WITHIN THE RANGE FOR STABILITY THE BUND SIDE

615
STABILITY
CHAIN LINK FENCE SLOPES ARE TO BE SUCH THAT AS FAR AS POSSIBLE.
SURFACE CUT TO THE BUND ABOVE EXISTING GROUND LEVEL IS
LEVEL, SCARIFIED AND FORMED ENTIRELY FROM SUITABLE EXCAVATED
COMPACTED

1900
MATERIAL ( i.e. THE 'CUT AND FILL' ARE TO BE EQUAL).
DETAIL-2 B 75 DOWN WELL EXISTING GROUND 5000 (MIN.) 4. SIDE SLOPE PROTECTIONS ARE TO BE RELATED TO
GRADED MATERIAL LEVEL
1
THE SOIL TYPE, ITS ANGLE OF REPOSE, AND ITS
LAGOON BED COMPACTED TO 95% VARIES
n (SEE NOTE 5) MAX. DRY DENSITY EGL STABILITY.
5. SIDE SLOPE n:1. n TYPICALLY VARIES BETWEEN (2.5:4).
SURFACE CUT TO
STEEPER OR FLATTER SLOPES MAY BE USED BASED
LEVEL, SCARIFIED DETAIL-7 ON SITE CONDITIONS AND PROTECTION TYPE.
AND COMPACTED SECTION A-A TYPICAL BUND SECTION 6. MINIMUM WIDTH OF THE ROAD SHALL BE AT LEAST 5M
DETAIL-1 DETAIL-4
N.T.S OR AS AGREED BY THE DEPARTMENT.
7. LIGHTING POLE IS FOR INDICATIVE PURPOSES. ANY
INTERMEDIATE BERM IF REQURIED FOR STABILITY SOURCE OF OUTDOOR LIGHTING MAY BE USED UPON
ENGINEERS APPROVAL.

LEGEND
LAGOON BED

TWL TOP WATER LEVEL


SURFACE CUT TO LEVEL, SCARIFIED
AND COMPACTED TYP TYPICAL VALUE
SURFACE CUT TO LEVEL, 150 THICK LAYER OF 5 DOWN WELL
SCARIFIED AND COMPACTED GRADED CRUSHED ROCK COMPACTED MINIMUM 200 THICK LAYER OF D50 = 100 1
150 THICK LAYER OF 5 DOWN WELL GRADED CRUSHED TO 95% MAXIMUM DRY DENSITY ROCK FACING AND PACKED n (SEE NOTE 5)
ROCK COMPACTED TO 95% MAXIMUM DRY DENSITY

2 THICK SMOOTH HDPE LINER 2 THICK TEXTURED HDPE LINER

150 THICK LAYER OF 5 DOWN WELL GRADED DETAIL - 3 (a)


150 THICK LAYER OF 5 DOWN WELL
CRUSHED ROCK (LIGHTLY COMPACTED) N.T.S
GRADED CRUSHED ROCK COMPACTED
TO 95% MAXIMUM DRY DENSITY
150 THICK LAYER OF 75 DOWN ROCK
UNCOMPACTED
GEOTEXTILE MEMBRANE

300 THICK LAYER OF D50 = 200 RIP-RAP


DETAIL - 1 (a)
N.T.S DETAIL - 2 (a)
N.T.S

RIP-RAP
LINING

LAGOON BED

INTERMEDIATE BERM IF REQURIED FOR STABILITY

SURFACE CUT TO LEVEL,


SCARIFIED AND COMPACTED
REFERENCE DRAWINGS AND DOCUMENTS
150 THICK LAYER OF 5 DOWN WELL GRADED CRUSHED
SURFACE CUT TO LEVEL, SCARIFIED CONCRETE GEO-SYNTHETIC
ROCK COMPACTED TO 95% MAXIMUM DRY DENSITY STANDARD DRAWING - G.A. OF STORM WATER MANHOLES 201
AND COMPACTED CEMENTICIOUS COMPOSITE SHEETS
1 TO
2 THICK SMOOTH HDPE LINER
150 THICK LAYER OF 5 DOWN WELL LAYER OF 5 DOWN WELL GRADED n (SEE NOTE 5) 205
150 THICK LAYER OF 5 DOWN WELL GRADED GRADED CRUSHED ROCK COMPACTED CRUSHED ROCK COMPACTED TO 95% STANDARD DRAWING - TYPICAL DETAILS OF STORM WATER 701
CRUSHED ROCK (LIGHTLY COMPACTED) TO 95% MAXIMUM DRY DENSITY MAXIMUM DRY DENSITY OUTFALL
STANDARD DRAWING - STORM WATER LAGOON 901
CONCRETE GEO-SYNTHETIC CEMENTICIOUS ARRANGEMENT LAYOUT SHEET 1 OF 3
CONCRETE GEO-SYNTHETIC CEMENTICIOUS COMPOSITE SHEETS DETAIL - 3 (b)
COMPOSITE SHEETS STANDARD DRAWING - STORM WATER LAGOON
N.T.S 904
MISCELLANEOUS DETAILS
SHEET 1 OF 2
DETAIL - 1 (b) DETAIL - 2 (a) STANDARD DRAWING - STORM WATER LAGOON
N.T.S MISCELLANEOUS DETAILS 905
N.T.S
SHEET 2 OF 2

CONCRETE GEO-SYNTHETIC CEMENTICIOUS COMPOSITE SHEETS


LINING
No. REVISION-2 APP'D 2021
CLIENT
LAGOON BED INTERMEDIATE BERM IF REQURIED FOR STABILITY

TITLE
SURFACE CUT TO LEVEL,
SURFACE CUT TO LEVEL, SCARIFIED
STANDARD DRAWINGS
SCARIFIED AND COMPACTED
150 THICK LAYER OF 5 DOWN WELL GRADED CRUSHED
AND COMPACTED 10 THICK CONCRETE COVER
1
STORM WATER WORKS
ROCK COMPACTED TO 95% MAXIMUM DRY DENSITY
GEOCELL WITH CONCRETE INFILL GEOCELL WITH CONCRETE INFILL n (SEE NOTE 5)
2 THICK SMOOTH HDPE LINER DRAWING TITLE
(GRADE M25) (GRADE M25)
150 THICK LAYER OF 5 DOWN WELL GRADED
CRUSHED ROCK (LIGHTLY COMPACTED)
10 THICK CONCRETE COVER STANDARD DRAWING STORM
DETAIL - 3 (c)
N.T.S WATER LAGOON ARRANGEMENT
GEOCELL WITH CONCRETE INFILL
(GRADE M25) DETAIL - 2 (a)
N.T.S
LAYOUT SHEET 2 OF 3
10 THICK CONCRETE COVER

DRAWN - SCALE N.T.S


DETAIL - 1 (c)
N.T.S
GEOCELL WITH CONCRETE INFILL CHECKED - DATE -
LINING APPROVED - SIZE A1
PROJECT DWG.
No. - No.
902

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT
AND MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT
PROJECT REQUIREMENTS. THEY ARE EXPECTED TO BE
300 THICK LAYER OF 75 DOWN INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
WELL GRADED GRANULAR
150 THICK LAYER OF 5 DOWN WELL GRADED CHECKED AND APPROVED AS PART OF THE PROJECT
MATERIAL COMPACTED TO 95%
CRUSHED ROCK (LIGHTLY COMPACTED) 300 THICK LAYER OF 75 DOWN DRAWING SET.
MAXIMUM DRY DENSITY
WELL GRADED GRANULAR
EXISTING GROUND LEVEL 1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS
MATERIAL COMPACTED TO 95%
MAXIMUM DRY DENSITY OTHERWISE STATED.
2. IF EXCAVATED SURFACE CONTAINS SOFT SPOTS
1 THESE SHALL BE DUG OUT AND REPLACED WITH FIRM
LAGOON BED n (SEE NOTE 5) MATERIAL. ANY SHARP STONES OR PROJECTIONS
1
SURFACE CUT TO LEVEL AND VARIES
COMPACTED 2 THICK TEXTURED HDPE LINER SHALL BE REMOVED BEFORE PLACING THE
n (SEE NOTE 5)
1000 MINIMUM 200 THICK LAYER OF D50 = 100 1 MINIMUM 200 THICK LAYER OF D50 = 100 GEOTEXTILE / LINER.

500
120 150 THICK LAYER OF 5 DOWN WELL n (SEE NOTE 5)
SURFACE CUT TO LEVEL, SCARIFIED
GRADED CRUSHED ROCK COMPACTED ROCK FACING AND PACKED ROCK FACING AND PACKED 3. WITHIN THE RANGE FOR STABILITY THE BUND SIDE
AND COMPACTED SLOPES ARE TO BE SUCH THAT AS FAR AS POSSIBLE.
TO 95% MAXIMUM DRY DENSITY GEOTEXTILE MEMBRANE GEOTEXTILE MEMBRANE
DOUBLE WELDED 150 THICK LAYER OF 5 DOWN WELL 500 THE BUND ABOVE EXISTING GROUND LEVEL IS
JOINT FOR AIR TEST GRADED CRUSHED ROCK COMPACTED 2 THICK TEXTURED HDPE LINER FORMED ENTIRELY FROM SUITABLE EXCAVATED
TO 95% MAXIMUM DRY DENSITY 150 THICK LAYER OF 5 DOWN WELL MATERIAL ( i.e. THE 'CUT AND FILL' ARE TO BE EQUAL).
2 THICK TEXTURED HDPE LINER GRADED CRUSHED ROCK COMPACTED 4. SIDE SLOPE PROTECTIONS ARE TO BE RELATED TO
TO 95% MAXIMUM DRY DENSITY
THE SOIL TYPE, ITS ANGLE OF REPOSE, AND ITS
150 THICK LAYER OF 5 DOWN WELL GEOTEXTILE MEMBRANE STABILITY.
DETAIL - 6 (a) DETAIL - 7 (a)
GRADED CRUSHED ROCK COMPACTED
300 THICK LAYER OF D50 = 200 RIP-RAP
N.T.S N.T.S 5. SIDE SLOPE n:1; n TYPICALLY VARIES BETWEEN (2.5:4).
TO 95% MAXIMUM DRY DENSITY
STEEPER OR FLATTER SLOPES MAY BE USED BASED
GEOTEXTILE MEMBRANE DETAIL - 5 (a) SITE CONDITIONS AND PROTECTION TYPE.
N.T.S
300 THICK LAYER OF D50 = 200 RIP-RAP
DETAIL - 4 (a) LEGEND
N.T.S RIP-RAP TWL TOP WATER LEVEL
LINING
TYP TYPICAL VALUE

300 THICK LAYER OF 75 DOWN 300 THICK LAYER OF 75 DOWN


WELL GRADED GRANULAR WELL GRADED GRANULAR
MATERIAL COMPACTED TO 95% MATERIAL COMPACTED TO 95%
MAXIMUM DRY DENSITY MAXIMUM DRY DENSITY CONCRETE GEO-SYNTHETIC
LAYER OF 5 DOWN WELL GRADED
150 THICK LAYER OF 5 DOWN WELL GRADED CEMENTICIOUS COMPOSITE
CRUSHED ROCK COMPACTED TO 95%
CRUSHED ROCK (LIGHTLY COMPACTED) SHEETS
MAXIMUM DRY DENSITY
EXISTING GROUND LEVEL
1500

CONCRETE GEO-SYNTHETIC SURFACE CUT TO LEVEL AND SURFACE CUT TO LEVEL AND
COMPACTED COMPACTED 1
LAGOON BED CEMENTICIOUS COMPOSITE n (SEE NOTE 5)
1 VARIES
SHEETS LAYER OF 5 DOWN WELL GRADED LAYER OF 5 DOWN WELL GRADED
n (SEE NOTE 5) CRUSHED ROCK COMPACTED TO 95% CRUSHED ROCK COMPACTED TO 95%
1000
MAXIMUM DRY DENSITY MAXIMUM DRY DENSITY
120 SURFACE CUT TO LEVEL, SCARIFIED LAYER OF 5 DOWN WELL GRADED
AND COMPACTED CONCRETE GEO-SYNTHETIC CONCRETE GEO-SYNTHETIC CRUSHED ROCK COMPACTED TO 95%
DOUBLE WELDED CEMENTICIOUS COMPOSITE SHEETS CEMENTICIOUS COMPOSITE SHEETS MAXIMUM DRY DENSITY
150 THICK LAYER OF 5 DOWN WELL
JOINT FOR AIR TEST GRADED CRUSHED ROCK COMPACTED
DETAIL - 5 (b) DETAIL - 6 (b) ANCHOR TRENCH
TO 95% MAXIMUM DRY DENSITY
N.T.S N.T.S
2 THICK TEXTURED HDPE LINER

150 THICK LAYER OF 5 DOWN WELL DETAIL - 7 (b)


GRADED CRUSHED ROCK COMPACTED N.T.S
TO 95% MAXIMUM DRY DENSITY
GEOTEXTILE MEMBRANE

DETAIL - 4 (b)
N.T.S
CONCRETE GEO-SYNTHETIC CEMENTICIOUS COMPOSITE SHEETS REFERENCE DRAWINGS AND DOCUMENTS
LINING STANDARD DRAWING - G.A. OF STORM WATER MANHOLES 201
TO
205
STANDARD DRAWING - TYPICAL DETAILS OF STORM WATER 701
OUTFALL
STANDARD DRAWING - STORM WATER LAGOON 901
ARRANGEMENT LAYOUT SHEET 1 OF 3
STANDARD DRAWING - STORM WATER LAGOON
904
MISCELLANEOUS DETAILS
SHEET 1 OF 2
300 THICK LAYER OF 75 DOWN 300 THICK LAYER OF 75 DOWN STANDARD DRAWING - STORM WATER LAGOON
WELL GRADED GRANULAR WELL GRADED GRANULAR MISCELLANEOUS DETAILS 905
10 THICK CONCRETE COVER
10 THICK CONCRETE COVER MATERIAL COMPACTED TO 95% MATERIAL COMPACTED TO 95% SHEET 2 OF 2
MAXIMUM DRY DENSITY MAXIMUM DRY DENSITY

2853
GEOCELL WITH EXISTING GROUND LEVEL
150 THICK LAYER OF 5 DOWN WELL GRADED CONCRETE INFILL
CRUSHED ROCK (LIGHTLY COMPACTED) (GRADE M25)
No. REVISION-2 APP'D 2021
1 CLIENT
1500 SURFACE CUT TO LEVEL AND SURFACE CUT TO LEVEL AND n (SEE NOTE 5) VARIES
COMPACTED COMPACTED
SURFACE CUT TO GEOCELL WITH CONCRETE INFILL GEOCELL WITH CONCRETE INFILL
LAGOON BED LEVEL, SCARIFIED (GRADE M25) (GRADE M25) GEOCELL WITH CONCRETE INFILL
1 AND COMPACTED
(GRADE M25)
1000
n (SEE NOTE 5) 10 THICK CONCRETE COVER 10 THICK CONCRETE COVER TITLE
120 STANDARD DRAWINGS
ANCHOR TRENCH

DOUBLE WELDED
DETAIL - 5 (c) DETAIL - 6 (c) STORM WATER WORKS
150 THICK LAYER OF 5 DOWN WELL N.T.S
N.T.S
JOINT FOR AIR TEST GRADED CRUSHED ROCK COMPACTED
TO 95% MAXIMUM DRY DENSITY DETAIL - 7 (c) DRAWING TITLE
N.T.S
2 THICK TEXTURED HDPE LINER
STANDARD DRAWING STORM
150 THICK LAYER OF 5 DOWN WELL
GRADED CRUSHED ROCK COMPACTED WATER LAGOON ARRANGEMENT
TO 95% MAXIMUM DRY DENSITY
LAYOUT SHEET 3 OF 3
GEOTEXTILE MEMBRANE

DETAIL - 4 (c) DRAWN - SCALE N.T.S


N.T.S
GEOCELL WITH CONCRETE INFILL CHECKED - DATE -
LINING APPROVED - SIZE A1
PROJECT DWG.
No. - No.
903

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND

LAGOON INLET PIPELINE


MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT

EM INI NS AR
500 1000 1000 500

LAGOON OUTLET PIPE TO


M W E

NEAREST STORM WATER


200mm THICK LAYER REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED

ER MU TR TH SE

FROM STORMWATER
ACCESS

DO HEN

OR OTHER LOCATION
G M L EA CH E
D50 = 100 ROCK AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND

EN IN M A D
ROAD
PUMPING STATION COMPOUND APPROVED AS PART OF THE PROJECT DRAWING SET.

(PROVISIONAL)
CY ED CO NN ETA
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X EGL 2mm HDPE LINER EGL
PERIMETER FENCE

NETWORK

DEPTH TO SUIT
500

500
O LE ND EL IL-

HYDRAULICS &
GEOTEXTILE FABRIC 1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS

VE N IT D 1

TOPOGRAPHY
X
OTHERWISE STATED.

RF GT IO UG IN

NETWORK
X
LO H NS T DR
2. IF EXCAVATED SURFACE CONTAINS SOFT SPOTS

W IS

X
THESE SHALL BE DUG OUT AND REPLACED WITH

CH TO
ANCHORAGE TRENCH ANCHORAGE TRENCH FIRM MATERIAL. ANY SHARP STONES OR

AN BE

X
FOR HDPE LINE FOR HDPE LINE PROJECTIONS SHALL BE REMOVED BEFORE

NE DE
1 1
PROTECTION

X
PROTECTION

L SI
m (SEE NOTE 5) PLACING THE GEOTEXTILE / LINER.
m (SEE NOTE 5)

O A

X
3. WITHIN THE RANGE FOR STABILITY THE BUND SIDE

SU W

G
SLOPES ARE TO BE SUCH THAT AS FAR AS

IT ING

X
NE
AB N
VALVE POSSIBLE. THE BUND ABOVE EXISTING GROUND

D
LE o .

X
1000

BA
CHAMBER LEVEL IS FORMED ENTIRELY FROM SUITABLE

EN 905
(MIN.)

SE

X
EXCAVATED MATERIAL ( i.e. THE 'CUT AND FILL' ARE

D
PO
TO BE EQUAL).

X
N
IN
4. SIDE SLOPE n:1; n TYPICALLY VARIES BETWEEN

X
DETAIL-1 (2.5:4). STEEPER OR FLATTER SLOPES MAY BE

X
LAGOON EMERGENCY OVERFLOW - LINED CHANNEL USED BASED SITE CONDITIONS AND PROTECTION
TYPE.

X
N.T.S 5. SIDE SLOPE m:1; m TYPICALLY VARIES. STEEPER

X
X
OR FLATTER SLOPES MAY BE USED BASED SITE
PUMPING

X
X
CONTROL BUILDING CONDITIONS AND PROTECTION TYPE.
STATION
X
6. MINIMUM WIDTH OF THE ROAD SHALL BE AT LEAST

X
(INDICATIVE
X

5M OR AS AGREED BY THE DEPARTMENT.

X
ARRANGEMENT FOR
7. LIGHTING POLE IS FOR INDICATIVE PURPOSES.
GUIDANCE ONLY)

X
ANY SOURCE OF OUTDOOR LIGHTING MAY BE
PEDESTRIAN

X
USED UPON ENGINEERS APPROVAL.
GATE
X X

X
STANDARD
LAGOON PERIMETER FENCE
X X

MANHOLE

X
X

X X X X X X X X X X X X X X X X X X X XX X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
LEGEND
X

STORM WATER GRAVITY LINE


X

STORM WATER GRAVITY LINE

STORM WATER PRESSURE LINE

BTL BUND TOP LEVEL

TWL TOP WATER LEVEL

PS PUMPING STATION
5000

BUND
EGL EXISTING GROUND LEVEL

TYP TYPICAL VALUE


INLET PIPE TO
LAGOON

OUTFALL STRUCTURE
FROM OUTLET POINT

SEE DRAWING No. 904 FOR 15 LUX LIGHTING


OUTLET CHAMBER DETAILS INTENSITY (SEE
NOTE 7)
2000

ACCESS STAIRCASE
SEE DETAIL-2
REFERENCE DRAWINGS AND DOCUMENTS
STANDARD DRAWING - G.A. OF STORM WATER MANHOLES - 201
TO
STORM WATER LAGOON - PUMPING STATION LAYOUT 205
STANDARD DRAWING - TYPICAL DETAILS OF STORM - 701
N.T.S
WATER OUTFALL
STANDARD DRAWING - STORM WATER LAGOON - 901
ARRANGEMENT LAYOUT
STANDARD DRAWING - STORM WATER LAGOON - 902
ARRANGEMENT LAYOUT
15 LUX LIGHTING INTENSITY (SEE STANDARD DRAWING - STORM WATER LAGOON - 905
NOTE 7) MISCELLANEOUS DETAILS
SHEET 2 OF 2

5000 No. REVISION-2 APP'D 2021


CLIENT

GALVANISED MILD STEEL


FLAGGED TILED OR CONCRETE STAIRCASE
RAMP CLEAR WIDTH 1000 WITH TITLE
NORMAL TWL
HANDRAIL ON TWO SIDES. STANDARD DRAWINGS
3000
1500 SQUARE AT BASE x 250 STORM WATER WORKS
THICK IN-SITU REINFORCED
INTERMEDIATE BERM IF 1 1
CONCRETE SLAB
150 THICK LAYER OF 75 REQURIED FOR n (SEE NOTE 4) n (SEE NOTE 4) DRAWING TITLE
DOWN ROCK UNCOMPACTED STABILITY
1500 SQUARE AT BASE x GEOTEXTILE MEMBRANE SECURITY GATE STANDARD DRAWING STORM WATER
250 THICK IN-SITU IN PERIMETER
FENCE LAGOON MISCELLANEOUS DETAILS
REINFORCED CONCRETE

X
SLAB SHEET 1 OF 2

X
X
1
n (SEE NOTE 4) VARIES DRAWN - SCALE N.T.S
TREATMENT CELL BED
CHECKED - DATE -
DETAIL-2
STORM WATER LAGOON - ACCESS STAIRCASE APPROVED - SIZE A1
N.T.S PROJECT DWG. 904
No. - No.

THIRD EDITION - APRIL 2022


NOTES:
15 LUX LIGHTING THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
INTENSITY (SEE MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
NOTE 6) REQUIREMENTS. THEY ARE EXPECTED TO BE
PERIMETER INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
HANDRAIL CHECKED AND APPROVED AS PART OF THE PROJECT
RETAINING WALL DRAWING SET.
5000
VARIES
1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS
FENCE
X

LAGOON EMERGENCY BTL BTL (TWL + 1m FREE BOARD)


OVERFLOW PIPE TO CHANNEL OTHERWISE STATED.
X

NORMAL TWL
2. LAGOON EMERGENCY OVERFLOW WEIR TO BE SIZED
X

ASPHALT LEVEL AND SET AT A LEVEL SUCH THAT AN ABSOLUTE


MINIMUM 600 FREEBOARD IN THE LAGOON IS
1 INTERMEDIATE BERM IF ACHIEVED UNDER EMERGENCY CONDITIONS.
n (SEE NOTE 4) REQURIED FOR STABILITY NORMAL TWL
MINIMUM WEIR LEVEL TO BE AT LEAST 200 ABOVE
EMERGENCY
FLOW NORMAL TWL IN LAGOON. OVERFLOW WEIR IS TO
OVERFLOW WEIR
RETURN TO STORM WATER DISCHARGE INTO A CHANNEL WHICH TAKES THE
SYSTEM FOR EMERGENCY GRAVEL BUND TO SURROUND MANHOLE
(GRADED FROM 5-20mm) BUND IS FILLED WITH FLOW INTO A NON-INHABITED AREA.
OVERFLOW OR / AT
MORTAR / TO BE CONCRETE LINED TREATMENT CELL BED 3. WITHIN THE RANGE FOR STABILITY THE BUND SIDE
MAINTENANCE 1
n (SEE NOTE 4) SEDIMENTATION AREA BED SLOPES ARE TO BE SUCH THAT AS FAR AS
SEE OUTLET CHAMBER
POSSIBLE. THE BUND ABOVE EXISTING GROUND
LAGOON BED DETAIL
LEVEL IS FORMED ENTIRELY FROM SUITABLE
EXCAVATED MATERIAL ( i.e. THE 'CUT AND FILL' ARE
TO BE EQUAL).
OUTLET PIPE MINIMUM SIZE 300. TO BE DESIGNED AS PRESSURE PIPE 4. SIDE SLOPE n:1. n TYPICALLY VARIES BETWEEN
FLOW FLOW (2.5:4). STEEPER OR FLATTER SLOPES MAY BE USED
BASED ON SITE CONDITIONS AND PROTECTION
TYPE.
OUTLET CHAMBER 5. MINIMUM WIDTH OF THE ROAD SHALL BE AT LEAST
STANDARD
MANHOLE 5M OR AS AGREED BY THE DEPARTMENT.
6. LIGHTING POLE IS FOR INDICATIVE PURPOSES. ANY
PUMPING STATION WET WELL SOURCE OF OUTDOOR LIGHTING MAY BE USED
(INDICATIVE ARRANGEMENT FOR GUIDANCE ONLY)
TYPICAL OUTLET DETAIL SECTION UPON ENGINEERS APPROVAL.
N.T.S
LEGEND
BTL BUND TOP LEVEL

RUBBER DUCKBILL NON-RETURN TWL TOP WATER LEVEL


VALVE, 80 BORE AT FLANGE
VC VALVE CHAMBER
HDPE LINER FIXED TO CONCRETE
WALL BY M20 BOLTS AT 500 EGL EXISTING GROUND LEVEL
STAINLESS STEEL STUDS, CENTERS THROUGH 20x20 FIXING
ADDITIONAL HDPE LINER WASHER & NUT SEE DETAIL- XX STRIP. ALL MATERIAL TO BE 316
MATERIAL 350 SQUARE DOUBLE PS PUMPING STATION
SAFETY GRILL STAINLESS STELL
WELDED TO MAIN LINER STAINLESS STEEL 6 THICK FLANGE OVER END OF PIPE SEDIMENT TRAP
TYP TYPICAL VALUE
RING WITH 80 BORE PN16 DRILLING

300
ALL FLANGED
120 DOUBLE WELDED RADIAL TEE IN DI
(MIN.) JOINT FOR AIR TEST

FLANGE
LAGOON LINER WITH LAGOON LINER WITH

2000
STAINLESS STEEL 316 ADAPTOR IRON STEPS
GEOTEXTILE PROTECTION STANDARD 80 BORE GEOTEXTILE
FLANGE RING 80 BORE x 6 THICK FLANGE GASKETS
UNDERNEATH PROTECTION FLOW BLANK FLANGE
WITH STUDS TO PN16 PATTERN
UNDERNEATH
GROUND LEVEL AT VALVE IPF RC CHAMBER
FLEXIBLE

500
300 SQUARE OPENING IN LINER TANKING MEMBRANE
COUPLING AND PROTECTION BOARD
FLANGE
ADAPTOR CONCRETE
LAGOON PRESSURE RELIEF VALVE DETAILS, IF REQUIRED SUPPORT
N.T.S BLOCK
500 5000 SQUARE 500
REFERENCE DRAWINGS AND DOCUMENTS
SECTION A-A STANDARD DRAWING - G.A. OF STORM WATER MANHOLES - 201
3x150 WIDE PREEMBEDDED TO
CAST-IN-LINER 205
STANDARD DRAWING - TYPICAL DETAILS OF STORM WATER - 701
EXTRUSION WELD 5000 OUTFALL
STANDARD DRAWING - STORM WATER LAGOON - 901
150 THICK LAYER OF 5 DOWN WELL GRADED ARRANGEMENT LAYOUT
CRUSHED ROCK COMPACTED TO 95% MAXIMUM STANDARD DRAWING - STORM WATER LAGOON - 902
DRY DENSITY MISCELLANEOUS DETAILS
STANDARD DRAWING - STORM WATER LAGOON - 904
OPEN MESH GALVANISED MISCELLANEOUS DETAILS
2 THICK SMOOTH HDPE LINER
MILD STEEL FLOOR IN SHEET 1 OF 2
PANELS SUPPORTED BY
D50 TO D200 INLET APRON
EDGE ANGLES AND
INTERMEDIATE RSJs
150 THICK LAYER OF 5 DOWN WELL
GRADED CRUSHED ROCK
No. REVISION-2 APP'D 2021
A A CLIENT
STEP
5000

LAGOON BED IRONS

OUTLET PIPE SIZED FOR


REQUIRED EMPTYING TITLE
TIME BUT MINIMUM STANDARD DRAWINGS
DIAMETER IS 300
PANEL 990 SQUARE CLIPPED
TO SUPPORTING STEEL
STORM WATER WORKS
WORK
DRAWING TITLE

500 250
STANDARD DRAWING STORM WATER
50 THICK MORTAR
PLAN LAGOON MISCELLANEOUS DETAILS
SHEET 2 OF 2

OUTLET CHAMBER DETAILS DRAWN - SCALE AS SHOWN


OUTLET CHAMBER N.T.S
CHECKED - DATE -
DETAIL-XX WALL NOTE : CHAMBER IS SURROUNDED BY SEDIMENT TRAP
APPROVED - SIZE A1
N.T.S
PROJECT DWG.
No. - No.
905

THIRD EDITION - APRIL 2022


NOTES:

PVC WATERSTOP WATERPROOFING


MEMBRANE AS PER 1 CONSTRUCTION
STAGGERED LAPS STAGGERED LAPS SPECIFICATIONS - JOINT FOR KICKER
DOWEL CAP, END FILLED

30 (Min.)
POLYSULPHIDE SEALANT
EXTERNAL WITH COMPRESSIBLE
CJ 50mm MATERIAL

EQ. EQ.
WALL THICKNESS
BASE SLAB
HYDRO EXPANSIVE
WATERSTOP
RIBBED
MESH CRANKED OR 20 COMPRESSIBLE 16mmØ DOWEL BARS 600 LONG
PERMANENT FILLER BOARD
LOOSE BARS LAPPED AT400mm CENTRES, ONE HALF
FORMWORK CJ WATERPROOFING MEMBRANE DEBONDED WITH AS APPROVED
INTERNAL AS PER SPECIFICATIONS PROPRIETARY COMPOUND.
SEALANT 12 EXTENT/WIDTH 75mm THK. BLINDING
PLAN OF RIBBED
FORMWORK TYPICAL DETAIL
50mm THK.
PROTECTION 75mm THK. BLINDING TYPICAL CONSTRUCTION JOINT OF MOVEMENT JOINT - MJ
SCREED CONCRETE NTS
FOR WALLS
WATERPROOFING NTS
EXTERNAL
MEMBRANE
WATERSTOP
AS PER
SPECIFICATIONS SECTION
BASE SLAB CONSTRUCTION JOINT
NTS

WALL WALL
THICKNESS THICKNESS

WATERPROOFING
MEMBRANE AS PER
SPECIFICATIONS WATERPROOFING
MEMBRANE AS PER
STAGGERED LAPS SPECIFICATIONS

WATERSTOP PROTECTION PROTECTION


WELDED TO BOARD BOARD
REFERENCE DRAWINGS AND DOCUMENTS
WATERPROOF
SHEET PVC
MEMBRANE PVC
WATERSTOP
WATERSTOP
EXTERNAL
CJ WATERSTOP
EXTERNAL
WATERSTOP

DETAIL 1

HIGH KICKER
- 1 CJ
NTS

150mm
-

No. REVISION-1 APP'D 2020


CLIENT

PLAN SECTION
TITLE
EXTERNAL WALL VERTICAL CONSTRUCTION JOINTFOUNDATION SLAB TO WALL CONSTRUCTION JOINT STANDARD DRAWINGS
NTS NTS STORM WATER WORKS
DRAWING TITLE

STANDARD DETAILS
CONSTRUCTION AND
MOVEMENT JOINT

DRAWN - SCALE NTS


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No. 1001

THIRD EDITION - APRIL 2022


NOTES:
0.0 CIVIL AND STRUCTURAL ABBREVIATIONS STANDARD SYMBOLS STRUCTURAL STEEL WORK SYMBOLS BEAM NUMBERING TO BE READ AS FOLLOWS
APPROX = APPROXIMATELY MAX = MAXIMUM +0.00m SSL LEVELS ON SECTIONS OR ELEVATIONS
FULL MOMENT CONNECTIONS B B1 01
ABR = ALT. BARS REVERSED MEP = MECHANICAL ELECTRICAL & PLUMBING
ABS = ALT. BARS STAGGERED MECH = MECHANICAL (FOR STEEL COLUMNS) BEAM RUNNING NUMBERS
A. BOLT = ANCHOR BOLT MEZZ = MEZZANINE +00.000 SSL LEVELS ON PLANS OR GA FULL MOMENT CONNECTIONS
MIN = MINIMUM FLOOR LEVELS (B5 TO GF, T01 TO TS2)
ADJ = ADJUSTABLE (FOR RC COLUMNS)
ALT = ALTERNATE MISC = MISCELLANEOUS
ARCH = ARCHITECTURAL ML = MIDDLE LAYER REVISION MARK SIMPLE CONNECTION
BCE = BOTTOM CHORD EXTENSION
MOM = MOMENT 1 REBAR MARKERS TO BE READ AS FOLLOWS:
Mxx(E) = BENDING MOMENT ABOUT X-X
BLDG = BUILDING AXIS, kN-m DUE TO 2- T 16 - 200 - T1
BM = BEAM EARTHQUAKE
B, BOT = BOTTOM DETAIL TO BE CONFIRMED
Myy(E) = BENDING MOMENT ABOUT Y-Y
BRDG = BRIDGING AXIS, kN-m DUE TO No. OF BARS GRADE DIAMETER SPACING LAYER
BSMT = BASEMENT EARTHQUAKE TBC 1
B PL = BASE (BEARING) PLATE Mxx = BENDING MOMENT ABOUT X-X
BP = BASE POINT AXIS, kN-m SOP1 SETTING OUT POINT
LEGEND:
BS = BRITISH STANDARD Myy = BENDING MOMENT ABOUT Y-Y
AXIS, kN-m PERMANENT OPENING IN FLOOR OR WALL BOTTOM / FAR FACE BAR
C/C =
CENTRE TO CENTRE m = METRE
CRS =
CENTRES mm = MILLIMETRE
C
L =
CENTRE LINE MPa = MEGAPASCAL TEMPORARY OPENING (BOXOUT) IN
CANT =
CANTILEVER MN = MEGA NEWTON
CL =
CLEAR FLOOR OR WALL
MSRC = MODERATELY SULPHATE RESISTING CEMENT
Cf =
COMPRESSIVE FORCE, kN
Cf(E) =
COMPRESSIVE FORCE, kN NOM = NOMINAL
N = NEWTON STEP IN LEVEL ON PLANS OR GA
DUE TO EARTHQUAKE.
CH PL = CHEQUERED PLATE NF = NEAR FACE SLAB THICKNESS INDICATED ON PLAN
NO. = NUMBER 250 THK.
WALL THICKNESS INDICATED IN ELEVATION
CHS = CIRCULAR HOLLOW SECTION NTS = NOT TO SCALE
CSK = COUNTER SUNK N-S = NORTH-SOUTH
CHAM = CHAMFERED 200x600 BEAM SIZE ON PLAN
(WIDTHxDEPTH)
C = COLUMN OWSJ = OPEN WEB STEEL JOIST
CONC = CONCRETE OF = OUTSIDE FACE
CONSTR = CONSTRUCTION BREAK LINE
OPEN = OPENING
CONT = CONTINUOUS
C/W = CONNECT WITH O/A = OVER ALL
C
L CENTRE LINE
CJ = CONSTRUCTION JOINT
CG = CENTRE OF GRAVITY PL = PLATE
Pa = PASCAL BORE HOLE
DET = DETAIL PROJ = PROJECTION BH1
DEG = DEGREES P/O = PERMANENT OPENING
DIAG = DIAGONAL PRS = PAIRS GROUND WATER LEVEL
DIA,Ø = DIAMETER
DIM = DIMENSION RAD = REACTION, RADIUS
D = DEPTH Rf = VERTICAL REACTION, kN REINFORCED CONCRETE
DP = DEEP REF = REFERENCE
DL = DEAD LOAD RW = RETAINING WALL
DWG(S) = DRAWING(S) RC = REINFORCED CONCRETE
DWL(S) = DOWEL(S) REFT = REINFORCEMENT MASS CONCRETE
REINF = REINFORCE
RHS = RECTANGULAR HOLLOW SECTION
DSB = DOWNSTAND BEAM RSA = ROLLED STEEL ANGLE RC COLUMN STARTS FROM SSL
DN = DOWN RSC = ROLLED STEEL CHANNEL
EA = EACH RSJ = ROLLED STEEL JOIST
EE = EACH END REQD = REQUIRED
EF = EACH FACE REV = REVISION, REVISED RC COLUMN ENDS BELOW SSL
EGL = EXISTING GROUND LEVEL R/W = REINFORCE WITH
EL = ELEVATION LEVEL
ELEV = ELEVATION SECT = SECTION B-B101 DENOTES BEAM MARK
ELECT = ELECTRICAL SF = STRIP FOOTING
EQ = EQUAL S = SLAB
ES = EACH SIDE SHS = SQUARE HOLLOW SECTION
EW = EACH WAY SL = SLAB NORTH POINT
EXTG = EXISTING SOP = SETTING OUT POINT
EJ = EXPANSION JOINT SOG = SLAB ON GRADE
EXT = EXTERIOR SPECS = SPECIFICATIONS
EXTF = EXTERNAL FACE STD = STANDARD
E-W = EAST-WEST STRUCT = STRUCTURAL
SQ = SQUARE A ELEVATION MARK
FPBW = FULL PENETRATION BUTT WELD ST = STAIR S001 DRAWING No. WHERE ELEVATION IS SHOWN
FDN = FOUNDATION STG = STAGGERED
FF = FAR FACE T = TOP SECTION MARK (WHERE
FFL = FINISHED FLOOR LEVEL Ta = TENSION ANCHORAGE SECTION IS SHOWN ON A REFERENCE DRAWINGS AND DOCUMENTS
FGL = FINISHED GROUND LEVEL TM(E) = TORSIONAL MOMENT, kN-m 1 DIFFERENT DRAWING)
FIN = FINISHED DUE TO EARTHQUAKE S001 DRAWING No. WHERE SECTION IS SHOWN
FL = FLOOR TF(E) = TENSION FORCE, kN
FTG, F = FOOTING DUE TO EARTHQUAKE
FW = FILLET WELD THK = THICKNESS 1 1
TM = TORSIONAL MOMENT, kN-m SECTION MARK
GA = GENERAL ARRANGEMENT Tf = TENSION FORCE, kN
GALV = GALVANIZED TEMP = TEMPERATURE / TEMPORARY
GL = GROUND LEVEL TD = TYPICAL DETAIL
GEN = GENERAL TJ = TRANGULAR JOINT
GAG = GAUGE TYP = TYPICAL 1
TOC = TOP OF CONCRETE DETAIL MARK
GWT = GROUND WATER TABLE S001 DWG. No. WHERE DETAIL
TOS = TOP OF STEEL IS SHOWN
H, HORZ = HORIZONTAL T/O = TEMPORARY OPENING
Hf = HORIZONTAL FORCE, kN UB = UNIVERSAL BEAM
HSC = HORIZONTALLY SLOTTED UC = UNIVERSAL COLUMN
CONNECTION UL = UPPER LAYER ELEVATION A SUB-TITLE FOR
= HIGH STRENGTH FRICTION S002 ELEVATION
HSFG UNO = UNLESS NOTED OTHERWISE 1 : 100
GRIP
IF = INSIDE FACE U/S = UNDERSIDE DWG. No. WHERE ELEVATION No. REVISION-1 APP'D 2020
USB = UPSTAND BEAM MARK IS CALLED UP
IJ = ISOLATION JOINT CLIENT
INT = INTERIOR / INTERNAL V, VERT = VERTICAL
Vf = VERTICAL SHEAR, kN DETAIL A
J = JOINT VXB = VERTICAL CROSS BRACING SUB-TITLE FOR
VSC = VERTICALLY SLOTTED 1 : 50 S003 DETAIL
kg = KILOGRAM
kN = KILO NEWTON CONNECTION DWG. No. WHERE DETAIL
kN-m = KILO NEWTON METRE MARK IS CALLED UP
kN/m2 = kN PER SQUARE METRE WWF = WELDED WIRE FABRIC, TITLE
kN/m = KILO NEWTON PER METRE WELDED WIDE FLANGE. NOTES: STANDARD DRAWINGS
kPa = KILO PASCAL W = WIDE , WALL
1. IF A DETAIL/ SECTION/ ELEVATION IS SHOWN ON THE SAME DRAWING STORM WATER WORKS
L = LINTEL AS THE DETAIL/ SECTION/ ELEVATION MARK THEN "-" IS USED INSTEAD
LG = LONG OF DRAWING No. AS SHOWN BELOW.
DRAWING TITLE
LL = LIVE LOAD
LLV = LONG LEG VERTICAL
LLH = LONG LEG HORIZONTAL SECTION1 SUB-TITLE FOR STANDARD DETAILS
1 : 50 - SECTION
STRUCTURAL ABBREVIATIONS
2. IF A DETAIL/ SECTION/ ELEVATION IS CALLED UP ON MORE THAN 2 NOS. OF AND SYMBOLS
SUB-TITLE AS SHOWN BELOW:

DETAIL A
SUB-TITLE FOR
DRAWN - SCALE NTS
1 : 50 S200,S201,S202,S203. DETAIL
CHECKED - DATE -
DWG. No. WHERE DETAIL
MARK IS CALLED UP APPROVED - SIZE A1
PROJECT DWG.
No. - No. 1002

THIRD EDITION - APRIL 2022


NOTES:

STRUCTURAL DESIGN ASSUMPTIONS AND REFERENCES C. REINFORCEMENT


1 ALL STRUCTURAL DESIGN SHALL COMPLY WITH THE STANDARDS SET FORTH IN A8 UNLESS NOTED OTHERWISE, ALL DIMENSIONS ARE IN MILLIMETRES (mm) AND B5 UNLESS NOTED OTHERWISE, MINIMUM COVER TO ALL REINFORCEMENT C1 ALL REINFORCEMENT SHALL BE EPOXY COATED HIGH YIELD DEFORMED TYPE 2
THE 2013 ABU DHABI INTERNATIONAL BUILDING CODE (ADIBC). ALL LEVELS ARE IN METRES (m) RELATIVE TO ABU DHABI PORT DATUM. (INCLUDING LINKS) SHALL BE AS FOLLOWS: GRADE 460N/mm2 BARS TO ACI 318.

COVER IN RETAINING WALLS, FOUNDATIONS & BURIED SLABS: C2 ALL STARTER BARS AND BENT OUT BARS SHALL BE SURVEYED AND LOCATION
2 APPLIED LOADINGS FOR ALL STRUCTURES ARE AS FOLLOWS: A9 PRIOR TO CONSTRUCTION THE CONTRACTOR SHALL PRODUCE FULLY CONFIRMED IN AS-BUILT CONDITION, PRIOR TO PLACING COLUMN/WALL REINFORCEMENT.
CO-ORDINATED DRAWINGS FOR REVIEW BY THE ARCHITECT AND THE MOST SEVERE EXPOSURE CONTRACTOR SHALL SUBMIT AS-BUILT DRAWINGS OF STARTERS AND BENT OUT BARS
I) WIND LOADING IN ACCORDANCE WITH ADIBC AND ASCE7 CONSULTANT. THE DRAWING SHALL INCLUDE ALL CO-ORDINATED INFORMATION FACES EXPOSED TO WATER 75mm AND REPORT ANY DISCREPANCIES TO THE CONSULTANT PRIOR TO PLACING COLUMN/
EFFECTIVE WIND SPEED, Ve = 45 m/s RELATED TO DUCTS, OPENINGS, CAST-IN FIXINGS AND PENETRATIONS. THE EXTERNAL FACES CAST AGAINST SOIL 75mm WALL REINFORCEMENT.
SITE EXPOSURE - EXPOSURE C CONTRACTOR SHALL INCORPORATE ALL REQUIRED MEP ENGINEERING, EXTERNAL FACES CAST AGAINST FORMWORK 50mm
DRAWINGS PRODUCED BY SPECIALIST AND ASSOCIATED TRADES. RAFT/ TOP FACE 50mm C3 REINFORCEMENT IS SHOWN DIAGRAMATICALLY ON DRAWINGS. WHERE
II) SEISMIC LOADING IN ACCORDANCE WITH ADIBC. REINFORCEMENT IS ASSIGNED LAYER NUMBERS, FOR LAYER CONFIGURATION
A10 THE CONTRACTOR IS RESPONSIBLE FOR THE SAFETY OF THE WORKERS AT ALL SLABS 50mm
TIMES, AND SHALL IMPLEMENT A SITE SAFETY POLICY IN ACCORDANCE WITH COLUMNS 50mm REFER TO STANDARD DETAILS.
III) SUPERIMPOSED DEAD AND LIVE LOADS IN ACCORDANCE WITH ADIBC OR
AS PER LOAD REQUIREMENTS.
C4 SUPPORT ALL REINFORCEMENT ACCURATELY AND SECURELY ON APPROVED
REQUIREMENTS SHOWN IN RELEVANT DESIGN CALCULATIONS.
A11 THE CONTRACTOR SHALL PROVIDE A GENERAL METHOD STATEMENT CHAIRS PRIOR TO PLACING CONCRETE.
3 ALL MANHOLES / CHAMBERS ARE DESIGNED USING THE FOLLOWING
INDICATING DETAILS OF PHASING OF THE WORKS. THE METHOD STATEMENT B6 AGGREGATES SHALL BE FROM APPROVED SOURCES IN ACCORDANCE WITH THE
ASSUMPTIONS: C5 WELDING AND/OR SITE CUTTING OF REINFORCING SHALL NOT BE PERMITTED
SHALL PROVIDE THE CONTRACTOR'S PREFERABLE OPTIONS WHERE SUCH SPECIFICATION.
I) GROUNDWATER TABLE IS LOCATED AT FINISHED GROUND LEVEL.
OPTIONS ARE AVAILABLE. THE CONTRACTOR ALSO SHALL SUBMIT A METHOD UNLESS REVIEWED AND ACCEPTED IN WRITING BY THE CONSULTANT.
STATEMENT FOR ALL ELEMENTS OF WORK AND SHALL NOT PROCEED UNTIL B7 ALL PROPRIETARY FIXINGS SHALL BE INSTALLED IN ACCORDANCE WITH
II) NO PIPE THRUST FORCES ARE ACTING ON THE WALLS.
CONSULTANT'S WRITTEN APPROVAL IS GIVEN. MANUFACTURER'S INSTRUCTIONS. C6 LAPS SHALL BE IN ACCORDANCE WITH TABLE BELOW BASED ON THE DIAMETER OF
III) STABILITY SAFETY FACTORS: A12 ALL ELEMENTS OF THE STRUCTURE DESIGNED BY THE CONTRACTOR SHALL BE THE SMALLER BAR AT LAP LOCATION.
-FLOATATION - 1.1 SUBMITTED TO THE CONSULTANT FOR APPROVAL. B8 ALL CONCRETE SHALL BE COMPACTED USING A MECHANICAL VIBRATION
-SLIDING - 1.5 PROCESS. C7 LAPS SHALL BE IN ACCORDANCE WITH TABLE BELOW
-OVERTURNING / ROTATION - 2.0 A13 FIRE RESISTANCE REQUIREMENTS FOR THE STRUCTURE ARE:
-BEARING PRESSURE - 1.0 LOAD BEARING WALLS & COLUMNS.......................: 2hrs. B9 CONCRETE SHALL BE CURED BY AN APPROVED MEANS IN ACCORDANCE WITH
SPECIFICATIONS. LAPS
FLOOR CONSTRUCTION INCLUDING BEAMS...........: 2hrs.
IV) ALLOWABLE BEARING PRESSURES: GRADE 460
SHAFTS AND STAIRWAYS........................................: 2hrs. B10 FOR CLARITY, CHAMFERS ARE NOT SHOWN. GRADE 460
REINFORCEMENT TYPE
-DEEP STORMWATER MANHOLE (300-3000 DIA.) - 200 kPa GRADE 460 TYPE 2
-SHALLOW STORMWATER MANHOLE, INLET AND CATCH BASIN - 100 kPa TYPE 2 EPOXY COATED
A14 ALL ASTERISKED DIMENSIONS (INDICATED THUS: 123*) SHALL BE CONFIRMED FABRIC
B11 FOR ADDITIONAL REBATES, REFER TO THE CIVIL DRAWINGS. LAP LENGTH DEFORMED BAR DEFORMED BAR
3 ON SITE AND REPORTED TO THE CONSULTANT FOR CONSIDERATION.
V) SOIL SUBGRADE MODULUS - 8000 kN/m
B12 FOR ALL FALLS IN SLAB, DRIP GROOVES, REGLETS, CHAMFERS ETC. REFER TO A. LAPS ON TOP SURFACE OF 50 DIA 38 DIA 75 DIA
VI) DEAD LOAD A15 THE CONTRACTOR SHALL PRODUCE SHOP DRAWINGS AND SCHEDULES AS CIVIL DRAWINGS.
3 NECESSARY FOR COMPLETION OF THE WORKS AND RECORD DRAWINGS OF BEAMS AND SLABS WHERE
-CONCRETE DENSITY - 24.0 kN/m
3 THE AS-BUILT WORKS, (INCLUDING ELECTRONIC COPIES IN AUTOCAD DWG B13 FORMED SURFACES SHALL BE THE FOLLOWING FINISH TYPES AS DEFINED IN COVER IS LESS THAN
-SOIL DENSITY - 18.0 kN/m
FORMAT), ALL FOR THE CONSULTANT'S APPROVAL. SPECIFICATIONS. 2 x BAR DIA.
VII) SUPERIMPOSED DEAD LOAD: A16 THE CONTRACTOR SHALL COMPLY WITH ALL
-COVER SLAB - 2.5 kPa EXPOSED COLUMNS & WALLS : CATEGORY 1 (SUPERIOR) B. LAPS IN THE CORNERS OF 50 DIA 38 DIA 75 DIA
REQUIREMENTS OF
-BASE SLAB - 5.0 kPa ALL OTHER FORMED SURFACES : CATEGORY 3 (NORMAL)
ABU DHABI MUNICIPALITY AND ALL RELEVANT STATUTORY COLUMNS, WHERE COVER IS
BODIES. LESS THAN 2 x BAR DIA.
VIII) LIVE LOAD: B14 UNFORMED SURFACES SHALL RECEIVE THE FOLLOWING FINISH TYPES AS
-COVER SLAB - 33.3 kPa DEFINED IN THE SPECIFICATION.
-BASE SLAB - 5.0 kPa C. LAPS WHERE THE CLEAR 50 DIA 38 DIA 75 DIA

IX) MAXIMUM ALLOWED CRACK WIDTH TO BE 0.20 mm.


