BMS Pneumatic Waste System T&C

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 16

Pneumatic Waste Collection System Test Form

SOFTWARE FUNCTIONAL TEST FORM -1

Form No: ECC-NSCKWE-BMS-


Project: PROJECT THE ECC & NDCS @ SGH TESTFROM-0001

Equipment ID: PMW-XX-XX Date: Revision: 0

Process Description: Testing and Commissioning of PMW-XX-XX

Area/Location: Panel ID: PMW-XX-XX

EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Compactor
TEST – 1 Compactor
Monitoring Points

Alarm Status is “Normal”


PMW-XX-XX_EqAlmSts= “NORMAL”
1.
Simulate the condition is
PMW-XX-XX_EqAlmSts = “ALARM”
“Alarm”

Monitor the Mode to “Local” PMW-XX-XX_Mode = “LOCAL”


2.
Switch the Mode to “BMS” PMW-XX-XX_Mode = “BMS”
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Monitor the Status is “ON” PMW -XX-XX_EqSts = “ON


3.
Monitor the Status is “OFF” PMW -XX-XX_EqSts = “OFF”

Power Status is “Normal”


PMW-XX-XX_AlmSts= “NORMAL”
4.
Simulate the condition is
PMW-XX-XX_AlmSts = “FAIL”
“Alarm”

Monitor the BIN LIFT Status is


“ON” PMW -XX-XX_Sts = “ON
5.
Monitor the BIN LIFT Status is PMW -XX-XX_Sts = “OFF”
“OFF”

Monitor the Removal Count


Status is “ON” PMW -XX-XX_Sts = “ON
6.
Monitor the Removal Count PMW -XX-XX_Sts = “OFF”
Status is “OFF”

Send command to “Start”. PMW -XX-XX_Start = “START”


7.
Send command to “Stop”. PMW -XX-XX_Start = “STOP”

Fan Exhauster
TEST – 2 Fan Exhauster
Monitoring Points

Alarm Status is “Normal”


PMW-XX-XX_EqAlmSts= “NORMAL”
1.
Simulate the condition is
PMW-XX-XX_EqAlmSts = “ALARM”
“Alarm”

Monitor the Mode to “Local” PMW-XX-XX_Mode = “LOCAL”


2.
Switch the Mode to “BMS” PMW-XX-XX_Mode = “BMS”
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Monitor the Status is “ON” PMW -XX-XX_EqSts = “ON


3.
Monitor the Status is “OFF” PMW -XX-XX_EqSts = “OFF”

Power Status is “Normal”


PMW-XX-XX_AlmSts= “NORMAL”
4.
Simulate the condition is
PMW-XX-XX_AlmSts = “FAIL”
“Alarm”

Load station
TEST – 3 Load station
Monitoring Points

Alarm Status is “Normal”


PMW-XX-XX_EqAlmSts= “NORMAL”

Simulate the condition is


PMW-XX-XX_EqAlmSts = “ALARM”
“Alarm”

Monitor the Mode to “Local” PMW-XX-XX_Mode = “LOCAL”

Switch the Mode to “BMS” PMW-XX-XX_Mode = “BMS”

Monitor the Status is “ON” PMW -XX-XX_EqSts = “ON

Monitor the Status is “OFF” PMW -XX-XX_EqSts = “OFF”

Power Status is “Normal”


PMW-XX-XX_AlmSts= “NORMAL”

Simulate the condition is


PMW-XX-XX_AlmSts = “FAIL”
“Alarm”

Filtration system
TEST – 4 Filtration system
Monitoring Points

Prefilter Alarm Status is


“Normal” PMW-XX-XX_PreFiltSts= “NORMAL”

Simulate the condition is PMW-XX-XX_ PreFiltSts = “ALARM”


“Alarm”
Tested By: Acknowledged
Honeywell Pte Ltd
By: Kilowatts

NAME: NAME:

DATE: DATE:

Submitted and Penta-Ocean Construction Co, Witnessed and


RE/RTO
Checked By: Ltd. Checked BY:

NAME: NAME:

DATE: DATE:
Food Waste Collection & Digester System Test Form

SOFTWARE FUNCTIONAL TEST FORM -2

Form No: ECC-NSCKWE-BMS-


Project: PROJECT THE ECC & NDCS @ SGH TESTFROM-0002

Equipment ID: PMW-XX-XX Date: Revision: 0

Process Description: Testing and Commissioning of PMW-XX-XX

Area/Location: Panel ID: PMW-XX-XX

EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Food grinder / digester


TEST – 1 Food grinder / digester
Monitoring Points

Alarm Status is “Normal”


PMW-XX-XX_EqAlmSts= “NORMAL”
1
Simulate the condition is
PMW-XX-XX_EqAlmSts = “ALARM”
“Alarm”

Monitor the Mode to “Local” PMW-XX-XX_Mode = “LOCAL”


2
Switch the Mode to “BMS” PMW-XX-XX_Mode = “BMS”
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Monitor the Status is “ON” PMW -XX-XX_EqSts = “ON


