Professional Documents
Culture Documents
Unsymmetrical Fault Analysis
Unsymmetrical Fault Analysis
Unsymmetrical Fault Analysis
FAULT ANALYSIS
A fault in a power system refers to an abnormal condition where the normal flow of
electric current is interrupted due to various reasons such as equipment failures,
short circuits, insulation breakdowns, and external factors.
Fault analysis is critical for maintaining a reliable and secure electrical supply and
optimize system performance
Fault analysis can be of two types depending upon the impedances in each phase
i. Balanced / Symmetrical Faults
ii. Unbalanced / Unsymmetrical Faults
SYMMETERICAL AND UNSYMMETRICAL NETWORK
All three voltages (A, B, and C phases) are equal in magnitude and have a 120-
degree phase separation from one another .
NEGATIVE SEQUENCE COMPONENT
Negative sequence voltages typically arise from asymmetrical faults, unbalanced
loads, or other disturbances.
All three voltages (A, B, and C phases) are equal in magnitude and have a 120-
degree phase separation from one another in a direction opposite to that of positive
Sequence.
ZERO SEQUENCE COMPONENT
Zero sequence voltage refers to a set of voltages that are equal in magnitude and in
phase with each other.
All three voltages (A, B, and C phases) are equal in magnitude and have no phase
separation from one another
UNSYMMETRICAL NETWORK WITH
SYMMETRICAL COMPONENTS
1
Positive sequence current, IR1 = (IR +a IB+ a2Iy)
3
1
Negative sequence current, IR2 = (IR + a2 IB+ a IY)
3
1
Zero sequence current, IR3 = (IR + IB+ IY)
3
MATHEMATICAL PROBLEM
The current in a 3 phase unbalanced system are:
IR = (12+ j6) A , IB = (12- j12)A, IY = (-15+ j10) A
The phase sequence is RYB. Calculate the zero, negative and positive components of current.