B. CONCRETE BLINDING
SLABS (TO RECEIVE SCREED)
: FF (FLOATED)
: TF (TAMPED)
DISTANCE BETWEEN
ADJACENT LAPS IS LESS
SLABS WITHOUT SCREED : PF (POWERFLOAT) THAN 75mm.
X) EARLY THERMAL AND SHRINKAGE CRACKING PARAMETERS: B1 ALL WORKMANSHIP AND MATERIALS SHALL COMPLY WITH ACI 318 AND
-COEFFICIENT OF THERMAL EXPANSION, α 0.00001 REFERENCED CODES THEREIN.
ALL AREAS TO RECEIVE A POWERFLOATED OR BRUSHED FINISH SHALL HAVE AN
D. WHEN BOTH `A' OR `B' AND 70 DIA 54 DIA 105 DIA
-FALL IN TEMP. BETWEEN PEAK OF HYDRATION AND AMBIENT TEMP., T1 - 33 °C APPROVED SURFACE HARDENER AND DUST INHIBITOR APPLIED UNLESS THE
-FALL IN TEMP. DUE TO SEASONAL VARIATION, T2 - 17 °C B2 ALL CONCRETE SHALL BE PREMIXED BY A REVIEWED AND ACCEPTED SUPPLIER `C' APPLY, LAPS TO BE MIN.
CONSULTANT APPROVES OTHERWISE.
OR APPROVED SITE BATCHING PLANT.
IF THE ABOVE ASSUMPTIONS ARE NOT SATISFIED, THE CONSULTANT SHOULD VERIFY B15 CONSTRUCTION JOINTS: E. ALL OTHER TENSION/ 35 DIA 27 DIA 55 DIA
B3 CEMENT IS GENERALLY TO BE ORDINARY PORTLAND CEMENT. BLENDED CEMENTS COMPRESSION LAPS.
THE DESIGN BASED ON THE ACTUAL VALUES.
MAY BE USED IN PILING CONCRETE TO PROVIDE THE SPECIFIED DURABILITY
I) HORIZONTAL CONSTRUCTION JOINTS SHALL NOT BE MADE IN BEAMS,
REQUIREMENTS.
UNLESS SHOWN ON THE DOCUMENTS OR REVIEWED AND APPROVED BY
THE CONSULTANT.
B4 FOR THE FOLLOWING AREAS THE CONCRETE SHALL BE AS NOTED BELOW. C8 THE CONTRACTOR IS RESPONSIBLE FOR PROVISION OF, AND SCHEDULING OF
II) VERTICAL CONSTRUCTION JOINTS MAY BE MADE ONLY AT MIDSPAN OF
A. GENERAL REFER TO SPECIFICATION FOR PERFORMANCE REQUIREMENTS. BEAMS OR SLABS UNLESS OTHERWISE NOTED OR SHOWN OR DIRECTED CHAIRS, SPACERS ETC. FOR THE SUPPORT OF REINFORCEMENT.
AND THEIR LOCATION SHALL BE REVIEWED AND APPROVED BY THE
CONSULTANT ADHERE TO DESIGN DETAILS. C9 ALL STARTER BARS SHALL HAVE A MINIMUM EMBEDMENT EQUIVALENT TO THE
A1 TECHNICAL SPECIFICATIONS OR SPECIFIC INSTRUCTIONS ON DRAWINGS TAKE
I) - SUPERSTRUCTURE CONCRETE STRAIGHT TENSION EMBEDMENT LENGTH CORRESPONDING TO THE SIZE OF THE
PRECEDENCE OVER THESE NOTES.
SUSPENDED BEAMS & SLABS BARS. STARTER BARS FROM WALLS TO SLABS SHALL HAVE A MINIMUM
B16 OPENINGS, SLEEVES AND EMBEDDED DUCTS: EMBEDMENT OF 600mm INTO THE WALLS AND SLABS UNLESS OTHERWISE
A2 THESE DRAWINGS SHALL BE READ IN CONJUNCTION WITH ALL CIVIL GENERAL - CONCRETE FOR SUB-STRUCTURE / FOUNDATIONS I) NO SLEEVES SHALL BE PLACED VERTICALLY OR HORIZONTALLY THROUGH
BASEMENT ENVELOPE, RAFT, EXTERNAL WALLS & NOTED OR SHOWN.
ARRANGEMENT AND OTHER RELEVANT DRAWINGS AND SPECIFICATIONS AND BEAMS UNLESS REVIEWED AND APPROVED BY THE CONSULTANT.
THE ELEMENTS IN CONTACT WITH SOIL - VERY SEVERE EXPOSURE
WITH SUCH OTHER WRITTEN INSTRUCTIONS AS MAY BE ISSUED DURING THE
- CONCRETE FOR CIVIL WORKS C10 PROVIDE STARTER BARS TO WALLS AND COLUMNS SIMILAR IN NUMBER, SIZE
COURSE OF THE CONTRACT. II) NO OPENINGS SHALL BE MADE IN FLAT PLATE COLUMN STRIPS EXCEPT
(INCLUDING MANHOLES & CULVERTS) AND SPACING TO THE VERTICAL STEEL IN THE WALL OR COLUMN ABOVE
AS SHOWN ON TYPICAL DETAILS AND PLANS OR UNLESS REVIEWED AND UNLESS OTHERWISE NOTED OR SHOWN.
A3 ALL DISCREPANCIES SHALL BE REFERRED TO THE CONSULTANT FOR A APPROVED BY THE CONSULTANT. SEE TYPICAL DETAIL ALSO.
CEMENT MSRC
DECISION BEFORE PROCEEDING WITH THE WORK.
GRADE C40/20
III) LOCATE CONDUITS AND PIPES IN CENTRE OF SLABS WITH 30 CLEAR C11 SHAPE CODE SHALL BE TO ACI 315 SPECIFICATION FOR BENDING REFERENCE DRAWINGS AND DOCUMENTS
A4 ALL MATERIALS AND WORKMANSHIP SHALL BE IN ACCORDANCE WITH THE MIN. CEMENT CONTENT 420kg/m3 DIMENSIONED AND SCHEDULING OF REINFORCEMENT FOR CONCRETE.
SPACE BETWEEN. NO HOLES TO BE MADE IN SLAB WITHOUT APPROVAL
RELEVANT AND CURRENT SPECIFIED STANDARDS AND THE BY-LAWS AND MAX. W/C RATIO 0.42 OF CONSULTANT
ORDINANCES OF THE RELEVANT BUILDING AUTHORITIES EXCEPT WHERE C12 INSERTS SHALL BE PROVIDED AS NECESSARY, INCLUDING SUPPORT FOR
VARIED BY THE PROJECT SPECIFICATION AND/OR DRAWINGS. B17 PROVIDE CAMBER TO SLABS AND BEAMS AS NOTED ON PLANS AND/OR DETAILS. MASONRY AND SERVICES. REINFORCEMENT SHALL BE ADJUSTED TO SUIT.
II) BLINDING CAMBER BOTH UNDERSIDE AND TOP OF CONCRETE TO MAINTAIN THE SLAB AND PLASTIC TAPE SHALL BE USED TO PREVENT CONTACT OF DISSIMILAR METALS.
A5 SET OUT DIMENSIONS AND LEVELS SHOWN ON THE DRAWINGS SHALL BE BEAM DEPTH SHOWN ON THE DRAWINGS UNLESS OTHERWISE NOTED OR SHOWN.
CEMENT MSRC THE CONTRACTOR SHALL SUBMIT PROPOSALS FOR SPACERS, CHAIRS, ETC. FOR
VERIFIED BY THE CONTRACTOR AND REFER TO MECHANICAL, ELECTRICAL C13
GRADE C20 THE CONSULTANT'S APPROVAL.
AND CIVIL DRAWINGS. THE CONSULTANT SHALL BE NOTIFIED OF ANY B18 CONCRETE PROTECTIVE COATINGS SHALL BE AS PER SPECIFICATIONS.
DISCREPANCIES PRIOR TO CONSTRUCTION. MIN. CEMENT CONTENT 250kg/m3
MAX. W/C RATIO 0.50
C14 CONTRACTOR SHOULD COMPLY WITH ACI 318
A6 DIMENSIONS SHALL NOT BE OBTAINED BY SCALING FROM DRAWINGS. ONLY
WRITTEN DIMENSIONS SHALL BE FOLLOWED. C15 REINFORCEMENT DETAILING SHALL COMPLY WITH THE REQUIREMENTS OF ADIBC.
* FREE WATER/CEMENT RATIO IS INCLUSIVE OF
ALL CEMENTITIOUS MATERIAL INCLUDING SILICA FUME.
A7 THE CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING THE STABILITY OF
THE STRUCTURE AND ANY ASSOCIATED EXCAVATIONS UNTIL THEIR
COMPLETION AND SHALL ENSURE THAT NO PART IS OVERSTRESSED BY
EXCESSIVE CONSTRUCTION LOADS. THE CONTRACTOR SHALL PROVIDE
TEMPORARY BRACING AND PROPPING AS REQUIRED.

No. REVISION-1 APP'D 2020


CLIENT

TITLE
STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

STRUCTURAL STANDARD NOTES


SHEET 1

DRAWN - SCALE NTS


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No. 1003

THIRD EDITION - APRIL 2022


NOTES:

D. STRUCTURAL STEEL WORK E. FORMWORK


D1 COMPLY WITH ADIBC, AISC AND REFERENCED CODES THEREIN. E1 FORMWORK SHALL COMPLY WITH ACI 318.

D2 ALL STRUCTURAL STEEL WORK SHALL BE CORROSION PROTECTED AND E2 BUILD FORMWORK TO SPECIFIED STANDARDS AND FROM CIVIL
FIRE PROTECTED IN ACCORDANCE WITH THE SPECIFICATION. DRAWINGS. PROVIDE FOR BUILT-IN FIXINGS, REBATES, FLASHINGS, TIES &
MECHANICAL, ELECTRICAL AND PLUMBING SERVICES ETC..
D3 ALL SECTIONS USED SHALL BE OF ROLLED STEEL SECTIONS FROM A SOURCE
APPROVED BY THE CONSULTANT. BUILT UP SECTIONS OR FABRICATED E3 CONTRACTOR SHALL SUBMIT PROPOSALS FOR FORMWORK INCLUDING FORMWORK
SECTIONS SHALL NOT BE USED UNLESS ADVISED BY THE CONSULTANT. SYSTEMS AND DETAILS INCLUDING CALCULATIONS AT THE COMMENCEMENT
ALL STRUCTURAL STEEL WORK SHALL BE IN ACCORDANCE WITH AISC. OF THE PROJECT.
GRADE S275 (PREVIOUSLY GRADE 43)
SHALL BE PROVIDED EXCEPT WHERE NOTED OTHERWISE. E4 WHERE NOT EXPOSED IN THE FINAL STRUCTURE, FORMWORK SHALL BE
THE PARTICULAR QUALITY GRADE FOR EACH ELEMENT SHALL BE AS FOLLOWS: CONSTRUCTED TO PREVENT BLEEDING DURING POURING OF CONCRETE AND
TO TOLERANCES COMPATIBLE WITH APPLIED FINISHES & DETAILS.
S275JR FOR MATERIAL OF THICKNESS < 20mm.
S265JO FOR MATERIAL OF THICKNESS >20mm, <40mm. E5 WHERE EXPOSED IN THE FINAL STRUCTURE, FORMWORK SHALL BE
S245J2G3 FOR MATERIAL OF THICKNESS >40mm, <90mm. CONSTRUCTED TO PROVIDE THE SPECIFIED FINISH AS NOTED IN CONCRETE
S275JOH FOR HOLLOW SECTIONS <40mm. GENERAL NOTES.

D4 STEEL BOLTS AND NUTS SHALL COMPLY WITH THE REQUIREMENTS OF AISC. E6 STRIPPING OF FORMWORK SHALL COMPLY WITH THE SPECIFICATION.

D5 ALL STEEL WORK MOMENT CONNECTIONS INCLUDING SPLICES SHOULD BE E7 PROVIDE BACKPROPPING FOR THE EXTENT AND CAPACITY AS RESOLVED WITH
DESIGNED AND DETAILED BY CONTRACTOR USING HSFG BOLTS IN ACCORDANCE THE CONSULTANT TO SUIT CONCRETE STRENGTH, STRIPPING TIMES AND
WITH AISC. HIGH STRENGTH FRICTION GRIP BOLTS, NUTS AND WASHERS SUBSEQUENT CONSTRUCTION ACTIVITIES.
SHALL COMPLY WITH THE REQUIREMENTS OF AISC.

D6 WHERE MOMENT CONNECTIONS ARE CALLED FOR BUT FORCES ARE NOT
INDICATED, DESIGN CONNECTIONS FOR FULL MOMENT CAPACITY OF THE
SMALLER MEMBER JOINED.
F. EARTH WORKS
F1 CARRY OUT BULK EARTHWORKS TO THE LEVELS SHOWN ON THE DRAWINGS.
D7 UNLESS OTHERWISE SHOWN ALL GUSSET PLATES SHALL BE 10mm THICK AND
ALL END PLATES SHALL BE 8mm THICK. ALL FILLET WELDS SHALL BE A F2 ALL LEVELS ARE SHOWN IN ABU DHABI PORT DATUM.
MINIMUM 6mm LEG LENGTH AND ALL BUTT WELDS SHALL BE FULL PENETRATION.
TESTING OF WELDS SHALL BE IN ACCORDANCE WITH THE SPECIFICATION. WELD F3 REMOVE FROM SITE ALL DELETERIOUS MATERIALS ENCOUNTERED DURING BULK
SYMBOLS ARE TO AWS D1.1. ALL WELDS SHALL BE FULL PROFILE, U.N.O. EARTHWORKS.

D8 FOR COMPOSITE DECKING FLANGES IN CONTACT WITH DECKING SHALL NOT BE F4 REMOVE FROM SITE ALL EXCAVATED MATERIAL NOT REQUIRED IN THE
PAINTED BEFORE FIXING OF SHEAR STUDS. COMPLETED WORKS.
D9 PROVIDE MINIMUM LENGTH BEARING OF 200mm FOR ALL STEEL BEAMS
F5 WHERE PERIMETERS OF BULK EXCAVATIONS ARE NOT CONTAINED BY RETENTION
BEARING ON MASONRY AND CONCRETE AND A MINIMUM OF 100mm ON
SYSTEMS, MAINTAIN A NOMINAL SLOPE OF 1.5 HORIZONTAL TO 1 VERTICAL TO
STRUCTURAL STEEL, UNLESS OTHERWISE NOTED OR SHOWN.
ENSURE THE STABILITY OF THE EMBANKMENT.
D10 CENTRE BEARING PLATES UNDER BEAMS UNLESS OTHERWISE NOTED OR SHOWN.
F6 PRIOR TO THE CONSTRUCTION OF THE SLABS ON GRADE, ALL EARTHWORKS
SHALL BE COMPACTED TO 95% MODIFIED MAXIMUM DRY DENSITY FOR A DEPTH
D11 BEARING PLATE DIMENSION GIVEN FIRST INDICATES SIDE PARALLEL TO BEAM
OF 1m BELOW THE UNDERSIDE OF THE SLAB REFER SPECIFICATIONS
WEB.
FOR COMPACTION DETAILS.
D12 NO STRUCTURAL STEEL SHALL BE CUT IN THE FIELD UNLESS REVIEWED AND
F7 EARTH WORKS SHALL COMPLY AS PER SPECIFICATIONS
APPROVED BY THE CONSULTANT.
AND AS PER RECOMMENDATIONS PROVIDED
BY APPROVED SOIL INVESTIGATION REPORT.
D13 WHERE COLUMNS ARE STABILISED BY WALLS PROVIDE TIES AS DETAILED ON
THE DRAWINGS. PROVIDE TEMPORARY BRACING UNTIL WALLS ARE BUILT TIGHTLY
F8 BACKFILL MATERIAL PROPERTIES SHALL BE AS FOLLOWS :
TO COLUMNS.
- ANGLE OF INTERNAL FRICTION = 30°
D14 ALL WELDS EXPOSED TO VIEW SHALL BE GROUND SMOOTH. - AT- REST EARTH PRESSURE COEFFICIENT, ko = 0.50
- ACTIVE EARTH PRESSURE COEFFICIENT, ka = 0.33
D15 SPLICES SHALL BE DESIGNED TO DEVELOP THE FULL TENSION CAPACITY OF THE - PASSIVE EARTH PRESSURE COEFFICIENT, kp = 3.0
MEMBER AT THE POINT OF THE SPLICE UNLESS OTHERWISE NOTED OR - FRICTION COEFFICIENT, m =
DETAILED. NO SPLICES SHALL BE MADE UNLESS SHOWN ON THE DRAWINGS 0.577
IF THE ABOVE PROPERTIES ARE NOT ACHIEVED ON SITE, THE CONSULTANT SHOULD
AND REVIEWED AND APPROVED BY THE CONSULTANT. VERIFY THE DESIGN BASED ON THE ACTUAL SOIL PROPERTIES.

D16 PROVIDE WELDED STIFFENER PLATES OF MINIMUM 10mm UNO ON BOTH SIDES OF
THE WEB OF BEAMS AT POINTS OF CONCENTRATED LOAD INCLUDING BEAMS
SUPPORTING COLUMNS OR RUNNING OVER TOPS OF COLUMNS.

D17 CONNECT ALL COLUMNS TO THE BASE PLATES FOR THE LARGER OF THE
FOLLOWING FORCES IN ADDITION TO OTHER FORCES SHOWN:
G. BLOCKWORK NOTES REFERENCE DRAWINGS AND DOCUMENTS
A) AT BRACING FOR THE HORIZONTAL COMPONENTS FROM THE BRACING.
G1. ALL CONCRETE BLOCKS SHALL BE AS PER ASTM C129 FOR NON-LOAD BEARING CONCRETE MASONRY UNITS.
B) FOR 3% OF THE FACTORED VERTICAL COLUMN LOAD APPLIED
HORIZONTALLY. G2. MORTAR SHALL BE AS PER ASTM C270.
D18 SHAPE AND SIZE OF GUSSET PLATES SHALL CLEAR ARCHITECTURAL FINISHES,
G3. ALL EMBEDDED ITEMS SHALL BE GALVANISED STEEL
STRUCTURAL DECKING, MECHANICAL DUCTS, PIPES AND ELEVATOR SHAFTS.
G4. FOR LOCATION AND DETAILS OF MOVEMENT JOINTS, REFER TO THE CIVIL DRAWINGS AND THE
D19 THE ENDS OF ALL TUBULAR MEMBERS ARE TO BE SEALED WITH 6mm THICK
SPECIFICATION.
PLATES AND CONTINUOUS FILLET WELDS UNLESS NOTED OTHERWISE.
G5. HOLES AND CHASES IN MASONRY WALLS SHALL COMPLY WITH BS5628 AND SHALL NOT BE CARRIED
D20 MAINTAIN TEMPORARY BRACING UNTIL SUFFICIENT ELEMENTS OF THE LATERAL
OUT WITHOUT THE ENGINEER'S REVIEW.
LOAD RESISTING SYSTEM ARE CONSTRUCTED INCLUDING STEEL DECK AND
GRATING OR OTHER ELEMENTS. G6. ALL RETURNS SHALL BE FULLY BONDED.
D21 PROVIDE PRE CAMBER TO BEAMS AND GIRDERS AS SHOWN ON THE PLANS. G7. LINTELS ARE TO BE PROVIDED IN ACCORDANCE WITH THE SPECIFICATION & STANDARD DETAILS ON DWG.
PRE CAMBERS SHOWN ARE FOR ERECTED IN PLACE CONDITION OF MEMBERS
BEFORE INSTALLATION OF STEEL DECK OR GRATING. G8. FOR EXTERNAL BLOCK WALLS, BED JOINT REINFORCEMENT SHALL BE PROVIDED EVERY

D22 UNLESS NOTED OTHERWISE INSTALL 75x75x8mm ANGLE SEATS TO PROVIDE TWO COURSE.
SUPPORT FOR STEEL DECK OR GRATING AT CONNECTIONS, COLUMNS OR
OTHER IRREGULARITIES. No. REVISION-1 APP'D 2020
D23 DETAILED STRUCTURAL STEEL SHOP DRAWINGS, CONNECTION DETAILS AND
CLIENT
CALCULATIONS SHALL BE PREPARED BY THE CONTRACTOR IN ACCORDANCE
WITH AISC AND RELEVANT SCI PUBLICATIONS AND SUBMITTED AS DEFINED
IN THE CONTRACT. FABRICATION OR INSTALLATION SHALL NOT COMMENCE UNTIL
REVIEWED AND ACCEPTED. REVIEW OF THESE DRAWINGS DOES NOT ALLEVIATE
THE CONTRACTOR'S RESPONSIBILITIES. COORDINATE THE INPUT OF ALL TRADES ON
THE SHOP DRAWINGS. TITLE
D24 PROTECTIVE COATING FOR STRUCTURAL STEEL SHALL BE AS PER SPECIFICATIONS.
STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

STRUCTURAL
STANDARD NOTES
SHEET 2

DRAWN - SCALE NTS


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No. 1004

THIRD EDITION - APRIL 2022


NOTES:
PRECAST WALL SEGMENT CONNECTION SHOWN THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
ARE INDICATIVE MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
AND SHALL BE CONFIRMED AS PER SUPPLIER'S REQUIREMENTS. THEY ARE EXPECTED TO BE
REQUIREMENTS INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
SUBJECT TO ENGINEER'S APPROVAL. CHECKED AND APPROVED AS PART OF THE PROJECT
DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED
OTHERWISE.
2. MINIMUM CONCRETE COVER TO REINFORCEMENT TO BE
T20-150 T VARIES
T16-150 B VARIES B AS FOLLOWS :
-
BASE SLAB AND WALL (EXTERNAL) = 75mm
T12-150 T&B BASE SLAB AND WALL (INTERNAL) = 50mm
T12-150 T&B T12-150 T&B VARIES
T12-150 T&B ROOF SLAB = 50mm
VARIES VARIES VARIES
2x2T16 T&B 2x2T16 T&B 3. ALL REINFORCEMENT SHALL CONFORM TO ASTM A615.
T12-150 T&B T12-150 T12-150 4. ALL LAPS SHALL BE IN ACCORDANCE WITH ACI 318.
VARIES 5. REINFORCEMENT TO BE DISPLACED ON SITE TO AVOID SMALL
T12-150 T&B
VARIES DIAMETER PIPEWORK.
T20-150 T VARIES
T16-150 B VARIES D 6. THE MANHOLES ARE DESIGNED USING FULL GROUND WATER
-
T12-150 T12-150 LEVEL CONDITION WITH 1.1 FACTOR OF SAFETY FOR
T12-150 T&B FLOATATION.
T12-150 B T12-150 B VARIES
U-BAR A 2x2T16 T&B 7. FOUNDATION DESIGN IS BASED ON ALLOWABLE BEARING
U-BAR
PRESSURE OF 200 kN/m² AND SOIL SUBGRADE MODULUS OF
- T12-150 T&B
VARIES
2x2T16 T&B 8. DEWATERING OPERATIONS SHALL BE PROVIDED DURING
CONSTRUCTION AND MAY ONLY BE TERMINATED AFTER
ROOF SLAB HAS BEEN CASTED.
SECTIOND 9. ALL BELOW GROUND CONCRETE TO BE TANKED REFER .
- TO STANDARD DRAWING No. 801.
1 : 25
ROOF SLAB PLAN 10. ALL REINFORCEMENT TO BE EPOXY COATED.
1 : 25
BASE SLAB PLAN LEGEND:
1 : 25
BOTTOM / FAR FACE BAR

REINFORCEMENT
12 T16 24-150 EF
PRECAST
CONCRETE T12-150 TOTAL No. OF BARS BAR LOCATION/S*
SHAFT T12-150
T12-150 T12-150 TYPE OF STEEL CENTRES OF BARS
T12-150 U-BARS
T12-150 T12-150 BAR DIAMETER BAR MARK
C
T12-150 T12-150 T12-150
-
T12-150
* BAR LOCATIONS
T12-150 EF T12-150 EF T12-150 T12-150 T TOP FF FAR FACE
T12-150 T12-150 B BOTTOM EF EACH FACE
NF NEAR FACE EW EACH WAY
T12-150
T12-150
T12-150 T20-150 T T12-150
NOTE:

T12-150 T12-150 T12-150 T12-150

T12-150
T12-150 T16-150 B T12-150 U-BARS
REFERENCE DRAWINGS AND DOCUMENTS
201 - STANDARD DRAWING G.A. OF STORM WATER MANHOLE
SECTIONA SECTIONB SECTIONC ON PIPELINES 300mm TO 500mm DIA.
1 : 25 - 1 : 25 - 1 : 25 -

250
2x2T16 EF 2T16 EF EXTRA
T12-150 EF BARS ABOVE
EXTRA BARS
2x2T16 EF OPENING
250

250

DIAGONAL
EXTRA BARS No. REVISION-1 APP'D
T12-150 2T12 2020
1000

T12-150 EF 2x2T16 EF CLIENT


DIAGONAL 2T16 EF EXTRA
EXTRA BARS BARS
BELOW OPENING

250
TITLE
STANDARD DRAWINGS
REINFORCEMENT DETAIL FOR TYPICAL WALL PIPE OPENING STORM WATER WORKS
PRECAST CONCRETE SHAFT TRIMMER BARS DETAIL
1 : 25 1 : 25 DRAWING TITLE

STANDARD REINFORCEMENT DETAILS


FOR STORM WATER MANHOLE ON
PIPELINES 300 - 500mm DIA.

DRAWN - SCALE 1:25


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1010

THIRD EDITION - APRIL 2022


NOTES:
NOTE: THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
PRECAST WALL SEGMENT CONNECTION MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
SHOWN ARE INDICATIVE REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AND SHALL BE CONFIRMED AS PER AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
T20-150 T VARIES SUPPLIER'S REQUIREMENTS APPROVED AS PART OF THE PROJECT DRAWING SET.
T16-150 B VARIES T12-150 T&B SUBJECT TO ENGINEER'S APPROVAL.
B VARIES
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED
- OTHERWISE.
2x2T16 T&B
2x2T16 T&B 2. MINIMUM CONCRETE COVER TO REINFORCEMENT TO BE AS
T20-150 T VARIES T20-150 T VARIES T12-150 T&B T12-150 T&B FOLLOWS :
T16-150 B VARIES T16-150 B VARIES VARIES VARIES BASE SLAB AND WALL (EXTERNAL) = 75mm
BASE SLAB AND WALL (INTERNAL) = 50mm
T12-150 T12-150
T20-150 T VARIES ROOF SLAB = 50mm
T16-150 B VARIES
3. ALL REINFORCEMENT SHALL CONFORM TO ASTM A615.
4. ALL LAPS SHALL BE IN ACCORDANCE WITH ACI 318.
5. REINFORCEMENT TO BE DISPLACED ON SITE TO AVOID SMALL
T12-150 T12-150
DIAMETER PIPEWORK.
6. THE MANHOLES ARE DESIGNED USING FULL GROUND WATER
T12-150 T&B LEVEL CONDITION WITH 1.1 FACTOR OF SAFETY FOR
T12-150 T&B VARIES FLOATATION.
VARIES 7. FOUNDATION DESIGN IS BASED ON ALLOWABLE BEARING
T16-150 B T16-150 B 2x2T16 T&B
PRESSURE OF 100 kN/m² AND SOIL SUBGRADE MODULUS OF
U-BAR U-BAR A 8000 kN/m³.
- 2x2T16 T&B 8. DEWATERING OPERATIONS SHALL BE PROVIDED DURING
T12-150 T&B CONSTRUCTION AND MAY ONLY BE TERMINATED AFTER
VARIES ROOF SLAB HAS BEEN CASTED.
9. ALL BELOW GROUND CONCRETE TO BE TANKED REFER .
TO STANDARD DRAWING No. 801.
10. ALL REINFORCEMENT TO BE EPOXY COATED.

BASE SLAB PLAN ROOF SLAB PLAN COVER SLAB SECTION LEGEND:
1 : 25 1 : 25 1 : 25 BOTTOM / FAR FACE BAR

REINFORCEMENT
12 T16 24-150 EF

T16-150
TOTAL No. OF BARS BAR LOCATION/S*
PRECAST T16-150
CONCRETE SHAFT TYPE OF STEEL CENTRES OF BARS
T16-150
T16-150 T16-150 T16-150 BAR DIAMETER BAR MARK
U-BARS
T16-150 T16-150
C
- * BAR LOCATIONS
T16-150

T TOP FF FAR FACE


T16-150 T16-150
T16-150 T16-150 B BOTTOM EF EACH FACE
T16-150 T16-150 NF NEAR FACE EW EACH WAY
T16-150 T16-150
T16-150 T16-150

T16-150 T20-150 T T16-150 T16-150

T16-150 T16-150 T16-150


T16-150 T16-150

T16-150 REFERENCE DRAWINGS AND DOCUMENTS


T16-150 T16-150 B T16-150 U-BARS
202 - STANDARD DRAWING G.A. OF SHALLOW STORM WATER
SECTIONA SECTIONB SECTIONC MANHOLE ON PIPELINES 600mm TO 1400mm DIA.
- - 1 : 25 -
1 : 25 1 : 25

2x2T16 EF
EXTRA BARS 2T16 EF EXTRA BARS
400 ABOVE OPENING
2x2T16 EF
T16-150 EF EXTRA BARS
250

250
T16-150
1000

T16-150 No. REVISION-1 APP'D 2020


T16-150 EF
CLIENT
2x2T16 EF 2T16 EF EXTRA
EXTRA BARS BARS
BELOW OPENING
400
TITLE
STANDARD DRAWINGS
REINFORCEMENT DETAIL FOR TYPICAL WALL PIPE OPENING STORM WATER WORKS
PRECAST CONCRETE SHAFT TRIMMER BARS DETAIL DRAWING TITLE
1 : 25 1 : 25
STANDARD REINFORCEMENT
DETAILS FOR SHALLOW STORM
WATER MANHOLE ON PIPELINES
600 - 1400mm DIA.
DRAWN - SCALE 1:25
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1011

THIRD EDITION - APRIL 2022


NOTES:
NOTE: THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
PRECAST WALL SEGMENT CONNECTION MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
SHOWN ARE INDICATIVE REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AND SHALL BE CONFIRMED AS PER AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
T20-150 T VARIES SUPPLIER'S REQUIREMENTS APPROVED AS PART OF THE PROJECT DRAWING SET.
T16-150 B VARIES T12-150 T&B SUBJECT TO ENGINEER'S APPROVAL.
B VARIES T12-150 T&B 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED
- T12-150 T&B VARIES OTHERWISE.
VARIES 2. MINIMUM CONCRETE COVER TO REINFORCEMENT TO BE AS
2x2T16 T&B T12-150 T&B FOLLOWS :
T20-150 T VARIES T20-150 T VARIES T12-150 T&B
T12-150 T&B VARIES
T16-150 B VARIES T16-150 B VARIES VARIES VARIES 2x2T16 T&B BASE SLAB AND WALL (EXTERNAL) = 75mm
T12-150 T&B
2x2T16 T&B BASE SLAB AND WALL (INTERNAL) = 50mm
T20-150 T VARIES VARIES
ROOF SLAB = 50mm
T16-150 B VARIES
3. ALL REINFORCEMENT SHALL CONFORM TO ASTM A615.
4. ALL LAPS SHALL BE IN ACCORDANCE WITH ACI 318.
5. REINFORCEMENT TO BE DISPLACED ON SITE TO AVOID SMALL
2x2T16 T&B DIAMETER PIPEWORK.
T12-150 T&B 6. THE MANHOLES ARE DESIGNED USING FULL GROUND WATER
T12-150 T&B VARIES LEVEL CONDITION WITH 1.1 FACTOR OF SAFETY FOR
VARIES T12-150 T&B FLOATATION.
T12-150 T&B VARIES 7. FOUNDATION DESIGN IS BASED ON ALLOWABLE BEARING
T16-150 B T16-150 B VARIES
2x2T16 T&B PRESSURE OF 100 kN/m² AND SOIL SUBGRADE MODULUS OF
U-BAR U-BAR A 8000 kN/m³.
2x2T16 T&B
- 2x2T16 T&B 8. DEWATERING OPERATIONS SHALL BE PROVIDED DURING
CONSTRUCTION AND MAY ONLY BE TERMINATED AFTER
2x2T16 T&B T12-150 T&B ROOF SLAB HAS BEEN CASTED.
VARIES 9. ALL BELOW GROUND CONCRETE TO BE TANKED REFER .
TO STANDARD DRAWING No. 801.
10. ALL REINFORCEMENT TO BE EPOXY COATED.

BASE SLAB PLAN REDUCER SLAB PLAN ROOF SLAB PLAN LEGEND:
1 : 25 1 : 25 1 : 25
BOTTOM / FAR FACE BAR

REINFORCEMENT
PRECAST
CONCRETE SHAFT 12 T16 24-150 EF
T12-150 T12-150
1T12 1T12
TOTAL No. OF BARS BAR LOCATION/S*
T12-150 T12-150
TYPE OF STEEL CENTRES OF BARS
T16-150 BAR DIAMETER BAR MARK
T12-150 T12-150
C
-
T12

T12

* BAR LOCATIONS
T16-150
T16-150 T16-150 T16-150
T16-150 T16-150 T16-150 T16-150 T16-150 T16-150 T TOP FF FAR FACE
T16-150
U-BARS B BOTTOM
T16-150 T16-150 EF EACH FACE
NF NEAR FACE EW EACH WAY
T16-150 T16-150
T16-150
T16-150 T16-150
T16

T16

T16-150 T16-150
T16-150 T16-150 REFERENCE DRAWINGS AND DOCUMENTS
T16

T16

203 - STANDARD DRAWING G.A. OF DEEP STORM WATER


T16-150 MANHOLE ON PIPELINES 600mm TO 1400mm DIA.
T16-150 T20-150 T T16-150
T16-150 T16-150
T16-150

T16-150 T16-150
T16-150
T16-150 T16-150 U-BARS
T16-150 B

SECTIONA SECTIONB SECTIONC


1 : 25 - 1 : 25 - 1 : 25 -

No. REVISION-1 APP'D 2020


CLIENT
2T16 EF EXTRA
2x2T16 EF BARS ABOVE 250 T12-150 T12-150
DIAGONAL OPENING
EXTRA BARS T12-150 EF
TITLE
250

STANDARD DRAWINGS
250

T12-150 T12-150 T12-150


STORM WATER WORKS
1000

2T12
T12-150 EF
2x2T16 EF DRAWING TITLE
2T16 EF EXTRA
DIAGONAL
EXTRA BARS
BARS STANDARD REINFORCEMENT
BELOW OPENING
2x2T16 EF
250
DETAILS FOR DEEP STORM
EXTRA BARS
WATER MANHOLE ON PIPELINES
TYPICAL WALL PIPE OPENING REINFORCEMENT DETAIL FOR COVER SLAB SECTION 600 - 1400mm DIA.
TRIMMER BARS DETAIL PRECAST CONCRETE SHAFT 1 : 25
1 : 25 1 : 25 DRAWN - SCALE 1:25
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No. 1012

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE
INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
CHECKED AND APPROVED AS PART OF THE PROJECT
DRAWING SET.
T12-150 T12-150 T12-150 T12-150 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED
T12-150 T12-150 T12-150 T12-150 OTHERWISE.
2. MINIMUM CONCRETE COVER TO REINFORCEMENT TO
BE AS FOLLOWS :
T16-150 T16-150
T20 T20 BASE SLAB AND WALL (EXTERNAL) = 75mm
BASE SLAB AND WALL (INTERNAL) = 50mm
C C ROOF SLAB = 50mm
T20-150 T20-150 T20-150 T20-150 - -
T20-150 T16-150 T16-150 T20-150 T20-150 T20-150 3. ALL REINFORCEMENT SHALL CONFORM TO ASTM A615.
T20-150 T20-150 T20-150 T20-150 T16-150 T16-150 T16-150 T16-150 4. ALL LAPS SHALL BE IN ACCORDANCE WITH ACI 318.
T20-150 T16-150 T16-150 T20-150 5. REINFORCEMENT TO BE DISPLACED ON SITE TO AVOID SMALL
DIAMETER PIPEWORK.
6. THE MANHOLES ARE DESIGNED USING FULL GROUND WATER
T20-150 T20-150 LEVEL CONDITION WITH 1.1 FACTOR OF SAFETY
FOR FLOATATION.
T20

T20

T16

T16
T20-150 T20-150
7. FOUNDATION DESIGN IS BASED ON ALLOWABLE BEARING
PRESSURE OF 100 kN/m² AND SOIL SUBGRADE MODULUS OF
8000 kN/m³.

T20

T20
8. DEWATERING OPERATIONS SHALL BE PROVIDED DURING
CONSTRUCTION AND MAY ONLY BE TERMINATED AFTER
ROOF SLAB HAS BEEN CASTED.
T20

T20

T16

T16
9. ALL BELOW GROUND CONCRETE TO BE TANKED REFER .

T16
T20

T16
T20

TO STANDARD DRAWING No. 801.


10. ALL REINFORCEMENT TO BE EPOXY COATED.

T20

T20
LEGEND:
BOTTOM / FAR FACE BAR
T20

T16
T20

T16
REINFORCEMENT
T20-150 T20-150
T20-150 T16-150 T16-150 T20-150
T20-150 T20-150 T16-150 T16-150 12 T16 24-150 EF

T20-150 T20-150 TOTAL No. OF BARS BAR LOCATION/S*


TYPE OF STEEL CENTRES OF BARS
T20 T20 BAR DIAMETER BAR MARK
T16-150 T16-150
T16-150 T16-150

SECTIONA SECTIONB SECTIONC * BAR LOCATIONS


1 : 25 - 1 : 25 - 1 : 25 -

T TOP FF FAR FACE


B BOTTOM EF EACH FACE
NF NEAR FACE EW EACH WAY

A A
- -
2x2T20 EF
EXTRA BARS
2x2T20 EF
T20-150 T T16-150 B EXTRA BARS
T12-150 T&B REFERENCE DRAWINGS AND DOCUMENTS
T12-150 T&B 204 - STANDARD DRAWING G.A. OF SHALLOW STORM WATER
MANHOLE ON PIPELINES 1500mm TO 3000mm DIA.
2T20 EF EXTRA
BARS ABOVE
OPENING
T12-150 T&B
2x2T16 T&B

B B
- -

T16-150 B
No. REVISION-1 APP'D 2020
T12-150 T&B
T20-150 T 2T20 EF EXTRA CLIENT
T12-150 T&B BARS
BELOW OPENING
2x2T16 T&B

T12-150 T&B TITLE


2x2T20 EF STANDARD DRAWINGS
EXTRA BARS
STORM WATER WORKS
DRAWING TITLE
STANDARD REINFORCEMENT
TYPICAL WALL PIPE OPENING
DETAILS FOR SHALLOW STORM
BASE SLAB PLAN ROOF SLAB PLAN TRIMMER BARS DETAIL WATER MANHOLE ON PIPELINES
1 : 25 1 : 25 1 : 25 1500 - 3000mm DIA.
DRAWN - SCALE 1:25
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No. 1013

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE
INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
NOTE: CHECKED AND APPROVED AS PART OF THE PROJECT
PRECAST WALL SEGMENT CONNECTION SHOWN
DRAWING SET.
ARE INDICATIVE AND SHALL BE CONFIRMED AS
PER SUPPLIER'S REQUIREMENTS 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED
SUBJECT TO ENGINEER'S APPROVAL. OTHERWISE.
2. MINIMUM CONCRETE COVER TO REINFORCEMENT TO BE AS
FOLLOWS :
T12-150 T&B
VARIES BASE SLAB AND WALL (EXTERNAL) = 75mm
T12-150 BASE SLAB AND WALL (INTERNAL) = 50mm
2x2T16 T&B T12-150 T&B T12-150
ROOF SLAB = 50mm
VARIES
T12-150 T&B 3. ALL REINFORCEMENT SHALL CONFORM TO ASTM A615.
T12-150 T&B
VARIES
VARIES T12-150 EF 4. ALL LAPS SHALL BE IN ACCORDANCE WITH ACI 318.

250
T12-150 T12-150 T12-150 5. REINFORCEMENT TO BE DISPLACED ON SITE TO AVOID SMALL
C T12-150
DIAMETER PIPEWORK.

1000
-
T12-150 EF 6. THE MANHOLES ARE DESIGNED USING FULL GROUND WATER
T12-150 T&B
300 LEVEL CONDITION WITH 1.1 FACTOR OF SAFETY FOR
VARIES
FLOATATION.
7. FOUNDATION DESIGN IS BASED ON ALLOWABLE BEARING
2x2T16 T&B
PRESSURE OF 200 kN/m² AND SOIL SUBGRADE MODULUS OF
250
T12-150 T&B 8000 kN/m³.
VARIES 8. DEWATERING OPERATIONS SHALL BE PROVIDED DURING
2x2T16 T&B SECTIONC REINFORCEMENT DETAIL FOR CONSTRUCTION AND MAY ONLY BE TERMINATED AFTER
ROOF SLAB HAS BEEN CASTED.
1 : 25 - PRECAST CONCRETE SHAFT 9. ALL BELOW GROUND CONCRETE TO BE TANKED REFER .
1 : 25 TO STANDARD DRAWING No. 801.
ROOF SLAB PLAN 10. ALL REINFORCEMENT TO BE EPOXY COATED.
1 : 25
LEGEND:
BOTTOM / FAR FACE BAR

REINFORCEMENT

12 T16 24-150 EF

TOTAL No. OF BARS BAR LOCATION/S*


TYPE OF STEEL CENTRES OF BARS
BAR DIAMETER BAR MARK
B B
1006 1006

T20-150 T T16-150 B T16-150 T 2x2T16 T&B


* BAR LOCATIONS
T TOP FF FAR FACE
B BOTTOM EF EACH FACE
NF NEAR FACE EW EACH WAY
2x2T16 T&B

A A
1006 1006

REFERENCE DRAWINGS AND DOCUMENTS


T20-150 T
205 - STANDARD DRAWING G.A. OF DEEP STORM WATER
T16-150 B 2x2T16 T&B
MANHOLE ON PIPELINES 1500mm TO 3000mm DIA.

2x2T16 T&B
T12-150 T&B
VARIES
T16-150 T

No. REVISION-1 APP'D 2020


CLIENT

T12-150 T&B

BASE SLAB PLAN INTERMEDIATE SLAB PLAN TITLE


1 : 25 1 : 25 STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE
STANDARD REINFORCEMENT
DETAILS FOR DEEP STORM WATER
MANHOLE ON PIPELINES
1500-3000mm DIA. - SHEET 1
DRAWN - SCALE 1:25
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1014

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE
INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
CHECKED AND APPROVED AS PART OF THE PROJECT
PRECAST DRAWING SET.
PRECAST
CONCRETE SHAFT CONCRETE SHAFT 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED
OTHERWISE.
T12-150 T12-150 T12-150 2. MINIMUM CONCRETE COVER TO REINFORCEMENT TO BE AS
1 T20 1 T20 FOLLOWS :
BASE SLAB AND WALL (EXTERNAL) = 75mm
T20-150 T20-150
BASE SLAB AND WALL (INTERNAL) = 50mm
ROOF SLAB = 50mm
T12-150
3. ALL REINFORCEMENT SHALL CONFORM TO ASTM A615.
D D
- - 4. ALL LAPS SHALL BE IN ACCORDANCE WITH ACI 318.
T20-150 T20-150 T20-150 T16-150 T16-150 T20-150
5. REINFORCEMENT TO BE DISPLACED ON SITE TO AVOID SMALL
T20-150 T20-150 T16-150 T16-150 T16-150 DIAMETER PIPEWORK.
T20-150 T20-150
T16-150 6. THE MANHOLES ARE DESIGNED USING FULL GROUND WATER
T20-150 T20-150 LEVEL CONDITION WITH 1.1 FACTOR OF SAFETY FOR
FLOATATION.
T20

T20
7. FOUNDATION DESIGN IS BASED ON ALLOWABLE BEARING

T16

T16
PRESSURE OF 200 kN/m² AND SOIL SUBGRADE MODULUS OF
8000 kN/m³.
8. DEWATERING OPERATIONS SHALL BE PROVIDED DURING
CONSTRUCTION AND MAY ONLY BE TERMINATED AFTER
ROOF SLAB HAS BEEN CASTED.