3
Monitor the Status is “OFF” PMW -XX-XX_EqSts = “OFF”

Power Status is “Normal”


PMW-XX-XX_AlmSts= “NORMAL”
4
Simulate the condition is
PMW-XX-XX_AlmSts = “FAIL”
“Alarm”

Send command to “Start”. PMW -XX-XX_Start = “START”


5
Send command to “Stop”. PMW -XX-XX_Start = “STOP”

Monitor the Discharge Count


Status is “ON” PMW -XX-XX_Sts = “ON
6
Monitor the Discharge Count PMW -XX-XX_Sts = “OFF”
Status is “OFF”

Vacuum pump set (N+1


configuration) Vacuum pump set (N+1
TEST – 2
configuration)
Monitoring Points

Alarm Status is “Normal”


PMW-XX-XX_EqAlmSts= “NORMAL”
1
Simulate the condition is
PMW-XX-XX_EqAlmSts = “ALARM”
“Alarm”

Monitor the Mode to “Local” PMW-XX-XX_Mode = “LOCAL”


2
Switch the Mode to “BMS” PMW-XX-XX_Mode = “BMS”

Monitor the Status is “ON” PMW -XX-XX_EqSts = “ON


3
Monitor the Status is “OFF” PMW -XX-XX_EqSts = “OFF”
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Power Status is “Normal”


PMW-XX-XX_AlmSts= “NORMAL”
4
Simulate the condition is
PMW-XX-XX_AlmSts = “FAIL”
“Alarm”

Send command to “Start”. PMW -XX-XX_Start = “START”


5
Send command to “Stop”. PMW -XX-XX_Start = “STOP”

Throw station
TEST – 3 Throw station
Monitoring Points

Alarm Status is “Normal”


PMW-XX-XX_EqAlmSts= “NORMAL”
1
Simulate the condition is
PMW-XX-XX_EqAlmSts = “ALARM”
“Alarm”

Monitor the Mode to “Local” PMW-XX-XX_Mode = “LOCAL”


2
Switch the Mode to “BMS” PMW-XX-XX_Mode = “BMS”

Monitor the Status is “ON” PMW -XX-XX_EqSts = “ON


3
Monitor the Status is “OFF” PMW -XX-XX_EqSts = “OFF”

Power Status is “Normal”


PMW-XX-XX_AlmSts= “NORMAL”
4
Simulate the condition is
PMW-XX-XX_AlmSts = “FAIL”
“Alarm”

Send command to “Start”. PMW -XX-XX_Start = “START”


5
Send command to “Stop”. PMW -XX-XX_Start = “STOP”

Monitor the Discharge Count


Status is “ON” PMW -XX-XX_Sts = “ON
6
Monitor the Discharge Count PMW -XX-XX_Sts = “OFF”
Status is “OFF”
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Filtration system
TEST – 4 Filtration system
Monitoring Points

Prefilter Alarm Status is


“Normal” PMW-XX-XX_PreFiltSts= “NORMAL”
1
Simulate the condition is PMW-XX-XX_ PreFiltSts = “ALARM”
“Alarm”

Tested By: Acknowledged


Honeywell Pte Ltd
By: Kilowatts

NAME: NAME:

DATE: DATE:

Submitted and Penta-Ocean Construction Co, Witnessed and


RE/RTO
Checked By: Ltd. Checked BY:

NAME: NAME:

DATE: DATE:
Soiled Linen Collection System Test Form

SOFTWARE FUNCTIONAL TEST FORM -3

Form No: ECC-NSCKWE-BMS-


Project: PROJECT THE ECC & NDCS @ SGH TESTFROM-0003

Equipment ID: PMW-XX-XX Date: Revision: 0

Process Description: Testing and Commissioning of PMW-XX-XX

Area/Location: Panel ID: PMW-XX-XX

EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Trolley conveyor
TEST – 1 Trolley conveyor
Monitoring Points

Alarm Status is “Normal”


PMW-XX-XX_EqAlmSts= “NORMAL”
1
Simulate the condition is
PMW-XX-XX_EqAlmSts = “ALARM”
“Alarm”

Monitor the Mode to “Local” PMW-XX-XX_Mode = “LOCAL”


2
Switch the Mode to “BMS” PMW-XX-XX_Mode = “BMS”
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Monitor the Status is “ON” PMW -XX-XX_EqSts = “ON


3
Monitor the Status is “OFF” PMW -XX-XX_EqSts = “OFF”

Power Status is “Normal”


PMW-XX-XX_AlmSts= “NORMAL”
4
Simulate the condition is
PMW-XX-XX_AlmSts = “FAIL”
“Alarm”

Send command to “Start”. PMW -XX-XX_Start = “START”


5
Send command to “Stop”. PMW -XX-XX_Start = “STOP”

Monitor the Removal Count


Status is “ON” PMW -XX-XX_Sts = “ON
6
Monitor the Removal Count PMW -XX-XX_Sts = “OFF”
Status is “OFF”

