Professional Documents
Culture Documents
Gas 4105 G
Gas 4105 G
Pall
Pall prefilter
AquaSep
Plus stack
Coalescer
Pall with integral
prefilter prefilter
Separator Liquid
contaminant
Fuel out (dispersed
Fuel or phase) out
chemical with Fuel or chemical
liquid or solid with liquid
contaminants contaminants
Fuel in with Water without dirt
water and Fuel and out
solids water
without dirt
Figure 2: Pall AquaSep Plus Liquid/Liquid Separation
System with Coalescer in a Horizontal
Figure 1: AquaSep Plus Liquid/Liquid Coalescer Housing
System
Mechanism of Coalescing with
Conventional Glass Medium
Lower Disposal and Maintenance Costs One of the biggest operational problems for conventional
The long, useful life of the AquaSep Plus cartridges, is liquid/liquid coalescers is disarming. When a liquid/liquid
obtained from Pall’s specially formulated non-disarming coalescer is performing efficiently, water molecules bond
high voids volume medium that is properly protected with components on the glass fiber called a silenol
by Pall prefilters. Overall results are fewer cartridge functional group. The water molecules that collect on the
changeouts for low maintenance and disposal costs. glass fiber coalesce with incoming water molecules to
form a large droplet, which will eventually become heavy Performance Claims and Specifications
enough to drain from the coalescer. In an efficiently
operating coalescer, once a droplet has fallen from an Maximum Temperature: 66°C/150°F
active site, the coalescing process repeats (see Figure 3).
Initial Pressure Drop: 0.14 bard/2 psid
Recommended Changeout: 1.03 bard/15 psid
Step 1 Step 2
Fuel contains Water
small water molecules
droplets bond to silenol Ordering Information
group located
on glass fiber Part Outer Diameter Length
Glass Number Description (cm/in) (cm/in)
Fiber Glass
Fiber LCS2B1AH AquaSep Plus 9.53/33⁄4 50.8/20
Coalescer
Step 3 Step 4
LCS4B1AH AquaSep Plus 9.53/33⁄4 101.6/40
Water droplets Large water
coalesce with droplets drain;
Coalescer
bonded water molecules
LSS2F2H Separator 9.53/33⁄4 50.8/20
droplets to form bond to open
larger droplets silenol sites
Please call your Pall representative to confirm compatibility
Glass Glass To Drain
Fiber Fiber
for a specific application.
Glass Glass
Fiber Fiber
Step 3
Water droplets
pass through
glass fiber;
coalescer is
disarmed and
must be replaced
Glass
Fiber
United Kingdom
Europa House, Havant Street
Portsmouth PO1 3PD
Hampshire, England
+44 (0) 23 9230 2357 phone
+44 (0) 23 9230 2509 fax © Copyright 2001, 2006, Pall Corporation. Pall, and AquaSep are trademarks of Pall Corporation. ® Indicates a
processuk@pall.com email Pall trademark registered in the USA. is a service mark of Pall Corporation.