T16

T16
9. ALL BELOW GROUND CONCRETE TO BE TANKED REFER .
T20

T20
T20 TO STANDARD DRAWING No. 801.

T20
10. ALL REINFORCEMENT TO BE EPOXY COATED.

T16

T16
T16-150 LEGEND:
T16-150 BOTTOM / FAR FACE BAR
T20

T20

T16

T16
REINFORCEMENT
T20-150 T20-150
12 T16 24-150 EF

T20-150 T20-150 T16-150 T16-150


TOTAL No. OF BARS BAR LOCATION/S*
TYPE OF STEEL CENTRES OF BARS
BAR DIAMETER BAR MARK
T16-150 T16-150

SECTIONA SECTIONB * BAR LOCATIONS


1 : 25 1005 1 : 25 1005

T TOP FF FAR FACE


B BOTTOM EF EACH FACE
NF NEAR FACE EW EACH WAY

T20 T20 T16-150 T20 T20 T20-150

REFERENCE DRAWINGS AND DOCUMENTS


205 - STANDARD DRAWING G.A. OF DEEP STORM WATER
T16-150 T16-150 MANHOLE ON PIPELINES 1500mm TO 3000mm DIA.

T20-150 T20-150
T20-150 T20-150 T20-150 T20-150 T20-150 T20-150

T20-150 T20-150 T20-150 T20-150 T20-150 T16-150

T20-150 T16-150

T20-150 T16-150
T20

T16
No. REVISION-1 APP'D 2020
CLIENT
T20

T20
TITLE
T16-150 T16-150
T16-150
STANDARD DRAWINGS
STORM WATER WORKS
T16-150 T16-150 DRAWING TITLE
T20 T20
T16-150 STANDARD REINFORCEMENT DETAILS FOR
DEEP STORM WATER MANHOLE ON PIPELINES
SECTIOND T16 T20
1500-3000mm DIA. - SHEET 2
1 : 25 -
T16-150

MANHOLE SECTION PLAN FOR 90° BEND PIPE DRAWN - SCALE 1:25
1 : 25
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No. 1015

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED
OTHERWISE.
2. MINIMUM CONCRETE COVER TO REINFORCEMENT TO BE AS
FOLLOWS :
BASE SLAB AND WALL (EXTERNAL) = 75mm
BASE SLAB AND WALL (INTERNAL) = 50mm
B B ROOF SLAB = 50mm
- - 3. ALL REINFORCEMENT SHALL CONFORM TO ASTM A615.
4. ALL LAPS SHALL BE IN ACCORDANCE WITH ACI 318.
T12-150 5. REINFORCEMENT TO BE DISPLACED ON SITE TO AVOID SMALL
T16-150 B T12-150 T T12-150 T12-150 DIAMETER PIPEWORK.
6. THE MANHOLES ARE DESIGNED USING FULL GROUND WATER
LEVEL CONDITION WITH 1.1 FACTOR OF SAFETY FOR FLOATATION.
T16-150 B 7. FOUNDATION DESIGN IS BASED ON ALLOWABLE BEARING
PRESSURE OF 100 kN/m² AND SOIL SUBGRADE MODULUS OF
T12-150 T T12-150 T12-150 8000 kN/m³.
8. DEWATERING OPERATIONS SHALL BE PROVIDED DURING
CONSTRUCTION AND MAY ONLY BE TERMINATED AFTER
ROOF SLAB HAS BEEN CASTED.
9. ALL BELOW GROUND CONCRETE TO BE TANKED REFER .
A TO STANDARD DRAWING No. 801.
T12-150 T12-150 A
- 10. ALL REINFORCEMENT TO BE EPOXY COATED.
T12-150 T12-150 -
LEGEND:
BOTTOM / FAR FACE BAR
T12-150 T12-150
T12-150
REINFORCEMENT
BASE SLAB PLAN SECTIONC 12 T16 24-150 EF
1 : 20 1 : 20 -
TOTAL No. OF BARS BAR LOCATION/S*
TYPE OF STEEL CENTRES OF BARS
BAR DIAMETER BAR MARK

* BAR LOCATIONS

T TOP FF FAR FACE


B BOTTOM EF EACH FACE
NF NEAR FACE EW EACH WAY
C C
T12-150 - T12-150 -

T12-150
T12-150 T12-150 T12-150
T12-150 T12-150 T12-150 T12-150 T12-150
T12-150 T12-150
T12

T12
T12

T12
T12-150 T12-150
REFERENCE DRAWINGS AND DOCUMENTS
209 -STANDARD DRAWING G.A. OF STORM WATER INLET DETAILS
T12

T12
T12

T12
T12

T12

T12

T12
T12

T12

T12

T12
T12-150 T12-150 T12-150 T12-150

T16-150 T16-150
T12-150
T12-150 T12-150 T12-150

No. REVISION-1 APP'D 2020


CLIENT

T12-150 T12-150

SECTIONA SECTIONB TITLE


1 : 20 - 1 : 20 - STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

STANDARD REINFORCEMENT
DETAILS FOR STORM WATER INLET

DRAWN - SCALE 1:20


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No. 1016

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE
INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
CHECKED AND APPROVED AS PART OF THE PROJECT
DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED
OTHERWISE.
2. MINIMUM CONCRETE COVER TO REINFORCEMENT TO BE AS
FOLLOWS :
BASE SLAB AND WALL (EXTERNAL) = 75mm
BASE SLAB AND WALL (INTERNAL) = 50mm
ROOF SLAB = 50mm
3. ALL REINFORCEMENT SHALL CONFORM TO ASTM A615.
4. ALL LAPS SHALL BE IN ACCORDANCE WITH ACI 318.
5. REINFORCEMENT TO BE DISPLACED ON SITE TO AVOID SMALL
B C B C B C DIAMETER PIPEWORK.
- - - - - - 6. THE MANHOLES ARE DESIGNED USING FULL GROUND WATER
ROAD LEVEL CONDITION WITH 1.1 FACTOR OF SAFETY FOR
KERB OPENING FLOATATION.
T16-150 T T12-150 B T12-150 T12-150
KERB KERB 7. FOUNDATION DESIGN IS BASED ON ALLOWABLE BEARING
PRESSURE OF 100 kN/m² AND SOIL SUBGRADE MODULUS OF
8000 kN/m³.
8. DEWATERING OPERATIONS SHALL BE PROVIDED DURING
T12-150 CONSTRUCTION AND MAY ONLY BE TERMINATED AFTER
T12-150 B ROOF SLAB HAS BEEN CASTED.
T16-150 T T12-150 T12-150 9. ALL BELOW GROUND CONCRETE TO BE TANKED REFER .
T12-150 T12-150 TO STANDARD DRAWING No. 801.
A A A 10. ALL REINFORCEMENT TO BE EPOXY COATED.
- - -

LEGEND:
BOTTOM / FAR FACE BAR
T12-150 T12-150

REINFORCEMENT
BASE SLAB PLAN ROOF SLAB PLAN SECTIOND 12 T16 24-150 EF
1 : 20 1 : 20 1 : 20 -

TOTAL No. OF BARS BAR LOCATION/S*


TYPE OF STEEL CENTRES OF BARS
BAR DIAMETER BAR MARK

* BAR LOCATIONS
T TOP FF FAR FACE
B BOTTOM EF EACH FACE
NF NEAR FACE EW EACH WAY
T12-150
170

T12-150 T10-150 LINKS

T12-150 4T12 T12-150 T12-150 T12-150 T12-150 T12-150 T12-150 T12-150


200
T12-150 T12-150
D D D
T12-150 T12-150 - - -
T12-150 T12-150 REFERENCE DRAWINGS AND DOCUMENTS
T12-150 T12-150 T12-150 T12-150 T12-150 T12-150 T12-150 T12-150 T12-150 T12-150
211- STANDARD DRAWING G.A. OF STORM WATER CATCH
BASIN DETAILS
T12

T12

T12

T12

T12

T12
T12

T12

T12

T12

T12

T12
T12

T12

T12

T12

T12

T12
T12-150 U-BAR
T12

T12

T12

T12

T12

T12
T12-150 T12-150 T12-150 T12-150 T12-150 T12-150 T12-150 T12-150
T16-150 T16-150 T16-150 No. REVISION-1 APP'D 2020
T12-150 T12-150 T12-150 T12-150 T12-150 T12-150 CLIENT

T12-150 T12-150 T12-150 TITLE


STANDARD DRAWINGS
SECTIONA SECTIONB SECTIONC STORM WATER WORKS
1 : 20 - 1 : 20 - 1 : 20 -
DRAWING TITLE

STANDARD REINFORCEMENT
DETAILS FOR STORM WATER
CATCH BASIN

DRAWN - SCALE 1:20


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1017

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE
INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
CHECKED AND APPROVED AS PART OF THE PROJECT
DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED
OTHERWISE.
A C B 1350 2. MINIMUM CONCRETE COVER TO REINFORCEMENT TO BE AS
- - - FOLLOWS :
BASE SLAB AND WALL (EXTERNAL) = 75mm
C3 BASE SLAB AND WALL (INTERNAL) = 50mm
C1
COLUMNS = 40mm

3. ALL REINFORCEMENT SHALL CONFORM TO ASTM A615.

1350
4. ALL LAPS SHALL BE IN ACCORDANCE WITH ACI 318.
5. REINFORCEMENT TO BE DISPLACED ON SITE TO AVOID SMALL
DIAMETER PIPEWORK.
6. ALL BELOW GROUND CONCRETE TO BE TANKED REFER
6.00 meters
TO STANDARD DRAWING No. 801.
25 EXPANSION JOINT
7. ALL REINFORCEMENT TO BE EPOXY COATED.
C2
3000
PARTIAL BOUNDARY WALL PLAN LEGEND:
BOTTOM / FAR FACE BAR

REINFORCEMENT
230
T10-200 12 T16 24-150 EF
LINKS
350
TOTAL No. OF BARS BAR LOCATION/S*

230 TYPE OF STEEL CENTRES OF BARS


200
4T16 BAR DIAMETER BAR MARK

* BAR LOCATIONS

350
4T12 T10-200 LINKS
230

230
T10-200 LINKS T TOP FF FAR FACE
T10-200 LINKS
4T12 B BOTTOM EF EACH FACE
NF NEAR FACE EW EACH WAY
C1 C2 C3
FOR CORNER FOR BOUNDARY WALLS FOR MAIN ENTRANCE
BOUNDARY WALLS MAX. COLUMN SPACING MAX. COLUMN SPACING
3.0m CENTER TO CENTER 6.0m CENTER TO CENTER 2T12

1890
1790
COLUMN REINFORCEMENT
1 : 10 2T12

230

350 REFERENCE DRAWINGS AND DOCUMENTS


517 - TYPICAL DRAWING BLOCKWORK BOUNDARY WALL DETAILS
T10-200
LINKS SHEET 1 OF 2
BLOCKWORK 518 - TYPICAL DRAWING BLOCKWORK BOUNDARY WALL DETAILS
SHEET 2 OF 2

T10-200

T12-150
450

2 T16

700
FGL FGL FGL

950
No. REVISION-1 APP'D 2020
T12-150 2 T16 T12-150 T12-150 CLIENT
T10-200 T10-200 T10-200
500 500 385 385
800

800

T12-150 T16-150 T16-150 T12-150 TITLE


STANDARD DRAWINGS
1000

STORM WATER WORKS


300

300

DRAWING TITLE
500

T12-150 T16-150 T12-150 T16-150 STANDARD REINFORCEMENT


1000
1000 DETAILS FOR BOUNDARY WALL
T16-150 T16-150
SECTIONA 1350 SECTIONC
1 : 10 - 1 : 10 - DRAWN - SCALE 1:10
F1
CHECKED - DATE -
STRIP FOOTING REINFORCEMENT SECTIONB COLUMN & FOOTING REINFORCEMENT
- APPROVED - SIZE A1
1 : 10
PROJECT DWG.
No. - No.
1022

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS NOTED
OTHERWISE.
2. MINIMUM CONCRETE COVER TO REINFORCEMENT TO BE AS
FOLLOWS :
BASE SLAB AND WALL (EXTERNAL) = 75mm
BASE SLAB AND WALL (INTERNAL) = 50mm
COLUMNS = 40mm
3. ALL REINFORCEMENT SHALL CONFORM TO ASTM A615.
4. ALL LAPS SHALL BE IN ACCORDANCE WITH ACI 318.
5. REINFORCEMENT TO BE DISPLACED ON SITE TO AVOID SMALL
DIAMETER PIPEWORK.
6. ALL BELOW GROUND CONCRETE TO BE TANKED REFER
TO STANDARD DRAWING No. 801.
7. ALL REINFORCEMENT TO BE EPOXY COATED.
T12 DOWEL
PROJECTING FROM T12 DOWEL PROJECTING T12 DOWEL PROJECTING LEGEND:
PC FOOTING 80x90
C
L COLUMN FROM PC FOOTING CUT OUT 80 FROM PC FOOTING
80 BOTTOM / FAR FACE BAR
T12 T8-200 C/C T8-200 C/C T8-200 C/C
PRECAST WALL PRECAST
PANEL WALL PANEL REINFORCEMENT

12 T16 24-150 EF

TOTAL No. OF BARS BAR LOCATION/S*


T8-200 C/C T12 T12
TYPE OF STEEL CENTRES OF BARS
CLEAR
BAR DIAMETER BAR MARK
OPENING AT
T8-200 C/C T8-200 C/C
GATES
T12 DOWEL T12 DOWEL GATE COLUMNS T12 DOWEL PROJECTING * BAR LOCATIONS
PROJECTING FROM PC PROJECTING FROM FROM PC FOOTING
T16-150 TOP FOOTING PC FOOTING T TOP FF FAR FACE
PRECAST COLUMN
BOTH WAYS COLUMNS AT B BOTTOM EF EACH FACE
T12-150 T12-150 EXPANSION JOINT NF NEAR FACE
GATE COLUMN EW EACH WAY

T12-150 T12-150

T12-150 T12-150

CL WALL PANELS

PRECAST WALL PANEL


T12 DOWEL PROJECTING C
L COLUMN
FROM PC FOOTING 80
T12 T12
T12-150 BOT 80x90
BOTH WAYS T12 CUT OUT
T8-200 C/C
TYPICAL PRECAST FOOTING
T8-200 C/C T12
REINFORCEMENT DETAIL 80x90
REFERENCE DRAWINGS AND DOCUMENTS
1 : 15 CUT OUT
C 515 - TYPICAL DRAWING PRECAST BOUNDARY WALL DETAILS
L WALL PANELS

80
L SHEET 1 OF 2
T12
PRECAST WALL PANEL 516 - TYPICAL DRAWING PRECAST BOUNDARY WALL DETAILS
T8-200 C/C
T12 DOWEL SHEET 2 OF 2
T8-200 C/C T8-200 C/C PRECAST WALL PANEL T12
80x90 PROJECTING FROM
T12 DOWEL PROJECTING 80
CUT OUT PC FOOTING
FROM PC FOOTING T8-200 C/C 80
T12 DOWEL
80x90 PROJECTING FROM
CUT OUT PC FOOTING

INTERMEDIATE COLUMN
CORNER COLUMN

No. REVISION-1 APP'D 2020


CLIENT

PRECAST COLUMN REINFORCEMENT DETAILS


TITLE
STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

STANDARD REINFORCEMENT DETAILS


OF PRECAST COLUMNS AND FOOTING
FOR PRECAST BOUNDARY WALL

DRAWN - SCALE 1:25


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No. 1023

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE
INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
CHECKED AND APPROVED AS PART OF THE PROJECT
DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS
OTHERWISE STATED.
2. ENTRANCE AND SPACE WITHIN PUMPING STATION
SHALL BE
DESIGNED TO ENSURE HEAVY VEHICLES
MANEUVERING.

LEGEND
PVC-U POLYVINYL CHLORIDE-UNDERGROUND PIPE

180°

1 No. PVC-U
CABLE DUCT

EARTH PIT

REFERENCE DRAWINGS AND DOCUMENTS


STANDARD DRAWING - TANKING DETAILS - 801
STANDARD DRAWING - MISCELLANEOUS DETAILS - 207
LIGHTNING FOR MANHOLES

RAMP UP
EARTH PIT

1 No. PVC-U
CABLE DUCT
INSULATED COPPER FALL
CONDENSATE PIPE
COMPRESSOR
SPLIT UNIT

INSULATED COPPER
CONDENSATE PIPE
VA
LL

COMPRESSOR
EY

SPLIT UNIT
FALL

No. REVISION-2 APP'D 2021


1 No. PVC-U
CABLE DUCT CLIENT

LIGHTNING
EARTH PIT
TITLE
STANDARD DRAWINGS
STORM WATER WORKS
ROOF PLAN DRAWING TITLE

TYPICAL DRAWING PUMPING


STATION AT PEDESTRAIN
CROSSING LAYOUT

DRAWN - SCALE 1 : 100


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1101

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE
GRP KISOK INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
MCC PANEL CHECKED AND APPROVED AS PART OF THE PROJECT
DRAWING SET.
JUNCTION BOX
LONG AIR VENT
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
COVER 750x750 STATED.
COVER 750x750 2. PENSTOCK TO BE INSTALLED IN THE FIRST
HAND GRABS
MANHOLE UPSTREAM THE PUMPING STATION
3. AIR VALVE AND ASSOCIATED FITTINGS SHALL BE DESIGNED
ACCESS SUMP PUMP AND INSTALLED UPSTREAM THE CHECK VALVE TO ELIMINATE
PLATFORM VACUUM IF REQUIRED.
PVC-DUCT 4. ENTRANCE AND SPACE WITHIN PUMPING STATION SHALL BE

SLO
DESIGNED TO ENSURE HEAVY VEHICLES MANEUVERING.

PE
PVC-DUCT
IPF NRVFA GVBF
WET
WELL
PUMP-01 VALVE
IPF CHAMBER

B PUMP-02
B
SHORT AIR VENT

IPF

SEE DETAIL-1

180°

SECTION A-A PLAN AT COVER LEVEL

AIR VENT
DN100

WITH PROTECTION
MESH

ROOF SLAB

GRP KIOSK
MCC PANEL

ULTRASONIC 2No.110 DIA LONG AIR VENT DETAIL-3


LEVEL PVC DUCT (SEE DETAIL-3)
TRANSMITTER ALUMINIUM ACCESS ALUMINIUM ACCESS
HAND GRABS COVERS & FRAMES COVERS & FRAMES
FGL

SEE
DETAIL-2
MIN 2M

A GV
IPF NRVFA
A
1x110 DIA PVC PS REFERENCE DRAWINGS AND DOCUMENTS
DUCT FOR CABLE
STANDARD DRAWING - TANKING DETAILS - 801
STANDARD DRAWING - MISCELLANEOUS DETAILS - 207
FOR MANHOLES

SUMP PUMP
FRAME LIP FOR
EPOXY COATING TO ALL SEALING PLATE
INTERNAL SURFACES (4 LIPS) GAS TIGHT
EPDM RUBBER
S/S 316 PIPE SUPPORT
IL
DI HDPE
TANKING MEMBRANE
AND PROTECTION BOARD

FFL CONCRETE BENCHING


SLFA IPF
FLOAT SWITCH
No. REVISION-2 APP'D 2021
50mm THK. CEMENT/SAND SCREED RS-VIEW FS-VIEW CLIENT
TANKING MEMBRANE
75mm THICK C20 BLINDING
1000 GAUGE POLYETHYLENE SHEET (CONNECTION TO HDPE RISING MAIN) (PUMP GUIDE RAILS CONNECTION)

DI GRP TITLE
SECTION B-B STANDARD DRAWINGS
STORM WATER WORKS
IPF FC GRP DRAWING TITLE
COUPLING RS-VIEW FS-VIEW
TYPICAL DRAWING PUMPING
(CONNECTION TO GRP RISING MAIN) (PUMP WIRE ROPE CONNECTION)
STATION AT PEDESTRAIN
CROSSING PLAN AND SECTION
DETAIL-1 DETAIL-2
DRAWN - SCALE 1 : 100
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No. 1102

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE
INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
CHECKED AND APPROVED AS PART OF THE PROJECT
DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS
OTHERWISE STATED.
2. ENTRANCE AND SPACE WITHIN PUMPING STATION SHALL BE
POLE LIGHT DESIGNED TO ENSURE HEAVY VEHICLES MANEUVERING.

POLE LIGHT DISCHARGE PIPE TO GRAVITY NETWORK


LEGEND
1 No. PVC-U MCC MOTOR CONTROL CENTER
CABLE DUCT
PVC-U POLYVINYL CHLORIDE-UNDERGROUND PIPE
EARTH PIT

COVER COVER

COVER

COVER
COVER
1 No. PVC-U
CABLE DUCT
BOUNDARY WALL

27

EARTH PIT
ENTRANCE

REFERENCE DRAWINGS AND DOCUMENTS


STANDARD DRAWING - TANKING DETAILS - 801
STANDARD DRAWING - MISCELLANEOUS DETAILS - 207
LIGHTNING FOR MANHOLES
EARTH PIT

1 No. PVC-U
CABLE DUCT

INSULATED COPPER FALL


COMPRESSOR

CONDENSATE PIPE
SPLIT UNIT

VA
LLE
Y INSULATED COPPER
COMPRESSOR

CONDENSATE PIPE
MCC BUILDING
SPLIT UNIT

No. REVISION-2 APP'D 2021


FALL

CLIENT

1 No. PVC-U
CABLE DUCT
TITLE
LIGHTNING
EARTH PIT STANDARD DRAWINGS
POLE LIGHT POLE LIGHT STORM WATER WORKS
DRAWING TITLE

TYPICAL DRAWING PUMPING STATION


ROOF PLAN AT TRAFFIC UNDERPASS LAYOUT

DRAWN - SCALE 1 : 100


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1103

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
TRASH RACK
APPROVED AS PART OF THE PROJECT DRAWING SET.
DISCHARGE PIPE TO GRAVITY NETWORK DISCHARGE PIPE TO GRAVITY NETWORK
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
STATED.
2. PENSTOCK TO BE INSTALLED IN THE FIRST
MANHOLE UPSTREAM THE PUMPING STATION
3. AIR VENT INSTALLATION TO ELIMINATE VACUUM IN THE RISING
PIPES SHALL BE CONFIRMED DURING DETAIL DESIGN
ACCESS

SLOPE
SHORT AIR VENT STAGE OF THE PROJECT PRIOR TO CONSTRUCTION.
PLATFORM
4. AIR VENT SHALL BE 600mm ABOVE TOP WATER LEVEL (TWL).
COVER COVER 5. ENTRANCE AND SPACE WITHIN PUMPING STATION SHALL BE
DESIGNED TO ENSURE HEAVY VEHICLES MANEUVERING.
DISCHARGE
CHAMBER LEGEND
IPF DI DUCTILE IRON
PUMP-01
GRP GLASS REINFORCED PLASTIC

COVER SS STAINLESS STEEL

B IPF
IPF INTEGRAL PUDDLE FLANGE
PUMP-02 B COVER FGL FINISH GROUND LEVEL
PVC-DUCT COVER SHORT AIR VENT CL CONCRETE LEVEL
PVC-DUCT HAND GRABS
TWL TOP WATER LEVEL

RS RIGHT SIDE VIEW

SECTION A-A FS FRONT SIDE VIEW


PVC POLYVINYL CHLORIDE PIPE

2No.110 DIA
PVC DUCT
ALUMINIUM ACCESS ULTRASONIC SHORT AIR VENT
COVERS & FRAMES LEVEL
TRANSMITTER (SEE DETAIL-2)
HAND GRABS
CL

SEE VENT PIPE


DETAIL-1 (600mm ABOVE TWL)

IPF
PLAN AT COVER LEVEL

EPOXY COATING
DISCHARGE PIPE
TO GRAVITY NETWORK

FLAP VALVE/ NON RETURN VALVE


REFERENCE DRAWINGS AND DOCUMENTS
FRAME LIP FOR
SEALING PLATE
(4 LIPS) GAS TIGHT
EPDM RUBBER
DUCT FOR CABLE
1x110 DIA PVC

EPOXY COATING TO ALL RS-VIEW FS-VIEW


INTERNAL SURFACES

(PUMP GUIDE RAILS CONNECTION)

AIR VENT
No. REVISION-2 APP'D 2021
DN100
CLIENT
WITH PROTECTION
TRASH RACK S/S 316 PIPE SUPPORT MESH
RESERVOIR

RS-VIEW FS-VIEW ROOF SLAB TITLE


STANDARD DRAWINGS
STORM WATER WORKS
(PUMP WIRE ROPE CONNECTION)
TANKING MEMBRANE
DRAWING TITLE
AND PROTECTION BOARD DETAIL-1 DETAIL-2
FLOAT
SWITCH
CONCRETE BENCHING
TYPICAL DRAWING PUMPING
STATION AT TRAFFIC UNDERPASS
PLAN AND SECTIONS

50mm THK. CEMENT/SAND SCREED DRAWN - SCALE 1 : 100


TANKING MEMBRANE
SECTION B-B 75mm THICK C20 BLINDING CHECKED - DATE -
1000 GAUGE POLYETHYLENE SHEET
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1104

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.

1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS


OTHERWISE STATED.
2. SURGE SUPPRESSION SYSTEM TO BE CONFIRMED AS
PER APPROVED SURGE ANALYSIS PRIOR TO
INSTALLATION.
3. ENTRANCE AND SPACE WITHIN PUMPING STATION
SHALL BE DESIGNED TO ENSURE HEAVY VEHICLES
MANEUVERING.

LEGEND

NOTE-2
POLE LIGHT POLE LIGHT

FM
CHAMBER

1 No. PVC-U
CABLE DUCT

EARTH PIT LIGHTNING


EARTH PIT

INSULATED COPPER
CONDENSATE PIPE
1 No. PVC-U
CABLE DUCT
SPLIT UNIT
COMPRESSOR
750X750
COVER

VALVE
RAMP UP
CHAMBER

FALL

MCC BUILDING
Y
LLE
INSULATED COPPER
CONDENSATE PIPE
VA
JIB CRANE
FOUNDATION
FALL

SPLIT UNIT
COMPRESSOR

WET WELL

1 No. PVC-U
CABLE DUCT

REFERENCE DRAWINGS AND DOCUMENTS


LIGHTNING
EARTH PIT STANDARD DRAWING - TANKING DETAILS - 801
STANDARD DRAWING - MISCELLANEOUS DETAILS - 207
BOUNDARY WALL FOR MANHOLES
1 No. PVC-U - 407
CABLE DUCT STANDARD DRAWING - FLOW METER CHAMBER GENERAL
ARRANGEMENTS.
EARTH PIT STANDARD DRAWING - CONTROL BUILDING & GENERATOR -504
BUILDING

POLE LIGHT POLE LIGHT

ENTRANCE

No. REVISION-2 APP'D 2021


CLIENT

TITLE
STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE
ROOF PLAN
TYPICAL DRAWING FOR WET WELL
PUMPING STATION SUB SOIL
DRAIN/LIFTING STATION LAYOUT

DRAWN - SCALE 1 : 100


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No. 1105

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
B REQUIREMENTS. THEY ARE EXPECTED TO BE
INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
DETAIL-1 CHECKED AND APPROVED AS PART OF THE PROJECT
DRAWING SET.

TO FM 750X750 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE


BF CHAMBER COVER STATED.
PE IPF HAND GRABS
O 2. PENSTOCK TO BE INSTALLED IN THE FIRST
GV SL SHORT AIR VENT
MANHOLE UPSTREAM THE PUMPING STATION
FA 3. AIR VALVE AND ASSOCIATED FITTINGS SHALL BE DESIGNED
AND INSTALLED UPSTREAM THE CHECK VALVE TO ELIMINATE
NRV VALVE VACUUM IF REQUIRED.
LONG AIR VENT
CHAMBER 4. ENTRANCE AND SPACE WITHIN PUMPING STATION SHALL BE
SUMP PUMP DESIGNED TO ENSURE HEAVY VEHICLES MANEUVERING.

IPF IPF LEGEND


JIB CRANE
FOUNDATION DI DUCTILE IRON
COVER COVER GRP GLASS REINFORCED PLASTIC
HDPE HIGH-DENSITY POLYETHYLENE PIPE
ACCESS
PLATFORM GV GATE VALVE

PUMP-01 PUMP-02 NRV NON-RETURN VALVE

PVC-DUCT PVC-DUCT IPF INTEGRAL PUDDLE FLANGE


WET WELL
FA FLANGE ADAPTOR
COVER
750X750 BF BLANK FLANGE
PVC POLYVINYL CHLORIDE PIPE
PS PIPE SUPPORT
RS RIGHT SIDE VIEW
FS FRONT SIDE VIEW
SLFA SLIM FLANGE ASSEMBLY
B IL INVERT LEVEL
FGL FINISH GROUND LEVEL
FFL FINISH FLOOR LEVEL

SECTION A-A PLAN AT COVER LEVEL CL CONCRETE LEVEL

(4 LIPS) GAS TIGHT


EPDM RUBBER

FRAME LIP FOR


SEALING PLATE

DI HDPE

SLFA IPF

ALUMINIUM ACCESS ULTRASONIC RS-VIEW FS-VIEW


COVERS & FRAMES TO SUIT LEVEL
1000 x 1000 CLEAR OPENING TRANSMITTER (CONNECTION TO HDPE RISING MAIN)
(PUMP GUIDE RAILS CONNECTION)
2No.110 DIA REFERENCE DRAWINGS AND DOCUMENTS
SHORT AIR VENT PVC DUCT
CL (SEE DETAIL-3)
FGL FGL STANDARD DRAWING - TANKING DETAILS - 801
DI GRP
STANDARD DRAWING - MISCELLANEOUS DETAILS - 207
1x110 DIA PVC DUCT FOR CABLE

SEE FOR MANHOLES


DETAIL-2

A GV
A IPF FC GRP
COUPLING RS-VIEW FS-VIEW
EPOXY COATING TO ALL EPOXY COATING TO ALL
INTERNAL SURFACES FA NRV
IL INTERNAL SURFACES

PS IPF
TANKING MEMBRANE (CONNECTION TO GRP RISING MAIN) (PUMP WIRE ROPE CONNECTION)
AND PROTECTION BOARD
DETAIL-1 DETAIL-2

No. REVISION-2 APP'D 2021


S/S 316 PIPE SUPPORT CLIENT

TANKING MEMBRANE AIR VENT


AND PROTECTION BOARD DN100
FLOAT
CONCRETE BENCHING FFL SWITCH
WITH PROTECTION TITLE
MESH STANDARD DRAWINGS
STORM WATER WORKS
50mm THK. CEMENT/SAND SCREED
TANKING MEMBRANE ROOF SLAB
75mm THICK C20 BLINDING DRAWING TITLE
1000 GAUGE POLYETHYLENE SHEET
TYPICAL DRAWING FOR WET WELL
PUMPING STATION SUB SOIL
SECTION B-B DRAIN/LIFTING STATION PLAN &
DETAIL-3
SECTIONS
DRAWN - SCALE 1 : 100
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No. 1106

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
STATED.
2. SURGE SUPPRESSION SYSTEM TO BE CONFIRMED AS PER
APPROVED SURGE ANALYSIS PRIOR TO INSTALLATION.
3. ENTRANCE AND SPACE WITHIN PUMPING STATION SHALL BE
DESIGNED TO ENSURE HEAVY VEHICLES MANEUVERING.
LEGEND
MCC MOTOR CONTROL CENTER
PVC-U POLYVINYL CHLORIDE UNDERGROUND
PIPE

POLE LIGHT POLE LIGHT

NOTE-2
1 No. PVC-U
EARTH PIT
CABLE DUCT

FLOW METER
1 No. PVC-U CHAMBER LIGHTNING
CABLE DUCT EARTH PIT

SPLIT UNIT
COMPRESSOR
EARTH PIT
RAMP UP

MCC 1 No. PVC-U


CABLE DUCT

EARTH PIT
SPLIT UNIT
COMPRESSOR

PUMPING STATION

VAL
YLE
1 No. PVC-U
1 No. PVC-U CABLE DUCT
CABLE DUCT

EARTH PIT
FOR GENERATOR EARTH PIT
FOR
GENERATOR GENERATOR

REFERENCE DRAWINGS AND DOCUMENTS

1 No. PVC-U
1 No. PVC-U CABLE DUCT
CABLE DUCT

LIGHTNING
EARTH PIT EARTH PIT

No. REVISION-2 APP'D 2021


CLIENT
POLE LIGHT POLE LIGHT

ENTRANCE

TITLE
BOUNDARY WALL
STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

ROOF PLAN TYPICAL DRAWING FOR LIFTING


PUMPING STATION DRY WELL
ARRANGEMENTS LAYOUT

DRAWN - SCALE
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETRES
UNLESS OTHERWISE STATED.
2. PENSTOCK TO BE INSTALLED IN THE FIRST MANHOLE
UPSTREAM THE PUMPING STATION
3. ENTRANCE AND SPACE WITHIN PUMPING STATION SHALL BE
DESIGNED TO ENSURE HEAVY VEHICLES MANEUVERING.
LEGEND
DI DUCTILE IRON
GRP GLASS REINFORCED PLASTIC
HAND GRABS HDPE HIGH-DENSITY POLYETHYLENE PIPE
GV GATE VALVE
ACCESS COVER
PLATFORM DJGVCR 1000X1000 NRV NON-RETURN VALVE
IPF INTEGRAL PUDDLE FLANGE
DJ DISMANTLING JOINTS
GVDJ ER CR NRV DJGV COVER FA FLANGE ADAPTOR
CR CONCENTRIC REDUCER
DETAIL-1
IPF
PUMP-01 PRESSURE
ER ECCENTRIC REDUCER
GAUGE FC FLEXIBLE CONNECTION
FGL FINISH GROUND LEVEL
GVDJ ER CR NRV DJGV IPF COVER
B WET WELL B FFL
IL
FINISH FLOOR LEVEL
INVERT LEVEL
IPF PUMP-02 PRESSURE
TRASH GAUGE PS PIPE SUPPORT

PE
RACK BF BLANK FLANGE

O
SL
GVDJ ER CR NRV DJGV COVER

IPF PUMP-03 PRESSURE


GAUGE BF
VALVE
SUMP CHAMBER
PUMP COVER
ACCESS 1000X1000
PLATFORM
HAND GRABS

SECTION A-A PLAN AT COVER LEVEL

DI HDPE DIGRP

SLFA IPF IPF FC GRP


COUPLING

(CONNECTION TO HDPE RISING MAIN) (CONNECTION TO GRP RISING MAIN)

OVERHEAD CRANE
DETAIL-1

ALUMINIUM ACCESS
COVERS & FRAMES
ALUMINIUM ACCESS
HAND GRABS COVERS & FRAMES
CL REFERENCE DRAWINGS AND DOCUMENTS
FGL FGL
STANDARD DRAWING - TANKING DETAILS - 801
STANDARD DRAWING - MISCELLANEOUS DETAILS - 207
(4 LIPS) GAS TIGHT
ACCESS LADDER FOR MANHOLES
EPDM RUBBER

A PLATFORM FRAME LIP FOR


SEALING PLATE
A
IL
IPF
EPOXY COATING TO ALL S/S 316 PIPE SUPPORT
INTERNAL SURFACES

TANKING MEMBRANE
AND PROTECTION BOARD PUMP-02 EPOXY COATING TO ALL
INTERNAL SURFACES

GV TANKING MEMBRANE No. REVISION-2 APP'D 2021


CR NRV DJ AND PROTECTION BOARD
IL
GV CLIENT
DJ ER
PS PS PS PS FFL
IPF
FFL

50mm THK. CEMENT/SAND SCREED TITLE


TANKING MEMBRANE
75mm THICK C20 BLINDING
STANDARD DRAWINGS
1000 GAUGE POLYETHYLENE SHEET
SECTION B-B ROOF PLAN STORM WATER WORKS
DRAWING TITLE

TYPICAL DRAWING FOR LIFTING


PUMPING STATION DRY WELL
ARRANGEMENTS PLAN & SECTIONS

DRAWN - SCALE 1 : 150


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1108

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS OTHERWISE
STATED.
2. ENTRANCE AND SPACE WITHIN PUMPING STATION SHALL BE
DESIGNED TO ENSURE HEAVY VEHICLES MANEUVERING.

LEGEND
MCC MOTOR CONTROL CENTER
PVC-U POLYVINYL CHLORIDE-UNDERGROUND PIPE

STANDARD DRAWING - TANKING DETAILS - 801


STANDARD DRAWING - MISCELLANEOUS DETAILS - 207
FOR MANHOLES
STANDARD DRAWING - TRASH RACK / SCREEN CHAMBER - 704

POLE LIGHT POLE LIGHT

TRASH RACK / SCREEN CHAMBER

27

ENTRANCE

REFERENCE DRAWINGS AND DOCUMENTS


RAMP UP

EARTH PIT GENERATOR


LIGHTNING EARTH PIT
CABLE DUCT
CABLE DUCT 1 No. PVC-U
COMPRESSOR

1 No. PVC-U
COMPRESSOR
SPLIT UNIT

SPLIT UNIT

MCC GENERATOR
VAL
LEY

CABLE DUCT
1 No. PVC-U No. REVISION-2 APP'D 2021
CABLE DUCT CABLE DUCT
1 No. PVC-U 1 No. PVC-U EARTH PIT CLIENT
EARTH PIT EARTH PIT GENERATOR LIGHTNING
POLE LIGHT EARTH PIT POLE LIGHT

ROOF PLAN TITLE


STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

TYPICAL DRAWING FOR OUTFALL


PUMPING STATION MECHANICAL
DETAILS LAYOUT

DRAWN - SCALE 1 : 150


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1109

THIRD EDITION - APRIL 2022


NOTES:
Flanged DN---
C THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
Flap Valve/ Non Return
Valve End REQUIREMENTS. THEY ARE EXPECTED TO BE
INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
CHECKED AND APPROVED AS PART OF THE PROJECT
D FLOW
D DRAWING SET.
AXIAL FLOW TO OUTFALL TO OUTFALL 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
PUMP-01
STATED.
2. AIR VALVE AND ASSOCIATED FITTINGS SHALL BE DESIGNED
PUMP
B CHAMBER
B AND INSTALLED UPSTREAM THE CHECK VALVE TO
GRP pipe ELIMINATE VACUUM IF REQUIRED.
Flange 3. ENTRANCE AND SPACE WITHIN PUMPING STATION SHALL
BE DESIGNED TO ENSURE HEAVY VEHICLES MANEUVERING.
DRAIN CHANNEL AXIAL FLOW TO OUTFALL DETAIL(3) TO OUTFALL LEGEND
PUMP-02 Flanged DN---
DI DUCTILE IRON
Flap Valve/ Non Return GRP GLASS REINFORCED PLASTIC
SUMP PUMP Valve End
HDPE HIGH-DENSITY POLYETHYLENE PIPE
GV GATE VALVE
NRV NON-RETURN VALVE
FLOW IPF INTEGRAL PUDDLE FLANGE
FA FLANGE ADAPTOR
PENSTOCK AV AIR VALVE
PS PIPE SUPPORT
FFL FINISH FLOOR LEVEL
FGL FINISH GROUND LEVEL
PENSTOCK GRP pipe IL INVERT LEVEL
Flange
SS STAINLESS STEEL
SL

- DRAWING - TANKING DETAILS


STANDARD 801
O
PE

FLOW TO OUTFALL FLOW TO OUTFALL STANDARD DRAWING - MISCELLANEOUS DETAILS


- FOR MANHOLES 207
SECTION D-D STANDARD DRAWING - TRASH RACK / SCREEN CHAMBER
- 704

FLAP VALVE/ NON


RETURN VALVE PUMP-01 PUMP-02

27

27
0

(DETAIL 3)

°
IPF IPF
DI GRP
AV AV

NRV NRV
FA VALVE FA
CHAMBER IPF FC GRP
GV GV COUPLING
TO OUTFALL TO OUTFALL
AIR VENT
DN100
IPF (CONNECTION TO GRP RISING MAIN)
WITH PROTECTION
RS-VIEW FS-VIEW MESH

(PUMP GUIDE RAILS CONNECTION)


C DI HDPE
DETAIL-1 ROOF SLAB
PLAN AT COVER LEVEL

SECTION A-A SLFA IPF


REFERENCE DRAWINGS AND DOCUMENTS
VENT DETAILS
RS-VIEW FS-VIEW (CONNECTION TO HDPE RISING MAIN)

(PUMP WIRE ROPE CONNECTION) DETAIL-1


PENSTOCK
DETAIL-2 LOUVER
ALUMINIUM ACCESS HAND GRABS
AV AV COVERS & FRAMES
ALUMINIUM ACCESS LIFTING HOOK
HAND GRABS
COVERS & FRAMES AV GV GV
FGL FGL
GV
FGL FGL
SEE
DETAIL-1
(4 LIPS) GAS TIGHT
EPDM RUBBER
GRP PIPE (CONCRETE AV
FRAME LIP FOR ENCASEMENT NOT SHOWN) GV
A SEALING PLATE A NRVFA
ACCESS LADDER No. REVISION-2 APP'D 2021
EPOXY COATING TO OUTFALL
IL PS CLIENT
TO ALL
INTERNAL SURFACES PLATFORM

TANKING MEMBRANE
AND PROTECTION
BOARD TITLE
STANDARD DRAWINGS
EPOXY COATING TO ALL STORM WATER WORKS
INTERNAL SURFACES
DRAWING TITLE
AXIAL FLOW S/S 316 PIPE SUPPORT
PUMP TYPICAL DRAWING FOR
OUTFALL PUMPING STATION
TANKING MEMBRANE
AND PROTECTION BOARD MECHANICAL SECTIONS AND
FFL PLAN DETAILS
DRAWN - SCALE 1 : 100
50mm THK. CEMENT/SAND SCREED CHECKED - DATE -
TANKING MEMBRANE SECTION C-C 50mm THK. CEMENT/SAND SCREED
APPROVED - SIZE A1
SECTION B-B 75mm THICK C20 BLINDING
1000 GAUGE POLYETHYLENE SHEET
TANKING MEMBRANE
75mm THICK C20 BLINDING
1000 GAUGE POLYETHYLENE SHEET PROJECT DWG.
No. - No.
1110

THIRD EDITION - APRIL 2022


NOTES:

REFERENCE DRAWINGS AND DOCUMENTS

No. REV-1 APP'D 2020


CLIENT

TITLE
STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

DRAWN - SCALE
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.

THIRD EDITION - APRIL 2022


NOTES:

1. TARIFF METERING SHALL BE LOCATED OUTSIDE OF THE


PUMPING STATION BOUNDARY WALL, NEXT TO THE
ENTRANCE, IN A SUITABLY PROTECTIVE HOUSING (AS PER
RSB CUSTOMER METERING REGULATIONS).
2. CONTRACTOR SHALL PREPARE DETAILED CALCULATIONS
AND THE OTHER SUPPORTING DOCUMENTS, REQUIRED
FOR EQUIPMENT AND CABLE SIZING.
400 VOLTS 3 PH 4 WIRE 50 HZ 400 VOLTS 3 PH 4 WIRE 50 HZ 400 VOLTS 3 PH 4 WIRE 50 HZ 3. POWER FACTOR CORRECTION CAPACITORS SHALL
MAINS SUPPLY FROM ADDC MAINS SUPPLY FROM ADDC MAINS SUPPLY FROM GENERATOR IMPROVE THE OVERALL FACTOR TO 0.9 LAGGING.
(APPLICABLE FOR TOTAL CONNECTED LOAD UP TO 100 Amp.) (APPLICABLE FOR TOTAL CONNECTED LOAD > 100 Amp.) 4. MOTOR STARTERS SHALL BE AS PER THE SPECIFICATIONS.
R/Y/B N A AMMETER
5. THE RTU/PLC SHALL BE MAINTAINED IN OPERATION DURING
3
MAINS FAILURE, DRAWING POWER FROM THE BATTERY.
SUPPLY AVAILABLE SUPPLY AVAILABLE CONTACTOR
KWHR KILOWATT HOUR METER 6. MAIN INCOMER CIRCUIT BREAKER TO BE PROVIDED WITH
R Y B R Y B
EARTH LEAKAGE PROTECTION.THE SETTING TO BE
3P MCCB F INDICATOR LAMP CONFIRMED BY ADDC.
F
(MAX. 100 A) 7. ELCB TO BE PROVIDED FOR PUMPS UPTO 125A. FOR PUMPS
PUSHBUTTON ABOVE 125A,CBCT WITH RELAY TO BE PROVIDED.

F F MCCB
KWHR
F F
CIRCUIT BREAKER
M & E INTERLOCK
ACB/MCCB 4P ACB/MCCB 4P
FUSE
M & E INTERLOCK
4P MCCB
(MAX. 100 A) 3 TRANSFER SWITCH ATS/BYPASS 3 C1 HOUR RUN COUNTER
PM POWER MONITOR PM POWER MONITOR
TO BE PROVIDED WHERE SPECIFIED
C2 NO. OF START COUNTER

SOFTSTARTER
LIGHTNING PROTECTION
E/L EARTH LEAKAGE RELAY
1
TO (PFCC)
ST SHUNT TRIP
V PFR
V
F S VOLTMETER SELECTOR SWITCH

PM POWER MONITOR
400V, 3PH, 4W, 400A, 50Hz, 50kA/1 sec R/Y/B N ELECTRO TINNED HIGH CONDUCTIVITY COPPER BUSBAR
PFCC POWER FACTOR CORRECTION
CAPACITORS

E E
EMPR ELECTRONIC MOTOR PROTECTION
3P 3P 3P 4P 4P 4P 4P 4P 2P 2P 4P 4P 4P RELAY
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
+ ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB
NOTE 7 NOTE 7

1 2 3 1 2 3 1 2 3
TRANSDUCER TRANSDUCER TRANSDUCER
3 C1 C2 3 C1 C2 3 C1 C2
+ A + A + A
- - -

4 5 6 7 8 4 5 6 7 8 4 5 6 7 8

1 SUPPLY ON INDICATOR 1 SUPPLY ON INDICATOR 1 SUPPLY ON INDICATOR


2 RUN INDICATOR 2 RUN INDICATOR 2 RUN INDICATOR
3 TRIP INDICATOR 3 TRIP INDICATOR 3 TRIP INDICATOR REFERENCE DRAWINGS AND DOCUMENTS
4 START PUSH BUTTON 4 START PUSH BUTTON 4 START PUSH BUTTON
5 STOP PUSH BUTTON 5 STOP PUSH BUTTON 5 STOP PUSH BUTTON
6 LAMP TEST PUSH BUTTON 6 LAMP TEST PUSH BUTTON 6 LAMP TEST PUSH BUTTON
7 HOA SELECTOR SWITCH 7 HOA SELECTOR SWITCH 7 HOA SELECTOR SWITCH
8 PANEL HEATER OFF 8 PANEL HEATER OFF 8 PANEL HEATER OFF
AUTO-SWITCH AUTO-SWITCH AUTO-SWITCH

3 3
EMPR ELECTRONIC MOTOR EMPR ELECTRONIC MOTOR
PROTECTION RELAY PROTECTION RELAY

No. REV-1 APP'D 2020


CLIENT

EMERGENCY EMERGENCY EMERGENCY


PUSH BUTTON PUSH BUTTON PUSH BUTTON NOTE 3

TITLE
STANDARD DRAWINGS
STORM WATER WORKS
LIGHTING & SMALL POWER EXTERNAL LIGTHING DB COMMON CONTROL RTU / PLC PANEL SOCKET POWER FACTOR
PUMP No.1 PUMP No.2 SUMP PUMP LIFTING DAVIT OUTGOING FEEDER 1 OUTGOING FEEDER 2
DISTRIBUTION BOARD ( PROVISIONAL ) SECTION SECTION SECTION CORRECTION CAPACITORS SPARE DRAWING TITLE

DRAWN - SCALE
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.

THIRD EDITION - APRIL 2022


NOTES:

1. TARIFF METERING SHALL BE LOCATED OUTSIDE OF THE


PUMPING STATION BOUNDARY WALL, NEXT TO THE
ENTRANCE, IN A SUITABLY PROTECTIVE HOUSING (AS PER
RSB CUSTOMER METERING REGULATIONS).
400 VOLTS 3 PH 4 WIRE 50 HZ 400 VOLTS 3 PH 4 WIRE 50 HZ 400 VOLTS 3 PH 4 WIRE 50 HZ 2. CONTRACTOR SHALL PREPARE DETAILED CALCULATIONS
MAINS SUPPLY FROM ADDC MAINS SUPPLY FROM ADDC MAINS SUPPLY FROM GENERATOR AND THE OTHER SUPPORTING DOCUMENTS, REQUIRED
(APPLICABLE FOR TOTAL CONNECTED LOAD UP TO 100 Amp.) (APPLICABLE FOR TOTAL CONNECTED LOAD > 100 Amp.) FOR EQUIPMENT AND CABLE SIZING.
R/Y/B N 3. POWER FACTOR CORRECTION CAPACITORS SHALL
IMPROVE THE OVERALL FACTOR TO 0.9 LAGGING.
3 4. MOTOR STARTERS SHALL BE AS PER THE SPECIFICATIONS.
SUPPLY AVAILABLE SUPPLY AVAILABLE
KWHR KILOWATT HOUR METER 5. THE RTU/PLC SHALL BE MAINTAINED IN OPERATION DURING
R Y B R Y B
MAINS FAILURE, DRAWING POWER FROM THE BATTERY.
3P MCCB F F 6. MAIN INCOMER CIRCUIT BREAKER TO BE PROVIDED WITH
(MAX. 100 A) EARTH LEAKAGE PROTECTION.THE SETTING TO BE
CONFIRMED BY ADDC.
7. ELCB TO BE PROVIDED FOR PUMPS UPTO 125A. FOR PUMPS
F F ABOVE 125A,CBCT WITH RELAY TO BE PROVIDED.

KWHR
F F

M & E INTERLOCK
ACB/MCCB 4P ACB/MCCB 4P

M & E INTERLOCK
4P MCCB 3 TRANSFER SWITCH ATS/BYPASS 3
(MAX. 100 A)
PM POWER MONITOR PM POWER MONITOR
TO BE PROVIDED WHERE SPECIFIED

LIGHTNING PROTECTION
1
TO (PFCC)

V PFR
F

400V, 3PH, 4W, 400A, 50Hz, 50kA/1 sec R/Y/B N ELECTRO TINNED HIGH CONDUCTIVITY COPPER BUSBAR

E 3P E
3P 3P 4P 4P 4P 4P 4P 2P 2P 4P 4P 4P
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
+ ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB
NOTE 7 NOTE 7

1 2 3 1 2 3 1 2 3
TRANSDUCER TRANSDUCER TRANSDUCER
3 C1 C2 3 C1 C2 3 C1 C2
+ A + A + A
- - -

4 5 6 7 8 4 5 6 7 8 4 5 6 7 8 REFERENCE DRAWINGS AND DOCUMENTS


1 SUPPLY ON INDICATOR 1 SUPPLY ON INDICATOR 1 SUPPLY ON INDICATOR
2 RUN INDICATOR 2 RUN INDICATOR 2 RUN INDICATOR
3 TRIP INDICATOR 3 TRIP INDICATOR 3 TRIP INDICATOR
4 START PUSH BUTTON 4 START PUSH BUTTON 4 START PUSH BUTTON
5 STOP PUSH BUTTON 5 STOP PUSH BUTTON 5 STOP PUSH BUTTON
6 LAMP TEST PUSH BUTTON 6 LAMP TEST PUSH BUTTON 6 LAMP TEST PUSH BUTTON
7 HOA SELECTOR SWITCH 7 HOA SELECTOR SWITCH 7 HOA SELECTOR SWITCH
8 PANEL HEATER OFF 8 PANEL HEATER OFF 8 PANEL HEATER OFF
AUTO-SWITCH AUTO-SWITCH AUTO-SWITCH

3 3
EMPR
ELECTRONIC MOTOR EMPR ELECTRONIC MOTOR
PROTECTION RELAY PROTECTION RELAY

No. REV-1 APP'D 2020


CLIENT

TITLE
STANDARD DRAWINGS
STORM WATER WORKS
EMERGENCY EMERGENCY EMERGENCY DRAWING TITLE
PUSH BUTTON PUSH BUTTON PUSH BUTTON NOTE 3

LIGHTING & SMALL POWER EXTERNAL LIGTHING DB COMMON CONTROL RTU / PLC PANEL SOCKET POWER FACTOR
PUMP No.1 PUMP No.2 SUMP PUMP LIFTING DAVIT OUTGOING FEEDER 1OUTGOING FEEDER 2
DISTRIBUTION BOARD ( PROVISIONAL ) SECTION SECTION SECTION CORRECTION CAPACITORS SPARE
DRAWN - SCALE
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.

THIRD EDITION - APRIL 2022


NOTES:

1. TARIFF METERING SHALL BE LOCATED OUTSIDE OF THE


PUMPING STATION BOUNDARY WALL, NEXT TO THE
ENTRANCE, IN A SUITABLY PROTECTIVE HOUSING (AS PER
RSB CUSTOMER METERING REGULATIONS).
2. CONTRACTOR SHALL PREPARE DETAILED CALCULATIONS
AND THE OTHER SUPPORTING DOCUMENTS, REQUIRED
FOR EQUIPMENT AND CABLE SIZING.
400 VOLTS 3 PH 4 WIRE 50 HZ 400 VOLTS 3 PH 4 WIRE 50 HZ 400 VOLTS 3 PH 4 WIRE 50 HZ 3. POWER FACTOR CORRECTION CAPACITORS SHALL
MAINS SUPPLY FROM ADDC MAINS SUPPLY FROM ADDC MAINS SUPPLY FROM GENERATOR IMPROVE THE OVERALL FACTOR TO 0.9 LAGGING.
(APPLICABLE FOR TOTAL CONNECTED LOAD UP TO 100 Amp.) (APPLICABLE FOR TOTAL CONNECTED LOAD > 100 Amp.) 4. MOTOR STARTERS SHALL BE AS PER THE SPECIFICATIONS.
R/Y/B N 5. THE RTU/PLC SHALL BE MAINTAINED IN OPERATION DURING
MAINS FAILURE, DRAWING POWER FROM THE BATTERY.
3
SUPPLY AVAILABLE SUPPLY AVAILABLE 6. MAIN INCOMER CIRCUIT BREAKER TO BE PROVIDED WITH
KWHR KILOWATT HOUR METER
R Y B R Y B EARTH LEAKAGE PROTECTION.THE SETTING TO BE
CONFIRMED BY ADDC.
3P MCCB F F 7. ELCB TO BE PROVIDED FOR PUMPS UPTO 125A. FOR PUMPS
(MAX. 100 A)
ABOVE 125A,CBCT WITH RELAY TO BE PROVIDED.

F F

KWHR
F F

M & E INTERLOCK
ACB/MCCB 4P ACB/MCCB 4P

M & E INTERLOCK
4P MCCB POWER MONITOR
3 TRANSFER SWITCH ATS/BYPASS 3
(MAX. 100 A)
PM PM POWER MONITOR
TO BE PROVIDED WHERE SPECIFIED

LIGHTNING PROTECTION
1
TO (PFCC)

V PFR
F

400V, 3PH, 4W, 400A, 50Hz, 50kA/1 sec R/Y/B N ELECTRO TINNED HIGH CONDUCTIVITY COPPER BUSBAR

E E
3P 3P 3P 3P 4P 4P 4P 4P 4P 2P 2P 4P 4P 4P
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
+ ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB
NOTE 7 NOTE 7 NOTE 7

1 2 3 1 2 3 1 2 3 1 2 3
TRANSDUCER TRANSDUCER TRANSDUCER TRANSDUCER
3 C1 C2 3 C1 C2 3 C1 C2 3 C1 C2
+ A + A + A + A
- - - -

4 5 6 7 8 4 5 6 7 8 4 5 6 7 8 4 5 6 7 8 REFERENCE DRAWINGS AND DOCUMENTS


1 SUPPLY ON INDICATOR 1 SUPPLY ON INDICATOR 1 SUPPLY ON INDICATOR
2 RUN INDICATOR 1 SUPPLY ON INDICATOR
2 RUN INDICATOR 2 RUN INDICATOR
3 TRIP INDICATOR 2 RUN INDICATOR
3 TRIP INDICATOR 3 TRIP INDICATOR
4 START PUSH BUTTON 3 TRIP INDICATOR
4 START PUSH BUTTON 4 START PUSH BUTTON
5 STOP PUSH BUTTON 5 STOP PUSH BUTTON 4 START PUSH BUTTON
5 STOP PUSH BUTTON
6 LAMP TEST PUSH BUTTON 6 LAMP TEST PUSH BUTTON 5 STOP PUSH BUTTON
6 LAMP TEST PUSH BUTTON
7 7 HOA SELECTOR SWITCH 6 LAMP TEST PUSH BUTTON
7 HOA SELECTOR SWITCH HOA SELECTOR SWITCH
8 PANEL HEATER OFF 7 HOA SELECTOR SWITCH
8 PANEL HEATER OFF 8 PANEL HEATER OFF
AUTO-SWITCH AUTO-SWITCH 8 PANEL HEATER OFF
AUTO-SWITCH
AUTO-SWITCH

3 3 3
EMPR ELECTRONIC MOTOR EMPR ELECTRONIC MOTOR EMPR ELECTRONIC MOTOR
PROTECTION RELAY PROTECTION RELAY PROTECTION RELAY

No. REV-1 APP'D 2020


CLIENT

TITLE
STANDARD DRAWINGS
EMERGENCY EMERGENCY EMERGENCY EMERGENCY STORM WATER WORKS
PUSH BUTTON PUSH BUTTON PUSH BUTTON PUSH BUTTON NOTE 3
DRAWING TITLE

LIGHTING & SMALL POWER EXTERNAL LIGTHING DB COMMON CONTROL RTU / PLC PANEL SOCKET POWER FACTOR
PUMP No.1 PUMP No.2 PUMP No.3 SUMP PUMP LIFTING DAVIT OUTGOING FEEDER 1OUTGOING FEEDER 2
DISTRIBUTION BOARD ( PROVISIONAL ) SECTION SECTION SECTION CORRECTION CAPACITORS SPARE

DRAWN - SCALE
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.

THIRD EDITION - APRIL 2022


NOTES:

1. TARIFF METERING SHALL BE LOCATED OUTSIDE OF THE


PUMPING STATION BOUNDARY WALL, NEXT TO THE
ENTRANCE, IN A SUITABLY PROTECTIVE HOUSING (AS PER
RSB CUSTOMER METERING REGULATIONS).
2. CONTRACTOR SHALL PREPARE DETAILED CALCULATIONS
AND THE OTHER SUPPORTING DOCUMENTS, REQUIRED
400 VOLTS 3 PH 4 WIRE 50 HZ 400 VOLTS 3 PH 4 WIRE 50 HZ 400 VOLTS 3 PH 4 WIRE 50 HZ FOR EQUIPMENT AND CABLE SIZING.
MAINS SUPPLY FROM ADDC MAINS SUPPLY FROM ADDC MAINS SUPPLY FROM GENERATOR 3. POWER FACTOR CORRECTION CAPACITORS SHALL
(APPLICABLE FOR TOTAL CONNECTED LOAD UP TO 100 Amp.) (APPLICABLE FOR TOTAL CONNECTED LOAD > 100 Amp.) IMPROVE THE OVERALL FACTOR TO 0.9 LAGGING.
R/Y/B N 4. MOTOR STARTERS SHALL BE AS PER THE SPECIFICATIONS.
5. THE RTU/PLC SHALL BE MAINTAINED IN OPERATION DURING
SUPPLY AVAILABLE 3 SUPPLY AVAILABLE MAINS FAILURE, DRAWING POWER FROM THE BATTERY.
KWHR KILOWATT HOUR METER 6. MAIN INCOMER CIRCUIT BREAKER TO BE PROVIDED WITH
R Y B R Y B
EARTH LEAKAGE PROTECTION.THE SETTING TO BE
3P MCCB F F CONFIRMED BY ADDC.
(MAX. 100 A) 7. ELCB TO BE PROVIDED FOR PUMPS UPTO 125A. FOR PUMPS
ABOVE 125A,CBCT WITH RELAY TO BE PROVIDED.

F F

KWHR
F F

M & E INTERLOCK
ACB/MCCB 4P ACB/MCCB 4P

M & E INTERLOCK
4P MCCB
3 3
(MAX. 100 A) PM POWER MONITOR TRANSFER SWITCH ATS/BYPASS PM POWER MONITOR
TO BE PROVIDED WHERE SPECIFIED

LIGHTNING PROTECTION
1
TO (PFCC)

V PFR
F

400V, 3PH, 4W, 400A, 50Hz, 50kA/1 sec R/Y/B N ELECTRO TINNED HIGH CONDUCTIVITY COPPER BUSBAR

E E
3P 3P 4P 4P 4P 4P 4P 2P 2P 4P 4P 4P
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
+ ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB
NOTE 7 NOTE 7

1 2 3 1 2 3
TRANSDUCER TRANSDUCER
3 C1 C2 3 C1 C2
+
- A +
- A REFERENCE DRAWINGS AND DOCUMENTS

4 5 6 7 8 4 5 6 7 8

1 SUPPLY ON INDICATOR 1 SUPPLY ON INDICATOR


2 RUN INDICATOR 2 RUN INDICATOR
3 TRIP INDICATOR 3 TRIP INDICATOR
4 START PUSH BUTTON 4 START PUSH BUTTON
5 STOP PUSH BUTTON 5 STOP PUSH BUTTON
6 LAMP TEST PUSH BUTTON 6 LAMP TEST PUSH BUTTON
7 HOA SELECTOR SWITCH 7 HOA SELECTOR SWITCH
8 PANEL HEATER OFF 8 PANEL HEATER OFF
AUTO-SWITCH AUTO-SWITCH

3 3
ELECTRONIC MOTOR ELECTRONIC MOTOR
EMPR
PROTECTION RELAY
EMPR
PROTECTION RELAY
No. REV-1 APP'D 2020
CLIENT

TITLE
STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

EMERGENCY EMERGENCY
PUSH BUTTON PUSH BUTTON NOTE 3

DRAWN - SCALE
LIGHTING & SMALL POWER EXTERNAL LIGTHING DB COMMON CONTROL RTU / PLC PANEL SOCKET POWER FACTOR
PUMP No.1 PUMP No.2 LIFTING DAVIT OUTGOING FEEDER 1 OUTGOING FEEDER 2
DISTRIBUTION BOARD ( PROVISIONAL ) SECTION SECTION SECTION CORRECTION CAPACITORS SPARE CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.

THIRD EDITION - APRIL 2022


NOTES:

1. TARIFF METERING SHALL BE LOCATED OUTSIDE OF THE


PUMPING STATION BOUNDARY WALL, NEXT TO THE
400 VOLTS 3 PH 4 WIRE 50 HZ 400 VOLTS 3 PH 4 WIRE 50 HZ 400 VOLTS 3 PH 4 WIRE 50 HZ ENTRANCE, IN A SUITABLY PROTECTIVE HOUSING (AS PER
MAINS SUPPLY FROM ADDC MAINS SUPPLY FROM ADDC MAINS SUPPLY FROM GENERATOR
RSB CUSTOMER METERING REGULATIONS).
(APPLICABLE FOR TOTAL CONNECTED LOAD UP TO 100 Amp.) 2. CONTRACTOR SHALL PREPARE DETAILED CALCULATIONS
(APPLICABLE FOR TOTAL CONNECTED LOAD > 100 Amp.)
R/Y/B N AND THE OTHER SUPPORTING DOCUMENTS, REQUIRED
FOR EQUIPMENT AND CABLE SIZING.
SUPPLY AVAILABLE 3 SUPPLY AVAILABLE
3. POWER FACTOR CORRECTION CAPACITORS SHALL
KWHR KILOWATT HOUR METER IMPROVE THE OVERALL FACTOR TO 0.9 LAGGING.
R Y B R Y B 4. MOTOR STARTERS SHALL BE AS PER THE SPECIFICATIONS.
5. THE RTU/PLC SHALL BE MAINTAINED IN OPERATION DURING
3P MCCB F F MAINS FAILURE, DRAWING POWER FROM THE BATTERY.
(MAX. 100 A)
6. MAIN INCOMER CIRCUIT BREAKER TO BE PROVIDED WITH
EARTH LEAKAGE PROTECTION.THE SETTING TO BE
CONFIRMED BY ADDC.
F F 7. ELCB TO BE PROVIDED FOR PUMPS UPTO 125A. FOR PUMPS
ABOVE 125A,CBCT WITH RELAY TO BE PROVIDED.
KWHR
F F
M & E INTERLOCK
ACB/MCCB 4P ACB/MCCB 4P

M & E INTERLOCK
4P MCCB TRANSFER SWITCH ATS/BYPASS
3 3
(MAX. 100 A)
PM POWER MONITOR TO BE PROVIDED WHERE SPECIFIED PM POWER MONITOR

LIGHTNING PROTECTION
1
TO (PFCC)

V PFR
F

400V, 3PH, 4W, 400A, 50Hz, 50kA/1 sec R/Y/B N ELECTRO TINNED HIGH CONDUCTIVITY COPPER BUSBAR

E E
3P 3P 3P 4P 4P 4P 4P 2P 2P 4P 4P 4P
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
+ ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB
NOTE 7 NOTE 7

1 2 3 1 2 3 1 2 3
TRANSDUCER TRANSDUCER TRANSDUCER
3 C1 C2 3 C1 C2 3 C1 C2
+ A + A + A
- - -

4 5 6 7 8 4 5 6 7 8 4 5 6 7 8
REFERENCE DRAWINGS AND DOCUMENTS
1 SUPPLY ON INDICATOR 1 SUPPLY ON INDICATOR 1 SUPPLY ON INDICATOR
2 RUN INDICATOR 2 RUN INDICATOR 2 RUN INDICATOR
3 TRIP INDICATOR 3 TRIP INDICATOR 3 TRIP INDICATOR
4 START PUSH BUTTON 4 START PUSH BUTTON 4 START PUSH BUTTON
5 STOP PUSH BUTTON 5 STOP PUSH BUTTON 5 STOP PUSH BUTTON
6 LAMP TEST PUSH BUTTON 6 LAMP TEST PUSH BUTTON 6 LAMP TEST PUSH BUTTON
7 HOA SELECTOR SWITCH 7 HOA SELECTOR SWITCH 7 HOA SELECTOR SWITCH
8 PANEL HEATER OFF 8 PANEL HEATER OFF 8 PANEL HEATER OFF
AUTO-SWITCH AUTO-SWITCH AUTO-SWITCH

3 3
EMPR ELECTRONIC MOTOR EMPR ELECTRONIC MOTOR
PROTECTION RELAY PROTECTION RELAY

No. REV-1 APP'D 2020


CLIENT

TITLE
STANDARD DRAWINGS
STORM WATER WORKS
EMERGENCY EMERGENCY EMERGENCY DRAWING TITLE
PUSH BUTTON PUSH BUTTON PUSH BUTTON NOTE 3

LIGHTING & SMALL POWER EXTERNAL LIGTHING DB COMMON CONTROL RT / PLC PANEL SOCKET POWER FACTOR
TITLE PUMP No.1 PUMP No.2 SUMP PUMP OUTGOING FEEDER 1 OUTGOING FEEDER 2
DISTRIBUTION BOARD ( PROVISIONAL ) SECTION SECTION SECTION CORRECTION CAPACITORS SPARE
DRAWN - SCALE
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.

THIRD EDITION - APRIL 2022


NOTES:

1. TARIFF METERING SHALL BE LOCATED OUTSIDE OF THE


PUMPING STATION BOUNDARY WALL, NEXT TO THE
ENTRANCE, IN A SUITABLY PROTECTIVE HOUSING (AS PER
RSB CUSTOMER METERING REGULATIONS).
2. CONTRACTOR SHALL PREPARE DETAILED CALCULATIONS
AND THE OTHER SUPPORTING DOCUMENTS, REQUIRED
FOR EQUIPMENT AND CABLE SIZING.
3. POWER FACTOR CORRECTION CAPACITORS SHALL
IMPROVE THE OVERALL FACTOR TO 0.9 LAGGING.
4. MOTOR STARTERS SHALL BE AS PER THE SPECIFICATIONS.
5. THE RTU/PLC SHALL BE MAINTAINED IN OPERATION DURING
400 VOLTS 3 PH 4 WIRE 50 HZ 400 VOLTS 3 PH 4 WIRE 50 HZ MAINS FAILURE, DRAWING POWER FROM THE BATTERY.
MAINS SUPPLY FROM ADDC 400 VOLTS 3 PH 4 WIRE 50 HZ
MAINS SUPPLY FROM ADDC 6. MAIN INCOMER CIRCUIT BREAKER TO BE PROVIDED WITH
(APPLICABLE FOR TOTAL CONNECTED LOAD UP TO 100 Amp.) MAINS SUPPLY FROM GENERATOR
(APPLICABLE FOR TOTAL CONNECTED LOAD > 100 Amp.) EARTH LEAKAGE PROTECTION.THE SETTING TO BE
R/Y/B N CONFIRMED BY ADDC.
7. ELCB TO BE PROVIDED FOR PUMPS UPTO 125A. FOR PUMPS
SUPPLY AVAILABLE 3 SUPPLY AVAILABLE
KWHR KILOWATT HOUR METER ABOVE 125A,CBCT WITH RELAY TO BE PROVIDED.
R Y B R Y B

3P MCCB F F
(MAX. 100 A)

F F
KWHR
F F
M & E INTERLOCK
ACB/MCCB 4P ACB/MCCB 4P

M & E INTERLOCK
4P MCCB
(MAX. 100 A) 3 TRANSFER SWITCH ATS/BYPASS 3
PM POWER MONITOR PM POWER MONITOR
TO BE PROVIDED WHERE SPECIFIED

LIGHTNING PROTECTION
1
TO (PFCC)

V PFR
F

400V, 3PH, 4W, 400A, 50Hz, 50kA/1 sec R/Y/B N ELECTRO TINNED HIGH CONDUCTIVITY COPPER BUSBAR

E 3P E
3P 3P 3P 3P 4P 4P 4P 4P 4P 2P 2P 4P 4P 4P
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
+ ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB + ELCB
NOTE 7 NOTE 7 NOTE 7
NOTE 7

TRANSDUCER 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3
TRANSDUCER TRANSDUCER TRANSDUCER TRANSDUCER
3 C1 C2 3 C1 C2 3 C1 C2 3 C1 C2 3 C1 C2
+ A + A + A A + A
- - - - -

4 5 6 7 8 4 5 6 7 8 4 5 6 7 8 4 5 6 7 8 4 5 6 7 8
1 SUPPLY ON INDICATOR 1 SUPPLY ON INDICATOR 1 SUPPLY ON INDICATOR 1 SUPPLY ON INDICATOR 1 SUPPLY ON INDICATOR
2 RUN INDICATOR 2 RUN INDICATOR 2 RUN INDICATOR 2 RUN INDICATOR 2 RUN INDICATOR
3 TRIP INDICATOR 3 TRIP INDICATOR 3 TRIP INDICATOR 3 TRIP INDICATOR 3 TRIP INDICATOR
REFERENCE DRAWINGS AND DOCUMENTS
4 START PUSH BUTTON 4 START PUSH BUTTON 4 START PUSH BUTTON 4 START PUSH BUTTON 4 START PUSH BUTTON
5 STOP PUSH BUTTON 5 STOP PUSH BUTTON 5 STOP PUSH BUTTON 5 STOP PUSH BUTTON 5 STOP PUSH BUTTON
6 LAMP TEST PUSH BUTTON 6 LAMP TEST PUSH BUTTON 6 LAMP TEST PUSH BUTTON 6 LAMP TEST PUSH BUTTON 6 LAMP TEST PUSH BUTTON
7 HOA SELECTOR SWITCH 7 HOA SELECTOR SWITCH 7 HOA SELECTOR SWITCH 7 HOA SELECTOR SWITCH 7 HOA SELECTOR SWITCH
8 PANEL HEATER OFF 8 PANEL HEATER OFF 8 PANEL HEATER OFF 8 PANEL HEATER OFF 8 PANEL HEATER OFF
AUTO-SWITCH AUTO-SWITCH AUTO-SWITCH AUTO-SWITCH AUTO-SWITCH

3 ELECTRONIC MOTOR 3 3 ELECTRONIC MOTOR 3


ELECTRONIC MOTOR ELECTRONIC MOTOR
EMPR EMPR EMPR EMPR
PROTECTION RELAY PROTECTION RELAY PROTECTION RELAY PROTECTION RELAY

No. REV-1 APP'D 2020


CLIENT
EMERGENCY EMERGENCY EMERGENCY EMERGENCY EMERGENCY
PUSH BUTTON PUSH BUTTON PUSH BUTTON PUSH BUTTON PUSH BUTTON NOTE 3

TITLE
STANDARD DRAWINGS
PUMP No.1 PUMP No.2 PUMP No.3 PUMP No.4 SUMP PUMP LIFTING DAVIT
OUTGOING OUTGOING
LIGHTING
& SMALL POWER
EXTERNAL
LIGTHING DB
COMMON
CONTROL
RTU / PLC PANEL SOCKET POWER FACTOR SPARE STORM WATER WORKS
FEEDER 1 FEEDER 2 SECTION SECTION CORRECTION
DISTRIBUTION BOARD ( PROVISIONAL ) SECTION CAPACITORS
DRAWING TITLE

DRAWN - SCALE
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE
INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
CHECKED AND APPROVED AS PART OF THE PROJECT
DRAWING SET.
1. THIS DRAWING IS INDICATIVE ONLY.
2. TYPICAL CONNECTIVITY FOR ALL PUMPS AND MOTORISED
VALVES AND PENSTOCK
3. TYPICAL CONNECTIVITY FOR ALL PROXIMITY SWITCHES
4. REFER TO DRG. No.1301 FOR P&ID SYMBOLS AND LEGENDS.
5. ISOLATION PENSTOCK TO BE INSALLED INLINE OF MANHOLE
UPSTREAM INSIDE THE PUMPING STATION.

G GENERATOR
~
A AMMETER

E/L

REFERENCE DRAWINGS AND DOCUMENTS

No. REV-1 APP'D 2020


CLIENT

TITLE
STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

STANDARD DRAWING PROPOSED


STORM WATER - POND
SINGLE LINE DIAGRAM

DRAWN - SCALE NTS


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1207

THIRD EDITION - APRIL 2022


NOTES:
4790 580 1200 1200 VARIES 1240

FLEXIBLE COWL
BETWEN RADIATOR
INLET LOUVRE
ELECTRICALY
FUEL OIL
DAY TANK
EXTERNAL
LIGHTING DB
2
& LOUVRE ACTUATED
( PROVISIONAL ) 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
STATED.
2. ADDITIONAL DUCTS FOR POWER SUPPLY OF OTHER
CONSUMERS (PUMPS, ETC.) INSIDE PUMPING STATION
COMPOUND, SHALL BE PROVIDED AS REQUIRED BASED ON
ARRANGEMENT OF THE EQUIPMENTS.
3. BUILDING ORIENTATION TO SUIT SITE ACCESS ROADS.

1190
4. DOORS ORIENTATION SHALL SUIT SITE REQUIREMENTS.

980
5. DOORS SHALL BE SIZED TO ENSURE EASY ACCESS AND
OUTLET LOUVRE OPERATED BY 900 REMOVAL OF EQUIPMENT.
AIR PRESSURE OF RADIATOR FAN. MCC ROOM
LOUVRE TO BE FULL HEIGHT OF ROOM

SPLIT UNIT AIR CONDITIONER


SPLIT UNIT AIR CONDITIONER
GENERATOR ROOM
CERAMIC
WASH BASIN PFCC MCC
1

VARIES
FE-1
FE-2

FE-1
FE-2

1190
F FACP F

L&SP DB ETISALAT
JUNCTION BOX
FIRE ALARM TELEPHONE
CONTROL PANEL SOCKET

RAMP FROM GROUND LEVEL


TO FLOOR LEVEL OF CONTROL ROOM
2500

GROUND FLOOR PLAN


1 : 50

FLASHING LIGHT ACCESS LADDER REFERENCE DRAWINGS AND DOCUMENTS


ALARM BEACON
300

150 THICK R.C. PARAPET

WATERPROOFING & FINISH


FOR ROOF

150 THICK R.C. SLAB

No. REV-1 APP'D 2020


CLIENT

TITLE
STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

GL GL

16G VERTICALLY RIBBED ALUMINIUM


SHEETS FACING ON 5mm W.B.P. PLY

150
ON TIMBER CORES SCREWED TO
ALUMINIUM FRAMING. CORES TO BE
INSULATED WITH EXPANDED PLASTIC DRAWN - SCALE
INSULATION
ELEVATION A CHECKED - DATE -
1 : 50 APPROVED - SIZE A1
PROJECT DWG.
No. - No.

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
STATED.
2. ADDITIONAL DUCTS FOR POWER SUPPLY OF OTHER
CONSUMERS (PUMPS, ETC.) INSIDE PUMPING STATION
COMPOUND, SHALL BE PROVIDED AS REQUIRED BASED ON
ARRANGEMENT OF THE EQUIPMENTS.
3. BUILDING ORIENTATION TO SUIT SITE ACCESS ROADS.
4. DOORS ORIENTATION SHALL SUIT SITE REQUIREMENTS.
5. DOORS SHALL BE SIZED TO ENSURE EASY ACCESS AND
REMOVAL OF EQUIPMENT.

EXTERNAL
LIGHTING DB
( PROVISIONAL )

SPLIT UNIT AIR CONDITIONER

SPLIT UNIT AIR CONDITIONER


PFCC MCC
MCC ROOM
GENERATOR ROOM D

F
D F F F F F F F F F
D F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F
D

F
F

F
F

F
F

F
F

F
F F F F F F F F F F F F F F F F F F F
F
FE-1
FE-2

FE-1
FE-2F
F

BLOCKWORK MADE FROM SOLID


REFERENCE DRAWINGS AND DOCUMENTS

F
F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F F
F

BLOCKS 390 x 240 x 90

F
F

F
F

F
F FACP F

F
F
F

F
SL-1
L&SP DB ETISALAT
JUNCTION BOX
BLOCKWORK MADE FROM SOLID FIRE ALARM TELEPHONE
BLOCKS 390 x 240 x 90 CONTROL PANEL SOCKET

GROUND FLOOR PLAN


RAMP FROM GROUND LEVEL
TO FLOOR LEVEL OF CONTROL ROOM No. REV-1 APP'D 2020
CLIENT

TITLE
STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

STANDARD DRAWING CONTROL


& GENERATOR BUILDING FIRE
ALARM SYSTEM LAYOUT

DRAWN - SCALE 1:50


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1209

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
STATED.
EXTERNAL 2. ADDITIONAL DUCTS FOR POWER SUPPLY OF OTHER
LIGHTING DB CONSUMERS (PUMPS, ETC.) INSIDE PUMPING STATION
( PROVISIONAL ) COMPOUND, SHALL BE PROVIDED AS REQUIRED BASED ON
ARRANGEMENT OF THE EQUIPMENTS.
3. BUILDING ORIENTATION TO SUIT SITE ACCESS ROADS.
4. DOORS ORIENTATION SHALL SUIT SITE REQUIREMENTS.
5. DOORS SHALL BE SIZED TO ENSURE EASY ACCESS AND
EXIT REMOVAL OF EQUIPMENT.

E E

SPLIT UNIT AIR CONDITIONER


SPLIT UNIT AIR CONDITIONER
PFCC MCC

GENERATOR ROOM MCC ROOM


D

FE-1
FE-2

FE-1
FE-2
BLOCKWORK MADE FROM SOLID
BLOCKS 390 x 240 x 90

F EXIT FACP EXIT F

L&SP DB ETISALAT
JUNCTION BOX
BLOCKWORK MADE FROM SOLID FIRE ALARM TELEPHONE
BLOCKS 390 x 240 x 90 CONTROL PANEL SOCKET

RAMP FROM GROUND LEVEL


GROUND FLOOR PLAN TO FLOOR LEVEL OF CONTROL ROOM

REFERENCE DRAWINGS AND DOCUMENTS

4790 1780 5180

W/P W/P

FALL

INSULATED COPPER
CONDENSATE PIPE

No. REV-1 APP'D 2020


COMPRESSOR
SPLIT UNIT

CLIENT
3580

VALL
EY
INSULATED COPPER
CONDENSATE PIPE

TITLE
STANDARD DRAWINGS

COMPRESSOR
SPLIT UNIT
FALL
STORM WATER WORKS
DRAWING TITLE
STANDARD DRAWING
CONTROL & GENERATOR
BUILDING LIGHTING AND
SMALL POWER LAYOUT
DRAWN - SCALE 1:50
ROOF PLAN
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No. 1210

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
STATED.
2. ADDITIONAL DUCTS FOR POWER SUPPLY OF OTHER
CONSUMERS (PUMPS, ETC.) INSIDE PUMPING STATION
COMPOUND, SHALL BE PROVIDED AS REQUIRED BASED ON
ARRANGEMENT OF THE EQUIPMENTS.
3. BUILDING ORIENTATION TO SUIT SITE ACCESS ROADS.
4. DOORS ORIENTATION SHALL SUIT SITE REQUIREMENTS.
5. DOORS SHALL BE SIZED TO ENSURE EASY ACCESS AND
REMOVAL OF EQUIPMENT.

A/C A/C
1000 VARIES 1000

DB
EXTERNAL
LIGHTING

VARIES
PFCC MCC

1200
B

GL GL

STEEL BEAMS TO BE BOLTED


AS NECESSARY FOR SUPPORT

SECTION 1-1 -

REFERENCE DRAWINGS AND DOCUMENTS


SPLIT UNIT AIR CONDITIONER
1500 VARIES 1000

DB
DB EXTERNAL
L&SP LIGHTING
VARIES

CONTROL
PANEL

1000 CONTROL PANEL LENGTH VARIES (SEE NOTE) 1000

1500 MAXIMUM 1500 MAXIMUM


No. REV-1 APP'D 2020
1200

OUTLINE OF CONTROL
STEEL BEAMS TO BE BOLTED PANEL ABOVE TRENCH CLIENT
B AS NECESSARY FOR SUPPORT 600 TYPICAL CONTROL
300 300 PANEL WIDTH

GL GL

600
TITLE
STANDARD DRAWINGS
750

CHEQUER PLATE STORM WATER WORKS


150

FLOORING IN FRONT AND


TO SIDES OF PANEL

600
DRAWING TITLE
STANDARD DRAWING
CONTROL & GENERATOR
50

150 150 CONTROL PANEL TO REST ON


PVC-U SEALED DUCTS
50 WIDE x 20 DEEP RECESS FOR CHEQUER GALVANISED STEEL BEAMS TO CONCRETE & STEEL BEAMS BUILDING PLAN, SECTION &
PLATE FLOORING WITH GALVANISED SUPPORT CONTROL PANEL SPACED
FOR CABLES STEEL EDGING SET INTO CONCRETE AT 1500 CENTRES TRENCH DETAILS
DRAWN - SCALE 1:50
PLAN ON CONTROL PANEL TRENCH B CHECKED - DATE -
SECTION 2-2 -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1211

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
2500 MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE
- TO FLOOR LEVEL OF CONTROL ROOM INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
A RAMP FROM GROUND LEVEL CHECKED AND APPROVED AS PART OF THE PROJECT
DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
2 STATED.
2. ADDITIONAL DUCTS FOR POWER SUPPLY OF OTHER

1000
CONTROL PANEL SOCKET
FIRE ALARM TELEPHONE CONSUMERS (PUMPS, ETC.) INSIDE PUMPING STATION
JUNCTION BOX COMPOUND, SHALL BE PROVIDED AS REQUIRED BASED ON
L&SP DB ETISALAT ARRANGEMENT OF THE EQUIPMENTS.
3. BUILDING ORIENTATION TO SUIT SITE ACCESS ROADS.
4. DOORS ORIENTATION SHALL SUIT SITE REQUIREMENTS.
5. DOORS SHALL BE SIZED TO ENSURE EASY ACCESS AND
FACP F REMOVAL OF EQUIPMENT.

1190
FE-1
FE-2
INSULATED COPPER FALL
SPLIT UNIT AIR CONDITIONER

SPLIT UNIT AIR CONDITIONER


CONDENSATE PIPE

COMPRESSOR
VARIES
VA

SPLIT UNIT
MCC ROOM LLE
Y
INSULATED COPPER
WASH BASIN PFCC MCC CONDENSATE PIPE
CERAMIC JB
GENERATOR

COMPRESSOR
SPLIT UNIT
FALL

1 1

1190
1214

( PROVISIONAL )
LIGHTING DB
EXTERNAL
1640 1000 VARIES 1240
1214
2

GROUND FLOOR PLAN ROOF PLAN

REFERENCE DRAWINGS AND DOCUMENTS


ROOF
ACCESS LADDER

No. REV-1 APP'D 2020


CLIENT

TITLE
STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

GL GL
STANDARD DRAWING
CONTROL BUILDING PLAN,
ROOF PLAN & ELEVATION
ELEVATION A
-
DRAWN - SCALE 1:50
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1212

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
STATED.
2. ADDITIONAL DUCTS FOR POWER SUPPLY OF OTHER
CONSUMERS (PUMPS, ETC.) INSIDE PUMPING STATION
COMPOUND, SHALL BE PROVIDED AS REQUIRED BASED ON
ARRANGEMENT OF THE EQUIPMENTS.
3. BUILDING ORIENTATION TO SUIT SITE ACCESS ROADS.
4. DOORS ORIENTATION SHALL SUIT SITE REQUIREMENTS.
5. DOORS SHALL BE SIZED TO ENSURE EASY ACCESS AND
REMOVAL OF EQUIPMENT.

TO FLOOR LEVEL OF CONTROL ROOM


RAMP FROM GROUND LEVEL

CONTROL PANEL SOCKET


FIRE ALARM TELEPHONE
JUNCTION BOX

SL-1
L&SP DB ETISALAT

F
FACP F

F
F F F F F F F F F F

FE-1
FE-2 F
F
F F F F F F F

F
SPLIT UNIT AIR CONDITIONER

SPLIT UNIT AIR CONDITIONER


F
F
F
F
F F F F F

PFCC MCC
JB
GENERATOR

REFERENCE DRAWINGS AND DOCUMENTS


MCC ROOM

( PROVISIONAL )
LIGHTING DB
EXTERNAL

GROUND FLOOR PLAN No. REV-1 APP'D 2020


CLIENT

TITLE
STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

STANDARD DRAWING CONTROL


BUILDING FIRE ALARM SYSTEM
LAYOUT

DRAWN - SCALE 1:50


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1213

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE
INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
CHECKED AND APPROVED AS PART OF THE PROJECT
DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
STATED.
2. ADDITIONAL DUCTS FOR POWER SUPPLY OF OTHER
CONSUMERS, SHALL BE PROVIDED AS REQUIRED BASED ON
ARRANGEMENT OF THE EQUIPMENTS.
3. BUILDING ORIENTATION TO SUIT SITE ACCESS ROADS.
4. DOORS ORIENTATION SHALL SUIT SITE REQUIREMENTS.
5. DOORS SHALL BE SIZED TO ENSURE EASY ACCESS AND
REMOVAL OF EQUIPMENT.

S ADDRESSABLE SMOKE DETECTOR

H ADDRESSABLE FIXED HEAT DETECTOR

FIRE ALARM MANUAL STATION

FIRE ALARM SOUNDER WITH STROBE LIGHT


(110 CANDELA)

REFERENCE DRAWINGS AND DOCUMENTS

No. REV-1 APP'D 2020


CLIENT

TITLE
STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

STANDARD DRAWING PROPOSED


STORM WATER - POND
FIRE ALARM RISER DIAGRAM

DRAWN - SCALE NTS


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1214

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS
OTHERWISE STATED.
2. ADDITIONAL DUCTS FOR POWER SUPPLY OF OTHER
CONSUMERS (PUMPS, ETC.) INSIDE PUMPING STATION
COMPOUND, SHALL BE PROVIDED AS REQUIRED BASED
ON ARRANGEMENT OF THE EQUIPMENTS.
3. BUILDING ORIENTATION TO SUIT SITE ACCESS ROADS.
4. DOORS ORIENTATION SHALL SUIT SITE REQUIREMENTS.
5. DOORS SHALL BE SIZED TO ENSURE EASY ACCESS AND
REMOVAL OF EQUIPMENT.

TO FLOOR LEVEL OF CONTROL ROOM


RAMP FROM GROUND LEVEL

CONTROL PANEL SOCKET


FIRE ALARM TELEPHONE
JUNCTION BOX
L&SP DB ETISALAT

W/P W/P
FACP F
EXIT

FE-1
FE-2
INSULATED COPPER FALL
SPLIT UNIT AIR CONDITIONER

SPLIT UNIT AIR CONDITIONER


CONDENSATE PIPE

VA

COMPRESSOR
LLE

SPLIT UNIT
Y
INSULATED COPPER
PFCC MCC CONDENSATE PIPE
JB
GENERATOR

COMPRESSOR
FALL

SPLIT UNIT
E

MCC ROOM

EXIT REFERENCE DRAWINGS AND DOCUMENTS

( PROVISIONAL )
LIGHTING DB
EXTERNAL

No. REV-1 APP'D 2020


GROUND FLOOR PLAN ROOF PLAN CLIENT

TITLE
STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

STANDARD DRAWING CONTROL


BUILDING LIGHTING AND SMALL
POWER LAYOUT

DRAWN - SCALE 1:50


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1215

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE
INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
CHECKED AND APPROVED AS PART OF THE PROJECT
DRAWING SET.
1. THIS DRAWING IS INDICATIVE ONLY.
2. TYPICAL CONNECTIVITY FOR ALL PUMPS AND MOTORISED
VALVES AND PENSTOCK
3. TYPICAL CONNECTIVITY FOR ALL PROXIMITY SWITCHES
4. REFER TO DRG. No.1301 FOR P&ID SYMBOLS AND LEGENDS.
5. ISOLATION PENSTOCK TO BE INSALLED INLINE OF MANHOLE
UPSTREAM INSIDE THE PUMPING STATION.

REFERENCE DRAWINGS AND DOCUMENTS

No. REV-1 APP'D 2020


CLIENT

TITLE
STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

STANDARD DRAWING PROPOSED


STORM WATER - POND
LIGHTING & FIRE ALARM AND
EARTHING
DRAWN - SCALE NTS
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1216

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.

1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE


STATED.
1000 CONTROL PANEL LENGTH VARIES (SEE NOTE) 1000 2. ADDITIONAL DUCTS FOR POWER SUPPLY OF OTHER
CONSUMERS (PUMPS, ETC.) INSIDE PUMPING STATION
1500 MAXIMUM 1500 MAXIMUM COMPOUND, SHALL BE PROVIDED AS REQUIRED BASED ON
OUTLINE OF CONTROL ARRANGEMENT OF THE EQUIPMENTS.
STEEL BEAMS TO BE BOLTED PANEL ABOVE TRENCH 3. BUILDING ORIENTATION TO SUIT SITE ACCESS ROADS.
AS NECESSARY FOR SUPPORT 600 TYPICAL CONTROL 4. DOORS ORIENTATION SHALL SUIT SITE REQUIREMENTS.
PANEL WIDTH
5. DOORS SHALL BE SIZED TO ENSURE EASY ACCESS AND
REMOVAL OF EQUIPMENT.
600

CHEQUER PLATE
FLOORING IN FRONT AND
TO SIDES OF PANEL
600

50

GALVANISED STEEL BEAMS TO CONTROL PANEL TO REST ON


50 WIDE x 20 DEEP RECESS FOR CHEQUER SUPPORT CONTROL PANEL SPACED CONCRETE & STEEL BEAMS
PLATE FLOORING WITH GALVANISED AT 1500 CENTRES
STEEL EDGING SET INTO CONCRETE

PLAN ON CONTROL PANEL TRENCH B


-

A/C A/C SPLIT UNIT AIR CONDITIONER


1000 VARIES 1000 1000 VARIES 1500

REFERENCE DRAWINGS AND DOCUMENTS


DB DB
EXTERNAL L&SP
LIGHTING CONTROL
VARIES

VARIES
CONTROL
PANEL PANEL

1006
1200
B- B-
300 300 300 300

GL GL GL GL

STEEL BEAMS TO BE BOLTED


750

AS NECESSARY FOR SUPPORT No. REV-1 APP'D 2020

150
CLIENT

150 150 150 150 TITLE


PVC-U SEALED DUCTS STANDARD DRAWINGS
FOR CABLES
STORM WATER WORKS
DRAWING TITLE

SECTION 1-1 - SECTION 2-2 - STANDARD DRAWING CONTROL


SHT-1211 SHT-1211
BUILDING PLAN, SECTION &
TRENCH DETAILS

DRAWN - SCALE 1:50


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No. 1217

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
1. THE FORM OF SEPARATION FOR THE MCC SHALL BE ASPER
THE SPECIFICATIONS.

VARIES VARIES

LIFTING ARRANGEMENT A

CABLE BOXES BUS BAR CHAMBER CABLE BOXES

OUTGOING FEEDER 1
KWH
METER
PUMP
STARTER 1
OUTGOING FEEDER 2

INSTRUMENTATION &
C C C C
CONTROLS
A A FEEDER FOR A A
B B CAPACITOR BANK B B
L L L L
METERING E E E E
VARIES

FEEDER FOR
LIGHTING AND POWER
DISTRIBUTION BOARD
PUMP
C STARTER 2 C C C
H H INTERNAL H H REFERENCE DRAWINGS AND DOCUMENTS
A A PANEL A A
SOCKETS
M M M M
MAIN INCOMER B B B B
E E E E
R R LIFTING DAVIT R R
PLC / RTU

SPARE
SUMP PUMP
STARTER
GENERATOR INCOMER
EXTERNAL LIGHTING
DISTRIBUTION BOARD

No. REV-1 APP'D 2020


CLIENT

A
TITLE
STANDARD DRAWINGS
STORM WATER WORKS
SECTION A-A DRAWING TITLE

STANDARD DRAWING MCC FOR SUB


SOIL DRAINAGE TYPICAL
ARRANGEMENT

DRAWN - SCALE N.T.S


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1218

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE
INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
CHECKED AND APPROVED AS PART OF THE PROJECT
DRAWING SET.
1. THE FORM OF SEPARATION FOR THE MCC SHALL BE AS
PER THE SPECIFICATIONS.

VARIES VARIES

LIFTING ARRANGEMENT A

CABLE BOXES BUS BAR CHAMBER CABLE BOXES

OUTGOING FEEDER 1
KWH
METER
PUMP
STARTER 1
OUTGOING FEEDER 2

INSTRUMENTATION &
C C C C
CONTROLS
A A FEEDER FOR A A
B B CAPACITOR BANK B B
L L L L
METERING E E E E
VARIES

FEEDER FOR
LIGHTING AND POWER
DISTRIBUTION BOARD
PUMP
C STARTER 2 C C C
H H INTERNAL H H
A A PANEL A A
SOCKETS REFERENCE DRAWINGS AND DOCUMENTS
M M M M
MAIN INCOMER B B B B
E E E E
R R LIFTING DAVIT R R
PLC / RTU

SPARE
SUMP PUMP
STARTER
SPARE
EXTERNAL LIGHTING
DISTRIBUTION BOARD

No. REV-1 APP'D 2020


CLIENT

TITLE
STANDARD DRAWINGS
SECTION A-A STORM WATER WORKS
DRAWING TITLE

STANDARD DRAWING MCC FOR


LIFTING STATION TYPICAL
ARRANGEMENT

DRAWN - SCALE N.T.S


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No. 1219

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
1. THE FORM OF SEPARATION FOR THE MCC SHALL BE AS PER
THE SPECIFICATIONS.

VARIES VARIES

LIFTING ARRANGEMENT A

CABLE BOXES BUS BAR CHAMBER CABLE BOXES

OUTGOING FEEDER 1
KWH
METER
PUMP
STARTER 1
OUTGOING FEEDER 2

INSTRUMENTATION &
C C C C
CONTROLS
A A FEEDER FOR A A
B B CAPACITOR BANK B B
L L L L
PUMP
METERING E STARTER 2 E E E
VARIES

FEEDER FOR
LIGHTING AND POWER
DISTRIBUTION BOARD

C C C C
H H INTERNAL H H
A A PANEL A A
SOCKETS
M M M M
PUMP REFERENCE DRAWINGS AND DOCUMENTS
MAIN INCOMER B STARTER 3 B B B
E E E E
R R LIFTING DAVIT R R
PLC / RTU

SPARE

SPARE SUMP PUMP


STARTER EXTERNAL LIGHTING
DISTRIBUTION BOARD

No. REV-1 APP'D 2020


CLIENT
A

TITLE
SECTION A-A STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

STANDARD DRAWING MCC FOR LIFTING


STATION (DRY WELL) TYPICAL
ARRANGEMENT

DRAWN - SCALE N.T.S


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1220

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
1. THE FORM OF SEPARATION FOR THE MCC SHALL BE
AS PER THE SPECIFICATIONS.

VARIES VARIES

LIFTING ARRANGEMENT A

CABLE BOXES BUS BAR CHAMBER CABLE BOXES

OUTGOING FEEDER 1
KWH
METER
PUMP
STARTER 1
OUTGOING FEEDER 2

INSTRUMENTATION &
C C C C
CONTROLS
A A FEEDER FOR A A
B B CAPACITOR BANK B B
L L L L
METERING E E E E
VARIES

FEEDER FOR
LIGHTING AND POWER
DISTRIBUTION BOARD
PUMP
C STARTER 2 C C C
H H INTERNAL H H
A A PANEL A A
SOCKETS
REFERENCE DRAWINGS AND DOCUMENTS
M M M M
MAIN INCOMER B B B B
E E E E
R R LIFTING DAVIT R R
PLC / RTU

SPARE
SUMP PUMP
STARTER
GENERATOR INCOMER
EXTERNAL LIGHTING
DISTRIBUTION BOARD

No. REV-1 APP'D 2020


CLIENT

TITLE
STANDARD DRAWINGS
SECTION A-A STORM WATER WORKS
DRAWING TITLE

STANDARD DRAWING MCC FOR


TRAFFIC UNDERPASS TYPICAL
ARRANGEMENT

DRAWN - SCALE N.T.S


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1221

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
1. THE FORM OF SEPARATION FOR THE MCC SHALL BE
AS PER THE SPECIFICATIONS.

VARIES VARIES

LIFTING ARRANGEMENT A

CABLE BOXES BUS BAR CHAMBER CABLE BOXES

OUTGOING FEEDER 1
KWH
METER
PUMP
STARTER 1
OUTGOING FEEDER 2

INSTRUMENTATION &
C C C CONTROLS
A A FEEDER FOR A
B B CAPACITOR BANK B
L L L
METERING E E E
VARIES

FEEDER FOR
LIGHTING AND POWER
DISTRIBUTION BOARD
PUMP
C STARTER 2 C C
H H INTERNAL H
A A PANEL A
M M
SOCKETS
M REFERENCE DRAWINGS AND DOCUMENTS
MAIN INCOMER B B B
E E E
SPARE
R R R
PLC / RTU

SPARE
SUMP PUMP
STARTER
GENERATOR INCOMER
EXTERNAL LIGHTING
DISTRIBUTION BOARD

No. REV-1 APP'D 2020


CLIENT
A

TITLE
SECTION A-A STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

STANDARD DRAWING MCC FOR


PEDESTRAIN UNDERPASS
TYPICAL ARRANGEMENT

DRAWN - SCALE N.T.S


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No. 1222

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
1. THE FORM OF SEPARATION FOR THE MCC SHALL BE
AS PER THE SPECIFICATIONS.

VARIES VARIES

LIFTING ARRANGEMENT A

CABLE BOXES BUS BAR CHAMBER CABLE BOXES

PUMP OUTGOING FEEDER 1


KWH
METER STARTER 1

OUTGOING FEEDER 2

INSTRUMENTATION &
C C C C
CONTROLS
A PUMP A FEEDER FOR A A
B STARTER 2 B B B
CAPACITOR BANK
L L L L
METERING E E E E
VARIES

FEEDER FOR
LIGHTING AND POWER
DISTRIBUTION BOARD
PUMP
C C C C
STARTER 3
H H INTERNAL H H
A A PANEL A A
M SOCKETS M
M M
MAIN INCOMER B B B B REFERENCE DRAWINGS AND DOCUMENTS
E E E E
R PUMP R LIFTING DAVIT R R
STARTER 4
PLC / RTU

SPARE

GENERATOR INCOMER
SUMP PUMP
STARTER EXTERNAL LIGHTING
DISTRIBUTION BOARD

No. REV-1 APP'D 2020


A
CLIENT

SECTION A-A TITLE


STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

STANDARD DRAWING MCC FOR


OUTFALL PUMPING STATION
TYPICAL ARRANGEMENT

DRAWN - SCALE N.T.S


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1223

THIRD EDITION - APRIL 2022


NOTES:

PIPING SYMBOLS PIPING SYMBOLS EQUIPMENT SYMBOLS TYPICAL INSTRUMENT SYMBOLS TANK SYMBOLS

PRIMARY PROCESS LINE


GATE SOCKET WELD VALVE LOCALLY MOUNTED

NORMALLY CLOSED VALVE PANEL MOUNTED IN CONTROL ROOM


X X CHEMICAL LINE

PIPE CAP COMPRESSOR MOUNTED IN LOCAL PANEL


GATE VALVE, GENERAL SYMBOL

BALL VALVE LINE SIZE CHANGE


HAND PUMP
CHECK VALVE
STRAIGHTENING VANES

BUTTERFLY VALVE FI
VARIABLE AREA METER
FLAME ARRESTER
NEEDLE VALVE
SP
SPADE FI
PLUG VALVE

GLOBE VALVE TURBINE METER

I UNDEFINED INTERLOCK LOGIC


PISTON VALVE
M

Y-TYPE VALVE
ISOLATING JOINT MOTOR DRIVEN SUBMERSIBLE PUMP ELECTRIC SIGNAL
I.J.
DIAPHRAGM VALVE
// // // PNEUMATIC SIGNAL / AIR LINE
BLIND FLANGE

THREE WAY VALVE L L L HYDRAULIC SIGNAL / LINE


TUNDISH FAN
AV AIR RELEASE VALVE CONNECTION TO PROCESS
RO

ELECTRICAL MOTOR SYSTEM LINK/SOFTWARE SIGNAL


RESTRICTION ORIFICE
(SOFTWARE OR DATA LINK)

FO

ORIFICE FLOW ELEMENT


M MOTOR (PROCESS)
ABBREVIATIONS
DOUBLE B&B VALVE
CS COMMON STOP
D1 DUTY 1
M VFD DRIVEN MOTOR
D2 DUTY 2
ORIFICE PLATE
D3 DUTY 3
E/H D4 DUTY 4
ELECTROMAGNETIC FLOWMETER
TS
TEMPORARY STRAINER
CODINGS FOR TYPICAL INSTRUMENT FUNCTIONS
H

VENT TO ATMOSPHERE LEVEL ELECTRODE (3 PROBES)

SOLENOID OPERATED VALVE 3A1 3A1 SPECIFICATION CHANGE


ULTRASONIC LEVEL MEASUREMENT
A ANALYSIS ALARM
M
MOTORISED VALVE (ELECTRIC)
B BURNER, COMBUSTION USER'S CHOICE USER'S CHOICE REFERENCE DRAWINGS AND DOCUMENTS
Y-TYPE STRAINER
C CONDUCTIVITY CONTROL

SUBMERSIBLE PUMP D DENSITY DIFFERENTIAL


CONICAL ON-LINE STRAINER SENSOR (PRIMARY
SELF-ACTING CONTROL VALVE E VOLTAGE
ELEMENT)
F FLOW RATE RATIO (FRACTION
SPECIAL STRAINER CRANE G GAUGE GLASS, VIEWING DEVICE
HAND (MANUALLY
H HIGH
FLANGED JOINT M INITIATED)
TO RESERVOIR
I CURRENT (ELECTRICAL) INDICATE
ALTITUDE VALVE EXPANSION/FLEXIBLE JOINT J POWER SCAN
TIME RATE OR
D K TIME OR TIME SCHEDULE CONTROL STATION
DIESEL ENGINE CHANGE
CONTROL VALVE WITH HANDWHEEL SIPHON DRAIN
L LEVEL LIGHT (PILOT) LOW
MOISTURE HUMIDITY MIDDLE OR
M MOMENTARY
MOTOR . INTERMEDIATE No. REV-1 APP'D 2020
FLOAT VALVE BASKET STRAINER
PENSTOCK N USER'S CHOICE USER'S CHOICE USER'S CHOICE USER'S CHOICE CLIENT
M
O USER'S CHOICE
CONTROL VALVE (ELECTRIC) DAMPER
P PRESSURE OR VACUUM
INTGRATE OR
Q QUANTITY
TRASH RACK TOTALIZE
FAN TITLE
R RADIATION
STANDARD DRAWINGS
S SPEED, FREQUENCY SAFETY SWITCH
STORM WATER WORKS
LOUVRE T TEMPREATURE TRANSMITTER
U MULTIVARIABLE MULTIFUNCTION MULTIFUNCTION MULTIFUNCTION DRAWING TITLE
VIBRATION, MECH. VALVE, DAMPER OR
V
ANALYSIS LOUVRE
FLAP VALE W WEIGHT OR FORCE WELL
STANDARD DRAWING P&ID LEGEND
X UNCLASSIFIED X AXIS UNCLASSIFIED UNCLASSIFIED UNCLASSIFIED & SYMBOLS
EVENT, STATE OR RELAY, COMPUTE OR
Y Y AXIS
PRESENCE . CONVERT
DRIVER, ACTUATOR OR
POSITION, DIMENSION Z AXIS . UNCLASSIFIED FINAL
DRAWN - SCALE NTS
. CONTROL ELEMENT CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1301

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.

1. THIS DRAWING IS INDICATIVE ONLY.


M.C.C ROOM 2. TYPICAL CONNECTIVITY FOR ALL PUMPS AND MOTORISED
AIR CONDITION VALVES AND PENSTOCK
3. TYPICAL CONNECTIVITY FOR ALL PROXIMITY SWITCHES
SUPPLY FAN EXHAUST FAN
4. REFER TO DRG. NO.1301 FOR P&ID SYMBOLS AND LEGENDS.
TI FIRE ALARM PANEL OA OA 5.
LT FAULT FAULT
XX
II II
RUN/STOP RUN/STOP

II II
M.C.C PANEL AVAILABLE AVAILABLE

YI YI
RUN/STOP RUN/STOP

RTU/PLC

FAN

NOTE 5

LAH LA1

LAL LAS LALL LS LSL LSH LSH LSH LAH LAHH

LT LI LSLL LS LS LS LS LS LS LSHH
XX XX XX XX XX XX XX XX XX

HH

H
D4
D3

D2
D1
PENSTOCK CS
LL

TRASH RACK
REFERENCE DRAWINGS AND DOCUMENTS
WSH: TORQUE SWITCH ALARM
ZSH: PENSTOCK OPENED YC WAH YI ZY
ZSL: PENSTOCK CLOSED
ZE: PENSTOCK POSITION

I I I ZIC

WSH ZSH ZSL ZE

LOCAL CONTROL PANEL PLC/RTU PANEL


M M M

No. REV-1 APP'D 2020


CLIENT

PENSTOCK

TITLE
STANDARD DRAWINGS
PUMPING STATION VALVE CHAMBER
STORM WATER WORKS
DRAWING TITLE

STANDARD DRAWING
PROPOSED STORM WATER
UNDERPASS
P&ID
DRAWN - SCALE NTS
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1302

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
1. THIS DRAWING IS INDICATIVE ONLY.
2. TYPICAL CONNECTIVITY FOR ALL PUMPS AND MOTORISED
VALVES AND PENSTOCK
3. TYPICAL CONNECTIVITY FOR ALL PROXIMITY SWITCHES
4. REFER TO DRG. No.1301 FOR P&ID SYMBOLS AND LEGENDS.
5. ISOLATION PENSTOCK TO BE INSALLED INLINE OF MANHOLE
UPSTREAM INSIDE THE PUMPING STATION.

RTU/PLC

PT
XX

PI
XX
H

NOTE 2
OA HS
FAULT

LAH LA1 II AUTORUN


AVAILABLE
HA
LAL LAS LALL LS LSL LSH LAH LAHH YI HS
RUNNING

PI
XX
LT LI LSLL LS LS LS LS LSHH H
XX I
XX XX XX XX XX XX
WSH: TORQUE SWITCH ALARM
REFERENCE DRAWINGS AND DOCUMENTS
ZSH: PENSTOCK OPENED YC WAH YI ZY TIC
ZSL: PENSTOCK CLOSED
ZE: PENSTOCK POSITION

HH
TE TE TE
I I I ZIC LAL LAH
H LOCAL CONTROL PANEL
ZSL
M
WSH ZSH ZE

D2 LSL LSH
XX XX
PLC/RTU PANEL D1
LOCAL CONTROL PANEL
CS
TRASH RACK
LL H

L
No. REV-1 APP'D 2020
PENSTOCK CLIENT

PUMPING STATION VALVE CHAMBER

TITLE
STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

STANDRAD DRAWING
PROPOSED STORMWATER
SUBSOIL P&ID

DRAWN - SCALE NTS


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1303

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT
AND MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT
PROJECT REQUIREMENTS. THEY ARE EXPECTED TO BE
INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
CHECKED AND APPROVED AS PART OF THE PROJECT
DRAWING SET.
1. THIS DRAWING IS INDICATIVE ONLY.
2. TYPICAL CONNECTIVITY FOR ALL PUMPS AND MOTORISED
VALVES AND PENSTOCK
3. TYPICAL CONNECTIVITY FOR ALL PROXIMITY SWITCHES
4. REFER TO DRG. No.1301 FOR P&ID SYMBOLS AND LEGENDS.
5. ISOLATION PENSTOCK TO BE INSALLED INLINE OF MANHOLE
UPSTREAM INSIDE THE PUMPING STATION.

RTU/PLC

PT
XX

PI
XX
H

NOTE 2

FAULT OA HS

LAH LA1 II AUTORUN


AVAILABLE
HA
LAL LAS LALL LS LSL LSH LAH LAHH YI HS
RUNNING

PI
XX
LT LI LSLL LS LS LS LS LSHH H
XX I
XX XX XX XX XX XX
WSH: TORQUE SWITCH ALARM
ZSH: PENSTOCK OPENED YC WAH YI ZY TIC
ZSL: PENSTOCK CLOSED
ZE: PENSTOCK POSITION REFERENCE DRAWINGS AND DOCUMENTS

HH TE TE TE
I I I ZIC LAL LAH
H LOCAL CONTROL PANEL
ZSL
M
WSH ZSH ZE

D2 LSL LSH
XX XX
PLC/RTU PANEL D1
LOCAL CONTROL PANEL
CS
TRASH RACK
LL H
L

PENSTOCK
No. REV-1 APP'D 2020
PUMPING STATION VALVE CHAMBER CLIENT

TITLE
STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

STANDRAD DRAWING PROPOSED


STORMWATER LIFTING STATION
(WET WELL) P&ID

DRAWN - SCALE NTS


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1304

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE
INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
CHECKED AND APPROVED AS PART OF THE PROJECT
DRAWING SET.
1. THIS DRAWING IS INDICATIVE ONLY.
2. TYPICAL CONNECTIVITY FOR ALL PUMPS AND MOTORISED
VALVES AND PENSTOCK
3. TYPICAL CONNECTIVITY FOR ALL PROXIMITY SWITCHES
4. REFER TO DRG. No.1301 FOR P&ID SYMBOLS AND LEGENDS.
5. ISOLATION PENSTOCK TO BE INSALLED INLINE OF MANHOLE
UPSTREAM INSIDE THE PUMPING STATION.

RTU/PLC

NOTE 2
FAULT OA HS

II AUTORUN
AVAILABLE
HA
YI HS
RUNNING
I

TIC

TE TE TE

LOCAL CONTROL PANEL H


M

PI PI
XX XX
H H

PT
XX

LAH LA1 PI PI
XX XX
H H
LAL LAS LALL LS LSL LSH LSH LAH LAHH

WSH: TORQUE SWITCH ALARM LT LI LSLL LS LS LS LS LS LSHH PI PI


XX XX XX XX XX XX XX XX XX XX
ZSH: H H
PENSTOCK OPENED YC WAH YI ZY
REFERENCE DRAWINGS AND DOCUMENTS
ZSL: PENSTOCK CLOSED
ZE: PENSTOCK POSITION

I I I ZIC LAL LAH


HH

WSH ZSH ZSL ZE H

D3 LSL LSH
XX XX
PLC/RTU PANEL
D2
LOCAL CONTROL PANEL
D1
TRASH RACK
CS H
LL L
No. REV-1 APP'D 2020
PENSTOCK CLIENT

WET WELL VALVE CHAMBER

TITLE
PUMPING STATION STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE
STANDARD DRAWING
PROPOSED STORMWATER
LIFTING STATION (DRY WELL)
P&ID
DRAWN - SCALE NTS
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1305

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT
AND MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT
PROJECT REQUIREMENTS. THEY ARE EXPECTED TO BE
INCORPORATED AS TYPICAL DETAILS WHICH SHALL BE
CHECKED AND APPROVED AS PART OF THE PROJECT
DRAWING SET.

1. THIS DRAWING IS INDICATIVE ONLY.


2. TYPICAL CONNECTIVITY FOR ALL PUMPS AND MOTORISED
VALVES AND PENSTOCK
3. TYPICAL CONNECTIVITY FOR ALL PROXIMITY SWITCHES
4. REFER TO DRG. No.1301 FOR P&ID SYMBOLS AND LEGENDS.
5. ISOLATION PENSTOCK TO BE INSALLED INLINE OF MANHOLE
UPSTREAM INSIDE THE PUMPING STATION.

RTU/PLC

PT
XX

PI
XX
H

NOTE 2
FAULT OA HS

LAH LA1 II AUTORUN


AVAILABLE
HA
LAL LAS LALL LS LSL LSH LAH LAHH YI HS
RUNNING

PI
XX
WSH: TORQUE SWITCH ALARM LT LI LSLL LS LS LS LS LSHH I H
XX XX XX XX XX XX XX
ZSH: PENSTOCK OPENED YC WAH YI ZY
ZSL: PENSTOCK CLOSED TIC
ZE: PENSTOCK POSITION REFERENCE DRAWINGS AND DOCUMENTS

I I I ZIC TE TE TE
LAL LAH
HH

WSH ZSH ZSL ZE LOCAL CONTROL PANEL


H M
LSL LSH
XX XX
PLC/RTU PANEL
D2
LOCAL CONTROL PANEL
D1
TRASH RACK
CS H

LL L

No. REV-1 APP'D 2020


PENSTOCK
CLIENT

PUMPING STATION VALVE CHAMBER

TITLE
STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

STANDARD DRAWING
PROPOSED STORMWATER
PEDESTRIAN UNDERPASS
P&ID
DRAWN - SCALE NTS
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1306

THIRD EDITION - APRIL 2022


NOTES:

LT TI
XX

RTU/PLC

OA HS

LAH LA1
II

LAL LAS LALL LS LSL LSH LSH LSH LAH LAHH


YI HS

LSHH I
LI XX
LT LSLL LS LS LS LS LS LS
XX XX XX XX XX XX XX XX
TIC

TE TE TE LAH LAL

M
LSH LSL
XX XX

REFERENCE DRAWINGS AND DOCUMENTS

WSH: TORQUE SWITCH ALARM


ZSH: PENSTOCK OPENED YC WAH YI ZY
ZSL: PENSTOCK CLOSED
ZE: PENSTOCK POSITION
PI
XX
I I I ZIC
PT
XX
WSH ZSH ZSL ZE

PI
XX

M No. REV-1 APP'D 2020


CLIENT

TITLE
STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

OUTFALL

DRAWN - SCALE
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS. THEY ARE EXPECTED TO BE INCORPORATED
AS TYPICAL DETAILS WHICH SHALL BE CHECKED AND
APPROVED AS PART OF THE PROJECT DRAWING SET.
1. THIS DRAWING IS INDICATIVE ONLY.
2. TYPICAL CONNECTIVITY FOR ALL PUMPS AND MOTORISED
VALVES AND PENSTOCK
3. TYPICAL CONNECTIVITY FOR ALL PROXIMITY SWITCHES
4. REFER TO DRG. No.1301 FOR P&ID SYMBOLS AND LEGENDS.
5. ISOLATION PENSTOCK TO BE INSALLED INLINE OF MANHOLE
RTU/PLC UPSTREAM INSIDE THE PUMPING STATION.

LAH

LIT LIT LAH


ULTRASONIC
SLUDGE
LAYER
SENSOR
LT LT LSH
XX XX XX

CAPACITIVE
OIL LAYER H
THICKNESS
SENSOR

REFERENCE DRAWINGS AND DOCUMENTS

No. REV-1 APP'D 2020


CLIENT

TITLE
STANDARD DRAWINGS
STORM WATER WORKS
SLUDGE TRAP OIL INTERCEPTOR DRAWING TITLE

STANDARD DRAWING OIL


SEPARATOR P&ID

DRAWN - SCALE NTS


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
1308

THIRD EDITION - APRIL 2022


NOTES:

- The actuator of the penstock will be integrated to the


Stormwater Central SCADA
- The integration will be achieved through GSM based
communication with aid of an RTU installed in a KIOSK
beside the pond/Geocell location.
- Actuators shall have local control and remote control.
- Open/Close Push buttons and feedback signals shall be
installed inside the RTU/ control panel.
- The Control Cabinet will be powered from a nearest ADDC
feeder pillar/Service turret but will have battery back up.
- The Control unit of the interceptor shall be integrated to the
Central SCADA through the Local Control Kiosk.
- Level transmitters shall be installed to monitor the water
level and the Penstock operation (Open/Close) shall be
automated based on the levels.
- Level Switches shall be provided as backup to the level
transmitters.

RTU/PLC

AAH AA1 LAH LA1


WSH: TORQUE SWITCH ALARM
AAL AAS LAL LAS ZSO: PENSTOCK OPENED YC WAH YI ZY
ZSC: PENSTOCK CLOSED
ZE: PENSTOCK POSITION
LALL LSL LS1 LS2 LS3 LAH LAHH
AT AI LT LI
XX XX
I I I ZIC

LSLL LSL LS LS LS LSH LSHH WSH ZSO ZSC ZE


XX XX XX XX XX XX XX

REFERENCE DRAWINGS AND DOCUMENTS

No. REV-1 APP'D 2020


CLIENT

TITLE
STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

STANDARD DRAWING
POND SURFACE AERATOR
P&ID

DRAWN - SCALE
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.

THIRD EDITION - APRIL 2022


NOTES:

RTU/PLC

WSH: TORQUE SWITCH ALARM


ZSH: PENSTOCK OPENED YC WAH YI ZY
LAH LA1 ZSL: PENSTOCK CLOSED
ZE: PENSTOCK POSITION
LAL LAS

I I I ZIC
LALL LAHH
LT LI
XX WSH ZSO ZSC ZE

LSLL LSHH
XX XX PLC/RTU PANEL
LOCAL CONTROL PANEL M

REFERENCE DRAWINGS AND DOCUMENTS

PENSTOCK MOTORIZED PENSTOCK

No. REV-1 APP'D 2020


CLIENT

TITLE
STANDARD DRAWINGS
STORM WATER WORKS
DRAWING TITLE

STANDARD DRAWING
TEMPORARY FLOOD STORAGE PONDS
P&ID

DRAWN - SCALE
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.

THIRD EDITION - APRIL 2022


NOTES:

1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE


INDICATED.

2. ALL COVER SLAB TO BE 250mm THICK.


600 x 750 CLEAR OPENING
COVER & FRAME 3. NUMBER OF INCOMING PIPES & DIA. VARIES FROM c1 TO c3.

PAVED 4. WHERE PIPES ARE BUILT INTO STRUCTURES OR


600 x 750 CLEAR OPENING
COVER & FRAME MANHOLES, THE FLEXIBLE JOINTS SHALL BE POSITIONED

150
CHAMFER 20x20 FROM OUTSIDE OF THE STURCTURE THUS UNLESS
UNPAVED OTHERWISE RECOMMENDED BY THE MANUFACTURER.
PAVED CHAMFER 20x20
UNPAVED

250
FLEXIBLEJOINT
D D
PIPEDIA. 1sTFLEXIBLEJOINT 2ndFLEXIBLEJOINT

UPTO300 150MAX. 500MAX.FROM 1STJOINT

OVER300UPTO 600 300MAX. 2xPIPEDIA.MAXFROM1stJOINT


MANHOLE COVER & FRAME
OVER600 600MAX. 1200MAX.FROM1STJOINT
BRUSH APPLIED WATER PROOF
TO SPECIFICATION
h a h
5. DIA. OF PIPES ARE GIVEN THE NOMINAL DIAMETER.
d

6. EXTERNAL SURFACE OF MANHOLE SHALL BE PROTECTED


CONCRETE CLASS 20 20 BENCHING MANHOLE WALL WITH BRUSH APPLIED A PAINT SYSTEM TO THE
FALL 1 IN 6 TOWARDS CENTER OF MANHOLE
SPECIFICATION.
100 FLEXIBLE JOINTS
B MIN. B
7. ALL CONCRETE TO BE CLASS 40 20 UNLESS OTHERWISE
STATED.

8. PROPER CONSTRUCTION JOINTS REQUIRED FOR

750
DIFFERENT STAGE OF CONCRETING SHALL BE PROVIDED
c c2 ‫رات أ ي صا ص فيرصت‬ TO ENGINEER'S APPROVAL.
STORM WATER
75

9. STEEL REINFORCEMENT TO BE GRADE 460 (BS4449).


YEAR
g

10. MINIMUM COVER TO CONCRETE REINFORCEMENT TO BE


50mm.
75

Y8 AT 200 C/C IN BOTH DIRECTION 11. IN CASE OF HIGH WATER TABLE, THE WATER PROOFING
100 750 X 600 DUCTILE MEMBRANE WITH 25mm SCREED SHALL BE USED ON TOP
CONCRETE BLINDING CLASS 15/20 PIPE BEDDING AS SPECIFIED
BS EN 124 D400 OF THE CONCRETE BLINDING OF BASE SLAB.

SECTION A-A MANHOLE BASE

PIPE CONNECTION 150 300 150


600
AACM - DRAWINGS

c2
REFERENCE DRAWINGS AND DOCUMENTS

Y12 T&B TRIMMING BARS Y16-150 C/C T&B

TABLE 1 - DETAILS OF STORM-WATER DRAINAGE MANHOLE


A c c2 A CIRCULAR BAR
600 x 750
Y8 T&B No. REVISION-2 APP'D 2021
OPENING
MAX. DIA. OF OUT MAX. DEPTH FROM CLIENT
Y12 T&B INNER DIA. BASE SLAB
MANHOLE TYPE GOING PIPE COVER SLAB TO WALL TH. mm
TRIMMING BARS mm THICKNESS mm
mm INVERT LEVEL mm

a c d g h

TITLE
A 1000 350 3000 250 225 STANDARD DRAWINGS
B 1200 450 3500 250 225
AL AIN REGION
DRAWING TITLE
C 1400 600 3500 250 250

SURFACE DRAINAGE
c3 D 1600 800 3500 300 300
h a h MANHOLE DETAILS
E 1800 1000 3500 350 350 (SHEET 1 OF 2)
PLAN AT B-B COVER SLAB PLAN AT D-D
F 2000 1200 4000 400 350
DRAWN - SCALE N.T.S. @ A1
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
N-223

THIRD EDITION - APRIL 2022


NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
600 x 750 CLEAR OPENING INDICATED.
COVER & FRAME MANHOLE WALL
2. ALL COVER SLAB TO BE 250mm THICK.
PAVED FLEXIBLE JOINTS
TRIMMING BARS Y10 T&B 3. NUMBER OF INCOMING PIPES & DIA. VARIES FROM c1 TO c3.
UNPAVED CHAMFER 20x20

250
D D 4. WHERE PIPES ARE BUILT INTO STRUCTURES OR
600 x 750 MANHOLES, THE FLEXIBLE JOINTS SHALL BE POSITIONED
CIRCULAR BAR Y8 T&B OPENING
FROM OUTSIDE OF THE STURCTURE THUS UNLESS
OTHERWISE RECOMMENDED BY THE MANUFACTURER.

FLEXIBLEJOINT

PIPEDIA. 1sTFLEXIBLEJOINT 2ndFLEXIBLEJOINT


Y16 T&B AT 150 C/C
UPTO300 150MAX. 500MAX.FROM 1STJOINT
f

OVER300UPTO 600 300MAX. 2xPIPEDIA.MAXFROM1stJOINT

b PIPE BEDDING AS SPECIFIED OVER600 600MAX. 1200MAX.FROM1STJOINT


i i

i b i MANHOLE BASE

5. DIA. OF PIPES ARE GIVEN THE NOMINAL DIAMETER.


COVER SLAB PLAN AT D-D PIPE CONNECTION
6. EXTERNAL SURFACE OF MANHOLE SHALL BE PROTECTED
CHAMFER 20x20 WITH BRUSH APPLIED A PAINT SYSTEM TO THE
d

SPECIFICATION.
C C
j

7. ALL CONCRETE TO BE CLASS 40 20 UNLESS OTHERWISE


STATED.

h a h 8. PROPER CONSTRUCTION JOINTS REQUIRED FOR


BRUSH APPLIED WATER PROOF DIFFERENT STAGE OF CONCRETING SHALL BE PROVIDED
TO SPECIFICATION TO ENGINEER'S APPROVAL.
Y12 T&B
TRIMMING BARS Y16-150 C/C T&B 9. STEEL REINFORCEMENT TO BE GRADE 460 (BS4449).
CONCRETE CLASS 20 20 BENCHING
FALL 1 IN 6 TOWARDS CENTER OF MANHOLE Y12 T&B TRIMMING BARS 10. MINIMUM COVER TO CONCRETE REINFORCEMENT TO BE
e

50mm.
100
B MIN. B
11. IN CASE OF HIGH WATER TABLE, THE WATER PROOFING
MEMBRANE WITH 25mm SCREED SHALL BE USED ON TOP
b OF THE CONCRETE BLINDING OF BASE SLAB.

c c2
75

CIRCULAR BAR
Y8 T&B
g

750
Y8 AT 200 C/C IN BOTH DIRECTION
‫رات أ ي صا ص فيرصت‬ AACM - DRAWINGS
75

100 CONCRETE BLINDING CLASS 15 20


STORM WATER
SECTION A-A REDUCER SLAB PLAN AT C-C YEAR REFERENCE DRAWINGS AND DOCUMENTS

c2 600 x 750 CLEAR OPENING


COVER & FRAME 750 X 600 DUCTILE
BS EN 124 D400
PAVED
150

CHAMFER 20x20
UNPAVED

150 300 150


600

No. REVISION-2 APP'D 2021


MANHOLE COVER & FRAME CLIENT
A c c2 A

TABLE 1 - DETAILS OF STORM-WATER DRAINAGE MANHOLE TITLE


STANDARD DRAWINGS
MAX. DIA. OF MAX. DEPTH FROM MIN. DEPTH OF MIN. DEPTH OF LOWER SHAFT UPPER SHAFT
AL AIN REGION
LOWER SHAFT UPPER SHAFT DIA. BASE SLAB REDUCER SLAB
MANHOLE TYPE OUTGOING PIPE COVER SLAB TO LOWER SHAFT UPPER SHAFT WALL WALL
DIA. mm mm THICKNESS mm THICKNESS mm
mm INVERT LEVEL mm mm mm THIICKNESS mm THIICKNESS mm DRAWING TITLE

a b c d e f g h i j SURFACE DRAINAGE
MANHOLE DETAILS
G 1400 1000 600 5500 2100 600 300 300 200 300
(SHEET 2 OF 2)
c3
H 1600 1000 800 5500 2100 600 300 300 200 300
h a h
DRAWN - SCALE N.T.S. @ A1
I 1800 1000 1000 7500 2400 600 350 350 200 300
PLAN AT B-B CHECKED - DATE -
J 2000 1000 1200 8000 2600 600 400 350 200 300 APPROVED - SIZE A1
PROJECT DWG.
No. - No.
N-224

THIRD EDITION - APRIL 2022


NOTES:
1. MINIMUM TRENCH WIDTH 'A' SHOULD BE:

· OD+0.6m FOR PIPES OF NOMINAL DIAMETERS UP TO


FGL FGL
600mm
PAVEMENT LAYERS · OD+0.8m FOR PIPES OF NOMINAL DIAMETERS 700mm

DEPTH 600mm OR 900mm


(PAVEMENT SUB GRADE) AND ABOVE
TYPE C COMPACTED TO 95% MDD SELECTED EXCAVATED MATERIAL
WITH PI ≤ 6% COMPACTED 2. TO AVOID CONCRETE PROTECTION THE CROWN OF PIPE

(SEE NOTE-6)
FGL IN LAYERS TO 90% MDD SHOULD BE MINIMUM 1.2m FROM THE FINISHED ROAD
(UNLESS OTHERWISE INSTRUCTED LEVEL (UNLESS INSTRUCTED OTHERWISE)
PAVEMENT LAYERS
BY THE CLIENT/ENGINEER)
(PAVEMENT SUB GRADE) 3. THE ENGINEER'S/CLIENT'S PRIOR APPROVAL SHALL BE
TYPE B FILL COMPACTED TO 95% MDD TAKEN BY THE CONTRACTOR FOR THE PIPE PROTECTION
TYPE C COMPACTED TO 95% MDD
AND SPECIFIC BACKFILLING AS REQUIRED.

8.00m>H>1.2m

8.00m>H>1.2m
SELECTED EXACATED MATERIAL 4. THE REQUIRED COMPACTION OF DUNE SAND USED FOR
WITH ≤6% COMPACTED BEDDING & SURROUND OF PIPES SHALL BE ACHIEVED WITH
IN LAYERS TO 90% MDD HYDRAULIC COMPACTION BY FLOODING WITH WATER.

VARIES
H<1.2
5. THE SELECTED EXCAVATED MATERIAL, ACCEPTED FOR
TYPE B FILL COMPACTED TRENCH BACKFILL, SHALL BE LAID IN SPECIFIED LAYERED
TO 95% MDD THICKNESS AND COMPACTED TO 90% OF ITS MDD.

6. THE TYPE-B MATERIAL (IMPORTED OR AVAILABLE FROM


TRENCH EXCAVATION) FOR TRENCH BACKFILL UP TO
BOTTOM LEVEL OF PAVEMENT SUB-GRADE SHALL BE LAID

300

300
IN 150mm THICK LAYERS AND COMPACTED TO 95% OF ITS
MDD FOR THE BELOW GIVEN DEPTHS:

150
DUNE SAND COMPACTED BY
FLOODING WITH WATER DUNE SAND COMPACTED BY DUNE SAND COMPACTED BY · 900mm FROM THE TOP LEVEL OF PAVEMENT SUB-GRADE
FLOODING WITH WATER FLOODING WITH WATER FOR TRENCHES UNDER EXISTING ROADS. FOOTHPATHS,
SHOULDERS AND VERGES.

DIA

DIA

DIA
uPVC/GRP PIPE uPVC/GRP PIPE uPVC/GRP PIPE · 600mm FROM THE TOP LEVEL OF PAVEMENT SUB-GRADE
FOR TRENCHES UNDER THE PROPOSED NEW ROADS,
150mm CONCRETE
FOOTHPATHS, SHOULDERS & VERGES.
CLASS 20 20 SURROUND
150

150

150
7. THE BACKFILL & BEDDING SHOWN IN THIS DRAWING IS
COMMONLY USED IN AL AIN CITY.
'A' 'A' 'A'
(SEE NOTE-1) (SEE NOTE-1) (SEE NOTE-1)

UNDER ROAD INCLUDING UNDER ROAD INCLUDING OUTSIDE ROAD F.G.L FINISHED GROUND LEVEL

FOOTPATH / SHOULDER & VERGE FOOTPATH / SHOULDER & VERGE DRY TRENCH
DETAIL - 1 DETAIL - 2 DETAIL - 3

FGL FGL FGL FGL


PAVEMENT LAYERS
SELECTED EXCAVATED TYPE C COMPACTED TO 95% MDD
MATERIAL
WITH PI ≤ 6% COMPACTED
(PAVEMENT SUB GRADE)
AACM - DRAWINGS
SELECTED EXCAVATED

DEPTH 600mm OR 900mm


IN LAYERS TO 90% MDD
(UNLESS OTHERWISE SELECTED EXCAVATED MATERIAL COMPACTED
INSTRUCTED BY THE MATERIAL COMPACTED IN IN LAYERS TO 90%

(SEE NOTE-6)
TYPE B FILL COMPACTED
LAYERS TO 90% MDD MDD (UNLESS OTHERWISE REFERENCE DRAWINGS AND DOCUMENTS
CLIENT/ENGINEER) TO 95% MDD
(UNLESS OTHERWISE INSTRUCTED BY THE
INSTRUCTED BY THE CLIENT/ENGINEER
CLIENT/ENGINEER)
SELECTED EXCAVATED

H
8.00m>H>1.2m

MATERIAL WITH PI ≤ 6
H>8.00m

COMPACTED IN

H
LAYERS TO 90% MDD
(UNLESS OTHERWISE
INSTRUCTED BY THE
CLIENT/ENGINEER

VARIES
DUNE SAND UP TO 300mm
ABOVE W.T. AND
COMPACTED No. REVISION-1 APP'D 2020
BY FLOODING WITH WATER
CLIENT

300

300
WATER TABLE LEVEL DUNE SAND
DUNE SAND COMPACTED BY DUNE SAND COMPACTED BY
150

150

COMPACTED BY FLOODING WITH FLOODING WITH WATER


GEO TEXTILE FABRIC FLOODING WITH WATER
3
AGGREGATE WATER TITLE
8
STANDARD DRAWINGS
DIA

DIA

DIA

DIA
uPVC/GRP PIPE uPVC/GRP PIPE
RC PIPE RC PIPE
AL AIN REGION
150mm CONCRETE
3
CLASS 20 20 SURROUND AGGREGATE
4 3 DRAWING TITLE
AGGREGATE COMPACTED
150

150

150

150
4
COMPACTED
IN 150mm LAYERS
IN 150mm LAYERS
'A' 'A' 'A' 'A' SURFACE DRAINAGE
(SEE NOTE-1) (SEE NOTE-1) (SEE NOTE-1) (SEE NOTE-1) TRENCH BACKFILL DETAILS FOR
OUTSIDE ROAD OUTSIDE ROAD UNDER ROAD INCLUDING OUTSIDE ROAD
DIFFERENT DEPTH OF PIPES
WET TRENCH CONCRETE SURROUND FOOTHPATH & VERGE/SHOULDER RC PIPE BED AND SURROUND
DRAWN - SCALE N.T.S
DETAIL - 4 DETAIL - 5 DETAIL - 6 DETAIL - 7
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
N-225
THIRD EDITION - APRIL 2022
NOTES:
TYPE-1
1. ALL DIMENSIONS ARE IN MILLIMETERS, UNLESS OTHERWISE
INLET COLLECTOR 300mm (MIN.) 1. INLET CONNECTIONS SHALL BE INSTALLED IN STRAIGHT ALIGNMENT ON A SPECIFIED.
MINIMUM UNIFORM SLOPE OF 1 PERCENT.
CORRIDOR 7.0m 2. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL
INLET INLET INLET INLET 2. MAXIMUM NUMBER OF INLETS CONNECTED TO MANHOLE IS FOUR. BE IN ACCORDANCE WITH THE SPECIFICATIONS AND
PARKING 2.5m VERIFIED BY ENGINEER.
MAIN DRAINAGE LINE MH2 MAIN DRAINAGE LINE MH1 MAIN DRAINAGE LINE 3. MAXIMUM LENGTH OF INLET CONNECTION DRAINS IS 35m.
TRAVEL 6.8m
3. IF THERE IS A DISCREPANCY BETWEEN THE REQUIREMENTS
4. PROPOSED STORM WATER DRAINAGE PIPE LINES AND MANHOLES SHALL IN THE SPECIFICATIONS AND THOSE SHOWN ON THIS
5.0m DIAMETER VARIES DIAMETER VARIES DIAMETER VARIES
MEDIAN FOLLOW THE PROPOSED INFRASTRUCTURE FRAMEWORK PLAN AND UTILITY
DRAWING, THE SPECIFICATIONS SHALL BE FOLLOWED.
CORRIDORS MANUAL.
TRAVEL 6.8m 4. FOR PIPE TRENCH BEDDING AND PROTECTION DETAILS
5. THIS TYPE OF DRAINAGE NETWORK IS COMMONLY USED IN AREAS WITH LOW
PARKING IMPACT OF SANDSTORMS AND LOW GROUND WATER LEVEL SUCH AS AL AIN REFER TO DWG. No. N-215.
2.5m
CITY, OR AS DIRECTED BY THE ENGINEER.
INLET INLET INLET INLET
CORRIDOR 6.7m 5. PIPE MATERIAL COMMONLY USED IN ABU DHABI IS AS
FOLLOWS;
INLET COLLECTOR FOR DIA ≤500 USE uPVC OR GRP
INLETS CONNECTED TO MAIN DRAIN WITH MANHOLE 300mm (MIN.)
TYPE-1 FOR DIA >500 USE RC

6. THE PIPE MATERIAL SHALL BE SPECIFIED OR AS DIRECTED


BY THE ENGINEERS ON SITE.
INLET
400mm INLET
COLLECTOR
COLLECTOR
300mm (MIN.) LEGEND:

CORRIDOR 7.0m IN3 IN4 CB2


INLET INLET CATCH BASIN STORM WATER MAIN PIPELINES
PARKING 2.5m
MANHOLE (MH)
MH4 MAIN DRAINAGE LINE MH3 MAIN DRAINAGE LINE MH2 MAIN DRAINAGE LINE MH1
TRAVEL 6.8m
FLOW DIRECTION
MANHOLE MANHOLE MANHOLE MANHOLE
MEDIAN 5.0m COLLECTOR DRAIN 500mm (MIN.) CATCH BASIN
600mm (MIN.) 600mm (MIN.) 600mm (MIN.) INLET
TRAVEL 6.8m
PARKING 2.5m
INLET INLET CATCH
CORRIDOR 6.7m
IN1 IN2 BASIN CB1

INLET INLET TYPE-2


COLLECTOR COLLECTOR
INLETS CONNECTED TO MAIN DRAIN WITH
TYPE-2 300mm (MIN.) 400mm CATCH BASIN & MANHOLE 1. THE SYSTEM SHOWN CONNECT INLETS TOGETHER IN A LINEAR
PATTERN USING COLLECTOR DRAINS WITH 300mm OR 400mm
DIAMETER PIPES BETWEEN INLETS UP TO DOWN STREAM CATCH
BASIN.

2. 500mm DIAMETER COLLECTOR PIPES CONNECT THE DOWNSTREAM


CATCH BASIN IN THE SERIES TO THE STORM WATER MAIN DRAIN
MANHOLES.

3. THIS TYPE OF DRAINAGE NETWORK IS COMMONLY USED IN AREAS


WHICH HAVE HIGH GROUND WATER LEVEL AND SANDSTORMS SUCH
AS ABU DHABI CITY OR AS DIRECTED BY THE ENGINEER.

REFERENCE DRAWINGS AND DOCUMENTS

No. REVISION-1 APP'D 2020


CLIENT

TITLE
STANDARD DRAWINGS
MAIN ROADS
DRAWING TITLE
SURFACE DRAINAGE SAMPLE
STORM DRAINAGE LAYOUT PLAN
-(TYPE 1 & TYPE 2) AND UTILITY
DISPOSITION SECTION
DRAWN - SCALE N.T.S
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No. N-229

THIRD EDITION - APRIL 2022


NOTES:
1. ALL DIMENSIONS ARE IN METERS, UNLESS OTHERWISE
SPECIFIED.

2. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL


BE IN ACCORDANCE WITH THE SPECIFICATIONS AND

MH3

CB1

IN2

IN1
VERIFIED BY THE ENGINEER.

6.0
3. IF THERE IS A DISCREPANCY BETWEEN THE REQUIREMENTS
IN THE SPECIFICATIONS AND THOSE SHOWN ON THIS
DRAWING, THE SPECIFICATIONS SHALL BE FOLLOWED.
5.0
4. THE CONTRACTOR SHALL VERIFY ALL LEVELS AND AMEND
WHERE REQUIRED AND AS APPROVED BY THE ENGINEER.

4.0 5. THE LEVELS, PIPE DIAMETERS AND SPACING OF MANHOLES


Ø500
ARE ONLY INDICATIVE AND PROPER PROFILES SHALL BE
PROVIDED TO REFLECT PROJECT REQUIREMENTS.
3.0
6. FOR PIPE TRENCH BEDDING AND PROTECTION DETAILS
REFER TO DWG. No. N-215.
DATUM -2.00
7. PIPE MATERIAL COMMONLY USED IN ABU DHABI IS AS
SECTION SIZE 500mm 400mm 300mm FOLLOWS;
SLOPE 0.180% 0.210% FOR DIA ≤500 USE uPVC OR GRP
FOR DIA >500 USE RC.

5.91

5.80

5.81

1.51 4.35 5.86


GROUND LEVEL
8. BRANCH SEWER INLET SHALL HAVE LEVEL SOFFITS WITH A

1.96 3.95
1.93 3.98

1.77 4.03
1.67 4.13

1.62 4.19
1.52 4.29
INVERT LEVEL LARGER PIPE DIAMETER/OUTLET PIPE.

DEPTH TO INVERT
LEGEND:
LENGTH 28.00 28.00 28.00
PROPOSED GROUND LEVEL
PIPE MATERIAL uPVC / GRP

BEDDING TYPE BEDDING SHALL BE AS PER SPECIFICATIONS PROPOSED PIPE LINE

0+000

0+028

0+056

0+084
STATION
PROPOSED MANHOLE

COLLECTOR DRAIN TO MH3

MH1

MH2

MH3

MH4
6.0 REFERENCE DRAWINGS AND DOCUMENTS

5.0

4.0
INCOMING LINE
FROM CB1 & CB2
IL=3.95
3.0

DATUM -2.00
SECTION SIZE 600mm
SLOPE 0.20%(min.) 0.20%(min.) 0.20%(min.) No. REVISION-1 APP'D 2020
CLIENT
3.63 5.67

3.71 5.77

2.06 3.85 5.91

2.09 3.97 6.06


GROUND LEVEL

INVERT LEVEL
2.04

2.06

DEPTH TO INVERT TITLE


LENGTH 40.00 70.00 60.00
STANDARD DRAWINGS
PIPE MATERIAL RC
MAIN ROADS
BEDDING TYPE BEDDING SHALL BE AS PER SPECIFICATIONS DRAWING TITLE
0+000

0+040

0+110

0+170

STATION SURFACE DRAINAGE


SAMPLE OF TYPICAL STORM
DRAINAGE PROFILE
MAIN STORM DRAINAGE GRAVITY LINE

DRAWN - SCALE N.T.S


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
N-230

THIRD EDITION - APRIL 2022


NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS INDICATED
DUCTILE IRON 700x700 SINGLE SIDED CONCRETE BARRIER OR OTHERWISE.
B TOP OF PAVEMENT
GUTTER TYPE INLET DOUBLE SIDED CONCRETE BARRIER/
GRATE AND FRAME FLUSH INLET CONCRETE KERB 2. IF THERE IS DISCREPANCY BETWEEN THE REQUIREMENTS
IN THE SPECIFICATIONS AND THOSE SHOWN ON THIS
DRAWING, THE PROJECT SPECIFICATIONS SHALL BE
FOLLOWED.
C C 3. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL
BE IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS
GRATE TO BE CENTERED 1000
PIPE END CAP TERMINATED AND VERIFIED BY THE ENGINEER.
ON STRUCTURE
500mm BEFORE UPSTREAM NON PERFORATED PIPE PROTECTIVE EPOXY COATING ON
CATCH PIPT ALL INTERNAL SURFACES 4. IF THE SUBSURFACE DRAINAGE PIPE DOES NOT
TERMINATE IN AN INLET AND IS ALLOWED TO RUN OUT TO
50 CHAMFER FOR ONE WAY FIT 20 225Ø PERFORATED PIPE 225Ø PERFORATED PIPE A SURFACE OUTLET, THE LAST 4m SHOULD BE SOLID WALL
100
DRAINAGE PIPE.
JOINT FILLER AND SEALER
0.2% SLOPE 5. SUBSURFACE DRAINS ARE PROVIDED TO CONTROL THE
OUTLET PIPE 0.2% SLOPE GROUND WATER LEVEL CAUSED BY EXCESS
700x700mm DUCTILE PRECIPITATION OR IRRIGATION, HIGH TIDES, TRAPPED
IRON GRATE WATER OR UNDERGROUND FLOWS FROM UPLAND AREAS.

1000
A A COLLECTOR PIPE COLLECTOR PIPE 6. THE SUBSURFACE PIPE LEVEL AND DIAMETER SHOULD BE
DETERMINED ACCORDING TO IT'S FUNCTION OF
DUCTILE IRON FRAME LESSENING / MAINTAINING THE GROUNDWATER LEVEL OR
DNØ300 / AND EXCESSIVE IRRIGATION WATER DRAINAGE.

FROM INLET FROM INLET


SINGLE SIDED CONCRETE BARRIER OR
DOUBLE SIDED CONCRETE BARRIER/
CONCRETE KERB
ROADWAY PAVEMENT
OUTLET PIPE

500
60m MAX. LENGTH INSTALL PERFORATED PIPE BETWEEN
INLETS OR CATCH BASIN OUTLET ONE END ONLY
WATERPROOFING MEMBRANE TYPE A WITH 2 LAYERS
OF ASPHALT HARDBORAD PROTECTION (TYP.)

B BLINDING, C15 CONCRETE (TYP.)

WATERPROOFING MEMBRANE TYPE A ONLY,


NO HARDBOARD UNDER BOTTOM SLAB (TYP.)
PLAN
SECTION B-B
TYPICAL LAYOUT FOR SUB SURFACE DRAINAGE
INSTALLATION AGAINST CONCRETE BARRIERS TYPICAL ELEVATION
PAVEMENT SUB SURFACE DRAINAGE INSTALATION

FINISHED GROUND LEVEL

FINISHED GROUND LEVEL

DUCTILE IRON 700x700 GUTTER TYPE SINGLE SIDED CONCRETE BARRIER OR


SINGLE SIDED CONCRETE BARRIER OR INLET GRATE AND FRAME DOUBLE SIDED CONCRETE BARRIER/
DOUBLE SIDED CONCRETE BARRIER/ JOINT SEALER REFERENCE DRAWINGS AND DOCUMENTS
CONCRETE KERB
CONCRETE KERB RECESS GRTAE 20 BELOW PAVEMENT LEVEL
AND MATCH CROSS SLOPE OF PAVEMENT
700
TOP OF PAVEMENT
20 350 150 MIN.
PREFORMED JOINT FILLER SLOPE
50mm MORTAR JOINT
PAVEMENT
ROADWAY

SECTION

400

600 MIN.
20 CHAMFER (TYP.)

VARIES
GRANULAR FILTER MATERIAL
Ø225 PERFORATED PIPE 525
OVERLAP WATERPROOFING
WATERPROOFING MEMBRANE TYPE A WITH GEOTEXTILE FILTER FABRIC
MEMBRANE AROUND PIPE
2 LAYERS OF ASPHALT HARDBOARD
PROTECTION (TYP.) No. REVISION-1 APP'D 2020
PROTECTIVE EPOXY COATING ON Ø225 (MIN.) uPVC PERFORATED
ALL INTERNAL SURFACES SUB-SURFACE DRAINAGE PIPE CLIENT
OUTLET PIPE
STORM WATER DRAINAGE PIPE
100 MIN.
LONGITUDINAL STORM WATER DRAINAGE
(FOR PIPE TRENCH DETAIL REFER DWG. No. N-215) TITLE
STANDARD DRAWINGS
CONSTRUCTION JOINT TRENCH BACKFILL MATERIAL MAIN ROADS
500

FOR DETAIL REFER DWG. No. N-202 VARIES


DRAWING TITLE
200

150
SURFACE DRAINAGE TYPICAL DETAILS
100

BLINDING, C15 CONCRETE (TYP.)


OF SUB SURFACE DRAINAGE AGAINST
200 300 300 200
WATERPROOFING MEMBRANE TYPE A ONLY, CONCRETE BARRIERS
NO HARDBOARD UNDER BOTTOM SLAB (TYP.) SECTION C-C
SECTION A-A TYPICAL SECTION FOR SUB SURFACE DRAINAGE AGAINST DRAWN - SCALE N.T.S
CONCRETE BARRIERS COMBINATION WITH STORM WATER DRAIN CHECKED - DATE -
TYPICAL SECTION FOR SUB SURFACE DRAINAGE
INSTALLATION AGAINST CONCRETE BARRIERS APPROVED - SIZE A1
PROJECT DWG.
No. - No.
N-231

THIRD EDITION - APRIL 2022


NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
INDICATED.

2. IF THERE IS DISCREPANCY BETWEEN THE REQUIREMENTS


IN THE SPECIFICATIONS AND THOSE SHOWN ON THE
DRAWINGS. THE SPECIFICATIONS SHALL BE FOLLOWED.

F.G.L. F.G.L. F.G.L. F.G.L. 3. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL
BE IN ACCORDANCE WITH THE SPECIFICATIONS AND
VERIFIED BY ENGINEER.

4. FLOW ARROWS ARE FOR TYPICAL SITUATION. NUMBER


AND DIRECTION OF INCOMING OR OUTGOING PIPES ARE AS
PER SURFACE DRAINAGE PLAN DRAWINGS.
10000
5. FOR SITES WITH HIGH GROUND WATER, THE CONTRACTOR
TEMPORARY SHAFT TEMPORARY SHAFT 10000 TEMPORARY SHAFT TEMPORARY SHAFT IS REQUIRED TO PERFORM A STABILITY CHECK FOR THE
STRUCTURES AGAINST UPLIFT / FLOATATION WHICH
350 5700 350
SHALL BE APPROVED BY ENGINEER PRIOR TO
INSTALLATION.
10000 10000
6. THE DIMENSIONS OF TEMPORARY SHAFT AND MANHOLE
ARE FOR COMMONLY USED R.C. PIPES OF 2400mm

5000
350 5700 350 DIAMETER AND FOR GUIDANCE ONLY.

MICRO TUNNEL MICRO TUNNEL MICRO TUNNEL 400 MICRO TUNNEL


250 250 250 250 7. THE DETAILS (DIMENSIONS AND PIPE SIZES) SHALL VARY

500
ACCORDING TO THE METHOD STATEMENT PROVIDED BY
SPECIALIST CONTRACTOR AND THE MICRO TUNNELING
350 5700 350 MACHINE BEING USED. THE METHOD STATEMENT SHALL BE
2400

2400

2400
3000

3000

3000

2400
3000
INVERT LEVEL INVERT LEVEL INVERT LEVEL INVERT LEVEL APPROVED BY ENGINEER PRIOR TO EXECUTION.
FOOTING ACCESS
SHAFT
50mm MEMBRANE
PROTECTION GRADE C15 (TYP.) F.G.L = FINISHED GROUND LEVEL

75mm BLINDING CONCRETE WATERPROOFING MEMBRANE TYPE A ONLY


GRADE C15 (TYP.) NO HARDBOARD UNDER BOTTOM SLAB (TYP.)

STAGE 1 STAGE 2 STAGE 3 STAGE 4


* PREPARATION OF TEMPORARY SHAFTS.
* SURFACE PREPARATION TO RECEIVE PERMANENT WORK * CAST AROUND AND ABOVE THE MICROTUNNEL * CAST A 5.0m WALL ABOVE PIPE AS SHOWN ABOVE
* EXECUTION OF MICROTUNNEL
* CAST THE ACCESS SHAFT FOOTING AND WALL UP TO THE * PLACE THE PIPE IN ITS LOCATION
BOTTOM OF MICROTUNNEL

EMATIC COVERS B125


CAST IN SITU
COVERS AND BEAMS
F.G.L. F.G.L. F.G.L. CONNECTION F.G.L.

350 5700 350

350 5700 350


REFERENCE DRAWINGS AND DOCUMENTS
PRE-CAST GRP LADDER
SLAB GRP SAFETY CAGE
TEMPORARY SHAFT HANDRAIL
5000

5000

5000
TEMPORARY SHAFT TEMPORARY SHAFT
WATER PROOFING MEMBRANE
TYPE A WITH 2LAYERS OF
ASPHALT HARDBOARD
PROTECTION (TYP.)
PROTECTIVE COATINGS ON
ALL INTERNAL CONCRETE 350mm THICK
SURFACES (TYP.) REINFORCED CONCRETE
5000

5000

5000

LANDING
BACKFILL
MICRO TUNNEL MICRO TUNNEL MICRO TUNNEL MICROTUNNEL

SAFETY CHAIN
STAINLESS STEEL No. REVISION-1 APP'D 2020
2400

2400

2400
3000

3000

3000

INVERT LEVEL INVERT LEVEL INVERT LEVEL CLIENT


50mm MEMBRANE
ENTRY RING AND PROTECTION GRADE
LAUNCH SEAL C15 (TYP.)
75mm BLINDING CONCRETE WATERPROOFING MEMBRANE TYPE TITLE
GRADE C15 (TYP.) A ONLY NO HARDBOARD UNDER STANDARD DRAWINGS
BOTTOM SLAB (TYP.)
MAIN ROADS
DRAWING TITLE

STAGE 6 STAGE 7
SURFACE DRAINAGE DETAILS OF
STAGE 5 STAGE 8
MICRO TUNNEL TEMPORARY
* CAST A 5.00m WALL SEGMENT AS SHOWN ABOVE * CAST THE REMAINING OF WALL UP TO THE HORIZONTAL * CAST THE PRE-CAST SLAB AND CAST THE * CAST THE REMAINING WALL SEGMENT ACCESS SHAFT AND INSTALLATION
SLAB LEVEL IN SITU CONNECTION
* INSTALL THE WATERPROOFING
OF DEEP MANHOLE
* STAGE 5 SHALL BE REPEATED AS REQUIRED BASED
ON THE ACCESS SHAFT HEIGHT
* INSTALL THE ACCESS SHAFT FURNITURE DRAWN - SCALE N.T.S

* START BACKFILLING CHECKED - DATE -


APPROVED - SIZE A1
PROJECT DWG.
No. - No.
N-232

THIRD EDITION - APRIL 2022


NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS INDICATED
OTHERWISE.

2. IF THERE IS DISCREPANCY BETWEEN THE REQUIREMENTS


HEAVY DUTY TRIANGULAR IN THE SPECIFICATIONS AND THOSE SHOWN ON THIS
DUCTILE IRON COVER AND DRAWING, THE PROJECT SPECIFICATIONS SHALL BE
FRAME TO EN124 CLASS D400
FOLLOWED.
WITH 675 DIA. CLEAR OPENING
3. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL
4000 x 2000 OPENING
BE IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS
ERMATIC COVERS B125
AND VERIFIED BY THE ENGINEER.
6400 (MAX.)
LEVELLING BOLTS IN THE DIRECTION OF MICRO-TUNNEL CORRIDOR
HEAVY DUTY TRIANGULAR
HINGED BEAM SUPPORT 4. THE REINFORCEMENT ARE FOR GUIDANCE ONLY.THE

600mm THICK
DUCTILE IRON COVER AND

TOP SLAB
4600 (MAX.) CONTRACTOR SHALL PREPARE AND SUBMIT DRAWING
FRAME TO EN124 CLASS D400
WITH 675 DIA. CLEAR OPENING COVER OPENING DIRECTION SHOWING REINFORCEMENT DETAILS WITH REQUIRED
4000 X 2000
REMOVABLE BEAM ERMATIC COVERS B125 STRUCTURAL CALCULATIONS FOR THE ENGINEER

2000
COVERS & 4 BEAMS APPROVAL.
F.G.L. F.G.L.

5. THE DIFFERENTIAL SETTLEMENT IS EXPECTED, SO A SHORT

500 2000 (MIN.)


PIECE OF PIPE WITH APPROPRIATE LENGTH SHALL BE

2000 MIN.
PROVIDED FOR BOTH SIDES OF THE STRUCTURE
BEAMS SUBJECTED TO THE APPROVAL OF ENGINEER. FOR DETAILS
OF SHORT PIECE REFER TO DRAWING No. N-215.

VARIES 6000 (MAX.)


500
6. DIMENSIONS OF PRECAST BASE AND INTERMEDIATE UNITS
4000 ARE INDICATIVE ONLY.
GRP LADDER
GRP LADDER
GRP SAFETY CAGE
SECTION 1-1
WATER PROOFING MEMBRANE TYPE
1 1
A WITH 2LAYERS OF ASPHALT F.G.L = FINISHED GROUND LEVEL
HAND RAIL
HARDBOARD PROTECTION

DEPTH VARIES ACCORDING TO SITE CONDITIONS


LANDING

300 (TYP.)
350mm THICK REINFORCED
LANDING CONCRETE WALL LANDING
1500

FALSE WALL (DEPTH VARIES ACCORDING 350mm THICK REINFORCED


TO SITE CONDITION)

VARIES 6000 MAX

300
MIN.TEE Ø 800mm CONCRETE WALL
SURFACE DRAINAGE GRP PIPE
GRP SAFETY CAGE
Ø800mm MIN.
2 2
ACCESS SHAFT 20,000 TO 24,000

END CAP
HAND RAIL

(TYP.)

(TYP.)
1000

1000
SURFACE WATER PIPE
Ø800mm MIN.
1200

1500 (TYP.)
(TYP.)
250
VARIES 6000 MAX

VARIES 6000 (MAX.)


SECTION 2-2
VARIES

GRP DROP SHAFT Ø800mm MIN.


PROTECTIVE COATINGS ON ALL
INTERNAL CONCRETE SURFACES
REFERENCE DRAWINGS AND DOCUMENTS
A STAINLESS STEEL BRACKET
(SPACING AS PER SPECIFICATIONS)
900

00 600 MIN. 600 MIN. REINFORCED CONCRETE WALL


57
Ø TO ATTACHED TO ENTRY RING
00

SAFETY CHAIN STAINLESS STEEL


Ø24

1:12
SAFETY CHAIN
STAINLESS STEEL
430

Ø2400
700
B B GRADE C35 3 3
CONCRETE BENCHING
1:12

800mm THICK BASE 800mm THICK BASE ENTRY RING AND LAUNCH SEAL No. REVISION-1 APP'D 2020
SAFETY CHAIN SLAB GRADE C35 SLAB GRADE C35 CLIENT
STAINLESS STEEL
BLINDING, C15 CONCRETE (TYP.) BLINDING, C15 CONCRETE (TYP.)
3200 3200 350 350
350 350 WATERPROOFING MEMBRANE TYPE A ONLY 850 5700 850 WATERPROOFING MEMBRANE
FALSE WALL NO HARDBOARD UNDER BOTTOM SLAB (TYP.) TITLE
SURFACE DRAINAGE PIPE 850 5700 850 TYPE A ONLY NO HARDBOARD
A UNDER BOTTOM SLAB (TYP.) STANDARD DRAWINGS
MAIN ROADS
DRAWING TITLE
SECTION 3-3 SECTION A-A SECTION B-B
SURFACE DRAINAGE DETAILS
OF MICRO TUNNEL PERMANENT
ACCESS SHAFT

DRAWN - SCALE N.T.S


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
N-233

THIRD EDITION - APRIL 2022


NOTES:
CONCRETE BARRIER 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS INDICATED
UPSTAND TO SUPPORT
OTHERWISE.
CONCRETE COVER
300 X 100MM CONCRETE COVER
2. IF THERE IS DISCREPANCY BETWEEN THE REQUIREMENTS
300 STORM WATER SURFACE INLET GULLY IN THE SPECIFICATIONS AND THOSE SHOWN ON THIS
ASPHALT FILL DRAWING, THE SPECIFICATIONS SHALL BE FOLLOWED.
DUCTILE IRON GUTTER TYPE INLET GRATE

110
ASPHALT
STORM WATER SURFACE INLET GULLY
3. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL
AND FRAME VARIES (600 MAX)

150
150 DECK SLAB BE IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS
100

250
AND VERIFIED BY THE ENGINEER.
E D PRECAST SLAB
TOP OF ASPHALT
4. DIMENSIONS OF BRIDGE AND STRUCTURAL ELEMENTS
250 250

(MIN.)
ROAD SLOPE (MIN. 2%) SHOWN ARE INDICATIVE ONLY.

100
TOP FLANGE

110
ASPHALT
5. HANGERS TO BOTTOM OF BRIDGE SLAB TO BE PROVIDED

(MIN.)
AT SUITABLE DISTANCES AND ARRANGEMENT SHALL BE

250
(MIN.)
SLOPE (MIN. 2%)

100
DECK SLAB APPROVED BY ENGINEER.
'I' BEAM
6. COLLECTION PIPE SLOPE AND LENGTH TO BE DETERMINED

300 (MIN.)
ACCORDING TO THE FLOW AND SHALL BE APPROVED BY
'I' BEAM ENGINEER.
'I' BEAM
PRECAST SLAB 7. FOR OPERATION AND MAINTENANCE DETAILS REFER TO
SECTION D-D
WA-726-3 APPENDIX ''K''
100MM HIGH COVER & FRAME STORM WATER SURFACE INLET GULLY
D
600

MIN. Ø100mm uPVC PIPE WITH FLUSH END ONE

110
ASPHALT
SIDE AND FLANGED END OTHER SIDE (TO BE
E FIXED ON TOP OF PRECAST SLAB)
BENCHING

(MIN.)
250
DECK SLAB DECK SLAB
300 x 100 (MIN.) DRAIN CHANNEL 300x100 TEE

20 800 20
MIN. Ø300mm uPVC COLLECTION PIPE

SECTION C-C

150MM DEPTH ARE TO BE BROKEN


ASPHALT ROAD

IN EXISTING DECK SLAB 'I' BEAM


300 X 100mm PFC
BARRIER

MIN. Ø100mm uPVC PIPE


100 600

SECTION E-E
250
300

800

C C

STANDARD 600 x 600 HANGERS AND FIXING TO


150 DUCTILE IRON DOUBLE ENGINEER'S APPROVAL SLOPE%
250

TRIANGULAR INLET GRATE


GALVANIZED STEEL AND FRAME
SLOPE%
STRUCTURE SURFACE
ASPHALT ROAD

DUCTILE IRON D400 REFERENCE DRAWINGS AND DOCUMENTS


BARRIER

ACCORDING TO EN-124
SURFACE ENTRY INLET
(755x755x100)
SCREW
ANCHORAGE COLLAR 45°

S=5% min

DETAIL-B
PLAN AT SURFACE ENTRY INLET PIPE HANGER TYPICAL DETAIL
ASPHALT ROAD
SLOPE (MIN. 1%)

150MM DEPTH ARE TO BE BROKEN


IN EXISTING DECK SLAB
L ( Variable)
300 X 100mm PFC
MIN. Ø300mm UPVC PIPE
BARRIER

MIN. Ø100mm uPVC PIPE


100 155.00 mm . Min . PIPE
No. REVISION-2 APP'D 2021
HANGER (SEE DETAIL-B)
CLIENT
300 UPWARD CLEAN OUT
(SEE NOTE 7)
250

SPACING SPECIFIED BY
THE DESIGNER
S=1.0m (MIN.)
OUTLET TO BE CONNECTED TO
STORMWATER DRAINAGE SYSTEM
CATCH BASIN/MANHOLE TITLE
300

800

C C MIN. Ø300mm UPVC PIPE GROUND LEVEL STANDARD DRAWINGS


500

DOWNWARD CLEAN OUT


MAIN ROADS
(SEE NOTE 7)
150
DRAWING TITLE
250

300

300

300
SURFACE DRAINAGE TYPICAL
CONCRETE THRUST BLOCK
DETAILS OF DECK DRAINAGE
BARRIER

SLOPE (MIN. 1%)

(SHEET 1 OF 2)
ASPHALT ROAD

CATCH BASIN/MANHOLE
L ( Variable)

DRAWN - SCALE N.T.S


CHECKED - DATE -
DRAINAGE AT PIERS APPROVED - SIZE A1
PLAN FOR SLOTTED TRENCH PROJECT DWG.
No. - No.
N-234

THIRD EDITION - APRIL 2022


NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
INDICATED.

2. IF THERE IS DISCREPANCY BETWEEN THE REQUIREMENTS

DECK SLAB
IN THE SPECIFICATIONS AND THOSE SHOWN ON THIS

EXISTING
ASPHALT ROAD
DRAWING, THE SPECIFICATIONS SHALL BE FOLLOWED.

Ø150mm DEPTH ARE TO BE BROKEN


IN EXISTING DECK SLAB 3. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL
BE IN ACCORDANCE WITH THE SPECIFICATIONS AND
BARRIER

BARRIER
MIN. Ø300mm uPVC PIPE 720 VARIES(600 MAX) VERIFIED BY ENGINEER.
100 VARIES (1.30m Max)
MIN. Ø300mm uPVC PIPE
4. DIMENSIONS OF BRIDGE AND STRUCTURAL ELEMENTS
SHOWN ARE INDICATIVE ONLY.

5. HANGERS TO BOTTOM OF BRIDGE SLAB TO BE PROVIDED


AT SUITABLE DISTANCES AND SHALL BE APPROVED BY
ENGINEER.

800

800
C C WATER FLOW
6. COLLECTION PIPE SLOPE AND LENGTH TO BE DETERMINED
ACCORDING TO THE FLOW CALCULATIONS AND SHALL BE
APPROVED BY ENGINEER.

100
BARRIER

BARRIER
DUCTILE IRON D400

ASPHALT ROAD
ACCORDING TO EN-124

DECK SLAB
EXISTING
SURFACE ENTRY INLET

SECTIONAL PLAN A-A SECTIONAL PLAN B-B


AT SURFACE ENTRY INLET AT DECK SLAB LEVEL

STORM WATER SURFACE INLET GULLY


600

150 110
ASPHALT

150
DECK SLAB
CONCRETE BARRIER
800
PRECAST SLAB

REFERENCE DRAWINGS AND DOCUMENTS

(MIN.)
TOP FLANGE

100
ASPHALT FILL

STORM WATER SURFACE INLET GULLY


DUCTILE IRON GUTTER TYPE INLET GRATE
AND FRAME 'I' BEAM

100 VARIES (1300 MAX.) 150


SECTION D-D
E D
TOP OF ASPHALT
ROAD SLOPE (MIN 2%)
110

ASPHALT
100mm HIGH COVER & FRAME STORM WATER SURFACE INLET GULLY
B
150

250

B SLOPE (MIN 2%)


DECK SLAB
600
No. REVISION-1 APP'D 2020
CLIENT

110
(MIN.)

ASPHALT
300

'I' BEAM
'I' BEAM

250
PRECAST SLAB DECK SLAB

TITLE
D
20 800 20 STANDARD DRAWINGS
MAIN ROADS
MIN. Ø300mm uPVC PIPE WITH FLUSH END
ONE SIDE AND FLANGED END OTHER SIDE DRAWING TITLE
E (TO BE FIXED ON TOP OF PRECAST SLAB)

600x150 (MIN.) DRAIN CHANNEL


300x300mm TEE
'I' BEAM
SURFACE DRAINAGE TYPICAL
DEATILS OF DECK DRAINAGE
(SHEET 2 OF 2)
SECTION C-C
MIN. Ø300mm uPVC COLLECTION PIPE SECTION E-E
DRAWN - SCALE N.T.S
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
N-235

THIRD EDITION - APRIL 2022


NOTES:

1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS INDICATED


OTHERWISE.

2. IF THERE IS DISCREPANCY BETWEEN THE REQUIREMENTS


IN THE SPECIFICATIONS AND THOSE SHOWN ON THIS
DRAWING, THE SPECIFICATIONS SHALL BE FOLLOWED.

ACCESS
INTERLOCKING BLOCKS

GATE
6000
ACCESS ROAD 3. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL
PUMP STATION
BE IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS
AND VERIFIED BY THE ENGINEER.
OUTLET PIPE
4. THE SHOWN LAYOUT PLAN IS FOR GUIDANCE ONLY. TO
ADDRESS THE UNITS SHOULD BE CONSIDERED FOR
PROPER STORMWATER DRAINAGE PUMP STATION

BYPASS CHAMBER 5. UNITS AND DIMENSIONS SHOWN IN THE PUMP STATION


DRAWING N-238, N-239 AND N-240 ARE GIVEN FOR
GRP INLET OIL WATER SEPARATOR GRP INLET GUIDANCE ONLY. UNITS, DIMENSIONS AND ARRANGEMENT
PIPE TO OWS PIPE FROM OWS SHALL BE MODIFIED ACCORDING TO THE SITE CONDITIONS.
DESIGN FLOW CALCULATIONS SHALL BE APPROVED BY
THE ENGINEER.

INLET PIPE FROM BYPASS

CAST ALUMINIUM DECORATIVE FENCE

MCC ROOM

INLET PIPE
ACCESS ROAD

REFERENCE DRAWINGS AND DOCUMENTS

2800 2800

150
160
200

300
1750
1450
No. REVISION-1 APP'D 2020
CLIENT

100
80mm THICK INTERLOCKING BLOCK 60mm THICK APPROVED INTERLOCKING BLOCK

1100
50mm THICK COMPACTED CRUSHED SAND
50mm COMPACTED CRUSHED SAND TITLE
200mm AGGREGATE ROAD BASE OF MIN.
80% C.B.R. AT 95% MAX. DRY DENSITY
STANDARD DRAWINGS
150mm SUB BASE TYPE II MIN. 30% CBR @ 95% MDD.
150mm THICK IMPROVEMENT SUBGRADE OF 900 MAIN ROADS
MINIMUM 30% CBR @ 95% MDD
DRAWING TITLE
CONCRETE PAVING INTERLOCKING BLOCKS CONCRETE PAVING INTERLOCKING BLOCKS ELEVATION SURFACE DRAINAGE
DETAIL FOR CARRIAGEWAY DETAIL FOR FOOTPATH CAST ALUMINUM DECORATIVE FENCE DRAINAGE PUMP STATION
GENERAL LAYOUT PLAN

DRAWN - SCALE N.T.S


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
N-237

THIRD EDITION - APRIL 2022


NOTES:

1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS INDICATED


OTHERWISE.

2. IF THERE IS DISCREPANCY BETWEEN THE REQUIREMENTS


IN THE SPECIFICATIONS AND THOSE SHOWN ON THIS
C DRAWING, THE SPECIFICATIONS SHALL BE FOLLOWED.
C SS CHEQUER PLATE CLEAR OPENING
GRP KIOSK (TYP.)
(1300x450) (TYP.) 3. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL
BE IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS
500

500
Ø150mm VENTILATION AND VERIFIED BY THE ENGINEER.
COWL

750
4. ALL ANCHOR BOLTS SHALL BE AS PER S.S. 316.

PE
PENSTOCK
INLET PIPE

O
(NORMALLY CLOSE)

SL
2000

2000
B B B 600 B 5. INTERNAL AND EXTERNAL SURFACES ARE TO BE
PROTECTED IN ACCORDANCE WITH THE SPECIFICATIONS.
PENSTOCK
SUMP PIT (NORMALLY OPEN)

450

450
600x600x200 6. PENSTOCK TO BE MOTORIZED WITH NON RISING SPINDLE.
500

500
1300 1300 7. SPINDLE TO BE SIZED TO AVOID ANY BUCKLING AT THE
LINE OF PENSTOCK CLOSING AND THE CONTRACTOR TO
500 8000 500 500 8000 500 VERIFY THE SUPPORTS AS PER MANUFACTURER'S
REQUIREMENTS.
C
Ø500 TO OIL WATER SEPARATOR TOP PLAN 8. WATER-PROOFING MEMBRANE TYPE 'A' WITH 2 LAYERS OF
Ø500 BYPASS PIPE
ASPHALTIC HARD BOARD PROTECTION SHALL BE APPLIED
TO THE EXTERIOR SURFACE OF ALL STORM WATER
DRAINAGE STRUCTURES PRIOR TO BACKFILLING.

C 9. WATER-PROOFING MEMBRANE UNDER THE BOTTOM SLAB


SHALL BE AS SPECIFIED.
SECTIONAL PLAN A-A
10. ALL DIMENSIONS ARE GIVEN FOR GUIDANCE ONLY, UNITS,
DIMENSIONS AND ARRANGEMENT SHALL BE MODIFIED
ACCORDING TO SITE CONDITIONS, THE DESIGN FLOW
CALCULATIONS SHALL BE APPROVED BY THE ENGINEER.

11. THE CAPACITY OF THE PUMP STATION SHOWN IS 0.35


CUM/SEC AND PUMP HEAD IS 17.0 METER. PUMP NUMBERS
AND CONFIGURATION MAY VARY ACCORDING TO DESIGN
FLOWS.

12. ALL DIMENSIONS PROVIDED IN THE DRAWING ARE


INDICATIVE ONLY AND ACTUAL DIMENSIONS SHALL BE
DEFINED BY THE CONSULTANT FOR THE SPECIFIC
Ø150 VENTILATION COWL
PROJECT.
0 0 0

INTERLOCK Ø100 G.I. BARRIER

FINISHED GROUND LEVEL FINISHED GROUND LEVEL

A A

REFERENCE DRAWINGS AND DOCUMENTS

SS PLATFORM
WATERPROOFING MEMBRANE TYPE A WATERPROOFING MEMBRANE TYPE A
WITH 2 LAYERS OF ASPHALT WITH 2 LAYERS OF ASPHALT
HARDBOARD PROTECTION (TYP.) HARDBOARD PROTECTION (TYP.)
OPENING 600x600

SS SAFETY CAGE
SPINDLE SUPPORT
SS LADDER

No. REVISION-1 APP'D 2020


Ø500 INLET PIPE Ø500 TO OIL/WATER SEPARATOR CLIENT
Ø500 BYPASS PIPE 750 I.L. OF
OUTLET PIPE
I.L. OF I.L. OF
INLET PIPE Ø500 BYPASS PIPE
OUTLET PIPES

TITLE
(MIN.)

(MIN.)
STANDARD DRAWINGS
700

500
SLOPE SLOPE
MAIN ROADS
500

500
BLINDING CLASS C15 CONCRETE (TYP.)
DRAWING TITLE
100

100
BLINDING (CLASS C15 CONCRETE WATERPROOFING MEMBRANE TYPE A ONLY SURFACE DRAINAGE DETAILS OF
NO HARDBOARD UNDER BOTTOM SLAB (TYP.)
100 500 500 8000 500 500 100 100 500 500 2000 500 500 100 DRAINAGE PUMP STATION, BYPASS
CHAMBER PLANS & SECTIONS
SECTION B-B SECTION C-C
DRAWN - SCALE N.T.S
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No. N-238

THIRD EDITION - APRIL 2022


NOTES:
BARRIER 100mmØ GI PIPE 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS INDICATED
D Ø150 VENTILATION OUTLET PIPE
OTHERWISE.
Ø100 VENTILATION OUTLET 300

OUTLET PIPE
HANDHOLD (SEE DETAIL-1) 2. IF THERE IS DISCREPANCY BETWEEN THE REQUIREMENTS
19
IN THE SPECIFICATIONS AND THOSE SHOWN ON THIS

300
GRP VENT COWL DRAWING, THE SPECIFICATIONS SHALL BE FOLLOWED.

1200
300 3700 300

3. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL


300

800
300
GRP PIPE
C BE IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS
15 EXPANSION SLEEVE
C AND VERIFIED BY THE ENGINEER.

750
Ø150 VENTILATION OUTLET PIPE
S.S ANCHOR

1550

1550
1200
14 4. DETAILS OF LADDERS, PLATFORMS, HANDRAIL, ETC. SHOP
3300x1050 CLEAR OPENING
4500 450 600 (4 Nos. 1050x750 COVER) DRAWINGS TO BE PREPARED BY CONTRACTOR AND
13
APPROVED BY ENGINEER.

SL
O

450

450
PE
900 5. INTERNAL AND EXTERNAL SURFACES ARE TO BE LINED IN

750
12 SUMP 600x600x200

350
3 ACCORDANCE WITH THE SPECIFICATIONS.

750
800

1200
1200x600 CLEAR 6. PIPE SUPPORT TYPE AND SPACING TO BE VERIFIED BY
10 OPENING WITH
6000

6000
COVER & FRAME CONTRACTOR AS PER SPECIFICATION AND TO THE
600 400
APPROVAL OF ENGINEER.

1200
S.S. SCREEN BARS
11 8 7 6 5 4 16 2 1

CONCRETE 7. PIPES, VALVES, FITTINGS AND PUMPS SHALL BE MADE OF

4000

4000
3300
B 10 B B B MATERIAL OF HIGH RESISTIVITY TO CHLORINE AND
SALINITY AS PER SPECIFICATION, MANUFACTURER

1200
11 8 7 6 5 4 3 2 1 RECOMMENDATION AND APPROVED BY THE ENGINEER.
TYPICAL AIR VENT DETAIL 8. WATER-PROOFING MEMBRANE SHALL BE APPLIED TO THE
MIN. Ø150 VENTILATION
10
INLET EXTERIOR SURFACE OF ALL STORM WATER DRAINAGE

800
STRUCTURES PRIOR TO BACKFILLING AS SPECIFIED.

350
7 6 5 4 3 2 1 10x45° CHAMFER
9
300

300
1050 450 9. WATER-PROOFING MEMBRANE SHALL BE APPLIED UNDER

450

450
150

150
450 BOTTOM SLAB AS SPECIFIED.

120
150 150

220
10. ALL DIMENSIONS ARE GIVEN FOR GUIDANCE ONLY,

150
300 3550 450 50
300 3700 300 50 F F DIMENSIONS SHALL BE MODIFIED ACCORDING TO THE

2000

2000
300 300 300

600
DESIGN FLOW CALCULATIONS AND APPROVED BY THE
Ø150 VENTILATION INLET
D ENGINEER..
S.S. LADDER WITH 750
S.S. SAFETY CAGE (TYP.) DETAIL-1 SECTION F-F 11. THE CAPACITY OF THE PUMP STATION SHOWN IS 0.35
CUM/SEC AND PUMP HEAD IS 17.0 METER. PUMP

400

400
NUMBERS AND CONFIGURATION MAY VARY ACCORDING
400 4000 400 400 4000 400 TO DESIGN FLOW.
PIPE FROM OWS

F.G.L.
Ø500 GRP INLET

C C
Ø500 BYPAS.S.

12. SAND TRAP IS PROVIDED THROUGH THE OIL WATER

350
INLET PIPE

SEPARATOR INSTALLED ON THE UPSTREAM OF THE PUMP


SECTIONAL PLAN A-A TOP PLAN STATION. REFER DWG. No. N-237.

14
LEGEND:
D.I. - DUCTILE IRON
S.S. - STAINLESS STEEL

3350
F.G.L. FL - FLANGE
9 10 11 10 11 10 12 13 15
F.G.L. F.G.L - FINISHED GROUND LEVEL
G.I. - GALVANIZED IRON
350

1300

GRP - GLASS REINFORCED PLASTIC


1500

I.L. - INVERT LEVEL


GUIDERAILS FOR
PUMP REMOVAL

350
14 AND MAINTENANCE

6
S.S. SAFETY CAGE (TYP.)
Ø150 VENTILATION

100
3350

7 OUTLET PIPE
100 500 300 6000 300 500 100
5 4 3 2 2 2 2 REFERENCE DRAWINGS AND DOCUMENTS
A A
I.L. OF OUTLET PIPE
10 HANDRAIL SECTION D-D
850

8 S.S. LADDER (TYP.)


STEEL
PLARFORM
DIAMETER OF THE CLAMP IS
350

400
SUFFICIENT TO ALLOW VERTICAL
MOVEMENT OF THE PIPE
100

100
100 300 3550 800 800
1550 300 500 100
LEVELS TO BE CONFIRMED BY PUMP MANUFACTURER
& VERIFIED ON SITE AND SUBJECT TO APPROVAL OF
ENGINEER 16
CONTROL SEQUENCE LEVEL

LEVEL ALARM L1 E E
FIRST PUMP START L2
SECOND PUMP START L3 No. REVISION-1 APP'D 2020
200 1300
HIGH LEVEL ALARM L4 PIPE SUPPORT I.L. OF Ø500 GRP PIPE WATERPROOFING MEMBRANE TYPE A PIPE DIA.
S.S. BOLTS WITH
CLIENT
INLET WITH 2 LAYERS OF ASPHALT CHEMICAL ANCHORS
(SEE DETAIL-2) PIPE
SCHEDULE OF PIPES AND FITTINGS 18 18 18 18
L4 HARDBOARD PROTECTION (TYP.)
ALL PIPES AND FITTINGS
TO BE D.I. ONLY UNLESS OTHERWISE SPECIFIED
2000

1
NO. DESCRIPTION LENGTH ENDS QTY.
450

L3
SUBMERSIBLEPUMP,ELECTRICDRIVENMOTOR SCREEN
1 FL-FL 3 PCS. TITLE
FLOW:111L/s@17mHEAD,37kwELECTRICAL
COMSUMPTION
17 L1
L2
1 1 1
RISER SUPPORT DETAIL-2 STANDARD DRAWINGS
2 Ø300 90° BEND FL-FL 3 PCS.
100

MAIN ROADS
200

3 Ø300STRAIGHTPIPEWITHPUDDLEFLANGE 1100 FL-FL 3 PCS. 100 500 400 2000


4 Ø300 DISMANTLING JOINT 190 FL-FL 3 PCS.
PE
800

(MIN.)

O
DRAWING TITLE
(MIN.)

5 Ø300 NON RETURN VALVE 698 FL-FL 3 PCS. SL


700
700

SUMP SUMP
400

6 Ø300 GATE VALVE (MOTORIZED) 356 FL-FL 3 PCS. LEVEL LEVEL


GRP LINER
7 PRESSUREGAUGE&PRESSURETRANSMITTER - - 3 PCS.
500

500

8 Ø300 STRAIGHT PIPE 500 FL-FL 3 PCS. SURFACE DRAINAGE TYPICAL


9
10
Ø450 BLANK FLANGE
Ø450x450x300 TEE
-
950
FL
FL-FL-FL
1 PC.
3 PCS.
DETAILS OF PUMP STATION
100

100

11
12
Ø450 STRAIGHT PIPE
Ø450x450x100 TEE
245
950
FL-FL
FL-FL-FL
2 PCS.
1 PC. 500 450 4500 450 500 100 100 500 450 4000 450 500 100
PLANS AND SECTIONS
13 Ø450 DISMANTLING JOINT 302 FL-FL 1 PC. 100
14 Ø450 GATE VALVE 650 FL-FL 1 PC.
15 Ø450STRAIGHTPIPEWITHPUDDLEFLANGE 1300 FL-FL 1 PC. SECTION B-B BLINDING C15 CONCRETE (TYP.)
SECTION C-C WATERPROOFING MEMBRANE TYPE A ONLY
NO HARDBOARD UNDER BOTTOM SLAB (TYP.)
6mm THICK NEOPRENE DRAWN - SCALE N.T.S
PAD AROUND PIPE
16 Ø100 DRAIN PIPE - - 1 PC.
17 Ø300x150 REDUCER 470 FL-FL 3 PCS.
CHECKED - DATE -
18 9460 FL-FL 3 PCS. APPROVED - SIZE A1
Ø300 STRAIGHT PIPE
SECTION E-E
19 Ø450 COUPLER 9460 FL-GRP 1 PC.
PROJECT DWG.
No. - No.
N-239

THIRD EDITION - APRIL 2022


NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETERS AND LEVELS ARE IN
METERS.

2. IF THERE IS DISCREPANCY BETWEEN THE REQUIREMENTS IN


SAMPLE FOR FLOW = 35L/sec. THE SPECIFICATIONS AND THOSE SHOWN ON THIS DRAWING,
THE SPECIFICATIONS SHALL BE FOLLOWED.

3. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL BE


IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS AND
VERIFIED BY THE ENGINEER.
MANHOLE COVER CLASS D 400
4. FOR SITES WITH HIGH GROUND WATER, THE CONTRACTOR IS
SAND FILLING BUILD IN REQUIRED TO PERFORM A STABILITY CHECK FOR THE
PAVEMENT ACCORDING LAYERS AND COMPACTED STRUCTURES AGAINST UPLIFT/FLOTATION CONSIDERING
BACKFILL
F.G.L. TRAFFIC LOAD DIFFERENT CASES OF LOADING AND APPROVED BY THE
ENGINEER.

VARIES 100
5. FOR OIL REMOVAL FROM THE OIL WATER SEPARATOR, THE
OPERATOR SHALL CHECK THE STATUS OF OIL PIT EVERY 6
MONTHS MIN. PERIOD OR AS SPECIFIED BY THE
MANUFACTURER.

6. OIL WATER SEPARATOR IS BUILT WITH GRP BODY AND


TO PUMP STATION FROM BYPASS CHAMBER
(REFER DWG. No. N-239)
INTERNAL COATING OF MULTI-LAYERS EPOXY RESIN.
(REFER DWG. No. N-238)

7. THE AREA OF INSTALLATION CAN BE UP TO CLASS LOAD D400


AND COMPLIES WITH EN B58/DIN1999.

8. CONCRETE ANCHORS, AND STABILITY ROPES SHALL BE


VERIFIED AS PER SITE CONDITIONS.

9. THE CONTRACTOR SHALL VERIFY THE TRAFFIC LOAD AGAINST


TURNBUCKLE
1 THE SEPARATOR DEPTH AND WHETHER A PROTECTION SLAB IS
REQUIRED AS PER MANUFACTURER RECOMMENDATION AND
2
TRIPLE CLAMP SUBJECT TO APPROVAL OF ENGINEER.
CONCRETE DEADMAN
ANCHOR 10. THE CONTRACTOR SHALL PROVIDE THE BACKFILL REQUIRED
AS PER SPECIFICATION AND AS PER APPROVAL OF ENGINEER.

11. VENTILATION PROVISION TO BE PROVIDED IF REQUIRED AS PER


MANUFACTURER'S RECOMMENDATION.
CONCRETE DEADMAN WIRE ROPE
· THE SHOWN INSTALLATION IS FOR SMALL TO MEDIUM DEPTHS UNDISTURBED SOIL CONCRETE SLAB BEARING LIMIT OF EXCAVATION
ANCHOR 12. THE CONTRACTOR SHALL VERIFY THE REQUIRED ANCHORING
· CONCRETE SLAB ON TOP OF SEPARATOR IS USED FOR LOAD AND RECOMMENDATION FROM SUPPLIER TO AVOID
YIELD AND BOUYANCY PROTECTION. CROSS SECTION SEPARATOR FLOATATION DUE TO WATER TABLE AND SUBJECT
TO APPROVAL OF ENGINEER.
· SEPARATOR SHOULD BE FILLED WITH WATER DURING PLACEMENT
OF SAND FILLING CONTINOUSLY.
13. DURING CONSTRUCTION OF GRP OIL WATER SEPARATOR THE
LONGITUDINAL SECTION CONTRACTOR SHALL MAKE PROPER AND CONTINUOUS
DEWATERING TO AVOID UPLIFT COMING FORM WATER TABLE
UNTIL THE TANK IS BURIED AS PER SPECIFICATION AND
APPROVED BY ENGINEER.

14. CONCRETE SLAB BEARING DETAIL FOR THE TANK TO BE


PROVIDED AS PER MANUFACTURER'S STRUCTURAL
REQUIREMENT RECOMMENDATION AND SUBJECT TO
APPROVAL OF ENGINEER.

15. THE DIMENSIONS AND CAPACITY OF THE OIL WATER


SEPARATOR SHOULD BE ACCORDING TO THE DESIGN FLOW
FOR EACH PROJECT AND AS APPROVED BY THE ENGINEER.

16. THE OIL WATER SEPARATOR SHOWN IN THIS DRAWING SHALL


ALLOW FLOW OF 35L/sec AND THE EXTRA FLOW SHOULD BE
DIRECTED THROUGH BYPASS.

1600
REFERENCE DRAWINGS AND DOCUMENTS

OIL/WATER SEPARATOR - OPERATION AND MAINTENANCE


1. THE SEPARATOR SHALL HAVE CAPACITY AS DESIGNED. THE EXCESS INFLOW UPSTREAM OF THE
PUMP STATION IS DIRECTED THROUGH THE BYPASS TO THE PUMP STATION.
SECTION VIEW
2. THE UNIT INCLUDES A CORE TUBE WITH REPLACEABLE MEDIA.