Fan Exhauster
TEST – 2 Fan Exhauster
Monitoring Points

Alarm Status is “Normal”


PMW-XX-XX_EqAlmSts= “NORMAL”
1
Simulate the condition is
PMW-XX-XX_EqAlmSts = “ALARM”
“Alarm”

Monitor the Mode to “Local” PMW-XX-XX_Mode = “LOCAL”


2
Switch the Mode to “BMS” PMW-XX-XX_Mode = “BMS”

Monitor the Status is “ON” PMW -XX-XX_EqSts = “ON


3
Monitor the Status is “OFF” PMW -XX-XX_EqSts = “OFF”

Power Status is “Normal”


PMW-XX-XX_AlmSts= “NORMAL”
4
Simulate the condition is
PMW-XX-XX_AlmSts = “FAIL”
“Alarm”
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Send command to “Start”. PMW -XX-XX_Start = “START”


5
Send command to “Stop”. PMW -XX-XX_Start = “STOP”

Load station
TEST – 3 Load station
Monitoring Points

Alarm Status is “Normal”


PMW-XX-XX_EqAlmSts= “NORMAL”
1
Simulate the condition is
PMW-XX-XX_EqAlmSts = “ALARM”
“Alarm”

Monitor the Mode to “Local” PMW-XX-XX_Mode = “LOCAL”


2
Switch the Mode to “BMS” PMW-XX-XX_Mode = “BMS”

Monitor the Status is “ON” PMW -XX-XX_EqSts = “ON


3
Monitor the Status is “OFF” PMW -XX-XX_EqSts = “OFF”

Power Status is “Normal”


PMW-XX-XX_AlmSts= “NORMAL”
4
Simulate the condition is
PMW-XX-XX_AlmSts = “FAIL”
“Alarm”

Send command to “Start”. PMW -XX-XX_Start = “START”


5
Send command to “Stop”. PMW -XX-XX_Start = “STOP”

Monitor the Discharge Count


Status is “ON” PMW -XX-XX_Sts = “ON
6
Monitor the Discharge Count PMW -XX-XX_Sts = “OFF”
Status is “OFF”

Filtration system
TEST – 4 Filtration system
Monitoring Points
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Prefilter Alarm Status is


“Normal” PMW-XX-XX_PreFiltSts= “NORMAL”
1
Simulate the condition is PMW-XX-XX_ PreFiltSts = “ALARM”
“Alarm”

Tested By: Acknowledged


Honeywell Pte Ltd
By: Kilowatts

NAME: NAME:

DATE: DATE:

Submitted and Penta-Ocean Construction Co, Witnessed and


RE/RTO
Checked By: Ltd. Checked BY:

NAME: NAME:

DATE: DATE:
Soiled Linen Collection System Test Form

SOFTWARE FUNCTIONAL TEST FORM -4

Form No: ECC-NSCKWE-BMS-


Project: PROJECT THE ECC & NDCS @ SGH TESTFROM-0004

Equipment ID: PMW-XX-XX Date: Revision: 0

Process Description: Testing and Commissioning of PMW-XX-XX

Area/Location: Panel ID: PMW-XX-XX

EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Air compressor
TEST – 1 Air compressor
Monitoring Points

Alarm Status is “Normal”


PMW-XX-XX_EqAlmSts= “NORMAL”
1
Simulate the condition is
PMW-XX-XX_EqAlmSts = “ALARM”
“Alarm”

Monitor the Mode to “Local” PMW-XX-XX_Mode = “LOCAL”


2
Switch the Mode to “BMS” PMW-XX-XX_Mode = “BMS”
EXPECTED RESULT

(INITIAL &
SR.NO. TESTING ACTIVITY RESULT REMARKS
DATE)
BMS – SOFTWARE ONLINE & GRAPHIC
DISPLAY

Monitor the Status is “ON” PMW -XX-XX_EqSts = “ON


3
Monitor the Status is “OFF” PMW -XX-XX_EqSts = “OFF”

Power Status is “Normal”


PMW-XX-XX_AlmSts= “NORMAL”
4
Simulate the condition is
PMW-XX-XX_AlmSts = “FAIL”
“Alarm”

Send command to “Start”. PMW -XX-XX_Start = “START”


5
Send command to “Stop”. PMW -XX-XX_Start = “STOP”

Air receiver tank


TEST – 4 Air receiver tank
Monitoring Points

Alarm Status is “Normal” PMW-XX-XX_AlmSts= “NORMAL”

1
Simulate the condition is PMW-XX-XX_ AlmSts =
“Alarm” “Hi/LoALARM”

Tested By: Acknowledged


Honeywell Pte Ltd
By: Kilowatts

NAME: NAME:

DATE: DATE:

Submitted and Penta-Ocean Construction Co, Witnessed and


RE/RTO
Checked By: Ltd. Checked BY:
NAME: NAME:

DATE: DATE: