Details Stabilite Chambre Existante
Details Stabilite Chambre Existante
2019
HEB300 - SEDEC Lausanne.xmcd
Simple design showing that sf against overturning (EQU) is < 1,0 during excavation (temporary phase) and
therefore the beams are necessairy.
Yellow_boxes = indata
Orange_boxes = calculations
kg
ρc 2600 Density reinforced concrete
3
m
kN
ρremblais 20 Density of fill
3
m
1
Calculation EQU EN-1997-1 need of 03.06.2019
HEB300 - SEDEC Lausanne.xmcd
h PA1 h ch 1 m 3.95 m
5
Distance from point of moment to external
2 overload (excavator)
h ch
h PA2 2.483 m Distance from point of moment to active
3 earth pressure
kN
PA1 20 1 m 20 kN Overload from excavator
m
PA2 ρremblais
hch hch cos(α) 1m 480.666 kN Resultant from active earth pressure
2
wch
mch 2 h ch tch 1m ρc g 166.344 kN Mass of chambre
2
2
Calculation EQU EN-1997-1 need of 03.06.2019
HEB300 - SEDEC Lausanne.xmcd
3
Calculation EQU EN-1997-1 need of 03.06.2019
HEB300 - SEDEC Lausanne.xmcd
wch
Edst Estb.2
2 1 Which is less than shear obtained in Plaxis
VN1 76.1 kN
γG.stb h N1 h N1 m model (121,79 kN/m), see following page.
4
Output Version 2019.0.0.0
-2,50 -2,00 -1,50 -1,00 -0,50 0,00 0,50 1,00 1,50 2,00 2,50 3,00 3,50 [kN/m]
833,00 160
140
832,50
120
832,00
100
831,50
80
831,00
60
830,50
40
830,00 20