3. THE UNIT IS EQUIPPED WITH A CLOSURE DEVICE INCLUDING A FLOAT. AS THE OIL LEVEL BUILDS UP
FORMING A LAYER, THE CLOSURE DEVICE MOVES DOWNWARDS TO PREVENT THE PASSAGE OF OILY
WATER.

4. THE UNIT MUST BE EMPTIED AFTER THE CLOSURE DEVICE OPERATION AND THE COALESCER MEDIA
SHOULD BE INSPECTED.
No. REVISION-1 APP'D 2020
5. OIL PROBE SHOULD BE POSITIONED TO DETECT THE ACCUMULATION OF OIL WHEN LOW/NO FLOW
CONDITIONS. WHEN THE ALARM OPERATES THE OIL SHOULD BE REMOVED AFTER REACHING 90% OF CLIENT
THE MAXIMUM OIL STORAGE CAPACITY.
Ø200 BYPASS ARRANGEMENT
775

6. THE SEPARATOR SHOULD BE INSPECTED FREQUENTLY AS EXPERIENCE DICTATES.


Ø200

Ø200
1600

TITLE
OIL/WATER SEPARATOR - OIL REMOVAL PROCEDURE
STANDARD DRAWINGS
MAIN ROADS
800

1. OIL SHOULD BE REMOVED WHEN NO FLOW ENTERING THE UNIT.

2. REMOVE THE OIL BEFORE ATTEMPTING TO REMOVE THE COALESCER MEDIA. DRAWING TITLE
3. REMOVE THE OIL FLOATING ON THE SURFACE IN THE SEPARATION CHAMBER BY DISLODGING HOSE.

4. LOWER THE HOSE TO REACH THE BOTTOM AND REMOVE SLUDGES AT THE BOTTOM OF THE TANK. SURFACE DRAINAGE DETAILS OF
5248
5. REMOVE THE OIL PROBE, CLEAN AND VERIFY IF WORKING PROPERLY. GRP OIL WATER SEPARATOR
6. REMOVE COALESCER MEDIA - IF REQUIRED - CLEAN OR REPLACE.
PLAN VIEW 7. CHECK THE FLOAT/CLOSURE DEVICE OPERATION.
DRAWN - SCALE N.T.S
OIL WATER SEPARATOR DIMENSION NOTE: THE ABOVE PROCEDURES ARE GUIDELINES AND MIGHT VARIES AR PER MANUFACTURER'S CHECKED - DATE -
(REFERENCE : MANUFACTURER CATALOGUE) RECOMMENDATIONS
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
N-240

THIRD EDITION - APRIL 2022


NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS INDICATED
OTHERWISE.

2. IF THERE IS DISCREPANCY BETWEEN THE REQUIREMENTS


IN THE SPECIFICATIONS AND THOSE SHOWN ON THIS
DRAWING, THE SPECIFICATIONS SHALL BE FOLLOWED.

3. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL


BE IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS
AND SHALL BE VERIFIED BY THE ENGINEER.

4. LADDERS TO BE PROVIDED IF DEPTH IS GREATER THAN 2m.


D
5. ALL DIMENSIONS ARE GIVEN FOR GUIDANCE ONLY, UNITS,
E DIMENSIONS AND ARRANGEMENT SHALL BE MODIFIED
200 1500 200 200 1500 200
ACCORDING TO SITE CONDITIONS, THE DESIGN FLOW

200
CALCULATIONS TO BE APPROVED BY THE ENGINEER.
200

OIL COLLECTION
CHAMBER WITH 600x600
HEAVY DUTY ACCESS 6. THE REINFORCED CONCRETE OIL WATER SEPARATOR IS
1500

1500
COVER COMMONLY USED FOR HIGH FLOWS.

100mmØ AIR VENT


200

200
300
2000 200 2500 200 2500 300
300 2000 200 2500 200 2500 300 PUDDLE FLANGE
(TYPICAL)

300

300
500mmØ GRP 500mmØ GRP

2100
1500
C C

W
INLET
OUTLET TO
DISTRIBUTION MANHOLE

300

300
100mmØ AIR VENT 100mmØ AIR VENT
TOP PLAN
E D DI MANHOLE COVER DI MANHOLE COVER

300 L 300

SECTIONAL PLAN

1900 VARIES 2100 2100

200 1500 200 300 1500 300 300 1500 300


100mmØ AIR VENT CLASS 'A
DI MANHOLE COVER DI MANHOLE COVER CONCRETE HAUNCH THICKNESS 150mm'
CLEAR OPENING HEAVY
100mmØ AIR VENT 100mmØ AIR VENT
DUTY DI COVER AND FRAME
OUTLET PIPE TO OIL REFERENCE DRAWINGS AND DOCUMENTS
COLLECTION CHAMBER 3 COATS RUBBERISED BITUMIN EMULSION 3 NO. 50
PRE-CAST CONCRETE EXTENSION RINGS (TYP) PAVED UNPAVED
PROTECTED WITH 3 COATS OF EPOXY PAINT

75
FGL FGL FGL FGL FGL
PUDDLE FLANGE 3 COATS OF EPOXY PAINT PROTECTION
150x150 SQ. VENTS

250
500mmØ GRP 150x150 SQ. (TYPICAL)
(TYPICAL) VENTS (TYPICAL) TO ALL EXPOSED INTERNAL CONCRETE 200mmØ uPVC
500mmØ GRP SURFACES 600

REINFORCED CONCRETE REINFORCED CONCRETE


GRP LAMINATE OR 10mm EPOXY MORTAR
VARIES 350

350

GRADE C25 IN WALLS GRADE C25 IN WALLS


INLET OUTLET TO BENCHING AND CHANNEL
VARIES

& BASE SLAB & BASE SLAB


350

350

350
350
S.S. CLAMPS
WATERPROOFING MEMBRANE TYPE A
1100

1100

(TYPICAL)
D

1100
S.S. CLAMPS

1100
MASS CONCRETE WITH 2 LAYERS OF ASPHALT
Ø500mm GRP (TYPICAL) HARDBOARD PROTECTION (TYP.)

75
TEE (TYP.)
WATERPROOFING MEMBRANE TYPE A ONLY
NO HARDBOARD UNDER BOTTOM SLAB (TYP.) 100 200 1500 200 100

300 25mm SCREED


300 CONCRETE CLASS 'C15' CONCRETE BLINDING (TYP.)
450 2000 200 2500 200 2500 300 450 BLINDING
OIL COLLECTION No. REVISION-1 APP'D 2020
8000 LAYER OIL SEPARATOR
CHAMBER OIL SEPARATOR CLIENT
8900

SECTION D-D SECTION E-E


SECTION C-C
TITLE
STANDARD DRAWINGS
MAIN ROADS
DRAWING TITLE

SURFACE DRAINAGE DETAILS


OF REINFORCED CONCRETE
OIL WATER SEPARATOR

DRAWN - SCALE N.T.S.


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
N-241

THIRD EDITION - APRIL 2022


NOTES:
C 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS INDICATED
OTHERWISE.
250 1800 250 250 1800 250
2. IF THERE IS DISCREPANCY BETWEEN THE REQUIREMENTS
LIFTING POCKET LIFTING POCKET IN THE SPECIFICATIONS AND THOSE SHOWN ON THIS
DRAWING, THE SPECIFICATIONS SHALL BE FOLLOWED.

3. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL


300 300

W1 (W1=O/D+200 MIN.)
BE IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS
W (W=O/D+200 MIN.)

MIN MIN
AND VERIFIED BY THE ENGINEER.

18
A.
DI

00
4. THE REINFORCEMENT ARE FOR GUIDANCE ONLY.THE
D1

A A B B

D2
00

DI
CONTRACTOR SHALL PREPARE AND SUBMIT DRAWING

18

A.
SHOWING REINFORCEMENT DETAILS WITH REQUIRED
STRUCTURAL CALCULATIONS FOR THE PRIOR APPROVAL OF
THE ENGINEER.
REINFORCEMENT
VARIES ACCORDING TO REFER TO SECTION
D2>D1 5. THE DIFFERENTIAL SETTLEMENT IS EXPECTED, SO A SHORT
DIMENSION OF LONG
RADIUS ELBOW (MIN. 250mm) PIECE OF PIPE WITH APPROPRIATE LENGTH SHALL BE
PROVIDED FOR BOTH SIDES OF THE STRUCTURE
SUBJECTED TO THE APPROVAL OF ENGINEER. FOR DETAILS
OF SHORT PIECE REFER TO DRAWING No. N-220A.
PLAN VIEW A1 PLAN VIEW A3
250 1800 250 250 1800 250 6. DIMENSIONS OF PRECAST BASE AND INTERMEDIATE UNITS
ARE INDICATIVE ONLY.
LIFTING POCKET LIFTING POCKET
7. THE SHOWN CHAMBER DIMENSIONS ARE ACCEPTABLE FOR
FORCE MAIN PIPE DIAMETER UP TO 200mm. FOR BIGGER
PIPE DIAMETERS, THE CHAMBER DIMENSIONS SHALL BE
GRP ACCESS LADDER DESIGNED ACCORDINGLY.

8. RECTANGULAR DISCHARGE CHAMBERS CAN BE USED FOR


18

18
50 DIA.
PRESSURE DISSIPATION OF FORCE MAINS. DIMENSIONS TO
00

00
LAP
A A B B SUIT INCOMING FORCE MAIN DIAMETERS. (GENERALLY
DI

DI
A.

A.
WIDTH = 3x PIPE DIAMETER AND LENGTH = 3x WIDTH).

REINFORCEMENT
50 DIA REFER TO SECTION
LAP

PLAN VIEW A2
C
TOP OF FRAME
RECESS COVER 5mm (MIN.) BELOW FINAL PLAN VIEW A4
900x900x75 THICK PRE-CAST GRADE IN TRAFFIC AREAS
CONCRETE SEATING RING BEDDED (MATCH FINAL GRADE IN SIDEWALK AREAS)
ON CEMENT SAND MORTAR
PRECAST COVER SLAB
FINAL GRADE IN GREEN AREAS FINAL GRADE IN GREEN AREAS

2300 2300 2300


200 MIN.

200 MIN.

200 MIN.
250 1800 250 250 1800 250 250 1800 250
900 900 900 T20-200(T+B)
5mm

T20-200(T+B)
REFERENCE DRAWINGS AND DOCUMENTS
VARIES TO 300

VARIES TO 300

VARIES TO 300
MAKE UP UNIT

MAKE UP UNIT

MAKE UP UNIT
Z TIES AROUND
AS PER MATERIAL
SUBMISSION 10@200 10@200
WATERPROOFING MEMBRANE AS SPECIFIED. A4 A4 A4 A4

300

300

300
GRP LINER 6 THICK KEYED
300
INTERMEDIATE UNIT

INTERMEDIATE UNIT

INTERMEDIATE UNIT
TO CONCRETE.

GRP LADDER
1500

1500

1500
10@200 EF 10@200 EF
A2 A2 10@200 EF

VARIES ACCORDING TO 10@200 10@200 10@200 No. REVISION-1 APP'D 2020


DIMENSION OF LONG U-BARS U-BARS U-BARS
THE BACK FILLING MATERIAL SHALL BE SELECTED CLIENT
RADIUS ELBOW (MIN. 250mm) IN ACCORDANCE WITH THE SPECIFICATIONS.

JOINT BETWEEN PIPE & PRECAST BASE


MAX.

MAX.
250

250
TO BE FILLED WITH APPROVED GROUT/ SEALANT D2
TITLE
300
IN SITU GRP GRAVITY PIPE OF DIAMETER D2
300
GRADE C20
10@200 EF
STANDARD DRAWINGS
BASE UNIT

BASE UNIT

BASE UNIT
LINING NON 10@200
SLIP SURFACE
CONCRETE BENCHING
U-BARS MAIN ROADS
1500

1500

1500
300

300

A1 A1 A3 A3 A3 A3
DRAWING TITLE
200mm THICK
CONCRETE SURROUND.
SURFACE DRAINAGE DETAILS OF
400

400

400

150(TYP.)
DISCHARGE CHAMBER
16@150 T+B VARIES 16@150 T+B VARIES
FORCE MAIN OF 50 THICK PROTECTION GRADE C20
GRADE C20 16@150 T+B VARIES 16@150 T+B VARIES
DIAMETER D1 CONCRETE SCREED
CONCRETE BENCHING
WATER-PROOFING MEMBRANE AS SPECIFIED
DRAWN - SCALE N.T.S
200mm THICK
CONCRETE SURROUND
75mm THICK BLINDING REINFORCEMENT DETAILS REINFORCEMENT DETAILS CHECKED - DATE -
SECTION A-A COMPACTED SOIL / MATERIAL AS SPECIFIED
SECTION B-B SECTION C-C APPROVED - SIZE A1
POLYTHENE SHEET AS SPECIFIED
PROJECT DWG.
No. - No.
N-242

THIRD EDITION - APRIL 2022


NOTES:
3d (MIN.) SIDEWALK CARRIAGEWAY MEDIAN CARRIAGEWAY SIDEWALK 2d (MIN.)
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS INDICATED
OTHERWISE.

2. IF THERE IS DISCREPANCY BETWEEN THE REQUIREMENTS IN

5.0m (MIN.)
THE SPECIFICATIONS AND THOSE SHOWN ON THIS DRAWING,

5.0m (MIN.)

2W OR
1.0m 1.0m

2W OR
THE SPECIFICATIONS SHALL BE FOLLOWED.
(MIN.) (MIN.)
3. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL BE IN
ACCORDANCE WITH THE PROJECT SPECIFICATIONS AND

W (MIN.)

W (MIN.)
VERIFIED BY THE ENGINEER.

W1
4. THE REINFORCEMENT ARE FOR GUIDANCE ONLY.THE

W2
CONTRACTOR SHALL PREPARE AND SUBMIT DRAWING SHOWING
REINFORCEMENT DETAILS WITH REQUIRED STRUCTURAL

Wc
CALCULATIONS FOR THE ENGINEER APPROVAL.

3W (MIN.)

3W (MIN.)
W

W
3d 2d 5. ALL EXPOSED CONCRETE EDGES SHALL HAVE A 25x25mm
CHAMFER.

Wc
6. RIPRAP SHALL BE PROVIDED ON THE UPSTREAM AND
DOWNSTREAM SIDES OF CULVERT. THE EXTENT OF RIPRAP

W (MIN.)

W (MIN.)
SHALL SUIT SITE CONDITIONS.

W1
7. CONCRETE COVER TO REINFORCEMENT SHALL BE AS PER
SPECIFICATION.
5.0m (MIN.)

5.0m (MIN.)
2W OR

2W OR
8. APPROACH SLABS SHOULD BE PROVIDED FOR FILL HEIGHTS
LESS THAN OR EQUAL TO 0.60m.

9. FOR SITES WITH HIGH GROUND WATER, THE CONTRACTOR IS


REQUIRED TO PERFORM A STABILITY CHECK FOR THE
3d (MIN.) 2d (MIN.) STRUCTURES AGAINST UPLIFT/FLOATATION CONSIDERING
DIFFERENT CASES OF LOADING TO THE APPROVAL OF THE
DOWNSTREAM PROTECTION EXTEND GROUTED
PLAN
UPSTREAM PROTECTION EXTEND GROUTED ENGINEER.
RIPRAP (d=DEPTH OF WATER) RIPRAP (d=DEPTH OF WATER)
10. LOCATION OF DRAINAGE CULVERT SHALL BE DECIDED ON SITE
CULVERT LENGTH SUBJECT TO THE APPROVAL OF THE ENGINEER.

3d WALL LENGTH SIDEWALK CARRIAGEWAY MEDIAN CARRIAGEWAY SIDEWALK WALL LENGTH 3d

H
SCOUR PROTECTION AT OUTLET SCOUR PROTECTION AT INLET W1 W W2 W W1 d WATER DEPTH
RC TOP SLAB OF CULVERT H MAX. HEIGHT OF FILL
D DEPTH OF CULVERT
SLOPE RECOMMENDED EMBANKMENT SLOPE
SLOPE

T2
W TOTAL WIDTH OF CULVERT
SEE DETAIL-1 Wc WIDTH OF CULVERT CELL
1
2 W1 THICKNESS OF END WALL
GROUTED RIPRAP THICKNESS GROUTED RIPRAP THICKNESS W2 THICKNESS OF MIDDLE WALL
(1.5 x STONE DIAMETER LENGTH OF CULVERT
(1.5 x STONE DIAMETER
T1 THICKNESS OF BOTTOM SLAB
OR 150mm MIN.)
OR 150mm MIN.) BETWEEN CONSTRUCTION T2 THICKNESS OF TOP SLAB
JOINTS TO BE NOT FLOW DIRECTION LENGTH OF CULVERT BETWEEN EXPANSION
MORE THAN 15m JOINTS TO BE NOT MORE THAN 35m CJ CONSTRUCTION JOINT
EJ EXPANSION JOINT

D
CONSTRUCTION JOINT EXPANSION JOINT CONSTRUCTION JOINT 100mm BLINDING
GEOTEXTILE (SEE DETAIL-4) (SEE DETAIL-3) (SEE DETAIL-4) CONCRETE GEOTEXTILE
FILTER MATERIAL CUT OFF WALL SHOULD BE CAST FILTER MATERIAL
AGAINST EARTH
TYPICAL LONGITUDINAL SECTION OF CULVERT
300 20 EJ.

T1
300 25 DIA. DOWEL BAR 300 LONG AT 500 C/C
900

100
TOP PORTION TO BE WRAPPED IN DENSO TAPE, 12mm THICK FILLER
SPLIT 150 IN BRACKET AND 150 IN SLAB REFERENCE DRAWINGS AND DOCUMENTS

BLINDING, C15 CONCRETE (TYP.)


3 LAYERS OF
Ø20-150 ROOFING FELT TYPICAL CROSS SECTION OF CULVERT
Ø16-150

DETAIL "1" SEE DETAIL-2

Ø16-150 Ø20-150

TRANSVERSE STEEL APPROACH SLAB


H≤ 0.6m PROVIDE MIN LENGTH 4000
50

H
WATER STOP W1 W W2 APPROACH SLAB W1
4Ø 16

300 300
5% 5%

T2
No. REVISION-1 APP'D 2020
300

300
Ø16-150
T

DETAIL "2" CLIENT

300
300
LONGITUDINAL BARS SAME DIAMETER AS 300
D

LONGITUDINAL REINFORCEMENT WATER STOP ON ALL SURFACES TITLE


DETAIL-3 400 400
EXPANSION JOINT DETAILS
IN CONTACT WITH SOIL STANDARD DRAWINGS
APPROACH SLAB
MIN LENGTH 4000 SEE DETAIL-5
MAIN ROADS
SEALANT
REINF. STEEL JOINT FILLER DRAWING TITLE
MATERIAL
10
CAP WITH COMPRESSIBLE
T1

MATERIAL
SURFACE DRAINAGE TYPICAL
25

ON DEBONDED SIDE
100

DETAILS OF BOX CULVERT


T1

LONGITUDINAL BARS TO BE BEND AS SHOWN


TRANSVERSE STEEL
JOINT SEALANT
20 DIA. SMOOTH DOWEL BAR PAINTED & TYPICAL CROSS SECTION OF CULVERT
LUBRICATED ON ONE SIDE ONLY TO
PREVENT BOND WITH CONCRETE AT 300mm FOR FILL COVER LESS THAN 0.60m DRAWN - SCALE N.T.S
DETAIL-5
DETAIL-4 CHECKED - DATE -
LONGITUDINAL PART SECTION
CONSTRUCTION JOINT DETAIL APPROVED - SIZE A1
CONTRACTION JOINT DETAIL
PROJECT DWG.
No. - No.
N-243

THIRD EDITION - APRIL 2022


NOTES:

3d (MIN.) VERGE SHOULDER CARRIAGEWAY MEDIAN CARRIAGEWAY SHOULDER VERGE 2d (MIN.)


1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS INDICATED
d=WATER DEPTH d=WATER DEPTH OTHERWISE.

2. IF THERE IS DISCREPANCY BETWEEN THE REQUIREMENTS IN


THE SPECIFICATIONS AND THOSE SHOWN ON THIS DRAWING,
THE SPECIFICATIONS SHALL BE FOLLOWED.

3. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL BE IN

5.0m (MIN.)

5.0m (MIN.)
ACCORDANCE WITH THE PROJECT SPECIFICATIONS AND

2W OR

2W OR
VERIFIED BY THE ENGINEER.

(MIN.)

(MIN.)
4. THE CONTRACTOR SHALL PREPARE AND SUBMIT DRAWING

1000

1000
SHOWING REINFORCEMENT DETAILS WITH REQUIRED
STRUCTURAL CALCULATIONS FOR THE ENGINEER APPROVAL.

ROAD
5. ALL EXPOSED CONCRETE EDGES SHALL HAVE A 25 x 25mm

3W (MIN.)
W

W
3W (MIN.)
CHAMFER.

°
30
6. RIPRAP SHALL BE PROVIDED ON THE UPSTREAM AND

250
DOWNSTREAM SIDES OF CULVERT. THE EXTENT OF RIPRAP

30°
SHALL SUIT SITE CONDITIONS.

250 250
3d 2d
A A

W
7. CONCRETE COVER TO REINFORCEMENT SHALL BE AS PER
SPECIFICATIONS.

D
250

500mm (MIN.)

30°
30°

8. R.C. PIPE GRADE SHALL BE ACCORDING TO BACKFILLING DEPTH

D/2 OR
PIPE CULVERT
& BEDDING CALCULATIONS.
GUARD RAIL

W
300 300
GUARD RAIL 9. FOR SITES WITH HIGH GROUND WATER, THE CONTRACTOR IS
(MIN.) (MIN.)
REQUIRED TO PERFORM A STABILITY CHECK FOR THE
STRUCTURES AGAINST UPLIFT/FLOATATION CONSIDERING
(MIN.)

(MIN.)
300 300
1000

1000
DIFFERENT CASES OF LOADING TO THE APPROVAL OF THE
(MIN.) (MIN.)
5.0m (MIN.)

5.0m (MIN.)
ENGINEER.
2W OR

2W OR
10. LOCATION OF DRAINAGE CULVERT SHALL BE DECIDED ON SITE
SUBJECT TO THE APPROVAL OF THE ENGINEER.

11. PIPE SIZES & Nos. SHALL BE AS PER THE DESIGN FLOW
REQUIREMENTS AND TO THE APPROVAL OF THE ENGINEER.

PLAN

VERGE SHOULDER CARRIAGEWAY MEDIAN CARRIAGEWAY SHOULDER VERGE

F.R.L. F.R.L.
300
(MIN.)

(MIN.)
COVER 700x700 DUCTILE
300
300

300
B (MIN.) -2.0%
LEVEL IRON GRATE
-2.0% (MIN.)
B
4 OR 6 10:1 10:1 4 OR 6
1 1
GROUTED RIPRAP
GROUTED RIPRAP THICKNESS
THICKNESS

(MIN.)
(MIN.)

(1.5 x STONE DIAMETER

100
100

(1.5 x STONE DIAMETER


OR 150mm MIN.)
OR 150mm MIN.)

SHORT PIECE PIPE FOR SHORT PIECE PIPE FOR 300 300

SAND TRAP

(MIN.)
(MIN.)

NATURAL GROUND R.C. PIPE AS SPECIFIED

750
750

300 300 DIFFERENTIAL SETTLEMENT DIFFERENTIAL SETTLEMENT


GEOTEXTILE GEOTEXTILE REFERENCE DRAWINGS AND DOCUMENTS

500
FILTER MATERIAL SHORT PIECE PIPE FOR FILTER MATERIAL
DIFFERENTIAL SETTLEMENT

SECTION A-A
B B

3W (MIN.)

W W W

EDGE OF SHOULDER GUARD RAIL EDGE OF VERGE

No. REVISION-1 APP'D 2020


CLIENT
(MIN.)
300

VARIES

TITLE
GROUTED RIPRAP THICKNESS
(1.5 x STONE DIAMETER OR 150mm MIN.)
GROUTED RIPRAP THICKNESS
(1.5 x STONE DIAMETER OR 150mm MIN.)
STANDARD DRAWINGS
250 250
MAIN ROADS
NATURAL GROUND LEVEL NATURAL GROUND LEVEL
D

DRAWING TITLE

SURFACE DRAINAGE TYPICAL


(MIN.)
100

DETAILS OF PIPE CULVERT


150mm THICK
GEOTEXTILE 1000 D/2 OR 1000 GROUTED RIPRAP
GEOTEXTILE

(MIN) 500mm (MIN) (MIN)


FILTER MATERIAL FILTER MATERIAL DRAWN - SCALE N.T.S
PLAIN CONCRETE
REINFORCED CONCRETE
SECTION B-B 50mm (MIN.) CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
N-244

THIRD EDITION - APRIL 2022


NOTES:

1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS INDICATED


OTHERWISE.
SHOULDER SHOULDER
2. IF THERE IS DISCREPANCY BETWEEN THE REQUIREMENTS
IN THE SPECIFICATIONS AND THOSE SHOWN ON THIS
GROUTED RIPRAP PROTECTION BLANKET
DRAWING. THE SPECIFICATIONS SHALL BE FOLLOWED.
GROUTED RIPRAP PROTECTION BLANKET
3. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL
BE IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS

A
AND VERIFIED BY THE ENGINEER.
WEEPHOLES Ø75mm.
SHOULDER (SEE NOTE 5)
4. WEEPHOLES ARE PLACED @ 0.5m. FROM TOE AND
GROUTED

A
VARIES

VARIES
STAGGERED AT 1.00m. VERTICALLY AND 3.00m.
RIPRAP
PROTECTION HORIZONTALLY AND THE ARRANGEMENT SUBJECT TO

30
BLANKET STUBS AT 10.00m INTERVALS & ENGINEER'S APPROVAL.

A
AT THE ENDS OF PROTECTION

10
30
10

00
5. GRADATION OF THE FILTER MATERIAL SHOULD SATISFY THE

00

0
GRAVEL FILTER
VARIES

GROUND LEVEL GROUND LEVEL 300 FOLLOWING CRITERIA:


(SEE NOTE 5)
GROUND LEVEL
a) IN RELATION TO BASE MATERIAL RETAINED BEHIND THE
30

A
1.50 MIN. OR AS DIRECTED 1.50m MIN. OR AS DIRECTED STUBS AT 10m INTERVALS & FILTER
0

PLACE RIPRAP AGAINST


500

BY THE ENGINEER. BY THE ENGINEER. AT THE ENDS OF PROTECTION - D15f / D85b < 5 *f=FILTER
UNDISTURBED MATERIAL
- 5 < D50f / D50b < 25 *b=BASE
BACKFILL TO BE COMPACTED BACKFILL TO BE COMPACTED
BACKFILL TO BE PLACE RIPRAP AGAINST - D20f / D20b > 5
500 PLACE RIPRAP AGAINST
COMPACTED UNDISTURBED MATERIAL
UNDISTURBED MATERIAL b) IN RELATION TO WEEPHOLES
750 750 - D85f / Dhole > 1-2

GROUTED RIPRAP SLOPE PROTECTION SECTION WHERE D15f, D20f, D50f AND D85f ARE USED TO DESIGNATE
FOR HEIGHT OF PROTECTION < 1.00m
GROUTED RIPRAP SLOPE PROTECTION THE SIZE OF THE SIEVE THAT ALLOWS 15%, 20%, 50% AND
SECTION 85% RESPECTIVELY BY WEIGHT OF THE FILTER MATERIAL
FOR HEIGHT OF PROTECTION ≥ 1.00m AND ≤ 2.00m.
GROUTED RIPRAP SLOPE PROTECTION WITH WEEPHOLES TO PASS THROUGH IT.
FOR HEIGHT OF PROTECTION > 2.00m

ALSO, D20b, D50b AND D85b ARE USED TO DESIGNATE THE


SIZE OF THE SIEVE THAT ALLOWS 20%, 50% AND 85%
RESPECTIVELY BY WEIGHT OF THE BASE MATERIAL TO
PASS THROUGH IT. Dhole IS USED TO DESIGNATE THE
DIAMETER OF THE WEEPHOLE..

IF ONE LAYER OF THE FILTER DOES NOT SATISFY THE


SHOULDER ABOVE CRITERIA, SEVERAL LAYERS MAY BE USED,
PROVIDED THAT EACH LAYER IS AT LEAST GREATER OF 5 x
D50f OR150 mm THICK.

16mm Ø BARS @ 200mm


CENTRES (BOTH WAYS)

12mm Ø BARS @ 0.30m

B
SHOULDER
12mm Ø BARS @ 0.30m
LOOSE RIPRAP

60
VARIES
CENTRES (BOTH WAYS)
D50 = 0.50m

0
REINFORCED CONCRETE WEEPHOLES Ø75mm. STAGGERED
PROTECTION BLANKET

15
GROUND LEVEL
1.00m. VERT.& 3.00m. HORIZ. (SEE NOTE 5)

500
12

200 1000
VARIES

B
300

1000
GROUND LEVEL REFERENCE DRAWINGS AND DOCUMENTS
GRAVEL FILTER (SEE NOTE 5)

12mm Ø BARS @ 300 CENTRES


500

6000 300 12mm Ø BARS @ 0.3m. C/C


12mm Ø BARS @ 300 CENTRES FILTER

POUR AGAINST UNDISTURBED MATERIAL 14mm Ø BARS THRU-OUT TOE WALL


300

REINFORCED CONCRETE SLOPE PROTECTION REINFORCED CONCRETE SLOPE PROTECTION


FOR HEIGHT OF PROTECTION < 1.00m FOR HEIGHT OF PROTECTION > 1.00m

No. REVISION-1 APP'D 2020


LIMITS OF PROTECTION AS SHOWN ON THE PLANS CLIENT
OR DIRECTED BY THE ENGINEER
LIMITS OF PROTECTION AS SHOWN ON THE PLANS 6.00m MAX. SPACING 6.00m MAX. SPACING
OR DIRECTED BY THE ENGINEER
150

10.00m MAX. SPACING 10.00 MAX. SPACING 12mm Ø BARS @ 300


100 12mm PREMOLDED FILLER
CENTRES (BOTH WAYS)
END STUB INTERMEDIATE STUB TITLE
STANDARD DRAWINGS
MAIN ROADS
600
300

16mm Ø BARS @ 0.20m


6Ø12mm
COMPACTED EMBANKMENT
1000

COAT LEDGE WITH


EXCAVATE TO NEAT LINES EXCAVATE TO NEAT LINES
MASTIC ASPHALT DRAWING TITLE
& PLACE THE STONES AND POUR CONCRETE
END STUB 300 12mm Ø BARS @ 300 300
& GROUT. WITHOUT FORMS
COMPACTED
600 EMBANKMENT 600 INTERMEDIATE STUB
SURFACE DRAINAGE
TYPICAL DETAILS OF
SECTION OF STUBS EMBANKMENT PROTECTION
SECTION OF STUBS SECTION B - B
SECTION A - A REINFORCED CONCRETE SLOPE PROTECTION
FOR HEIGHT OF PROTECTION ≥ 1.00m DRAWN - SCALE N.T.S
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No. N-245

THIRD EDITION - APRIL 2022


NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS INDICATED
OTHERWISE.

MINIMUM LONGITUDINAL SWALE


PERFORATED PIPE IN CASE 2. IF THERE IS DISCREPANCY BETWEEN THE REQUIREMENTS
OF HIGH GROUND WATER IN THE SPECIFICATIONS AND THOSE SHOWN ON THIS
DRAWING, THE SPECIFICATIONS SHALL BE FOLLOWED.

GRADE OF 1 IN 1000
3. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL
BE IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS
AND VERIFIED BY THE ENGINEER.

4. WHERE SWALE SIDE SLOPES EXCEED 1 IN 4, PROVIDE


GROUTED STONE RIPRAP WITH AN AVERAGE SLOPE DEPTH
OF 300mm OR SIMILAR SCOUR PROTECTION SUBJECT TO
THE APPROVAL OF THE ENGINEER.

5. PLACE GEOTEXTILE FILTER FABRIC UNDER ALL SCOUR


A
PROTECTION AS PER SPECIFICATIONS.

TOP OF SWALE

TOP OF SWALE
MINIMUM LONGITUDINAL SWALE
A
700x700 DUCTILE IRON GRATE

GRADE OF 1 IN 1000
W-BEAM
PERFORATED SUB BASE GUARD RAIL OR CONCRETE BARRIER
Ø300 uPVC DRAINAGE AS SPECIFIED IN ROAD FURNITURE
DESIGN DRAWINGS

APPROXIMATE SLOPE OF SCOUR SECTION TYPICAL SWALE DRAIN PLAN


FROM CHAMBER TO FINISH GROUND FACE
SHALL BE 1 IN 3
VARIES VARIES

6 (MIN.) AND 4 (MAX.) EPOXY COATING CONCRETE TOP OF PAVEMENT


700x700 DUCTILE IRON GRATE TO BE FLUSH WITH TOP O GRATE
TO SUIT SITE CONSTRAINTS OR
AS SPECIFIED (SEE NOTE 4)
REFERENCE DRAWINGS AND DOCUMENTS

MIN.
H=4 TO 6

100
COVER LEVEL
1 EPOXY
SWALE DEPTH

COATING MIN. 300 THICK GROUTED RIPRAP OR


1:3 SIMILAR APPROVED SCOUR PROTECTION

1
6 (MIN.) AND 4 (MAX.)
TO SUIT SITE CONSTRAINTS OR
150

BASE OF AS SPECIFIED (SEE NOTE 4)


EPOXY COATING SWALE

GEOTEXTILE OR APPROVED EQUIVALENT FILTER


EXTERIOR UPPER LIMIT OF
FABRIC UNDER SCOUR PROTECTION
WATERPROOFING (TYP.)
C/L OF SWALE
VARIES

No. REVISION-1 APP'D 2020


MIN Ø300 PERFORATED PIPE CLIENT

CHAMBER DETAILS INCLUDING CONCRETE


THICKNESSES AND REINFORCEMENT TO BE
TO NATURAL GROUND/DEPPRESSION
IN ACCORDANCE WITH FLUSH CATCH BASIN
STANDARD DRAWINGS, ADDITIONAL REINFORCEMENT
TITLE
TO BE PROVIDED AROUND GRATE AS SHOWN STANDARD DRAWINGS
MAIN ROADS
500 (MIN.)

DRAWING TITLE

SURFACE DRAINAGE DETAIL OF


SWALE DRAIN IN A CATCH BASIN

BLINDING, C15 CONCRETE (TYP.)


DRAWN - SCALE N.T.S
CHECKED - DATE -
SECTION A-A APPROVED - SIZE A1
PROJECT DWG.
No. - No.
N-246

THIRD EDITION - APRIL 2022


2999 NOTES:
300 2400 299 FLEXIBLE COUPLING
FRAME TYPE 4 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS INDICATED
5000 (MIN.) 200 200 5000 (MIN.) OTHERWISE.
(MIN.) (MIN.)
2. IF THERE IS DISCREPANCY BETWEEN THE REQUIREMENTS
SLOPE1:1 SLOPE1:1 IN THE SPECIFICATIONS AND THOSE SHOWN ON THIS
DRAWING, THE SPECIFICATIONS SHALL BE FOLLOWED.

3. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL


BE IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS

MIN.

MIN.
300

300
SAND TRAP SAND TRAP
BLINDING CONCRETE AND VERIFIED BY THE ENGINEER.
BLINDING CONCRETE
100mm MIN. (TYP.)
100mm MIN. (TYP.)

D2
4. THE THICKNESS OF CONCRETE LINING AS WELL AS THE
SHORT PIPE
ANCHOR DEPTH SHALL BE DETERMINED ACCORDING TO
SOIL CONDITIONS AND APPROVED BY THE ENGINEER ON
SITE.

5. FOR CATCH BASIN DETAILS REFER TO DWG. No. N-200 &


N-201.
SEE NOTE 5

(MIN.)
500

601
300
450 600 1799 (MIN.) 600 450

SECTION A-A

1965

FRAME TYPE 4
(FOR COVER DETAIL REFER
TO DWG. No. N-214)

2115
C B
5000 (MIN.) 200 200 5000 (MIN.)
(MIN.) (MIN.)

MIN.
250
MIN.
250

REFERENCE DRAWINGS AND DOCUMENTS


MIN.

MIN.
250

250
2115
D1

A A
MIN.

MIN.
250

250

.
MAX

30°
30°

MAX
SLOPE 1:1 SLOPE 1:1
.
MIN.

MIN.
250

250
1965
TRIANGULAR DITCH

C RECTANGULAR DITCH B
PLAN
DITCH TO CATCH BASIN CONNECTION No. REVISION-1 APP'D 2020
VARIES
CLIENT
250 250
MIN. MIN.
MIN.
250

TITLE
250 VARIES 250
STANDARD DRAWINGS
MIN. MIN. MAIN ROADS
DRAWING TITLE
MIN.

MIN.
250

250
SURFACE DRAINAGE TYPICAL
100 100
DETAILS OF DITCH OUTLET
MIN. 1 1 MIN. INTO CATCH BASINS
1 1
REINFORCED CONCRETE
0
10

DRAWN - SCALE N.T.S

BLINDING CONCRETE
CHECKED - DATE -
100mm MIN. (TYP.)
APPROVED - SIZE A1
SECTION B-B SECTION C-C
PROJECT DWG.
No. - No. N-247

THIRD EDITION - APRIL 2022


NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS INDICATED
OTHERWISE.

2. IF THERE IS DISCREPANCY BETWEEN THE REQUIREMENTS


IN THE SPECIFICATIONS AND THOSE SHOWN ON THIS
DRAWING, THE SPECIFICATIONS SHALL BE FOLLOWED.
MEDIAN CARRIAGE WAY VERGE
3. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL
BE IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS
AND VERIFIED BY THE ENGINEER.

ASPHALT AND SUB BASE


4. SUBSURFACE DRAINS ARE PROVIDED TO CONTROL THE
GROUND WATER LEVEL TO BE UNDER PAVEMENT LAYERS

COURSE (TYP.)
AS RAISING OF GROUND WATER SHOULD BE CAUSED BY
EXCESS IRRIGATION WATER, HIGH TIDES, TRAPPED
COMPACTED GRANULAR SUB BASE
WATER OR UNDERGROUND FLOWS FROM UPLAND AREAS.
5%
5. THE SUBSURFACE PIPE LEVEL AND DIAMETER SHOULD BE
EXISTING PAVEMENT DETERMINED ACCORDING TO IT'S FUNCTION AS
COMPACTED GRANULAR SUB BASE

300
LESSENING / MAINTAINING THE GROUNDWATER LEVEL OR
/ AND EXCESSIVE IRRIGATION WATER DRAINAGE.
2.50%

300
DEPTH VARIES

DEPTH VARIES
(MIN.)
150
FILTER MATERIAL

(MIN.)
250
FILTER MATERIAL
500 (MIN.) GEOTEXTILE
GEOTEXTILE SUB-GRADE
Ø225 (MIN.)
SUB-BASE
PERFORATED
(MIN.)

(MIN.)
Ø225 (MIN.) PERFORATED uPCV PIPE uPVC PIPE
150

150
600
600
(MIN.)
(MIN.)

SUB SURFACE DRAIN SECTIONS ALONG HIGHWAY

REFERENCE DRAWINGS AND DOCUMENTS

W-BEAM GUARD RAIL

CONCRETE BARRIER
1000 (MIN.) 1000 (MIN.)

℄ OF SUB SURFACE BARRIER OPENING ℄ OF SUB SURFACE


DRAINAGE PIPE
DRAINAGE PIPE 3000
(MIN.)

3000
150

TOP OF (TYP.) TOP OF


(TYP.) PAVEMENT PAVEMENT
1 1
6 6
1 1
6
(MIN.)

(MIN.)
6
200

200
COMPACTED COMPACTED GRANULAR SUB BASE

GRANULAR
SUB BASE
(MIN.)

(MIN.)
DEPTH VARIES
Ø225 (MIN.) No. REVISION-1 APP'D 2020
200
300

CONCRETE FOUNDATION
uPVC
PERFORATED CLIENT
Ø225 (MIN.) uPVC PERFORATED PIPE
PIPE

GEOTEXTILE FILTER FABRIC GEOTEXTILE FILTER FABRIC


GRANULAR FILTER MATERIAL GRANULAR FILTER MATERIAL
(MIN.)

TITLE
(MIN)
150

150

STANDARD DRAWINGS
MAIN ROADS
100 OR D/2 100 OR D/2 100 OR D/2 100 OR D/2
DRAWING TITLE
(MIN.) (MIN.) (MIN.) (MIN.)

TYPICAL SECTION FOR SUB SURFACE DRAINAGE TYPICAL SECTION FOR SUB SURFACE DRAINAGE SURFACE DRAINAGE TYPICAL
IN SWALE DRAIN WITH CONCRETE BARRIER IN SWALE DRAIN WITH W-BEAM GUARD RAIL
DETAILS OF SUB SURFACE DRAINAGE

DRAWN - SCALE N.T.S


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
N-248

THIRD EDITION - APRIL 2022


NOTES:
B
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS INDICATED
OTHERWISE.

2. IF THERE IS DISCREPANCY BETWEEN THE REQUIREMENTS


IN THE SPECIFICATIONS AND THOSE SHOWN ON THIS
DRAWING, THE SPECIFICATIONS SHALL BE FOLLOWED.
500

3. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL


BE IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS
AND VERIFIED BY THE ENGINEER.

800 4. PLACE GEOTEXTILE FILTER FABRIC UNDER ALL SCOUR


PROTECTION WITH AN OVERLAP OF 1000mm AT JOINTS.

5. THE DETAILS SHOWN FOR A SOAKAWAY IS COMMONLY


USED FOR SMALL CATCHMENTS IN AREAS HAVING DEEP
GROUND WATER AND WHERE THERE IS A SPACE
LIMITATIONS TO PROVIDE TRENCH SOAKAWAYS. THIS TYPE
OF SOAKAWAY CAN BE USED IN RURAL AND LANDSCAPED
1000

800
A A URBAN AREAS.

6. THE REINFORCEMENT ARE FOR GUIDANCE ONLY.THE


CONTRACTOR SHALL PREPARE AND SUBMIT DRAWING
SHOWING REINFORCEMENT DETAILS WITH REQUIRED
STRUCTURAL CALCULATIONS FOR THE ENGINEER
APPROVAL.

7. THE NUMBER OF SOAKAWAYS SHALL BE DETERMINED


BASED ON THE DESIGN FLOW AND SOIL CHARACTERISTICS.

8. MAXIMUM DEPTH OF SOAKAWAY SHOULD BE 0.5m MINIMUM


ABOVE THE GROUND WATER TABLE.
500

500 1000 500

PLAN
APPLY EPOXY COATING TO ALL
EXTERIOR CONCRETE SURFACES
B MIN. 300 DEEP GROUTED ROCK RIPRAP OR
REFER DRAWING No. N-200 FOR SIMILAR APPROVED SCOUR PROTECTION
WHERE WATERPROOFING GULLY GRATE AND FRAME DETAILS
MEMBRANE IS NOT PROVIDED
1000 1000
500 100 800 100 500 500 100 800 100 500
150

150

150
EXTERIOR UPPER LIMIT OF GEOTEXTILE OR APPROVED EQUIVALENT FILTER
WATERPROOFING FABRIC UNDER ALL SCOUR PROTECTION EXTERIOR UPPER LIMIT OF WATERPROOFING REFERENCE DRAWINGS AND DOCUMENTS
1000

WATERPROOFING MEMBRANE TYPE A


CONCRETE C35
WITH 2 LAYERS OF ASPHALT
Ø14@200 WATERPROOFING MEMBRANE TYPE A WITH 2 LAYERS Ø14@200 HARDBORAD PROTECTION (TYP.)
OF ASPHALT HARDBORAD PROTECTION (TYP.)
Ø14@200 Ø14@200 Ø14@200 Ø14@200

Ø14@200 Ø14@200

500 500 500 500


EPOXY COATING ON ALL
INTERIOR CONCRETE
SURFACES

GEOTEXTILE OR APPROVED EQUIVALENT


FILTER FABRIC SURROUNDING PERVIOUS
BACKFILL MATERIAL
No. REVISION-1 APP'D 2020
CLIENT

125 50 100 50 100 50 125 125 50 100 50 100 50 125


1000
1000

1000
50

50
TITLE
CONCRETE
STANDARD DRAWINGS
125 50 150

125 50 150
CONCRETE
PERFORATIONS
PERFORATIONS

PERVIOUS BACKFILL / COARSE


MAIN ROADS
AGGREGATE WITH 30% TO 40%
Ø14@200 VOID RATIO Ø14@200 DRAWING TITLE
CJ Ø14@200 CJ Ø14@200

SURFACE DRAINAGE DETAILS


200

OF FLUSH INLET DRAINING IN


A SOAKAWAY CHAMBER
100

100

CONCRETE C25 CONCRETE C25

SUBGRADE COMPACTED
150 500 200 600 200 500 150 TO 95% MAXIMUM DRY DENSITY 150 500 200 600 200 500 150 DRAWN - SCALE N.T.S
2300 2300
CHECKED - DATE -
SECTION A-A SECTION B-B APPROVED - SIZE A1
PROJECT DWG.
No. - No.
N-251

THIRD EDITION - APRIL 2022


NOTES:

1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS INDICATED


OTHERWISE.

2. IF THERE IS DISCREPANCY BETWEEN THE REQUIREMENTS


IN THE SPECIFICATIONS AND THOSE SHOWN ON THIS
DRAWING, THE SPECIFICATIONS SHALL BE FOLLOWED.

3. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL


BE IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS
AND VERIFIED BY THE ENGINEER.

4. WHERE POSSIBLE GULLY CONNECTION TO BE DIRECT TO


CATCH PITS.

5. MAXIMUM DEPTH OF SOAKAWAY SHOULD BE 0.5m MINIMUM


ABOVE THE GROUND WATER TABLE.

6. THE NUMBER OF SOAKAWAYS SHALL BE DETERMINED


BASED ON THE DESIGN FLOW AND SOIL CHARACTERISTICS.

STORM WATER PIPE WITH CONCRETE SURROUND

CL SOAKAWAY RECESS COVER 5mm BELOW


FINAL GRADE IN TRAFFIC AREAS
500 400 1800 400 500 TOP OF FRAME (MATCH FINAL GRADE IN SIDEWALK AREAS)

5mm
GRANULAR FILTER MATERIAL ON ALL GAP BETWEEN PIPE AND FINAL GROUND SURFACE
SIDES OF SOAKAWAY BLOCKWORK TO BE MADE IN GREEN AREAS
MINIMUM SIZE AGGREGATE 37mm UP WITH CONCRETE COVER AT 200mm PITCH IN
CLASS-B CONCRETE

250
100
BOTH DIRECTION

500
VARIES
2600

400

1200
MIN.
100

STORM WATER PIPE WITH


CONCRETE SURROUND

OPEN JOINTED BLOCK WORKS

OPEN JOINTED BLOCK WORKS


(SEE NOTE 6)

GRANULAR FILTER MATERIAL ON ALL


4000

SIDES OF SOAKAWAY
MINIMUM SIZE AGGREGATE 37mm

*
2200 REFERENCE DRAWINGS AND DOCUMENTS

655x755 CLEAR OPENING


HEAVY DUTY DUCTILE IRON GEOTEXTILE FILTER FABRIC GEOTEXTILE FILTER FABRIC
COVER AND FRAME ON
MORTAR BED

A A
500 400 400 500
MIN. MIN.

300

300
900 900
400

600 600 CONCRETE CLASS K250


CL

GRANULAR FILTER MATERIAL


500

MINIMUM SIZE AGGREGATE 37mm No. REVISION-1 APP'D 2020


CLIENT
SECTION A-A

TITLE
STANDARD DRAWINGS
TYPICAL PLAN VIEW MAIN ROADS
BOX SOAKAWAY
DRAWING TITLE

SURFACE DRAINAGE TYPICAL


BOX TYPE SOAKAWAY
STANDARD DETAILS

DRAWN - SCALE N.T.S


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
N-252

THIRD EDITION - APRIL 2022


NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS INDICATED
OTHERWISE.

2. IF THERE IS DISCREPANCY BETWEEN THE REQUIREMENTS


IN THE SPECIFICATIONS AND THOSE SHOWN ON THIS
DRAWING, THE SPECIFICATIONS SHALL BE FOLLOWED.

3. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL


BE IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS
AND VERIFIED BY THE ENGINEER.

4. WHERE GULLY/CATCH PIT CONNECTION RUNS UNDER


CARRIAGEWAY, GRANULAR BED AND SURROUND TO BE
REPLACED BY 150 CONCRETE SURROUND (GRADE C20).

5. SOAKAWAY CHAMBER SHALL PROVIDE A MINIMUM


800 GRP LADDER STORAGE DEPTH OF 2.0m BELOW INCOMING PIPE.
Ø1
MIN. 300uPVC
6. THE SHOWN PRECAST SOAKAWAY IS COMMONLY USED
C C FOR SMALL CATCHMENT HAVING DEEP GROUND WATER
AND WHERE THERE IS SPACE LIMITATIONS TO PROVIDE
TRENCH SOAKAWAYS.
INLET FROM GULLY
(FOR DETAILS REFER DWG. No. N-226)
7. THE SHOWN REINFORCEMENT IS FOR GUIDANCE ONLY THE
SHOP DRAWINGS WITH SUPPORTING CALCULATIONS
SHALL BE PREPARED BY CONTRACTOR AND APPROVED BY
THE ENGINEER.

8. GROUND WATER SHOULD BE 0.50m BELOW THE INVERT


LEVEL OF SOAKAWAY.

PLAN OF SINGLE GULLY AND SOAKAWAY ARRANGEMENT

TOP OF FRAME
FINAL GROUND SURFACE

5mm
IN GREEN AREAS

100
10mm MORTAR BED RECESS COVER 5mm BELOW
FINAL GRADE IN TRAFFIC AREAS
1000 (MAX.)

1000 (MAX.)
(MATCH FINAL GRADE IN SIDEWALK AREAS)
BLOCK

600
600 1 TO 3 COURSES OF PRECAST CONCRETE
C30 RINGS ON CLASS 1 MORTAR
REFERENCE DRAWINGS AND DOCUMENTS
HEAVY DUTY PRECAST COVER SLAB C30
250

CONCRETE. GRP LINER TO SOFFIT

GEOTEXTILE FOLDED OVER THE TOP OF


CRUSHED STONE SURROUND
MIN FALL GEOTEXTILE FILTER FABRIC OR SIMILAR
1%
APPROVED MATERIAL LINING TO EXCAVATION
ADEQUATELY SECURED TO SOAKAWAY COVER SLAB

GRANULAR BED AND SURROUND/ PRECAST CONCRETE CHAMBER RINGS TO BS 556


CONCRETE SURROUND BEDDED ON CLASS 1 MORTAR
2400 (MAX.)

(SEE NOTE 4)

GRP LADDER
1800
No. REVISION-1 APP'D 2020
CLIENT
CRUSHED STONE SURROUND 75mm SIZE WITH
LITTLE OR NO FINES MINIMUM WIDTH 250mm

TITLE
GRADE C20 CONCRETE FOOTING STANDARD DRAWINGS
MAIN ROADS
150

75mm BLINDING CONCRETE GRADE C15


DRAWING TITLE
300 300

CRUSHED STONE 75Ømm


SURFACE DRAINAGE TYPICAL
GRANULAR BEDDING MATERIAL
WITH LITTLE OR NO FINES DETAILS OF CIRCULAR
225mm THICKNESS SECTIONAL ELEVATION C-C
SOAKAWAY PRECAST UNITS

DRAWN - SCALE N.T.S


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
N-253

THIRD EDITION - APRIL 2022


NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS INDICATED
OTHERWISE.
PAVEMENT CONSTRUCTION LAYERS ROAD CROSSING PAVEMENT CONSTRUCTION LAYERS ROAD CROSSING
FOOTPATH LAYERS
37mm NOM. SINGLE STANDARD BACK FILL TO PIPE 37mm NOM. SINGLE 37mm NOM. SINGLE STANDARD BACK FILL TO PIPE CATCH PIT CHAMBER 2. IF THERE IS DISCREPANCY BETWEEN THE REQUIREMENTS IN
SIZE AGGREGATE UNDER ROAD PAVEMENT SIZE AGGREGATE SIZE AGGREGATE UNDER ROAD PAVEMENT
F.G.L. THE SPECIFICATIONS AND THOSE SHOWN ON THIS DRAWING,
ROAD GRADIENT THE SPECIFICATIONS SHALL BE FOLLOWED.

3.0m TO 4.0m MAX.


CATCH PIT CHAMBER 3. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL BE IN
ACCORDANCE WITH THE PROJECT SPECIFICATIONS AND
REMOVABLE 'T' FOR CATCH PIT CHAMBER VERIFIED BY THE ENGINEER.
0.2% MIN. (0.3 TO 0.5% PR CATCH PIT CHAMBER
HIGH PRESSURE EFERABLE)
RODDING 4. MAXIMUM SPACING OF CATCH PIT CHAMBER SHALL NOT EXCEED
ACCESS (TYP.) 0.2% MIN. (0.3 TO 0.5% PR 75 METERS.
EFERABLE)

300Ø uPVC PERFORATED DISTRIBUTOR 5. GROUND WATER LEVEL SHALL BE MINIMUM OF 0.5M BELOW THE
PIPE, PERFORATIONS, 8 HOLES 10mm Ø INVERT LEVEL OF CATCH PITS.
STAGGERED EVERY 200mm (MIN.) SUMP FOR SEDIMENT STORAGE
300Ø uPVC PERFORATED 6. A MINIMUM DISTANCE OF 3m-6m BETWEEN A SUB SURFACE
GRANULAR BEDDING MATERIAL NON-PERFORATED PIPE UNDER DISTRIBUTOR PIPE NON-PERFORATED PIPE UNDER
DRAINAGE SYSTEM AND A BUILDING SHOULD BE ADOPTED
ROAD CROSSING TO EXTEND 1.00m. GRANULAR BEDDING MATERIAL ROAD CROSSING TO EXTEND 1.00m.
BEYOND KERB LINE. DEPENDING ON GROUND CONDITIONS.
BEYOND KERB LINE.
MAX. SPACING 75 METERS MAX. SPACING 75 METERS

COMPACTED BACKFILL
UNDER PAVEMENT
PAVEMENT CONSTRUCTION LAYERS ROAD CROSSING PAVEMENT CONSTRUCTION LAYERS ROAD CROSSING
FOOTPATH LAYERS FOOTPATH LAYERS
37mm NOM. SINGLE STANDARD BACK FILL TO PIPE 37mm NOM. SINGLE STANDARD BACK FILL TO PIPE
SIZE AGGREGATE UNDER ROAD PAVEMENT SIZE AGGREGATE UNDER ROAD PAVEMENT
F.G.L.
ROAD GRADIENT

CATCH PIT CHAMBER

2.50m.
MAX.

3.00m.
MAX.
EFERABLE)
0.2% MIN. (0.3 TO 0.5% PR
EFERABLE) 0.2% MIN. (0.3 TO 0.5% PR

CATCH PIT CHAMBER


300Ø uPVC PERFORATED DISTRIBUTOR
NON-PERFORATED PIPE UNDER 300Ø uPVC PERFORATED NON-PERFORATED PIPE UNDER
PIPE, PERPORATIONS, 8 HOLES 10mm Ø SUMP FOR SEDIMENT STORAGE ROAD CROSSING TO EXTEND 1.00m.
ROAD CROSSING TO EXTEND 1.00m. DISTRIBUTOR PIPE
STAGGERED EVERY 200mm (MIN.) BEYOND KERB LINE. CATCH PIT CHAMBER
BEYOND KERB LINE. GRANULAR BEDDING MATERIAL
GRANULAR BEDDING MATERIAL

TYPE 1 - TYPICAL LONGITUDINAL SECTION OF TRENCH SOAKAWAY UNDER UNPAVED AREAS WITH CATCH PIT CHAMBERS

EXCAVATED TRENCH WITH OPEN GRADED


AGGREGATE WITH MAX. DIA. 75mm AND MIN. COMPACTED BACKFILL
DIA. OF 40mm BACKFILL AND GEOTEXTILE UNDER PAVEMENT
FILTER FABRIC TYPE A CONCRETE SURROUND CATCH PIT CHAMBER

37mm NOM. SINGLE 37mm NOM. SINGLE 37mm NOM. SINGLE


RC PROTECTION SLAB PAVEMENT CONSTRUCTION LAYERS RC PROTECTION SLAB PAVEMENT CONSTRUCTION LAYERS CATCH PIT CHAMBER
SIZE AGGREGATE SIZE AGGREGATE SIZE AGGREGATE
F.G.L.
ROAD GRADIENT

3.0m TO 4.0m MAX.


CATCH PIT CHAMBER REFERENCE DRAWINGS AND DOCUMENTS

REMOVABLE 'T' FOR


HIGH PRESSURE 0.2% MIN. (0.3 TO 0.5% PR
EF ERABLE)
RODDING
ACCESS (TYP.) 0.2% MIN. (0.3 TO 0.5% PR
EFERABLE)

300Ø uPVC PERFORATED DISTRIBUTOR TO MANHOLE


PIPE, PERPORATIONS, 8 HOLES 10mm Ø
SUMP FOR SEDIMENT STORAGE
STAGGERED EVERY 200mm (MIN.)
GRANULAR BEDDING MATERIAL 300Ø uPVC PERFORATED
DISTRIBUTOR PIPE
GRANULAR BEDDING MATERIAL
MAX. SPACING 75 METERS MAX. SPACING 75 METERS

No. REVISION-1 APP'D 2020


CLIENT
CATCH PIT CHAMBER CATCH PIT CHAMBER CATCH PIT CHAMBER

37mm NOM. SINGLE 37mm NOM. SINGLE


RC PROTECTION SLAB PAVEMENT CONSTRUCTION LAYERS RC PROTECTION SLAB PAVEMENT CONSTRUCTION LAYERS
SIZE AGGREGATE SIZE AGGREGATE
F.G.L.
ROAD GRADIENT
TITLE
STANDARD DRAWINGS
MAIN ROADS
2.50m.
MAX.

3.00m.
MAX.

REMOVABLE 'T' FOR


EFERABLE) DRAWING TITLE
0.2% MIN. (0.3 TO 0.5% PR
EFERABLE) 0.2% MIN. (0.3 TO 0.5% PR HIGH PRESSURE
RODDING
ACCESS (TYP.) SURFACE DRAINAGE
TYPICAL TRENCH
300Ø uPVC PERFORATED DISTRIBUTOR
SUMP FOR SEDIMENT STORAGE
300Ø uPVC PERFORATED SOAKAWAY STANDARD
PIPE, PERPORATIONS, 8 HOLES 10mm Ø DISTRIBUTOR PIPE
STAGGERED EVERY 200mm (MIN.) GRANULAR BEDDING MATERIAL DETAILS (SHEET 1 OF 3)
GRANULAR BEDDING MATERIAL
DRAWN - SCALE N.T.S
CHECKED - DATE -
TYPE 2 - TYPICAL LONGITUDINAL SECTION OF TRENCH SOAKAWAY UNDER PAVED AREAS WITH CATCH PIT CHAMBERS
APPROVED - SIZE A1
PROJECT DWG.
No. - No. N-254

THIRD EDITION - APRIL 2022


NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS INDICATED
OTHERWISE.

2. IF THERE IS DISCREPANCY BETWEEN THE REQUIREMENTS


IN THE SPECIFICATIONS AND THOSE SHOWN ON THIS
DRAWING, THE SPECIFICATIONS SHALL BE FOLLOWED.

3. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL


TOP OF FRAME BE IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS

5mm
AND VERIFIED BY THE ENGINEER.
FINAL GROUND SURFACE
IN GREEN AREAS
4. WHERE POSSIBLE GULLY CONNECTION TO BE DIRECT TO

100
RECESS COVER 5mm BELOW CATCH PITS.
FINAL GRADE IN TRAFFIC AREAS
(MATCH FINAL GRADE IN SIDEWALK AREAS) 5. WHERE GULLY/CATCH PIT CONNECTION RUNS UNDER
1200
CARRIAGEWAY, GRANULAR BED TO BE REPLACED BY 150
CONSTRUCTION JOINT UPPER LIMIT OF EXTERIOR WATERPROOFING
150 900 150 CONCRETE SURROUND (GRADE C20).

37mm NOM. SINGLE


SIZE AGGREGATE Ø160 PIPE MIN. PROTECTIVE COATINGS ON ALL
INTERIOR CONCRETE SURFACES
GEOTEXTILE
Ø300 uPVC PERFORATED DISTRIBUTOR WATERPROOFING MEMBRANE
PIPE, PERFORATIONS, 8 HOLES Ø10mm WITH 2 LAYERS OF ASPHALT
STAGGERED EVERY 200m HARDBOARD PROTECTION (TYP.)
MIN. FALL 1%

CRUSHED STONE SURROUND Ø300 GRP ACCESS LADDER

500
75mm SINGLE SIZE
150mm THICK CONCRETE

600
BED AND SURROUND C20
IN CASE COVER DEPTH ABOVE THE 00
Ø3

150
PIPE SOFFIT IS LESS THAN 1.20m.

GULLY
Ø300 HIGH PRESSURE TEE
FOR RODDING ACCESS

500 (MIN.)
500
155

300
361

GRP ACCESS LADDER

200
DIA.

A A

100
BLINDING, C15 CONCRETE (TYP.)
361

150 900 150

1000
1200

WATER PROOFING MEMBRANE TYPE A ONLY


155

MIN. Ø160mm uPVC PIPE


NO HARDBOARD UNDER BOTTOM SLAB (TYP.)
Ø300 HIGH PRESSURE TEE
SECTION A-A
150 550 150 FOR RODDING ACCESS GULLY CONNECTION TO CATCHPIT

PRECAST CONCRETE
150

CATCH PIT CHAMBER


REFERENCE DRAWINGS AND DOCUMENTS
SHORT PIECE OF PIPE
GEOTEXTILE OVERLAP OVER BACKFILL
Ø300
500

CRUSHED STONE SURROUND 160Ø PIPE MIN. FULL WIDTH TRENCH STAINLESS STEEL SCREEN TO PREVENT
75mm SINGLE SIZE INGRESS OF AGGREGATE
F.G.L.

GEOTEXTILE
FABRIC TYPE A

MIN.
300 MIN.

500
37mm NOM. SINGLE
SIZE AGGREGATE
Ø300 uPVC PERFORATED DISTRIBUTOR MIN. FALL 1%

PIPE, PERFORATIONS, 8 HOLES Ø10mm


STAGGERED EVERY 200m

1700
300MIN.
Ø300 No. REVISION-1 APP'D 2020

VARIES
500MAX.
GEOTEXTILE
FABRIC TYPE A CLIENT
PLAN MINIMUM SIZE AGGREGATE
GULLY CONNECTION TO CATCHPIT GRANULAR 37mm
Ø300 uPVC PERFORATED
DISTRIBUTOR PIPE TITLE
GRANULAR BEDDING MATERIAL STANDARD DRAWINGS

200
FOR DETAILS REFER DWG. No. N-215
MAIN ROADS
1500
DRAWING TITLE

SURFACE DRAINAGE TYPICAL


GULLY DIRECT CONNECTION TO TRENCH SOAKAWAY TRENCH SOAKAWAY STANDARD
DETAILS (SHEET 2 OF 3)

DRAWN - SCALE N.T.S


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
N-255

THIRD EDITION - APRIL 2022


NOTES:
1. ALLDIMENSIONSAREINMILLIMETERSUNLESSINDICATED
OTHERWISE.

2. IFTHEREISDISCREPANCYBETWEENTHEREQUIREMENTSIN
THESPECIFICATIONSANDTHOSESHOWNONTHISDRAWING,
DUCTILE IRON FRAME & GRATE THESPECIFICATIONSSHALLBEFOLLOWED.
GEOTEXTILE OVERLAP OVER FULL WIDTH OF TRENCH PRECAST CONCRETE MAKE UP
3. ALLMATERIALS,FABRICATIONANDCONSTRUCTIONSHALLBEIN
SLAB ANCHORAGE
UPSTAND KERB ACCORDANCEWITHTHEPROJECTSPECIFICATIONSAND
150mm THICK CONCRETE SLAB (SEE DETAIL-B)
SIDEWALK AS PECIFIED VERIFIEDBYTHEENGINEER.
MESH REINFORCED CONCRETE BACKING
(SEE DETAIL-A) SLOPE 4. WHEREGULLY/CATCHPITCONNECTIONRUNSUNDER
GRADE C20
CARRIAGEWAY,GRANULARBEDANDSURROUNDTOBE
REPLACEDBY150CONCRETESURROUND(GRADEC20).
GRANULAR SUB-BASE

5. WHEREPOSSIBLEGULLYCONNECTIONTOBEDIRECTTO
475x475
CATCHPITS.
1000
MIN.

6. THESHOWNREINFORCEMENTISFORGUIDANCEONLYAND
REINFORCEMENTFORSPECIFICPROJECTISTOBEDESIGNED

300
ACCORDINGTOSITECONDITIONSANDSHOWNONSHOP
DRAWINGS SUBJECTEDTOTHEAPPROVALOFTHEENGINEER.
MIN.
150

275Ø 3 ROWS OF 50Ø HOLES, EACH ROW

300 MIN.
300MIN. CONSISTING OF 8 HOLES EQAULLY
500MAX. SPACED ON CIRCUMFERENCE
500 MIN. FALL 1%
(MIN.)

FOR FLUSH INLET GULLY


300MIN.
(REFER DWG. No. N-226)
VARIES

500MAX.
1000
MIN.

150mm THICK CONCRETE SLAB


GEOTEXTILE REINFORCED TO BS A393
200 340 DIA 200

MINIMUM SIZE AGGREGATE


GRANULAR 37mm 740 DIA

Ø300 uPVC PERFORATED

150
DISTRIBUTOR PIPE
300

GRANULAR BEDDING MATERIAL

2400

1000(MIN)

TYPICAL GULLY CONNECTION UNDER PARKING AREAS MESH REINFORCEMENT


DETAIL "A"

LIGHTING POLE REFERENCE DRAWINGS AND DOCUMENTS


150mm THICK CONCRETE SLAB

1000
100

OVERLAP OVER FULL WIDTH OF TRENCH


VARIES

37mm SINGLE SIZED AGGREGATE

SELECTED COMPACTED BACK FILL 150mm THICK CONCRETE SLAB


300
REINFORCED TO BS A393
TYPICAL REINFORCED
CONCRETE FOUNDATION
75

GEOTEXTILE

150
No. REVISION-1
VARIES

APP'D 2020
Ø12mm @150mm
CLIENT
Ø300 uPVC PERFORATED
DISTRIBUTION PIPE

200mm THICK CONCRETE


TITLE
INLET GULLY WALL STANDARD DRAWINGS
MAIN ROADS
GRANULAR BEDDING
MATERIAL Ø300 uPVC NON DRAWING TITLE
PERFORATED PIPE WITH
150Ø CONCRETE SURROUND 200
SURFACE DRAINAGE TYPICAL
TRENCH SOAKAWAY STANDARD
DETAILS (SHEET 3 OF 3)
TYPICAL DETAIL OF SOAKAWAY UNDER LIGHTING COLUMN ANCHORAGE DETAIL
DETAIL "B"
DRAWN - SCALE N.T.S
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
N-256

THIRD EDITION - APRIL 2022


NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS INDICATED
OTHERWISE.

2. IF THERE IS DISCREPANCY BETWEEN THE REQUIREMENTS


IN THE SPECIFICATIONS AND THOSE SHOWN ON THIS
DRAWING, THE SPECIFICATIONS SHALL BE FOLLOWED.

3. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL


BE IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS
AND VERIFIED BY THE ENGINEER.

4. MODULAR STORAGE UNIT TO BE HYDRO-INTERNATIONAL'S


STORMBLOC OR APPROVED EQUIVALENT BY ENGINEER.

5. GEOTEXTILE TO BE AS PER MODULAR STORAGE UNITS


CLEANOUT
MANUFACTURERS SPECIFICATION AND GUIDELINES.
19 TO 50mm WASHED
PLASTIC SOAKAWAY
CRUSHED ANGULAR
STONE 6. GROUND WATER TABLE PRIOR TO CONSTRUCTION SHOULD
BE AT LEAST 500mm BELOW THE BASE OF THE MODULAR
NON CORROSIVE HOSE STORAGE UNITS. WHERE LESS THAN 500mm THE

VARIES
CLAMP TO FASTEN LINER CONTRACTOR SHALL NOTIFY THE ENGINEER TO ASSESS
TO PIPE TO PREVENT
BACKFILL FROM FOR FLOATATION.
ENTERING STRUCTURE

7. THE CONTRACTOR IS RESPONSIBLE TO ENSURE THE


FLOW GRP LADDER
STRUCTURAL STABILITY OF THE MODULAR SOAKAWAY
UNDER THE EXTERNAL LOADS AS PER THE
PIPE SLOPE 1% VARIES
VARIES Min.
MANUFACTURER'S RECOMMENDATIONS AND SUBJECTED
TO THE APPROVAL OF THE ENGINEER.
NON CORROSIVE HOSE CLAMP TO
ROAD WAY SIDE

FASTEN LINER TO PIPE TO 8. INSPECTION CHAMBERS TO BE ADDED AS PER


PREVENT BACKFILL FROM MANUFACTURER'S RECOMMENDATIONS.
ENTERING STRUCTURE
100 VARIES 100 NON-WOVEN GEOTETILE
CLEANOUT MEMBRANE(ASSSHTO M288
CLASS 2)

PLAN

RECESS GRATE 20 BELOW PAVEMENT BACKFILL MATERIAL COMPACTED 150 SQUARE SURFACE BOX
DUCTILE IRON GUTTER TYPE COVER AND FRAME TO SUIT
LEVEL AND MATCH CROSS SLOPE OF IN 150mm LIFT TO 95% MAX. POSITIONED TO SUIT THE
INLET GRATE AND FRAME Ø600 CLEAR OPENING
PAVEMENT DRY DENSITY STANDARD EXTENSION SPINDLE
INLET 20 TO 50mm WASHED CHAMBER 25x25
5 5 FINISHED GROUND LEVEL
655 130 CRUSHED ANGULAR STONE
CLEANOUT
SLOPE
CONCRETE HUNCHING

REFERENCE DRAWINGS AND DOCUMENTS

VARIES
PROTECTIVE COATING
VARIES

ON INTERIOR SURFACES
GRP LADDER
WATERPROOFING MEMBRANE TYPE A.
WITH 2 LAYERS ASPHALTIC
GV WITH EXTENSION SPINDLE
HARDBOARD PROTECTION

1000 100
INLET PIPE
Ø300mm MIN. PROPOSED GATE VALVE OR AS
CONSTRUCTION JOINT (TYP) DIRECTED BY THE MANUFACTURE
OR THE ENGINEER ON SITE
(MIN.)
500

Ø100mm MIN.

100
200

200 600 200 NON CORROSIVE HOSE CLAMP TO FASTEN


100

LINER TO PIPE TO PREVENT BACKFILL FROM PLASTIC SOAKAWAY MODULE No. REVISION-1 APP'D 2020
NON CORROSIVE HOSE CLAMP TO FASTEN
WATERPROOFING MEMBRANE TYPE A ONLY, ENTERING STRUCTURE 100 VARIES 100
BLINDING, C15 CONCRETE (TYP.) LINER TO PIPE TO PREVENT BACKFILL FROM CLIENT
NO HARDBOARD UNDER BOTTOM SLAB (TYP.) ENTERING STRUCTURE
SECTION NON-WOVEN GEOTEXTILE MEMBRANE
(ASSSHTO M288 CLASS 2)

TYPICAL LONGITUDINAL SECTION TITLE


STANDARD DRAWINGS
MAIN ROADS
DRAWING TITLE

SURFACE DRAINAGE TYPICAL


DETAILS OF PLASTIC SOAKAWAY

DRAWN - SCALE N.T.S


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
N-257

THIRD EDITION - APRIL 2022


NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS INDICATED
OTHERWISE.

2. IF THERE IS DISCREPANCY BETWEEN THE REQUIREMENTS


IN THE SPECIFICATIONS AND THOSE SHOWN ON THIS
DRAWING, THE SPECIFICATIONS SHALL BE FOLLOWED.

3. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL


BE IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS
AND VERIFIED BY THE ENGINEER.

4. THE DEPTHS OF PAVEMENTS, BALLAST AND SUB-BALLAST


A, B, C & D SHALL BE DETERMINED ACCORDING TO TRACK
PAVEMENT
DESIGN REQUIREMENTS.
0 TRACK/ROAD SACKED PERVIOUS DRAIN ROCK
10
KERB & ℄ 5. THIS DRAWING SHALL BE READ IN ACCORDANCE WITH THE
GUTTE
R SPECIFICATIONS.

A
BALLAST

(MIN.)
SUB-BALLAST

D
VARIES

(MIN.)

VARIES TRACK
350
200

250
SUBGRADE

C
CONCRETE TIE
GEO-TEXTILE
PERVIOUS MATERIAL
(FILTER MEDIA)

Ø300mm MIN. SEMI-PERFORATED UNDER DRAIN PIPE


BALLAST 2.5% 300 300
℄ (PERFORATION ON UPPER HALF OF THE PIPE)
100 SUB-BALLAST (MIN.) (MIN.) 150mm FROM BOTTOM
GEO-TEXTILE 95% RELATIVE COMPACTION
(IF REQUIRED) OF PIPE
200 SUB-GRADE

SINGLE TRACK - EMBEDDED UNDERDRAIN DETAIL-A


(SEE DETAIL-A)
UNDER DRAIN

REFERENCE DRAWINGS AND DOCUMENTS


CONCRETE TIE CONCRETE TIE
PAVEMENT PAVEMENT

TRACK/ROAD
4"

KERB &
G UTTER
200

200
250

250
No. REVISION-1 APP'D 2020
2.5% BALLAST BALLAST 2.5% CLIENT
℄ SUB-BALLAST
200 ℄
100 SUB-BALLAST
95% RELATIVE COMPACTION GEO-TEXTILE GEO-TEXTILE 95% RELATIVE COMPACTION
(IF REQUIRED) (IF REQUIRED) UNDERDRAIN
UNDERDRAIN
200 SUB-GRADE 200 SUB-GRADE (SEE DETAIL-A)
(SEE DETAIL-A)
300 300 300 300
(MIN.) (MIN.) (MIN.) (MIN.)
CATENARY POLE FOUNDATION TITLE
STANDARD DRAWINGS
DOUBLE TRACK - EMBEDDED MAIN ROADS
DRAWING TITLE
SURFACE DRAINAGE DETAILS OF
TRACK DRAINAGE FOR
SINGLE/DOUBLE TRACK EMBEDDED
(CASE OF HIGH GROUND WATER)
DRAWN - SCALE N.T.S
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
N-258

THIRD EDITION - APRIL 2022


NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS INDICATED
OTHERWISE.

2. IF THERE IS DISCREPANCY BETWEEN THE REQUIREMENTS


IN THE SPECIFICATIONS AND THOSE SHOWN ON THIS
DRAWING, THE SPECIFICATIONS SHALL BE FOLLOWED.

3. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL


TRACK ℄ TRACK
℄ GUIDEWAY ℄ BE IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS
AND VERIFIED BY THE ENGINEER.

4. THE DETAILED SHOP DRAWINGS WITH SUPPORTING


CALCULATIONS SHALL BE PREPARED BY CONTRACTOR
AND SHALL BE APPROVED BY THE ENGINEER PRIOR TO
CATENARY POLE EXECUTION.

CONCRETE CROSS TIE (TYP.)

BALLAST (TYP)
200 MIN
CUT SECTION (TYP)

300 (MIN.)
2 2
300 900 400 1 1 300
400
3 (MIN.) (MIN) (MIN.)
1
3 3
1 1

2.5% 2.5%
(MIN.)
300

COMPACTED SUBGRADE (TYP.) 200 SUB-BALLAST (TYP.)

EXISTING GROUND EXISTING GROUND

DRAINAGE FLOW DIRECTION FILL SECTION (TYP)

BALLASTED DOUBLE TRACK - TANGENT SECTION - UNCONSTRAINED

TRACK ℄ TRACK

SUPERELEVATION (Ea)
℄ GUIDEWAY ℄

CATENARY POLE
CONCRETE CROSS TIE (TYP.)
BALLAST (TYP)
200 MIN

CUT SECTION (TYP)


2
REFERENCE DRAWINGS AND DOCUMENTS
2 1
1
2
300 900 400 1
400 300
(MIN) (MIN.)
3

(MIN.)
1 3 3

300
1 1

2.5% 2.5%
300 (MIN)

COMPACTED SUBGRADE (TYP.) 200 SUB-BALLAST (TYP.)

EXISTING GROUND
EXISTING GROUND
DRAINAGE FLOW DIRECTION FILL SECTION (TYP)

BALLASTED DOUBLE TRACK - SUPERELEVATED SECTION - UNCONSTRAINED No. REVISION-1 APP'D 2020
CLIENT

TITLE
STANDARD DRAWINGS
MAIN ROADS
DRAWING TITLE

SURFACE DRAINAGE DETAILS OF


TRACK DRAINAGE FOR BALLASTED
DOUBLE TRACK - UNCONSTRAINED

DRAWN - SCALE N.T.S


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
N-259

THIRD EDITION - APRIL 2022


NOTES:

A C 1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS INDICATED

5.00m
(MIN.)
OTHERWISE.
FENCE BOUNDARY TO BE FAR BY NOT LESS THAN 5.0m
FOR MAINTENANCE VEHICLE TO MANOEUVRE
2. IF THERE IS DISCREPANCY BETWEEN THE REQUIREMENTS
TRACK IN THE SPECIFICATIONS AND THOSE SHOWN ON THIS
DRAWING, THE SPECIFICATIONS SHALL BE FOLLOWED.

)
(MIN.
5m
3. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL
BE IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS
ACCESS GATE
DETAIL AND VERIFIED BY THE ENGINEER.
C 1
4. EMPTYING TIME OF POND WILL VARY BASED ON

B
POND EVAPORATION RATE AND SOIL PERMEABILITY.
RETENTION POND VOLUME TO BE DETERMINED OUTFALL
SIDE SLOPE = 1:H
(H = 4-6 ACCORDING TO SITE CONDITIONS)
BASED ON CATCHMENT AREA INLET PIPE 5. AERATORS MIGHT BE REQUIRED TO ENSURE WATER
MIN 5 QUALITY AND REDUCE STAGNATION.
.00m

GROUTED RIPRAP PROTECTION 6. FOR EVAPORATION PONDS GROUTED RIPRAP SHALL BE

B
GROUTED RIPRAP FOR RAMP USED FOR POND BOTTOM.

FENCE

TRACK
5m
VARIES
STEPS GROUTED RIPRAP MIN. 5m ACCESS RAMP FOR
TREAD = 0.50m
APPROX. 50m A MAINTENANCE VEHICLE
RISER = 0.20m SLOPE ACCORDING TO AASHTO
(SEE TYPICAL SECTION) ACCESS GATE

FREE BOARD (MIN.)


300mm
FENCE

FENCE
5000 (MIN.) 5000
250 SLOPE 1:H
TOP LVL ± 250 TOP LVL ±
E.G.L MAINTENANCE (H = 4-6 ACCORDING TO SITE MAXIMUM WATER LEVEL SLOPE 1:H MAINTENANCE E.G.L
H
CONDITIONS) (H = 4-6 ACCORDING TO SITE
1
CONDITIONS) 1 H
(MIN.)

(MIN.)
1000

1000
150mm THICK ROAD BASE STORAGE VOLUME 150mm THICK ROAD BASE
POND BOTTOM LEVEL
GEOTEXTILE MEMBRANE
GEOTEXTILE MEMBRANE

500 500

(MIN.)

(MIN.)
1000

1000
(MIN.) (MIN.)
300mm THK. LOOSE RIPRAP

200mm FILTER MATERIAL


GEOTEXTILE MEMBRANE
500 500
FREE BOARD (MIN.)

300mm THK. LOOSE RIPRAP (MIN.) (MIN.)


200mm FILTER MATERIAL CROSS SECTION A-A
300mm

GEOTEXTILE MEMBRANE

FENCE
5000
250
TOP LVL ±
M.W.L TRACK E.G.L

REFERENCE DRAWINGS AND DOCUMENTS

(MIN.)
1000
SLOPE 1:H
(H = 4-6 ACCORDING TOHSITE
CONDITIONS) 1 PAVEMENT AS DESIGNED

GEOTEXTILE MEMBRANE

POND BOTTOM LVLEL ± 500


(MIN.)
(MIN.)
1000

CROSS SECTION B-B


500 300mm THK. LOOSE RIPRAP
(MIN.) 200mm FILTER MATERIAL
GEOTEXTILE MEMBRANE
D

INLET PIPE No. REVISION-1 APP'D 2020


CLIENT
TOP LVL ±
(MIN.)
POND LIMIT

1000

RIM LVL
250 250 200x200 ENERGY
°
60
RISER

DISSIPATOR (TYP.)

VARIES
30° TITLE
.)
STANDARD DRAWINGS
VARIES

(MIN GROUTED RIPRAP


(MIN.)
1000

TREAD INLET PIPE (3d OR 5m MIN.)


ENERGY DISSIPATION 400 MAIN ROADS
48000.00

VARIES
(IF REQUIRED)
D/2 OR IL DRAWING TITLE
GROUTED RIPRAP

500 250mm (MIN.)


(3d OR 5m MIN.

350

POND BOTTOM
(MIN.)
1000 1000
SURFACE DRAINAGE TYPICAL DETAILS
300mm THK. LOOSE RIPRAP
OF STORM WATER PERCOLATION
70
(MIN.)

BLINDING C15 FILTER MATERIAL


1000

SEALANT
200mm FILTER MATERIAL CONCRETE POND PLAN & SECTIONS
GEOTEXTILE MEMBRANE
500 350 VARIES 500 GEOTEXTILE
5000
500 5000 DRAWN - SCALE N.T.S
(MIN.) D
CHECKED - DATE -
SECTION D-D
TYPICAL SECTION @ STEP AREA DETAIL-1 APPROVED - SIZE A1
SECTION C-C PROJECT DWG.
No. - No.
N-260

THIRD EDITION - APRIL 2022


NOTES:
1. ALL DIMENSIONS ARE IN MILLIMETRES UNLESS INDICATED
OTHERWISE.

2. IF THERE IS DISCREPANCY BETWEEN THE REQUIREMENTS


IN THE SPECIFICATIONS AND THOSE SHOWN ON THIS
DRAWING, THE SPECIFICATIONS SHALL BE FOLLOWED.

3. THE FABRIC SHALL BE SECURELY FASTENED TO THE


CORNER, STRAINING AND END POSTS WITH STRETCHER
BARS AS SHOWN AND FASTENED TO THE TENSION WIRE AT
500MM INTERVALS.

4. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL


BE IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS
150000 MAX.
AND VERIFIED BY THE ENGINEER.
3000 TENSION WIRES
3000 3000
5. FOUNDATIONS TO BE C20 CONCRETE. THE ENTIRE
CHAIN LINK FABRIC H=1600 STRETCHER BAR 20X5 FOUNDATION HOLE SHALL BE FILLED WITH CONCRETE, THE
USE OF PARTLY BACKFILLED HOLES WILL NOT BE
PERMITTED.
500

6. WHERE A FENCE FORMS A BOUNDARY BETWEEN THE


HIGHWAY AND PRIVATE PROPERTY, THE FABRIC SHALL BE
1500

500

FIXED ON THE PRIVATE PROPERTY SIDE.

7. THE FENCE TYPE SHALL BE FOLLOWED/COORDINATED WITH


HIGHWAY PROPOSED FENCES AND SHALL BE APPROVED BY
500

THE ENGINEER.
200
900

BRACE TUBE L=3000


CONCRETE FOOTING
500X500X500
LINE POST L=2600
100

CONCRETE FOOTING
END POST L=2700
300X300X800
CONCRETE FOOTING
300X300X1000
CHAIN LINK FENCE ELEVATION

60.3 OD.

TWISTED AND BARBED

GALV. END BAND-2 WAY GALV. STRETCHER BAR BAND


5000 25x6 25x6

STRAINING POST
REFERENCE DRAWINGS AND DOCUMENTS
STRETCHER
60.3 OD.
BAR 20X5

STRETCHER

300
BAR BAND

200
25X6

45°
BRACE
TUBE 42.2 GALV. END BAND 25x6 GALV. WELDED LUG 20x5
OD

100
LINE POST
STEEL BOLT
BANDS ON CORNER/STRAINING POST
LOCK WIRE 2.8
TENSION WIRE

300
200
PLASTIC OR VINYL COATED
ALUMINIUM CAP STIRRUP WIRE
1100 (Min.)

No. REVISION-1 APP'D 2020

100
ALTERNATE TENSION WIRE CLIENT
EXTENSION ARMS
POST CAP ELEVATION STRRUIP PLAN

SECURITY GATE CORNER/ STRAINING/ END POST DETAIL


TITLE
INTERMEDIATE POST DETAIL STANDARD DRAWINGS
100

GATE POST
CONCRETE MAIN ROADS
FOOTING
500X500X500
DRAWING TITLE

SURFACE DRAINAGE TYPICAL


DETAILS OF POND FENCE

DRAWN - SCALE N.T.S


CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No. N-261
THIRD EDITION - APRIL 2022
NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
A REQUIREMENTS.
THEY ARE EXPECTED TO BE INCORPORATED AS TYPICAL
DETAILS WHICH SHALL BE CHECKED AND APPROVED AS
PART OF THE PROJECT DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
STATED.
2. ALL CONCRETE TO BE C40 UNLESS OTHERWISE STATED.
3. ALL INTERNAL AND EXTERNAL CONCRETE CORNER TO BE
ROUNDED AND CHAMFERED.
4. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL
BE IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS
AND VERIFIED BY THE ENGINEER.
5. GROUND WATER TABLE SHALL BE VERIFIED AT SITE & THE
WEIGHT OF THE CATCH BASIN CONCRETE PAD SHALL BE
Kerb Line Retaining Wall PROPORTIONATE TO RESIST UPLIFT.
6. MANUFACTURER TO SUBMIT CLASS AND DIMENSIONS OF
COVER ACCORDING TO SPECIFICATIONS BASED ON
ACTUAL SITE CONDITIONS & TO BE APPROVED PRIOR TO
SLOPE % SLOPE % MANUFACTURING.

Road Inside Underpass


Retaining Wall

Pipe

Catch Basin
(see DETAIL A for connection between Catch Basins)
To Pump
Room

UNDERPASS PLAN
A

LC

Embankment

Underpass
Tunnel Tunnel
Clear Height Clear Height
Retaining Wall

Kerb Kerb REFERENCE DRAWINGS AND DOCUMENTS


Catch Catch
Basin Road SLOPE % SLOPE % Road Basin
To Pump
Room

min slope = 0.001 m/m

SECTION (A - A)
Pipe from Catch Basin UNDERPASS CROSS SECTION AT LOWEST LEVEL
No. REVISION-2 APP'D 2021
Road CLIENT

Kerb Line
TITLE
STANDARD DRAWINGS
MAIN ROADS
DRAWING TITLE

Pipe to Catch Basin Pipe from Catch Basin


UNDERPASS DRAINAGE DETAILS
Anchoring Lugs
Heavy Duty D.I.
Grating and Frame
CATCH BASINS

DETAIL A
PLAN - CATCH BASINS CONNECTIONS DRAWN - SCALE N.T.S
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
N-262

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
A REQUIREMENTS.
THEY ARE EXPECTED TO BE INCORPORATED AS TYPICAL
Kerb Line Inlet Structure Retaining Wall DETAILS WHICH SHALL BE CHECKED AND APPROVED AS
PART OF THE PROJECT DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
STATED.
2. ALL CONCRETE TO BE C40 UNLESS OTHERWISE STATED.
3. ALL INTERNAL AND EXTERNAL CONCRETE CORNER TO BE
ROUNDED AND CHAMFERED.
4. ALL MATERIALS, FABRICATION AND CONSTRUCTION SHALL
BE IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS
AND VERIFIED BY THE ENGINEER.
Flow 655 Cast-in-situ flush kerb Flow
5. GROUND WATER TABLE SHALL BE VERIFIED AT SITE & THE
with slotted drain channel WEIGHT OF THE CATCH BASIN CONCRETE PAD SHALL BE
PROPORTIONATE TO RESIST UPLIFT.
Road Inside Underpass 6. MANUFACTURER TO SUBMIT CLASS AND DIMENSIONS OF
COVER ACCORDING TO SPECIFICATIONS BASED ON
Pipe
ACTUAL SITE CONDITIONS & TO BE APPROVED PRIOR TO
SLOPE % SLOPE % MANUFACTURING.

655 Cast-in-situ flush kerb


Flow with slotted drain channel Flow

Inlet Structure Retaining Wall


To Pump
Room

UNDERPASS PLAN
A

LC

Embankment

Underpass
Tunnel Tunnel
Clear Height Clear Height
Retaining Wall

Kerb Kerb REFERENCE DRAWINGS AND DOCUMENTS

Slotted Slotted
Trench
Road SLOPE % SLOPE % Road Trench
To Pump
Room

min slope = 0.001 m/m

Kerb
CAST-IN-SITU SECTION (A - A)
TOP OF KERB
FLUSH
MATCH FINAL GRADE KERB UNDERPASS CROSS SECTION AT LOWEST LEVEL
300
CROSS SLOPE
No. REVISION-2 APP'D 2021
CROSS SLOPE %
CLIENT

TITLE
STANDARD DRAWINGS
MAIN ROADS
GEOTEXTILE FABRIC DRAWING TITLE
150 355 150
CLASS B CONCRETE
UNDERPASS DRAINAGE DETAILS
PRE-CAST POLYESTER CONCRETE DRAIN
LAY PLASTIC SHEET OVER
CHANNEL WITH INTEGRAL DUCTILE IRON FRAME
SLOTTED TENCHES
EXPOSED PERVIOUS BACKFILL
MATERIAL PRIOR TO CASTING AND BOLT DOWN GRATE FOR HEAVY DUTY USE,
CONCRETE. IN 150 CONCRETE BEDDING, INSTALL ON GRADE
TO MATCH FINISHED PAVEMENT GRADE.
DRAWN - SCALE N.T.S
SLOTTED TRENCH DRAIN INSTALLATION CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
N-263

THIRD EDITION - APRIL 2022


NOTES:
THESE DETAILS REPRESENT A MINIMUM REQUIREMENT AND
MAY BE VARIED, SUBJECT TO APPROVAL, TO SUIT PROJECT
REQUIREMENTS.
THEY ARE EXPECTED TO BE INCORPORATED AS TYPICAL
DETAILS WHICH SHALL BE CHECKED AND APPROVED AS
ROAD MEDIAN ROAD ROAD MEDIAN ROAD ROAD MEDIAN ROAD PART OF THE PROJECT DRAWING SET.
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE
STATED.
2. ALL CONCRETE TO BE C40 UNLESS OTHERWISE STATED.
3. GRP CHANNEL SHOULD BE COMPLY TO EN1433
STANDARDS.
LONG. SLOPE %

LONG. SLOPE %

LONG. SLOPE %
4. EXCAVATE A TRENCH OF SUFFICIENT WIDTH; ENSURE THAT
AT LEAST 8 CM OF BEDDING CONCRETE CAN BE PLACED
UNDER AND ALONGSIDE THE CHANNEL.
5. THE LOAD-BEARING CAPACITY OF THE SUBSOIL MUST BE
TAKEN ACCOUNT, OR A TRENCH BASE WITH ADEQUATE
LOAD-BEARING CAPACITY MUST BE INSTATED.
6. HORIZONTAL FORCES ON THE CHANNEL RUN – STEMMING
FROM ADJOINING CONCRETE AREAS OR REINFORCED
CATCH BASIN CONCRETE STRUCTURES - MUST BE EXCLUDED BY
TOP ENTRY INSTALLING EFFECTIVE LONGITUDINAL AND TRANSVERSE
KERB OPENING

KERB OPENING

KERB OPENING

KERB OPENING
EXPANSION JOINTS.
CATCH BASIN 7. THE ADJACENT PAVEMENT MUST BE INSTALLED IN SUCH A
KERB ENTRY WAY THAT NO HORIZONTAL FORCES ACT ON CHANNEL
GRP CHANNEL GRP CHANNEL GRP CHANNEL
ELEMENTS.
8. APPLY AN EQUAL CONCRETE SURROUND ON BOTH SIDES
OF THE CHANNELS.

STORM PIPE

STORM PIPE
LONG. SLOPE %

LONG. SLOPE %

LONG. SLOPE %
CONNECTION TO SURFACE DISCHARGE CONNECTION TO CATCH BASIN WITH TOP ENTRY CONNECTION TO CATCH BASIN WITH KERB ENTRY
PLAN PLAN PLAN

ROAD MEDIAN ROAD ROAD MEDIAN ROAD ROAD MEDIAN ROAD

CATCH BASIN CATCH BASIN


TOP ENTRY KERB ENTRY

GRP CHANNEL GRP CHANNEL GRP CHANNEL


for bedding and surround details
Kerb inlet grate Kerb inlet grate Kerb inlet grate
see DETAIL A

REFERENCE DRAWINGS AND DOCUMENTS


Soil Soil Soil

CONNECTION TO SURFACE DISCHARGE CONNECTION TO CATCH BASIN WITH TOP ENTRY CONNECTION TO CATCH BASIN WITH KERB ENTRY
SECTION SECTION SECTION

4
No. REVISION-2 APP'D 2021
CLIENT
1
LOADING CLASS TO EN 1433 B 125 C 250 D 400
Concrete Haunch X (mm) > 100 > 150 > 200
GRP Channel Concrete Haunch Z (mm) > 100 > 150 > 200
2 3 TITLE
Reinforcement bars NO YES YES STANDARD DRAWINGS
X 3 min. concrete quality for haunch C 20/25 C 20/25 C 25/30 MAIN ROADS
Z

* For Footways, pedestrian zones and comparable areas, car


DRAWING TITLE
4 parking spaces and decks. Choose B125 (Test load 125 kN)
* For Kerbsides of roads and pedestrian roads, verges and marginal
strips, parking areas. Choose C250 (Test load 250 kN)
* For Carriageways of roads, also pedestrian roads2), parking areas GRP CHANNEL
and comparable paved surfaces. Choose D400 (Test load 400 kN)
1- CONCRETE
2- SUB-BASE
3- CONCRETE HAUNCH
4- EARTH
DETAIL A
5- BLOCKING PAVING DRAWN - SCALE N.T.S
CHECKED - DATE -
APPROVED - SIZE A1
PROJECT DWG.
No. - No.
N-265

THIRD EDITION - APRIL 2022